Plan Review Details - Permit 20100775
Plan Review Stops For Permit 20100775
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-11-08 Cont ID  
Sent By jwitmer Date 2020-11-08 Time 15:14 Rev Time 0.00
Received By jwitmer Date 2020-11-08 Time 14:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-10-20 Cont ID  
Sent By jwitmer Date 2020-10-20 Time 16:16 Rev Time 0.00
Received By jwitmer Date 2020-10-20 Time 15:27 Sent To  
Notes
2020-10-20 15:28:03WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20100775
 ADD: 335 FRANKLIN RD.
 CONT: ST WRIGHT BUILDERS
 TEL: 561-385-2029
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. OCT. 20/2020
 ACTION: DENIED
  
 1) PLEASE NOTE THE SUBMITTED PLAN IS A COPYRIGHTED PLAN
 OF RICK BOYETTE P. E. 42485. THE 2ND ISSUE IS THIS PLAN
 DOES NOT HAVE A DIGITAL SEAL AND THE 3RD ISSUE IS THAT
 IT ALREADY HAS CITY STAMPS ON THE PLAN THAT DO NOT
 PERTAIN TO THIS PROJECT.
 FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A
 DOCUMENT IN THE FILE FOLDER, SCANNED, FACSIMILE,
 DIGITALLY CREATED OR COPIED IMAGE OF THE LICENSEE?S
 SIGNATURE SHALL NOT BE USED ON DIGITALLY SIGNED AND
 SEALED ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS.
 THE CONTRACTOR CAN DRAW THEIR OWN FLOOR PLAN
 IDENTIFYING THE ROOMS, WINDOW AND DOOR OPENING SIZES
 AND ASSOCIATED PRESSURES.
  
 CERTIFICATION BY CONTRACTOR.
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT
 WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE
 CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE.
 THE CONTRACTOR (QUALIFIER) THAT CREATED / DRAWN THE SET
 OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR
 OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME
 AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN
 AND PLANS DRAWN.
  
 2) THERE IS NO WIND DESIGN CRITERIA FOUND ON THE FLOOR
 PLAN, OR WIND CHART WITH DESIGN PRESSURES. PLEASE NOTE
 WIND DESIGN AND PRESSURE CHARTS FOR ENGINEERS HAVE TO
 BE LOADED INTO THE PLAN FOLDER TO VERIFY THE DIGITAL
 SIGNATURE. PAPER WIND CHARTS BY ENGINEERS WITH
 SIGNATURE AND SEALS CAN BE SUBMITTED THE INTAKING STAFF
 WILL VERIFY THE SIGNATURE AND SEAL OF ENGINEERED
 DRAWINGS. FLORIDA ADMINISTRATIVE CODE 61G15-23.005
 (3)(C) A DOCUMENT IN THE FILE FOLDER, SCANNED,
 FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE OF THE
 LICENSEE?S SIGNATURE SHALL NOT BE USED ON DIGITALLY
 SIGNED AND SEALED ENGINEERING PLANS.
  
 2017 FBC-B 1603.1.4 WIND DESIGN DATA. THE FOLLOWING
 INFORMATION RELATED TO WIND LOADS SHALL BE SHOWN,
 REGARDLESS OF WHETHER WIND LOADS GOVERN THE DESIGN OF
 THE LATERAL FORCE-RESISTING SYSTEM OF THE STRUCTURE:
 2.1 ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
 2.2 RISK CATEGORY.
 2.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE. ASCE 7-10 TABLE 30.3.1.
 2.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 2.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED
 BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR
 THE DESIGN OF THE STRUCTURE, PSF.
 2.6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.. ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED
 CONVERSION VULT TO VASD. NOTE IF ROOFS HAVE ALL HIPS
 AND VALLEYS.
  
 3) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 4) PLEASE NOTE THAT FOR BOTH THE FRONT DOOR AND SIDE
 DOOR1 SHEET THE EQUIVALENCY OF STANDARDS WAS SUBMITTED.
 IN BOTH CASES THERE IS A FL NUMBER ON THE PAGE BUT NONE
 OF THE TECHNICAL SHEETS WERE SUBMITTED FOR REVIEW. 2017
 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS: (31)(A) EXTERIOR DOORS,
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-11-08 Cont ID  
Sent By jwitmer Date 2020-11-08 Time 15:14 Rev Time 0.00
Received By jwitmer Date 2020-11-04 Time 14:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-10-20 Time 16:16 Rev Time 0.00
Received By lmarchan Date 2020-10-15 Time 15:45 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-11-08 Cont ID  
Sent By jwitmer Date 2020-11-08 Time 15:14 Rev Time 0.00
Received By jwitmer Date 2020-11-08 Time 14:44 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-10-20 Cont ID  
Sent By jwitmer Date 2020-10-20 Time 16:16 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2020-10-20 16:16:32SEE BUILDING REVIEW.