| 2020-10-20 15:28:03 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20100775 |
| | ADD: 335 FRANKLIN RD. |
| | CONT: ST WRIGHT BUILDERS |
| | TEL: 561-385-2029 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. OCT. 20/2020 |
| | ACTION: DENIED |
| | |
| | 1) PLEASE NOTE THE SUBMITTED PLAN IS A COPYRIGHTED PLAN |
| | OF RICK BOYETTE P. E. 42485. THE 2ND ISSUE IS THIS PLAN |
| | DOES NOT HAVE A DIGITAL SEAL AND THE 3RD ISSUE IS THAT |
| | IT ALREADY HAS CITY STAMPS ON THE PLAN THAT DO NOT |
| | PERTAIN TO THIS PROJECT. |
| | FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A |
| | DOCUMENT IN THE FILE FOLDER, SCANNED, FACSIMILE, |
| | DIGITALLY CREATED OR COPIED IMAGE OF THE LICENSEE?S |
| | SIGNATURE SHALL NOT BE USED ON DIGITALLY SIGNED AND |
| | SEALED ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR |
| | OTHER DOCUMENTS. |
| | THE CONTRACTOR CAN DRAW THEIR OWN FLOOR PLAN |
| | IDENTIFYING THE ROOMS, WINDOW AND DOOR OPENING SIZES |
| | AND ASSOCIATED PRESSURES. |
| | |
| | CERTIFICATION BY CONTRACTOR. |
| | 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE |
| | EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H) |
| | ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C) |
| | (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT |
| | WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE |
| | CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE. |
| | THE CONTRACTOR (QUALIFIER) THAT CREATED / DRAWN THE SET |
| | OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR |
| | OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME |
| | AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN |
| | AND PLANS DRAWN. |
| | |
| | 2) THERE IS NO WIND DESIGN CRITERIA FOUND ON THE FLOOR |
| | PLAN, OR WIND CHART WITH DESIGN PRESSURES. PLEASE NOTE |
| | WIND DESIGN AND PRESSURE CHARTS FOR ENGINEERS HAVE TO |
| | BE LOADED INTO THE PLAN FOLDER TO VERIFY THE DIGITAL |
| | SIGNATURE. PAPER WIND CHARTS BY ENGINEERS WITH |
| | SIGNATURE AND SEALS CAN BE SUBMITTED THE INTAKING STAFF |
| | WILL VERIFY THE SIGNATURE AND SEAL OF ENGINEERED |
| | DRAWINGS. FLORIDA ADMINISTRATIVE CODE 61G15-23.005 |
| | (3)(C) A DOCUMENT IN THE FILE FOLDER, SCANNED, |
| | FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE OF THE |
| | LICENSEE?S SIGNATURE SHALL NOT BE USED ON DIGITALLY |
| | SIGNED AND SEALED ENGINEERING PLANS. |
| | |
| | 2017 FBC-B 1603.1.4 WIND DESIGN DATA. THE FOLLOWING |
| | INFORMATION RELATED TO WIND LOADS SHALL BE SHOWN, |
| | REGARDLESS OF WHETHER WIND LOADS GOVERN THE DESIGN OF |
| | THE LATERAL FORCE-RESISTING SYSTEM OF THE STRUCTURE: |
| | 2.1 ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| | MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS |
| | DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1. |
| | 2.2 RISK CATEGORY. |
| | 2.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| | THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. |
| | HEIGHT AND EXPOSURE. ASCE 7-10 TABLE 30.3.1. |
| | 2.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| | 2.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED |
| | BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR |
| | THE DESIGN OF THE STRUCTURE, PSF. |
| | 2.6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| | EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| | BUILDING.. ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED |
| | CONVERSION VULT TO VASD. NOTE IF ROOFS HAVE ALL HIPS |
| | AND VALLEYS. |
| | |
| | 3) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE |
| | PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF |
| | RECORD AND BEFORE SUBMISSION TO THE BUILDING |
| | DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| | IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, |
| | MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED |
| | INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE |
| | PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1 |
| | INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN |
| | ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS. |
| | FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH |
| | INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM |
| | LOADS AND SPACING USED IN THE TESTS. |
| | |
| | 4) PLEASE NOTE THAT FOR BOTH THE FRONT DOOR AND SIDE |
| | DOOR1 SHEET THE EQUIVALENCY OF STANDARDS WAS SUBMITTED. |
| | IN BOTH CASES THERE IS A FL NUMBER ON THE PAGE BUT NONE |
| | OF THE TECHNICAL SHEETS WERE SUBMITTED FOR REVIEW. 2017 |
| | FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1 |
| | COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY |
| | AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 |
| | NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: (31)(A) EXTERIOR DOORS, |
| | |
| | 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 |
| | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |