Plan Review Details - Permit 20100803
Plan Review Stops For Permit 20100803
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2020-12-28 Cont ID  
Sent By cpuell Date 2020-12-28 Time 11:16 Rev Time 0.00
Received By cpuell Date 2020-12-28 Time 11:16 Sent To  
Notes
2020-12-28 11:17:55PERMIT ENCOMPASSES 7032 & 7034 OKEECHOBEE BLVD, 7034
 OKEECHOBEE BLVD TO BE RETIRED, MAIN ADDRESS WILL NOW BE
 7032 OKEECHOBEE BLVD.

Review Stop AD ADDRESSING
Rev No 2 Status N Date 2020-12-28 Cont ID  
Sent By shill Date 2020-12-28 Time 10:25 Rev Time 0.00
Received By shill Date 2020-12-28 Time 10:25 Sent To  
Notes
***NONE***

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2020-10-29 Cont ID  
Sent By cpuell Date 2020-10-29 Time 11:31 Rev Time 0.00
Received By cpuell Date 2020-10-29 Time 11:31 Sent To  
Notes
2020-10-29 11:32:40PLEASE EMAIL [email protected] WITH A FLOOR PLAN SHOWING
 THE EXACT LOCATION OF THE WORK BEING DONE.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 5 Status P Date 2020-12-23 Cont ID  
Sent By pvalenti Date 2020-12-23 Time 16:44 Rev Time 0.00
Received By pvalenti Date 2020-12-23 Time 16:44 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 4 Status P Date 2020-12-28 Cont ID  
Sent By jwitmer Date 2020-12-28 Time 10:24 Rev Time 0.00
Received By shill Date 2020-12-28 Time 10:24 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status F Date 2020-12-15 Cont ID  
Sent By jwitmer Date 2020-12-15 Time 09:42 Rev Time 0.00
Received By jwitmer Date 2020-12-15 Time 09:14 Sent To  
Notes
2020-12-15 09:35:26TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2020-11-19 Cont ID  
Sent By jwitmer Date 2020-11-19 Time 15:03 Rev Time 0.00
Received By jwitmer Date 2020-11-19 Time 14:00 Sent To  
Notes
2020-11-19 15:02:36TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-10-29 Cont ID  
Sent By jwitmer Date 2020-10-29 Time 10:32 Rev Time 0.00
Received By jwitmer Date 2020-10-29 Time 08:57 Sent To  
Notes
2020-10-29 10:32:23COMMERCIAL ASBESTOS
  
 TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-12-15 Cont ID  
Sent By jwitmer Date 2020-12-15 Time 10:04 Rev Time 0.00
Received By jwitmer Date 2020-12-15 Time 09:14 Sent To  
Notes
2020-12-15 09:33:39WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20100803
 ADD: 7032 OKEECHOBEE BLVD. BAY 2
 CONT: ELE8 CONSTRUCTION, INC.
 TEL: 561-430-4870
 E-MAIL: BOB#MWARCHITECTURE.COM
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 3RD REVIEW
 DATE: TUES. DEC.15TH/2020
 ACTION: BUILDING PROVISO
  
 1A) BUILDING PROVISOS/ DEFERRED SUBMITTALS: 2017 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS
 (C) PANEL WALLS: STOREFRONT WINDOW SYSTEMS.
  
 1B) BUILDING PROVISO: W. P. B. 107.3.4. PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY
 FLORIDA ADMINISTRATIVE CODE RULE 61G20 SHALL BE
 REVIEWED AND APPROVED IN WRITING (SHOP DRAWING STAMP OF
 APPROVAL) BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-11-19 Cont ID  
Sent By jwitmer Date 2020-11-19 Time 15:01 Rev Time 0.00
Received By jwitmer Date 2020-11-19 Time 14:00 Sent To  
Notes
2020-11-19 15:01:16WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20100803
 ADD: 7032 OKEECHOBEE BLVD. BAY 2
 CONT: ELE8 CONSTRUCTION, INC.
 TEL: 561-430-4870
 E-MAIL: BOB#MWARCHITECTURE.COM
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: THURS. NOV.19TH/2020
 ACTION: DENIED
  
 1-4) COMPLIED.
  
  
 5) 2ND REQUEST. THIS SHEET NOT REVISED FOR WALL
 FINISHES. SHEET A-520 ROOM FINISH SCHEDULE INDICATES
 THE WALLS TO BE GYPSUM/ PAINT. 2017 FBC-B 1210.2.2.
 WALLS & PARTITIONS. THIS COMMENT IS A RESULT OF THE
 BUILDING OFFICIAL INTERPRETATION. IN RESTROOMS EPOXY
 PAINT IS NO LONGER CONSIDERED A SMOOTH HARD,
 NON-ABSORBENT SURFACE.
 WALLS & PARTITIONS WITHIN 2 FEET OF SERVICE SINKS,
 URINALS, AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NON-ABSORBENT SURFACE TO A HEIGHT OF NOT LESS THAN 4
 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL ELEMENTS,
 THE MATERIAL USED IN SUCH WALLS SHALL BE OF A TYPE THAT
 IS NOT ADVERSELY AFFECTED BY MOISTURE.
  
 2509.1. WET AREAS. SHOWERS AND PUBLIC TOILET WALLS
 SHALL COMPLY WITH 1210.2.
  
 1210.2. FINISH MATERIALS. WALLS, BASE, FLOORS AND
 PARTITIONS IN TOILET AND BATHROOMS SHALL COMPLY WITH
 SECTIONS 1210.1 THROUGH 1210.4.
  
 6) SHEET A-5200 RESTROOM ELEVATIONS:
 6A) COMPLIED. GRAB BAR HEIGTHS.
  
 6B)2ND REQUEST. ELEVATION A THERE IS NO DIMENSION FOR
 THE ELEVATION OF THE MIRROR OVER THE SINK. 603.3
 MIRRORS. 2017 FBC-ACCESSIBILITY CODE. MIRRORS LOCATED
 ABOVE LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH
 THE BOTTOM EDGE OF THE REFLECTING SURFACE 40 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 6C) SEMI-COMPLIED.MISSING SPOUT HEIGHT FOR COMPLIANCE
 WITH 602.7 OF THE ACCESSIBILITY CODE.
 SPOUT OUTLETS/ DRINKING FOUNTAINS. 2017 FBC- ACCESS.
 CODE. SPOUT OUTLETS SHALL COMPLY WITH:
 602.4 SPOUT HEIGHT. 36 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND FOR WHEELCHAIR BOUND INDIVIDUALS.
 602.7 SPOUT HEIGHT FOR THE STANDING PERSONS SHALL BE
 BETWEEN 38TO 43 INCHES ABOVE FINISH FLOOR.
  
 7A) BUILDING PROVISOS/ DEFERRED SUBMITTALS: 2017 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS
 (C) PANEL WALLS: STOREFRONT WINDOW SYSTEMS.
  
 7B) BUILDING PROVISO: W. P. B. 107.3.4. PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY
 FLORIDA ADMINISTRATIVE CODE RULE 61G20 SHALL BE
 REVIEWED AND APPROVED IN WRITING (SHOP DRAWING STAMP OF
 APPROVAL) BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 8) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-10-29 Cont ID  
Sent By jwitmer Date 2020-10-29 Time 10:30 Rev Time 0.00
Received By jwitmer Date 2020-10-29 Time 08:57 Sent To  
Notes
2020-10-29 10:30:34WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20100803
 ADD: 7032 & 7036 OKEECHOBEE BLVD.
 CONT: ELE8 CONSTRUCTION, INC.
 TEL: 561-430-4870
 E-MAIL: BOB#MWARCHITECTURE.COM
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: THURS. OCT. OCT. 29TH/2020
 ACTION: DENIED
  
 1A) PLEASE NOTE THIS PERMIT APPLICATION CAME IN FOR TO
 1ST TIME TENANT BUILDOUTS THAT BOTH SUITES 7032 & 7036
 WILL REQUIRE CERTIFICATES OF OCCUPANCY. PLEASE PROVIDE
 THE PERMIT LIBRARIAN WITH A 2ND PERMIT APPLICATION FOR
 THE 2ND TENANT SPACE. FESS WILL ALSO NEED TO BE
 ADJUSTED ACCORDINGLY FOR BOTH PERMITS.
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATIVE CODE SECTION 111.2
 CERTIFICATE OF OCCUPANCY.
 1B) SHEET A-0.1 LIST THE PROJECT SPECIFIC CODE SUMMARY,
 LISTING A PRIMARY OCCUPANCY MERCANTILE AND SECONDARY
 OCCUPANCY BUSINESS. BECAUSE OF THE REQUIRED CERTIFICATE
 OF OCCUPANCY REQUIREMENTS 2 PERMITS REQUIRED, PLEASE
 LIST THE OCCUPANCIES BY THEIR ADDRESS. EXAMPLE 7032-
 MERCANTILE/ RETAIL AND 7036- BUSINESS. WE CAN HAVE ONE
 SET OF PLANS TO SHARE FOR THE 2 PERMITS.
 2) WITHIN THE SUBMITTED PLANS THERE IS NO LIFE SAFETY
 SHEET FOR EITHER OF THE TENANT SPACES NOR CHAPTER 10
 MEANS OF EGRESS.
 107.3.5 MINIMUM PLAN REVIEW CRITERIA.2017 FLORIDA
 BUILDING CODE W 2017 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATIVE CODE
 SECTION:
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS AND
 OR STRUCTURES.
 107.3.5.1 COMMERCIAL BUILDINGS
 107.3.5.1.1. BUILDING
  
 MISSING CODE DATA:
 LIFE SAFETY PLANS SHALL DETERMINE AND SHALL INCLUDE THE
 FOLLOWING:
 WALLS
 FURNITURE LAYOUT
 OCCUPANT LOAD AND EGRESS CAPACITIES
 GROSS OR NET
 DEAD END CORRIDORS
 DOOR SWING
 MEANS OF EGRESS EXIT ACCESS
 EXIT
 EXIT DISCHARGE / HOW MANY REQUIRED/ HOW MANY PROVIDED
  
 3) SHEET A-0.1 INDICATES UNDER THE HEADING OF DEFERRED
 SUBMITTALS DESIGN PRESSURES FOR ALUMINUM STOREFRONT AND
 A
 ALUMINUM DOORS, BUT THERE IS NO WIND DESIGN CRITERIA
 PROVIDED FOR THE PRESSURES.
 2017 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 3.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
  
 3.2. RISK CATEGORY.
  
 3.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE. ASCE 7-10 TABLE 30.3.1.
  
 3.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 3.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED
 BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR
 THE DESIGN OF THE STRUCTURE, PSF.
  
 3.6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING. ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED
 CONVERSION VULT TO VASD.
  
  
 4) THERE ARE NO SHEETS WITHIN THE PLAN SET SHOWING
 WHERE THE STOREFRONT WINDOW AND DOORS ARE TO BE
 INSTALLED? 107.2.1.2. ADDITIONAL INFORMATION REQUIRED.
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS AND
 OR STRUCTURES.
 107.3.5.1 COMMERCIAL BUILDINGS
 107.3.5.1.1. BUILDING
 ELEVATIONS.
  
 5) SHEET A-520 ROOM FINISH SCHEDULE INDICATES THE WALLS
 TO BE GYPSUM/ PAINT. 2017 FBC-B 1210.2.2. WALLS &
 PARTITIONS. THIS COMMENT IS A RESULT OF THE BUILDING
 OFFICIAL INTERPRETATION. IN RESTROOMS EPOXY PAINT IS NO
 LONGER CONSIDERED A SMOOTH HARD, NON-ABSORBENT SURFACE.
 WALLS & PARTITIONS WITHIN 2 FEET OF SERVICE SINKS,
 URINALS, AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NON-ABSORBENT SURFACE TO A HEIGHT OF NOT LESS THAN 4
 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL ELEMENTS,
 THE MATERIAL USED IN SUCH WALLS SHALL BE OF A TYPE THAT
 IS NOT ADVERSELY AFFECTED BY MOISTURE.
  
 2509.1. WET AREAS. SHOWERS AND PUBLIC TOILET WALLS
 SHALL COMPLY WITH 1210.2.
  
 1210.2. FINISH MATERIALS. WALLS, BASE, FLOORS AND
 PARTITIONS IN TOILET AND BATHROOMS SHALL COMPLY WITH
 SECTIONS 1210.1 THROUGH 1210.4.
  
 6) SHEET A-5200 RESTROOM ELEVATIONS:
 6A) IN ELEVATIONS A & B THE GRAB BARS ARE DIMENSIONED
 TO THE CENTERLINE OF THE GRAB BAR, NOT THE TOP OF THE
 GRAB BAR, THE GRIPPING SURFACE. 2017 FBC-ACCESSIBILITY
 CODE SECTION 609.4 POSITION OF GRAB BARS. GRAB BARS
 SHALL BE INSTALLED IN A HORIZONTAL POSITION, 33 INCHES
 MINIMUM AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR
 MEASURED TO THE TOP OF THE GRIPPING SURFACE, NOT
 CENTERLINE.
  
 6B) ELEVATION A THERE IS NO DIMENSION FOR THE ELEVATION
 OF THE MIRROR OVER THE SINK. 603.3 MIRRORS. 2017
 FBC-ACCESSIBILITY CODE. MIRRORS LOCATED ABOVE
 LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE
 BOTTOM EDGE OF THE REFLECTING SURFACE 40 INCHES MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.
  
 6C) SPOUT OUTLETS/ DRINKING FOUNTAINS. 2017 FBC-
 ACCESS. CODE. SPOUT OUTLETS SHALL COMPLY WITH:
 602.4 SPOUT HEIGHT. 36 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND FOR WHEELCHAIR BOUND INDIVIDUALS.
 602.7 SPOUT HEIGHT FOR THE STANDING PERSONS SHALL BE
 BETWEEN 38TO 43 INCHES ABOVE FINISH FLOOR.
  
 7) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-12-17 Cont ID  
Sent By jleahy Date 2020-12-17 Time 14:12 Rev Time 0.00
Received By jleahy Date 2020-12-17 Time 14:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-12-01 Cont ID  
Sent By equinone Date 2020-12-01 Time 13:37 Rev Time 0.00
Received By equinone Date 2020-12-01 Time 09:53 Sent To  
Notes
2020-12-01 09:54:41REVIEW STATUS DENIED (SEE COMMENTS BELOW):
  
 CONDUCTORS FOR RTU # 1 AND RTU # 2 ARE TOO SMALL. NEC
 240.4(D), NEC TABLE 310.15(B)(16)
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
  
 COMMENTS FROM FIRST ELECTRICAL REVIEW THAT NEED TO BE
 ADDRESED:
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE RISER DIAGRAM OF EXISTING SERVICE TO VERIFY
 EXISTING SERVICE IS ADEQUATE. DIAGRAM PROVIDED IS
 MISSING CONDUCTOR SIZES AND OCP SIZES, ONLY STATES
 "EXISTING" FBC 107.2.1 NEC 220
  
 2. MAINS MUST BE GROUPED PER NEC 230.72A. 1 EXISTING
 DISCONNECT IS SHOWN WITH 3 NEW DISCONNECTS (2,200AMP
 AND 1, 400AMP) THE ANOTHER METER IS SHOWN WITHOUT A
 DISCONNECT FOR EXISTING PANEL "HP" PROVIDE CORRECTION.
  
 3. PROVIDE ACCURATE LOAD CALCULATION OF EXISTING
 SERVICE TO VERIFY EXISTING SERVICE IS ADEQUATE NEC 220
 FBC 107.2.1 LOAD CALCULATION PROVIDED ONLY SHOWS PANELS
 "1B" AND "2A". A LOAD STUDY OF 30 DAYS FROM THE POWER
 UTILITY WILL ALSO SUFFICE PER NEC 220.87
  
 4. NORMALLY THE POWER UTILITY ONLY ALLOWS 1 METER PER
 SPACE FOR A TENANT. 2 METERS SHOWN IN 1 SPACE. 1 FOR
 PANEL "1B" AND 1 FOR "2A". PROVIDE DOCUMENTATION FROM
 POWER UTILITY "FLORIDA POWER AND LIGHT (FPL)"
  
 4. SHOW COMPLETE GROUNDING ELECTRODE SYSTEM TO INCLUDE
 CONDUCTOR SIZES. FBC 107.2.1 NEC 250.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-11-03 Cont ID  
Sent By fgiaquin Date 2020-11-03 Time 20:14 Rev Time 0.00
Received By fgiaquin Date 2020-11-03 Time 19:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2020-12-11 Cont ID  
Sent By bdolan Date 2020-12-11 Time 09:54 Rev Time 0.00
Received By bdolan Date 2020-12-11 Time 09:54 Sent To  
Notes
2020-12-11 09:54:28SAME PLANS FOR BUILDOUTS OF PERMIT 20100803 AND
 2010673; WILL REQUIRE NEW SEPERATE PERMITS FOR
 BUILDOUTS IF ANY CHANGES TO LIFESAFETY OR OCCUPANCY
 TYPE ARE MADE. BDOLAN621

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-11-19 Cont ID  
Sent By bdolan Date 2020-11-19 Time 1100 Rev Time 0.00
Received By bdolan Date 2020-12-11 Time 09:47 Sent To  
Notes
2020-12-11 09:49:27SAME PLANS FOR BUILDOUTS OF PERMIT 20100803 AND
 2010673; WILL REQUIRE NEW SEPERATE PERMITS FOR
 BUILDOUTS IF ANY CHANGES TO LIFESAFETY OR OCCUPANCY
 TYPE ARE MADE. BDOLAN621

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-10-23 Cont ID  
Sent By pleduc Date 2020-10-23 Time   Rev Time 0.00
Received By pleduc Date 2020-10-23 Time 09:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-12-28 Cont ID  
Sent By shill Date 2020-12-28 Time 10:26 Rev Time 0.00
Received By shill Date 2020-12-23 Time 15:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-12-17 Cont ID  
Sent By jleahy Date 2020-12-17 Time 14:13 Rev Time 0.00
Received By jleahy Date 2020-12-10 Time 16:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-12-01 Cont ID  
Sent By equinone Date 2020-12-01 Time 13:52 Rev Time 0.00
Received By equinone Date 2020-11-18 Time 14:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-11-03 Cont ID  
Sent By fgiaquin Date 2020-11-03 Time 20:14 Rev Time 0.00
Received By fgiaquin Date 2020-10-21 Time 14:16 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2020-12-16 Cont ID  
Sent By medwards Date 2020-12-16 Time 11:15 Rev Time 0.00
Received By medwards Date 2020-12-16 Time 11:14 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2020-11-19 Cont ID  
Sent By medwards Date 2020-11-19 Time 15:25 Rev Time 0.00
Received By medwards Date 2020-11-19 Time 12:08 Sent To  
Notes
2020-11-19 15:25:461ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20100803
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE A COMCHECK FOR EACH TENANT SPACE. IT
 SHOULD INCLUDE ONLY THE RTU?S FOR THAT PARTICULAR
 TENANT SPACE. FBC 107.2
  
 2) SHEET M-1- DRAWING INDICATES RTU-2 AND RTU-3 IN BAY
 2 (ADDRESS 7032-7034), THE ROOFTOP PACKAGE AIR
 CONDITIONING SCHEDULE DOES NOT INCLUDE RTU-3. PLEASE
 PROVIDE RTU-3 SCHEDULE DETAILS. FBC 107.2
  
 3) SHEET M-1: PLEASE USE THE OCCUPANT COUNT LOCATED ON
 SHEET A-0.1 FOR THE MERCANTILE OCCUPANCY FOR UNITS
 (ADDRESS 7032-7034) FBC 107.2
  
 4) SHEET M-1: THE FAN SCHEDULE INDICATES EF_1,2 ARE 525
 CFM, EF-1 ON THE DRAWING FOR TENANT ADDRESS (ADDRESS
 7032-7034) INDICATES THE FAN IS 90 CFM. PLEASE MAKE THE
 FAN SCHEDULE CONSISTENT. FBC 107.2
  
 5) SHEET M-1: THE FAN SCHEDULE INDICATES THE BATH
 EXHAUST FANS ARE ROOF MOUNTED BUT THE DRAWING INDICATES
 THAT BOTH EXHAUST FANS ARE MOUNTED AT CEILING AND
 DUCTED TO ROOF TERMINATIONS. PLEASE BE CONSISTENT. FBC
 107.2
  
 6) SHEET M-1: BAY 1 (ADDRESS 7036) OCCUPANCY IS
 BUSINESS PER SHEET A-1. PLEASE PROVIDE THE CORRECT
 OCCUPANCY (BUSINESS) IN THE OUTSIDE AIR CALCULATIONS ON
 SHEET M-1. FBC 107.2
  
 7) SHEET M-1: BAY 1 (ADDRESS 7036) THE FAN SCHEDULE
 INDICATES EF_1,2 ARE 525 CFM, EF-2 ON THE DRAWING FOR
 TENANT (ADDRESS 7036) INDICATES THE FAN IS 90 CFM.
 PLEASE MAKE THE FAN SCHEDULE CONSISTENT. FBC 107.2
 8) IS THE TENANT SPACE (ADDRESS-7036) GOING TO HAVE ANY
 DUCTWORK INSTALLED?
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-10-29 Cont ID  
Sent By medwards Date 2020-10-29 Time 09:14 Rev Time 0.00
Received By medwards Date 2020-10-29 Time 09:14 Sent To  
Notes
2020-10-29 09:19:03THIS APPEARS TO BE 2 COMPLETELY SEPERATE TENANT SPACES
 SEPERATED WITH A FIRE BARRIER. YOU WILL NEED TWO
 PERMITS, ONE FOR EACH TENANT SPACE. PLEASE SUBMIT BOTH
 SEPERATELY TO [email protected]
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-11-20 Cont ID  
Sent By ccole Date 2020-11-20 Time 08:54 Rev Time 0.00
Received By ccole Date 2020-11-19 Time 16:12 Sent To  
Notes
2020-11-20 09:31:17PLUMBING SUB-PERMIT REQUIRED.

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-10-29 Cont ID  
Sent By ccole Date 2020-10-29 Time 10:07 Rev Time 0.00
Received By ccole Date 2020-10-29 Time 07:37 Sent To  
Notes
2020-10-29 10:07:531ST REVIEW FBC-2017 PLUMBING
 PERMIT- 2010803
 10/29/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS A-0.1 & P1: PROVIDE PLUMBING FIXTURE
 CALCULATIONS IN ACCORDANCE WITH TABLE 403.3. PROVIDE A
 SCHEDULE ON THE PLAN THAT SHOWS THE NUMBER OF REQUIRED
 AND PROVIDED FIXTURES FOR EACH NEW OCCUPANCY.
  
 2) A-0.1: PLEASE INCLUDE THE WATER HEATER COMPLIANCE
 DATA IN THE COMCHECK ENERGY REPORT- TABLE C404.2 FBC
 EC.
  
 3) A-5: SHOW THE TURNING CIRCLE DIAMETERS IN THE TOILET
 ROOMS- SECTION 304.3 FBC ACC.
  
 4) A-5: SHOW THE REQUIRED 30 X 48 IN. CLEAR FLOOR SPACE
 FOR A FORWARD WHEELCHAIR APPROACH TO THE WHEELCHAIR
 ACCESSIBLE FOUNTAIN- SECTION 602.2 FBC ACC, AND SHOW
 HOW THE LOCATIONS OF THE FOUNTAINS WILL BE IN
 COMPLIANCE WITH SECTION 307.2 PROTRUSION LIMITS.
  
 5) A-5: PROVIDE AN ELEVATION DETAIL FOR THE DRINKING
 FOUNTAIN FOR STANDING PERSON USE SHOWING SPOUT HEIGHT
 AND SPOUT LOCATION- SECTION 602.7 FBC ACC.
  
 6) P1 & P2: PROVIDE A WATER RISER DRAWING- SECTION
 107.3.5.1.3 WPB.
  
 7) P1 & P2: TWO NEW TENANT OCCUPANCIES ARE SHOWN. SHOW
 THE LOCATIONS OF THE NEW WATER METERS AND MAIN SHUTOFF
 VALVES TO THE SPACES- SECTIONS 605.1 & 606.1 FBC P.
  
 8) P1 & P2: INDICATE HOW TEMPERED WATER WILL BE
 PROVIDED AT THE LAVATORY PER SECTION 416.5. PLEASE NOTE
 THAT TEMPERED WATER SHALL BE SUPPLIED THROUGH A WATER
 TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE 1070-
 SECTION 607.1.2 FBC P.
  
 9) P1 & P2: SHOW THE LOCATIONS OF WATER HAMMER
 ARRESTORS FOR SUPPLY LINES TO QUICK CLOSING VALVES-
 SECTION- 604.9 FBC P.
  
 10) P2: PROVIDE THE EFFICIENCY RATING OF THE WATER
 HEATER IN THE SCHEDULE- TABLE C404.2 FBC EC.
  
 11) P2, BAY 1B ISO: THE MOP SINK (P3) MUST BE
 INDIVIDUALLY VENTED BECAUSE IT CANNOT BE PART OF THE
 TOILET ROOM HORIZONTAL WET SYSTEM- SECTION 912.1 FBC P.
  
 12) P2, BAY 12 ISO: THE LAVATORY IS MISLABELED (P1)
 INSTEAD OF (P2).
  
 13) P2: SHOW THE TYPE AND SIZE OF HOT WATER PIPE
 INSULATION- TABLE C403.2.10 FBC EC.
  
 14) INDICATE THE TYPE OF WALL FINISHES TO BE INSTALLED
 IN THE RESTROOMS AND AT THE MOP SINK LOCATIONS IN
 ACCORDANCE WITH SECTION 310.3 FBC P, AND 1210.2.2 FBC
 B.
  
 15) PROVIDE A PLUMBING SUB-PERMIT APPLICATION- SECTION
 105.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-12-16 Cont ID  
Sent By medwards Date 2020-12-16 Time 11:17 Rev Time 0.00
Received By medwards Date 2020-12-16 Time 11:17 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-12-01 Cont ID  
Sent By equinone Date 2020-12-01 Time 13:51 Rev Time 0.00
Received By equinone Date 2020-12-01 Time 13:51 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-11-03 Cont ID  
Sent By equinone Date 2020-11-03 Time 13:42 Rev Time 0.00
Received By equinone Date 2020-11-03 Time 13:42 Sent To  
Notes
2020-11-03 20:14:19ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE RISER DIAGRAM OF EXISTING SERVICE TO VERIFY
 EXISTING SERVICE IS ADEQUATE. DIAGRAM PROVIDED IS
 MISSING CONDUCTOR SIZES AND OCP SIZES, ONLY STATES
 "EXISTING" FBC 107.2.1 NEC 220
  
 2. MAINS MUST BE GROUPED PER NEC 230.72A. 1 EXISTING
 DISCONNECT IS SHOWN WITH 3 NEW DISCONNECTS (2,200AMP
 AND 1, 400AMP) THE ANOTHER METER IS SHOWN WITHOUT A
 DISCONNECT FOR EXISTING PANEL "HP" PROVIDE CORRECTION.
  
 3. PROVIDE ACCURATE LOAD CALCULATION OF EXISTING
 SERVICE TO VERIFY EXISTING SERVICE IS ADEQUATE NEC 220
 FBC 107.2.1 LOAD CALCULATION PROVIDED ONLY SHOWS PANELS
 "1B" AND "2A". A LOAD STUDY OF 30 DAYS FROM THE POWER
 UTILITY WILL ALSO SUFFICE PER NEC 220.87
  
 4. NORMALLY THE POWER UTILITY ONLY ALLOWS 1 METER PER
 SPACE FOR A TENANT. 2 METERS SHOWN IN 1 SPACE. 1 FOR
 PANEL "1B" AND 1 FOR "2A". PROVIDE DOCUMENTATION FROM
 POWER UTILITY "FLORIDA POWER AND LIGHT (FPL)"
  
 4. SHOW COMPLETE GROUNDING ELECTRODE SYSTEM TO INCLUDE
 CONDUCTOR SIZES. FBC 107.2.1 NEC 250.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  