Plan Review Details - Permit 20100736
Plan Review Stops For Permit 20100736
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2021-01-21 Cont ID  
Sent By cpuell Date 2021-01-21 Time 10:53 Rev Time 0.00
Received By cpuell Date 2021-01-21 Time 10:53 Sent To  
Notes
2021-01-21 10:54:16BLDG 6 - 3596 VILLAGE BLVD

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2020-12-11 Cont ID  
Sent By cpuell Date 2020-12-11 Time 14:42 Rev Time 0.00
Received By cpuell Date 2020-12-11 Time 14:42 Sent To  
Notes
2020-12-11 14:42:42HAVE WORKED WITH DEVELOPER ON ADDRESSES, BUT WAS ASKED
 TO HOLD OFF UNTIL THEY OWNED THE PROPERTY. PLEASE
 CONTACT [email protected] TO CONFIRM ADDRESSES.

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status P Date 2021-03-25 Cont ID  
Sent By dbattles Date 2021-02-09 Time 14:30 Rev Time 0.00
Received By scwelter Date 2021-03-25 Time 14:12 Sent To  
Notes
2021-03-25 14:13:43PUBLIC ART FEE PAID - 1.22.2021
2021-02-09 14:31:58NOTES:
 ART ASSESSMENT APPLICATION RECEIVED/OPTION 2
 (CONTRIBUTION)
 INVOICE FOR ART FEE SENT 1.22.2021
 FEE NOT PAID
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2021-03-23 Cont ID  
Sent By rmcphers Date 2021-03-23 Time 08:01 Rev Time 0.00
Received By rmcphers Date 2021-03-23 Time 08:01 Sent To  
Notes
2021-03-26 10:38:18PROVISO ?
 SUBMIT A BUILDING UNDER CONSTRUCTION ELEVATION
 CERTIFICATE TO PLAN REVIEW, REQUIRED JUST AFTER
 FINISHED FLOOR IS POURED
 SUBMIT A FINISHED CONSTRUCTION ELEVATION CERTIFICATE TO
 PLAN REVIEW, REQUIRED AFTER FINISHED GRADE AND ALL
 MECHANICAL EQUIPMENT IS SET, BEFORE FINAL INSPECTION
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-03-19 Cont ID  
Sent By rmcphers Date 2021-03-19 Time 12:46 Rev Time 0.00
Received By rmcphers Date 2021-03-19 Time 12:12 Sent To  
Notes
2021-03-19 12:46:03NEW 4 STORY APARTMENT BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) STRAPPING IS NOT SHOWN FOR "TOWER TRUSS LAYOUT A" -
 DRAWING (S-2.1.6) HAS A STRAP CONNECTOR SCHEDULE - THE
 TRUSS FRAMING PLAN NEEDS TO SHOW THE LOCATION OF THE
 TRUSS CONNECTORS (STRAPPING).
  
  
  
  
  
  
 PERMIT FEE REVISED BASED ON 56294 SQ. FT. X ICC
 VALUATION 130.52 PER SQ.FT. = 7,347,492.00 JOB VALUE
2021-03-15 08:45:44PERMIT FEE REVISED BASED ON 51,298SQ.FT. X ICC
 VALUATION 130.52 PER SQ. FT. = $6,695,414.00

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-02-18 Cont ID  
Sent By rmcphers Date 2021-02-18 Time 09:32 Rev Time 0.00
Received By rmcphers Date 2021-02-18 Time 09:32 Sent To  
Notes
2021-02-18 09:36:16NEW 4 STORY APARTMENT BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) I DID NOT CATCH THIS ON THE FIRST REVIEW - ALL UNIT
 DOORS - PLEASE SHOW THE REQUIRED MANEUVERING SPACE (18"
 BESIDE THE DOOR) TO EXIT THE UNIT OR ROOM. FBC
 ACCESSIBILITY FHA REQUIREMENT ANSI 4.13.6
 2) I DID NOT CATCH THIS ON THE FIRST REVIEW - UNIT A1
 DISTANCE FROM THE KITCHEN ISLAND TO THE WALL LEADING TO
 THE KITCHEN (NO TURNING SPACE IN THE KITCHEN TO TURN
 AROUND) NEEDS TO BE MIN. 40" (DRAWING A-4.2.1) - USABLE
 KITCHENS WOULD MEET SECTION 100.205(C)(3)(IV)
 IF:(B)CLEARANCE BETWEEN COUNTERS AND ALL OPPOSING BASE
 CABINETS, COUNTERTOPS, APPLIANCES OR WALLS IS AT LEAST
 40 INCHES.
 3) WE ARE REQUIRING THAT YOU SHOW THE CLEAR FLOOR SPACE
 FOR THE PLUMBING FIXTURES ON EACH UNIT FLOOR PLAN TO
 SHOW THAT EACH UNIT COMPLIES WITH FAIR HOUSING
 ACCESSIBILITY REQUIREMENTS.
 4) DRAWING (S-2.1.6) HAS A STRAP CONNECTOR SCHEDULE -
 THE TRUSS FRAMING PLAN NEEDS TO SHOW THE LOCATION OF
 THE TRUSS CONNECTORS (STRAPPING).
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-11-18 Cont ID  
Sent By rmcphers Date 2020-11-18 Time 14:12 Rev Time 0.00
Received By rmcphers Date 2020-11-17 Time 09:58 Sent To  
Notes
2020-11-18 14:10:54NEW 4 STORY APARTMENT BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) SURVEY PROVIDED SHOWS FLOOD ZONE "ABE" WHAT IS THAT?
 2) SURVEY PROVIDED NEEDS TO BE ELECTRONICALLY/DIGITALLY
 SIGNED BY THE SURVEYOR FOR USE IN PROJECTDOX.
 3) PLEASE SHOW ELEVATOR SIZE TO COMPLY WITH FBC 3002.4
 ELEVATOR CAR TO ACCOMMODATE AMBULANCE STRETCHER.
 4) DRAWING (LS-0.2.0) SHOWS BUILDING CONSTRUCTION TYPE
 IIIB UNDER "PROJECT NARRATIVE" AND IB UNDER
 "CONSTRUCTION TYPE" PLEASE CLARIFY (CONSTRUCTION TYPE 1
 WOULD NEED TO SHOW ALL ROOF FRAMING AND SHEATHING TO BE
 FIRE RETARDANT PER FBC CHAPTER 6). (ALSO BUILDING
 DESCRIPTION IS NOT CORRECT IN THE "PROJECT
 NARRATIVE"BOX)
 5) DRAWING (LS-0.2.0) SHOULD ALSO SHOW THE HORIZONTAL
 FIRE SEPARATION REQUIREMENT PER FBC 420.3
 6) ACCESSIBILITY UNIT PLANS - MASTER BATH - PLEASE SHOW
 THE REQUIRED CLEAR FLOOR SPACE FOR THE DOORS THAT OPEN
 INTO THE BATHROOM FBC ACCESSIBILITY FHA REQUIREMENT 7
 (2)(B).
 7) DRAWING (S-6.2.1) SHOWS PER 2014 FBC - SHOULD BE
 2017 FBC.
 8) PLEASE SHOW THE UNIT DOOR NUMBER 1 ON THE DOOR
 SCHEDULE TO BE SELF-LATCHING AND CLOSING PER FBC
 716.5.9
 9) PLEASE SHOW THE SQUARE FOOTAGE OF THE BUILDING - PER
 FLOOR - TOTAL.
 10) DRAWING (A-2.2.3) PLEASE POINT OUT THE REQUIRED
 ROOF OVERFLOW SCUPPER LOCATIONS FBC 1503.4.1
 11) SOIL REPORT PROVIDED NEEDS TO BE
 ELECTRONICALLY/DIGITALLY SIGNED BY THE ENGINEER. SOIL
 REPORT IS BASED ON A 3-STORY BUILD IS THIS OK WITH YOU?
 12) DRAWING (A-10.2.2 AND 10.2.1) IN THE "LEGEND FOR
 WALL REINFORCING" SAYS TO SEE DRAWING (A-10.4) THAT
 DRAWING IS NOT UPLOADED TO PROJECTDOX.
 13) A "THRESHOLD/SPECIAL INSPECTOR AGREEMENT OF
 UNDERSTANDING" FORM WILL NEED TO BE FILLED OUT - PLEASE
 SEND AN EMAIL TO [email protected] AND ASK FOR "THE
 GUIDELINES AND POLICIES FOR THRESHOLD AND SPECIAL
 INSPECTORS"
 14) PLEASE PROVIDE A COPY OF THE FLOOR/CEILING SOUND
 TRANSMISSION REPORTS (IIC AND STC) AS NOTED ON THE
 DRAWINGS? - FBC1207
 15) DRAWING (S-2.1.6) HAS A STRAP CONNECTOR SCHEDULE -
 THE PLAN NEEDS TO SHOW THE LOCATION OF THE TRUSS
 CONNECTORS (STRAPPING).
 16) SEPARATE PERMITS AND REVIEWS ARE REQUIRED FOR -
 GAZEBOS, PARKING LOT, DUMPSTER ENCLOSURE, FENCE -
 PLEASE ACKNOWLEDGE THIS ON THE DRAWINGS.
 17) THRESHOLD BLDG. REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD SHALL CONTAIN A STATEMENT THAT,
 TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE,
 THE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 MINIMUM BUILDING CODES AND THE APPLICABLE FIRE-SAFETY
 STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND CHAPTER 633 FLORIDA
 STATUTES.
 18) PLEASE SHOW THE STAIRWAY HANDRAIL EXTENTION ON
 DRAWING (A-7.2.1) TO COMPLY WITH FBC 1014.6
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-02-10 Cont ID  
Sent By jleahy Date 2021-02-10 Time 14:59 Rev Time 0.00
Received By jleahy Date 2021-02-10 Time 13:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-12-01 Cont ID  
Sent By jleahy Date 2020-12-01 Time 10:10 Rev Time 0.00
Received By jleahy Date 2020-12-01 Time 07:14 Sent To  
Notes
2020-12-01 10:10:52ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E-3.2.1
  
 1) HOUSE SERVICE SHOWS ONE SET OF 250 AL FOR 400A
  
 2) AIC RATING OF SERVICE AND PANELS REQUIRED PER 110.9,
 110,10
  
 3) MAIN #2 1200A REQUIRES COMPLIANCE WITH 240.87(A)(B)
 PLEASE INDICATE METHOD TO BE USED.
  
  
 PAGE E-4.2.0
  
 1) NOTE #3 TO PANEL NOTES REFERENCES ROMEX IT IS NOT
 ASLLOWED IN A TYPE 1 B BUILDING. 334.10 (5) UNLESS
 INSTALLED IN CONDUIT.
  
 GENERAL NOTES
  
 FIRE ALARM, BDA, SITE LIGHTING, LOW VOLTAGE WORK
 REQUIRES SEPARATE PERMITS.

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2022-07-29 Cont ID  
Sent By jleahy Date 2022-07-29 Time 16:11 Rev Time 0.00
Received By jleahy Date 2022-07-29 Time 16:11 Sent To  
Notes
2022-07-29 16:11:42TV , VOICE , AND DATA AS PER PLANS JLEAHY

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2020-11-05 Cont ID  
Sent By rrossano Date 2020-11-05 Time   Rev Time  
Received By rrossano Date 2020-11-05 Time   Sent To  
Notes
2020-11-05 08:19:29ONSITE UTILITIES ARE PRIVATE. REVIEWING OVERALL
 ENGINEERING SUBMITTAL E20080019.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2021-03-16 Cont ID  
Sent By pleduc Date 2021-03-16 Time   Rev Time 0.00
Received By pleduc Date 2021-03-16 Time 10:20 Sent To  
Notes
2021-03-16 10:21:35FIRE PROVISO:
  
 1) ALL UNDERGROUND FIRE LINES SHALL BE INSTALLED UNDER
 SEPARATE PERMIT AND SHOP DRAWINGS PER NFPA 24
  
  
 2) PER NFPA 101 CH 8
  
 8.6.11 CONCEALED SPACES AND DRAFTSTOPS.
 8.6.11.1 ANY CONCEALED COMBUSTIBLE SPACE IN WHICH
 BUILDING
 MATERIALS HAVING A FLAME SPREAD INDEX GREATER THAN
 CLASS A ARE
 EXPOSED SHALL BE DRAFTSTOPPED AS FOLLOWS:
  
 (2) EVERY UNOCCUPIED ATTIC SPACE SHALL BE SUBDIVIDED BY
 DRAFTSTOPS
 INTO AREAS NOT TO EXCEED 3000 FT2 (280 M2).
  
 REVIEW AND INSTALL AS APPLICABLE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-01-22 Cont ID  
Sent By pleduc Date 2021-01-22 Time   Rev Time 0.00
Received By pleduc Date 2021-01-22 Time 13:55 Sent To  
Notes
2021-01-22 13:55:11FIRE PROVISO:
  
 1) ALL UNDERGROUND FIRE LINES SHALL BE INSTALLED UNDER
 SEPARATE PERMIT AND SHOP DRAWINGS PER NFPA 24
  
  
 2) PER NFPA 101 CH 8
  
 8.6.11 CONCEALED SPACES AND DRAFTSTOPS.
 8.6.11.1 ANY CONCEALED COMBUSTIBLE SPACE IN WHICH
 BUILDING
 MATERIALS HAVING A FLAME SPREAD INDEX GREATER THAN
 CLASS A ARE
 EXPOSED SHALL BE DRAFTSTOPPED AS FOLLOWS:
  
 (2) EVERY UNOCCUPIED ATTIC SPACE SHALL BE SUBDIVIDED BY
 DRAFTSTOPS
 INTO AREAS NOT TO EXCEED 3000 FT2 (280 M2).
  
 REVIEW AND INSTALL AS APPLICABLE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-11-18 Cont ID  
Sent By pleduc Date 2020-11-18 Time   Rev Time 0.00
Received By pleduc Date 2020-11-18 Time 12:38 Sent To  
Notes
2020-11-18 12:38:47FIRE PROVISO:
  
 1) ALL UNDERGROUND FIRE LINES SHALL BE INSTALLED UNDER
 SEPARATE PERMIT AND SHOP DRAWINGS PER NFPA 24
  
  
 2) PER NFPA 101 CH 8
  
 8.6.11 CONCEALED SPACES AND DRAFTSTOPS.
 8.6.11.1 ANY CONCEALED COMBUSTIBLE SPACE IN WHICH
 BUILDING
 MATERIALS HAVING A FLAME SPREAD INDEX GREATER THAN
 CLASS A ARE
 EXPOSED SHALL BE DRAFTSTOPPED AS FOLLOWS:
  
 (2) EVERY UNOCCUPIED ATTIC SPACE SHALL BE SUBDIVIDED BY
 DRAFTSTOPS
 INTO AREAS NOT TO EXCEED 3000 FT2 (280 M2).
  
 REVIEW AND INSTALL AS APPLICABLE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-03-24 Cont ID  
Sent By lmarchan Date 2021-03-24 Time 14:14 Rev Time 0.00
Received By lmarchan Date 2021-03-12 Time 15:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-02-26 Cont ID  
Sent By lcrespo Date 2021-02-26 Time 17:37 Rev Time 0.00
Received By lcrespo Date 2021-01-20 Time 09:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-12-11 Cont ID  
Sent By cpuell Date 2020-12-11 Time 14:42 Rev Time 0.00
Received By cpuell Date 2020-10-23 Time 16:05 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2021-04-15 Cont ID  
Sent By lmarchan Date 2021-04-15 Time 15:24 Rev Time 0.00
Received By lmarchan Date 2021-03-24 Time 14:14 Sent To  
Notes
2021-04-14 08:57:55RECEIPT MU-2021-14661 - $317,498.80 - PAID
2021-03-24 14:14:423/24/21 EMAILED IMPACT OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-11-18 Cont ID  
Sent By rmcphers Date 2020-11-18 Time 14:12 Rev Time 0.00
Received By rmcphers Date 2020-11-18 Time 14:12 Sent To  
Notes
2020-11-18 14:13:18PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2021-03-23 Cont ID  
Sent By medwards Date 2021-03-23 Time 08:06 Rev Time 0.00
Received By medwards Date 2021-03-23 Time 08:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-02-04 Cont ID  
Sent By medwards Date 2021-02-04 Time 07:49 Rev Time 0.00
Received By medwards Date 2021-02-04 Time 06:24 Sent To  
Notes
2021-02-04 07:50:201ST REVIEW FBC-2020 MECHANICAL
 PERMIT-20100736
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2020
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2020
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-4.2.1: PLEASE PROVIDE THE CALCULATIONS FOR
 EACH DRYER DUCT LENGTH AND EXPLAIN WHY A LONG VENT
 DRYER IS NOT REQUIRED. THE DRYER DUCT LENGTH LISTED IN
 EACH CHART, IS THAT LENGTH BEFORE THE 90 DEGREE AND 45
 DEGREE TURNS? PROVIDE THE DEVELOPED LENGTH OF PIPE
 BEFORE THE TURNS ARE ADDED. FROM OUR CONVERSATION YOU
 MUST SUBTRACT 10? FROM THE DRYER MANUFACTURERS DRYER
 DUCT LENGTH. EXAMPLE: A1 THE LENGTH IS 54? ? 10? = 44?;
 THE DRYER EXHAUST LENGTH LISTS 40? WITH THE ADDITION OF
 1 90 DEGREE AND 1 45 DEGREE TURN THIS BRINGS THE TOTAL
 ALLOWABLE LENGTH OF DRYER DUCT PIPING TO 36.5? WHICH IS
 LONGER THAN ALLOWED BY THE FBC M 504.8.4 WHICH WOULD
 MEAN THE LENGTH IDENTIFICATION MUST BE POSTED. FBC M
 504.8.5
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-11-17 Cont ID  
Sent By medwards Date 2020-11-17 Time 15:52 Rev Time 0.00
Received By medwards Date 2020-11-10 Time 09:15 Sent To  
Notes
2020-11-17 15:53:281ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20100736
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE A LETTER FROM THE DRYER MANUFACTURER
 STATING THAT THE X VENT DRYER EXHAUST TERMINATION IS
 ALLOWED WITH THEIR DRYER. THE X VENT IS UNIQUE IN THE
 FACT THAT IT USES BOTH THE BACK-DRAFT DAMPER AND THE
 LOUVER. THE INSTALLATION MANUAL DOES NOT ADDRESS THIS
 KIND OF INSTALLATION. WITH THE X VENT SYSTEM THE BOX OF
 THE X VENT IS MOUNTED INTO THE EXTERIOR OF THE WALL AND
 THE LOUVER IS FLUSH TO THE EXTERIOR WALL. THE EXHAUST
 OF THE DRYER MUST TRAVEL THROUGH THE EXHAUST DUCT, OPEN
 THE BACK-DRAFT DAMPER AND TRAVEL THROUGH THE X VENT
 COVER (LOUVER) BEFORE IT IS EXHAUSTED TO THE OUTDOORS.
 BECAUSE THIS PRODUCT USES BOTH THE BACK-DRAFT DAMPER
 AND THE OUTER COVER OF THE BOX (LOUVER) INSTEAD OF
 EITHER THE BACK-DRAFT DAMPER OR THE LOUVER THE DRYER
 MANUFACTURER MUST ADDRESS THE ASSEMBLY. WE MUST HAVE AN
 APPROVAL LETTER FROM THE SPECIFIC DRYER MANUFACTURER
 FOR THE SPECIFIC DRYER USED IN THIS PROJECT. FBC M
 504.8.4.2
  
 2) PLEASE PROVIDE SPECIFICATIONS THAT SHOW THE LOUVER
 SIZE MEETS FBC M 501.3.2. ?OPENINGS IN LOUVERS SHALL BE
 SIZED NOT LESS THAN ?? AND NOT LARGER THAN ??.
  
 3) PLEASE PROVIDE THE SPECIFICATIONS SHOWING THE XVENT
 LOUVER COMPLIES WITH AMCA 550.
  
 4) PLEASE PROVIDE SPECIFICATION SHEETS FOR THE X VENT
 AIR INTAKE TERMINATION. FBC 107.2
  
 5) PLEASE PROVIDE NATURAL VENTILATION CALCULATIONS. FBC
 M 402
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status P Date 2020-11-18 Cont ID  
Sent By rmcphers Date 2020-11-18 Time 14:14 Rev Time 0.00
Received By rmcphers Date 2020-11-18 Time 14:13 Sent To  
Notes
2020-11-18 14:16:31NEW BUILDING
 SURVEY SHOWS FLOOD ZONE - AE 14
 DRAWINGS SHOW FFE - 16.00 NAVD

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-03-19 Cont ID  
Sent By lcrespo Date 2021-03-19 Time 14:22 Rev Time 0.00
Received By lcrespo Date 2021-03-19 Time 14:22 Sent To  
Notes
2021-03-19 14:23:0903/19/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-02-26 Cont ID  
Sent By lcrespo Date 2021-02-26 Time 17:35 Rev Time 0.00
Received By lcrespo Date 2021-02-26 Time 17:35 Sent To  
Notes
2021-02-26 17:36:1302/26/21 2ND PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON COMMENTS ONE THOUGH 5, I MAY NOT HAVE PUT IN THE
 INCORRECT COMMENT SO THE RESPONSE IS FOR THE CLUBHOUSE.
 IF YOU REFER TO THE COMMENTS ON THE MASTER AS I DID A
 COPY AND PASTE AND MAY HAVE DONE IT WRONG AND I
 APOLOGIZE FOR IT.
  
 6. YOU CAN KEEP THE PERFORATED CAPS, BUT THE ISSUE IS
 NOT THE VENT. IT IS THE POSITIVE AND NEGATIVE FLOW. IF
 YOU PUT AN A.A.V IN A PLENUM, IT NEEDS AN ACCESS PANEL,
 AND THE PVC IS NOT A FIRE-RATED ASSEMBLE IN THE SMOKE
 INDEX WON?T WORK. A SUGGESTION IS TO TIE THE HEATER PAN
 AND CONDENSATE TOGETHER AND CONVERT TO CPVC THEN OFFSET
 INTO THE PLENUM. IN OTHER PLANS FOR THE REVIEWS, THEY
 ARE THE SAME COMMENT, SO PLEASE CALL ME FOR
 CLARIFICATION.
  
 7. DONE.
  
 8. COULD NOT FIND THE PAGES ARE CROSSED WITH 6.2.1.
 CALL ME ON THIS ONE, TOO, PLEASE.
  
 9. SHEET P5.2.4;
 A. DONE.
  
 B. PIPE IS STILL MISSING SIZES.
  
 C. PAGE 6.1.1 NOT FOUND.
  
 D. THE FLOOR DRAIN IS NOT VENTED PER THE 2017 FBC SEC.
 901.2.1 VENTING REQUIRED.
  
 E. PIPE FOR ELEVATOR DRAIN STILL NOT LABEL ON SIZE.
  
 10. DONE.
  
 11. THERMAL EXPANSION COULD NOT BE FOUND AS 6.2.2 IS
 THE SAME AS 6.1.1. THE COMMENT IS TO THE WATER HEATER
 THAT SHOWS A METER. IF THAT METER DOES NOT FLOW EITHER
 WAY, THEN AN EXPANSION VALVE WILL BE NEEDED AT THE SIDE
 OF THE OUTLET METER. IF YOU LIKE YOU CAN CALL ME TO
 DISCUSS THIS.
  
 12. DONE
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-12-01 Cont ID  
Sent By lcrespo Date 2020-12-01 Time 13:07 Rev Time 0.00
Received By lcrespo Date 2020-11-04 Time 11:07 Sent To  
Notes
2020-12-01 13:12:3512/01/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET C-172 THERE ARE BACKFLOW SHOWN WITH DETAILS
 AND COMMENTS PLEASE ADD THAT SEPARATE PERMITS ARE
 REQUIRED BY A LICENSED CONTRACTOR AND CERTIFIED BY THE
 CITY OF WEST PALM BEACH UTILITIES DEPARTMENT PER THE
 WPB AMENDMENTS TO THE FBC SEC. 105.1.
  
 2. ON SHEET A10.2.1 AND A 10.2.2 PLEASE SHOW ALL CLEAR
 FLOOR SPACE DIMENSIONS FOR ALL AREAS PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION.
  
 3. ON SHEET A10.2.3 PLEASE REMOVE SHOWERS CLEAR FLOOR
 SPACE NOT USED IN THIS BUILDING AND ANY OTHER DETAILS
 THAT DO NOT APPLY TO THIS BUILDING PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION.
  
 4. ON SHEET A10.2.1 FOR UNIT A1 WITH THE TUB OPTION, IT
 SHALL HAVE THE CLEAR FLOOR SPACE TO THE SIDE OF THE
 VALVE ACCESS IN ACCORDANCE WITH THE PARALLEL APPROACH
 FHADM 7.53.
  
 5. ON SHEET A10.2.1 AND 10.2.2 PLEASE PROVIDE DETAIL
 FOR LAV HEIGHT IN A10.2.3 THAT MEET THE REQUIREMENTS OF
 THE B BATHROOMS IN ACCORDANCE WITH THE FHADM 7.52.
  
 6. ON SHEET P5.2.1 FOR CONDENSATE AND PAN, IT HAS A
 PERFORATED CAP ON THE FOURTH FLOOR AND NOT VENT OR OUT
 THE WALL CAVITY PLEASE DETAIL OF A VENT THAT PROVIDES A
 FLOW OF AIR TO OR FROM A DRAINAGE SYSTEM, OR TO PROVIDE
 A CIRCULATION OF AIR WITHIN SUCH SYSTEM TO PROTECT TRAP
 SEALS FROM SIPHONAGE AND BACKPRESSURE PER THE 2017 FBC
 DEFINITIONS.
  
 7. ON SHEET P5.2.2 RISER 5 YOU HAVE A WASHING MACHINE
 ON A BATHROOM GROUP NOT ALLOWED PLEASE HAVE A SEPARATE
 STACK PER THE 2017 FBC SEC 912.2.1 HORIZONTAL WET VENT.
  
 8. ON SHEET P5.2.3 PLEASE VALVE AT ACCESSIBLE LOCATIONS
 FOR WATER RISERS PER THE 2017 FBC SEC. 606.1 LOCATION
 OF FULL-OPEN VALVES.
  
 9. SHEET P5.2.4;
 A. THERE ARE 5 WASHING MACHINES ON THE BATHROOM GROUP
 (NEXT TO STACK 5) THAT IS NOT ALLOWED PLEASE HAVE A
 SEPARATE STACK PER THE 2017 FBC SEC 912.2.1 HORIZONTAL
 WET VENT.
  
 B. PLEASE LABEL ALL PIPE SIZES FOR SANITARY DRAINAGE
 BRANCHES PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.5.1.3 (13) COMMERCIAL PLUMBING.
  
 C. PLEASE SHOW TRAP PRIMER FOR FLOOR DRAIN AND GIVE
 PAGE REFERENCE FOR DETAIL PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.5.1.3 (13) COMMERCIAL PLUMBING.
  
 D. THE FLOOR DRAIN IS NOT VENTED PER THE 2017 FBC SEC.
 901.2.1 VENTING REQUIRED.
  
 E. PLEASE PROVIDE PIPE SIZE FOR THE SUMP PUMP DRAINAGE
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.5.1.3 (13)
 COMMERCIAL PLUMBING.
  
 10. SHEET P5.2.5 PLEASE PROVIDE PIPE SIZING FOR THE
 WATER RISER REQUIRED PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.5.1.3 (13) COMMERCIAL PLUMBING.
  
 11. SHEET P6.2.1 THERE IS THE DETAIL FOR THE HEATER
 PLEASE PROVIDE THE THERMAL EXPANSION DEVICE PER THE
 2017 FBC SEC. FBC P 607.3.
  
 12. ON SHEET P6.2.2 UNDER ELECTRIC WATER SOURCE
 SCHEDULE HAS A MIN EFF. OF 0.92 BUT ACCORDING TO NEACA
 HOT WATER REGULATION 2015 AND IT SHOULD BE AT EF 0.95,
 PLEASE NOTE THAT 6.2.1 AND 6.2.2 ARE UPLOADED WITH THE
 NUMBER CROSSED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2020-11-18 Cont ID  
Sent By rmcphers Date 2020-11-18 Time 14:16 Rev Time 0.00
Received By rmcphers Date 2020-11-18 Time 14:16 Sent To  
Notes
2020-11-18 14:17:00DEFERRED

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-03-19 Cont ID  
Sent By rmcphers Date 2021-03-19 Time 12:49 Rev Time 0.00
Received By rmcphers Date 2021-03-19 Time 12:48 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-02-04 Cont ID  
Sent By medwards Date 2021-02-04 Time 07:55 Rev Time 0.00
Received By medwards Date 2021-02-04 Time 07:55 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-11-17 Cont ID  
Sent By medwards Date 2020-11-17 Time 16:03 Rev Time 0.00
Received By medwards Date 2020-11-10 Time 10:29 Sent To  
Notes
2020-11-17 16:05:03THE FOLLOWING SHEETS MUST BE DIGITALLY SIGNED AND
 SEALED BY THE DESIGNER: SOIL REPORT, SURVEY, OVER ALL
 SITE PLAN AND OSP-2
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status P Date 2021-02-18 Cont ID  
Sent By rmcphers Date 2021-02-18 Time 09:45 Rev Time 0.00
Received By rmcphers Date 2021-02-18 Time 09:45 Sent To  
Notes
***NONE***

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2020-11-18 Cont ID  
Sent By rmcphers Date 2020-11-18 Time 14:19 Rev Time 0.00
Received By rmcphers Date 2020-11-18 Time 14:19 Sent To  
Notes
2020-11-18 14:19:39PLEASE REVIEW THE "GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING THRESHOLD/SPECIAL INSPECTORS AND RESIDENT
 INSPECTORS" AND COMPLY WITH THE REQUIREMENTS AND
 COMPLETE THE REQUIRED FORMS.
 PLEASE E MAIL [email protected] FOR A COPY OF THE
 POLICIES.
  

Review Stop Z ZONING
Rev No 3 Status P Date 2021-03-24 Cont ID  
Sent By jroach Date 2021-03-24 Time 12:15 Rev Time 0.00
Received By jroach Date 2021-03-24 Time 12:15 Sent To  
Notes
2021-03-24 12:15:22ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 03.24.2021
 PERMIT NO.: 20100736
 ________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. THE SCOPE OF THIS PERMIT REVIEW IS LIMITED TO THE
 ?BUILDING TYPE II? ONLY. SEPARATE PERMITS REQUIRED FOR
 ALL OTHER BUILDINGS, SURROUNDING SITE WORK, FENCING,
 LANDSCAPING, IRRIGATION, ETC.
  
 2. THE BROADSTONE LAKESIDE RESIDENTIAL PLANNED
 DEVELOPMENT SHALL BE SUBJECT TO ALL DEVELOPMENT ORDER
 CONDITIONS AS OUTLINED IN RESOLUTION NO. 106-20, AND AS
 MAY BE AMENDED. ALL CONDITIONS OF APPROVAL IMPOSED BY
 RESOLUTION NO. 106-20, AS AMENDED, SHALL BE ADDRESSED
 WITHIN THE APPROPRIATE SPECIFIED TIMEFRAMES.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 2 Status F Date 2021-02-05 Cont ID  
Sent By jroach Date 2021-02-05 Time 11:43 Rev Time 0.00
Received By jroach Date 2021-02-05 Time 11:43 Sent To  
Notes
2021-02-05 11:43:29ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 02.05.2021
 PERMIT NO.: 20100736
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. [ SATISFIED ] - ALL LANDSCAPE PLANS, ETC. SHALL BE
 REMOVED FROM THE BUILDING PERMIT SUBMITTAL AND
 SUBMITTED AS PART OF SEPARATE PERMIT APPLICATIONS. THE
 ONLY PLANS THAT SHOULD BE SUBMITTED WITH THIS PERMIT
 APPLICATION ARE THOSE THAT ARE NECESSARY FOR THE REVIEW
 AND ISSUANCE OF THIS PERMIT. ALL PLANS ASSOCIATED WITH
 SEPARATE PERMITS SHOULD BE REMOVED FROM THE SUBMITTAL.
  
 2. [ NOT SATISFIED ] - AS MODIFICATIONS HAVE BEEN MADE
 SINCE ADOPTION OF THE DEVELOPMENT ORDER (RESOLUTION NO.
 106-20), A MINOR AMENDMENT SHALL BE SUBMITTED TO AND
 APPROVED BY THE DEVELOPMENT SERVICES DEPARTMENT ?
 PLANNING DIVISION. THIS IS WITH THE ASSUMPTION AND
 FUTURE CONFIRMATION THAT NONE OF THE CHANGES TRIGGER
 THE THRESHOLD FOR A MAJOR AMENDMENT, AS SPECIFIED IN
 THE CITY?S ZONING AND LAND DEVELOPMENT REGULATIONS.
  
 3. [ SATISFIED ] - PURSUANT TO RESOLUTION NO. 106-20,
 PRIOR TO THE ISSUANCE OF ANY BUILDING PERMIT:
  
 3.1. [ SATISFIED ] - THE DEVELOPER SHALL PAY TO THE
 CITY OF WEST PALM BEACH A CONTRIBUTION IN THE AMOUNT OF
 $30,000 TOWARD TO COST OF A SAFETY STUDY FOR VILLAGE
 BOULEVARD.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT - PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2020-12-11 Cont ID  
Sent By jroach Date 2020-12-11 Time 13:17 Rev Time 0.00
Received By jroach Date 2020-12-11 Time 13:17 Sent To  
Notes
2020-12-11 13:26:11ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 12.11.2020
 PERMIT NO.: 20100736
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. ALL LANDSCAPE PLANS, ETC. SHALL BE REMOVED FROM THE
 BUILDING PERMIT SUBMITTAL AND SUBMITTED AS PART OF
 SEPARATE PERMIT APPLICATIONS. THE ONLY PLANS THAT
 SHOULD BE SUBMITTED WITH THIS PERMIT APPLICATION ARE
 THOSE THAT ARE NECESSARY FOR THE REVIEW AND ISSUANCE OF
 THIS PERMIT. ALL PLANS ASSOCIATED WITH SEPARATE PERMITS
 SHOULD BE REMOVED FROM THE SUBMITTAL.
  
 2. AS MODIFICATIONS HAVE BEEN MADE SINCE ADOPTION OF
 THE DEVELOPMENT ORDER (RESOLUTION NO. 106-20), A MINOR
 AMENDMENT SHALL BE SUBMITTED TO AND APPROVED BY THE
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION.
 THIS IS WITH THE ASSUMPTION AND FUTURE CONFIRMATION
 THAT NONE OF THE CHANGES TRIGGER THE THRESHOLD FOR A
 MAJOR AMENDMENT, AS SPECIFIED IN THE CITY?S ZONING AND
 LAND DEVELOPMENT REGULATIONS.
  
 3. PURSUANT TO RESOLUTION NO. 106-20, PRIOR TO THE
 ISSUANCE OF ANY BUILDING PERMIT:
  
 3.1. THE DEVELOPER SHALL PAY TO THE CITY OF WEST PALM
 BEACH A CONTRIBUTION IN THE AMOUNT OF $30,000 TOWARD TO
 COST OF A SAFETY STUDY FOR VILLAGE BOULEVARD.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved