Plan Review Details - Permit 20100729
Plan Review Stops For Permit 20100729
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2021-01-21 Cont ID  
Sent By cpuell Date 2021-01-21 Time 10:30 Rev Time 0.00
Received By cpuell Date 2021-01-21 Time 10:30 Sent To  
Notes
2021-01-21 10:30:49CLUB HOUSE ADDRESS IS 3590 VILLAGE BLVD

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2020-12-11 Cont ID  
Sent By cpuell Date 2020-12-11 Time 14:59 Rev Time 0.00
Received By cpuell Date 2020-12-11 Time 14:59 Sent To  
Notes
2020-12-11 14:59:48HAVE WORKED WITH DEVELOPER ON ADDRESSES, BUT WAS ASKED
 TO HOLD OFF UNTIL THEY OWNED THE PROPERTY. PLEASE
 CONTACT [email protected] TO CONFIRM ADDRESSES.

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 2 Status P Date 2021-03-18 Cont ID  
Sent By shill Date 2021-03-18 Time 15:16 Rev Time 0.00
Received By shill Date 2021-03-18 Time 15:16 Sent To  
Notes
2021-03-18 15:18:47OK PER EMAIL FROM S.WELTER
  

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status N Date 2021-01-26 Cont ID  
Sent By dbattles Date 2021-01-26 Time 08:45 Rev Time 0.00
Received By dbattles Date 2021-01-26 Time 08:45 Sent To  
Notes
2021-01-26 08:46:04ART ASSESSMENT APPLICATION RECEIVED/OPTION 2
 (CONTRIBUTION)
 INVOICE FOR ART FEE SENT 1.22.2021
 FEE NOT PAID
  
 SYBILLE WELTER
 ADMINISTRATOR OF PUBLIC ART AND CULTURE
 DIRECT 561.822.1521
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-03-19 Cont ID  
Sent By rmcdouga Date 2021-03-19 Time 14:21 Rev Time 0.00
Received By rmcdouga Date 2021-03-19 Time 14:21 Sent To  
Notes
2021-03-19 14:18:31CLUBHOUSE
 A-3 OCCUPANCY
 TYPE V-B, UN-SPRINKLERED
 FBC SIXTH EDITION (2017)
  
 1) DEFERRED SUBMITTALS TO BE SUBMITTED AND APPROVED
 BEFORE INSTALLATION.
  
 2) SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE
 REQUIRED FOR:
 LIGHT POLES/SITE LIGHTING
 FIRE ALARM
 FIRE SPRINKLER
 LOW VOLTAGE
 ACCESS
 LANDSCAPING
 IRRIGATION
 PARKING LOT
 SWIMMING POOLS
 GENERATORS
 ALL OTHER ITEMS OTHER THAN BMEP
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-02-26 Cont ID  
Sent By rmcdouga Date 2021-02-17 Time 08:24 Rev Time 0.00
Received By rmcdouga Date 2021-02-17 Time 08:24 Sent To  
Notes
2021-02-16 17:00:59PLAN
 REVIEW COMMENTS
  
 CLUBHOUSE
 A-3 OCCUPANCY
 TYPE V-B, UN-SPRINKLERED
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PARTIALLY RESOLVED. [THE DATE OF THE REVISED
 GEOTECHINCAL REPORT IS 1/19/20 AND IT SHOULD BE
 1/19/21. ON SHEET OSP-1, THE NOTE UNDER FLOOD ZONE
 INFORMATION HAS FLOOD ZONE "ABE". PLEASE CORRECT.
 SUBMIT A PRE-CONSTRUCTION ELEVATION CERTIFICATE. NOTE:
 ALL EQUIPMENT THAT SERVICES THE BUILDING IS REQUIRED TO
 BE AT OR ABOVE 16' NAVD 88.] ACCORDING TO THE FLOOD
 INSURANCE RATE MAP WHICH WAS ADOPTED ON OCTOBER 5, 2017
 AND IS APPLICABLE TO THIS PROJECT, THE STRUCTURE IS IN
 AN AE FLOOD ZONE WHICH IS A SPECIAL FLOOD HAZARD AREA.
 THE FLOOD ZONE IS AE AND THE BFE IS 14' NAVD88. THE
 REQUIRED DFE IS 16' NAVD88. THE BUILDING AND ALL OF THE
 EQUIPMENT SERVICING IT ARE REQUIRED TO BE AT OR ABOVE
 THE DFE, 16' NAVD88. AS OF OCTOBER 5TH, 2017, THE CITY
 HAS ADOPTED NEW FLOOD INSURANCE RATE MAPS WHICH USE
 NAVD 88 AS THE VERTICAL DATUM. THE CITY ALSO ADOPTED A
 2' FREEBOARD WHICH REQUIRES THE FINISH FLOOR AND
 EQUIPMENT TO BE A MINIMUM OF TWO FEET ABOVE THE BFE.
 SPECIFY ALL ELEVATIONS IN NAVD 88. THREE ELEVATION
 CERTIFICATES ARE REQUIRED TO BE SUBMITTED. 1) A
 PRE-CONSTRUCTION ELEVATION CERTIFICATE BASED ON THE
 CONSTRUCTION PLANS IS REQUIRED BEFORE THE PERMIT IS
 ISSUED. 2) A BUILDING UNDER CONSTRUCTION ELEVATION
 CERTIFICATE WHEN FIRST FLOOR SLABS ARE POURED. 3) A
 FINISHED CONSTRUCTION ELEVATION WHEN THE JOB IS
 COMPLETE INCLUDING LANDSCAPING. THE FINAL ELEVATION
 CERTIFICATE IS REQUIRED TO BE SUBMITTED AND APPROVED
 BEFORE THE C.O. WILL BE ISSUED.
  
 2) RESOLVED. SPECIFY THE FINISH FLOOR ELEVATION ON THE
 ARCHITECTURAL PLANS. FBC 107.2.1
  
 3) RESOLVED. THE LIFE SAFETY LEGEND ON SHEET CH-LS-0.1
 HAS THE TRAVEL DISTANCE AS 200' FOR PROTECTED WITH
 AUTOMATIC FIRE SPRINKLERS. FBC TBL 1017.2 HAS 200' FOR
 NON-SPRINKLERED AND THIS BUILDING IS NOT SPRINKLERED.
 PLEASE CORRECT.
  
 4) RESOLVED. THE EXIT ACCESS TRAVEL DISTANCE FROM THE
 WORK ROOM SHOULD BE SHOWN FROM THE MOST REMOTE CORNER
 OF THE STORAGE ROOM. FBC 1017.3 MEASUREMENT. EXIT
 ACCESS TRAVEL DISTANCE SHALL BE MEASURED FROM THE MOST
 REMOTE POINT WITHIN A STORY ALONG THE NATURAL AND
 UNOBSTRUCTED PATH OF HORIZONTAL AND VERTICAL EGRESS
 TRAVEL TO THE ENTRANCE TO AN EXIT.
  
 5) RESOLVED. ON SHEET CH-LS-0.1, THE OCCUPANCY
 SEPARATION REQUIREMENTS SPECIFY FBC TBL. 508.4. THIS
 TABLE IS FOR SEPARATED OCCUPANCIES. SINCE YOU DO NOT
 SPECIFY AND FIRE RATED WALLS ON THE PLANS, IT APPEARS
 THAT YOU WISH TO USE NON-SEPARATED OCCUPANCIES. THE
 SECTION THAT WOULD APPLY TO THIS PROJECT WOULD BE FBC
 508.3 FOR NON-SEPARATED OCCUPANCIES.
  
 6) RESOLVED. THE BUILDING SECTIONS ON SHEET CH-2.2 ARE
 INCORRECTLY TAGGED AS BEING ON SHEET CH-3.2. THESE
 SECTION ARE ACTUALLY ON SHEET CH-3.3. PLEASE CORRECT.
  
 7) RESOLVED. PLEASE SHOW THE WHEEL CHAIR TURNING RADIUS
 SPACE IN THE BATHROOMS. FBC ACCESSIBILITY 304.3
  
 8) RESOLVED. SHOW THE REQUIRED ACCESSIBLE ACCESS TO THE
 EXERCISE EQUIPMENT. FBC ACCESSIBILITY 1004.1 CLEAR
 FLOOR SPACE. EXERCISE MACHINES AND EQUIPMENT SHALL HAVE
 A CLEAR FLOOR SPACE COMPLYING WITH 305 POSITIONED FOR
 TRANSFER OR FOR USE BY AN INDIVIDUAL SEATED IN A
 WHEELCHAIR. CLEAR FLOOR OR GROUND SPACES REQUIRED AT
 EXERCISE MACHINES AND EQUIPMENT SHALL BE PERMITTED TO
 OVERLAP.
  
 9) RESOLVED. THE DOOR TO THE WORK ROOM DOES NOT APPEAR
 TO HAVE THE REQUIRED MINIMUM 18" ON THE PULL SIDE. FBC
 ACCESSIBILITY 404.2.4.1 SWINGING DOORS AND GATES SHALL
 HAVE MANEUVERING CLEARANCES COMPLYING WITH TABLE
 404.2.4.1.
  
 10) RESOLVED. SHOW COMPLIANCE WITH FBC 1210.2.2 WALLS
 AND PARTITIONS. WALLS AND PARTITIONS WITHIN 2 FEET (610
 MM) OF SERVICE SINKS, URINALS AND WATER CLOSETS SHALL
 HAVE A SMOOTH, HARD, NONABSORBENT SURFACE, TO A HEIGHT
 OF NOT LESS THAN 4 FEET (1219 MM) ABOVE THE FLOOR, AND
 EXCEPT FOR STRUCTURAL ELEMENTS, THE MATERIALS USED IN
 SUCH WALLS SHALL BE OF A TYPE THAT IS NOT ADVERSELY
 AFFECTED BY MOISTURE.
  
 11) DEFERRED. FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT
 APPROVALS FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT
 ROOFING MATERIALS, WINDOWS (GLASS TYPES), STRUCTURAL
 MULLIONS AND EXTERIOR DOOR TYPES. THESE ITEMS CAN BE
 DEFERRED IF REQUESTED, HOWEVER, THE DOCUMENTS MUST BE
 SUBMITTED AND APPROVED BY THE BUILDING DEPARTMENT
 BEFORE THEY CAN BE INSTALLED. ONLY ONE SET IS REQUIRED
 TO BE UPLOADED FOR ELECTRONICALLY SUBMITTED DOCUMENTS.
  
 12) DEFERRED. FBC 107.3.4 SUBMIT TRUSS DRAWINGS, TRUSS
 LAYOUT PLANS, AND SHOP DRAWINGS FROM OTHER DELEGATE
 ENGINEERS FOR REVIEW.
  
 13) CORRECTION REQUIRED. [SHEET CH-LS-0.1 UNDER
 DEFERRED SUBMITTALS THERE ARE SOME ITEMS THAT ARE NOT
 CORRECT. THE DEFERRED SUBMITTALS CAN BE SUBMITTED TO
 THE BUILDING DEPARTMENT FOR REVIEW WITH THE PROPER
 SUBMITTAL FORM AS A NO FEE SUBMITTAL. THE ROOF COVERING
 WILL REQUIRE A ROOFING SUB-PERMIT THAT CAN BE APPLIED
 FOR AFTER THE ROOFING PRODUCT APPROVALS HAVE BEEN
 REVIEWED AND APPROVED BY THE BUILDING DEPARTMENT. THE
 WINDOWS, DOORS AND STOREFRONTS ARE COVERED UNDER THE
 BUILDING PERMIT AND DO NOT REQUIRE SEPARATE PERMITS.
 THE ONLY THING LISTED THAT REQUIRES A SEPARATE PERMIT
 IS THE LOW VOLTAGE.] FBC 107.3.4.1 DEFERRED SUBMITTALS.
 FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS
 ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE
 NOT SUBMITTED AT THE TIME OF THE APPLICATION AND THAT
 ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 14) RESOLVED. ART IN PUBLIC PLACES
 THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES
 ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR
 NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT
 APPLICATION WAS SUBMITTED AFTER 6/29/14, AND THE TOTAL
 PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $750,000 WILL NEED TO COMPLY WITH THIS ORDINANCE.
 PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND
 CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V,
 ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION
 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL
 PROJECT CONSTRUCTION COST.
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
 FOR INFORMATION PLEASE CONTACT: MS. SYBILLE WELTER, ART
 IN PUBLIC PLACES COORDINATOR AT 822-1515 OR E-MAIL:
 [email protected]
  
 15) RESOLVED. [THE CONSTRUCTION COSTS IN THE TAKEOFF
 THAT WAS PROVIDED OF $1,153,100.00 ONLY INCLUDES THE
 COSTS TO CONSTRUCT THE BUILDING.] IN ORDER TO AVOID
 PAYING DOUBLE, PLEASE PROVIDE A COST BREAK DOWN FOR THE
 ITEMS INCLUDED WITH THIS PERMIT THAT DO NOT REQUIRE
 SEPARATE PERMITS AND FEES. FBC 109.3 BUILDING PERMIT
 VALUATION. FOR PERMITTING PURPOSES, VALUATION OF
 BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE
 TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL,
 INTERIOR FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND
 DESIGN FEES, MARKETING COSTS, OVERHEAD AND PROFIT;
 EXCLUDING ONLY LAND VALUE. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT,
 MEANS, ETC.), AS PUBLISHED BY INTERNATIONAL CODE
 CONGRESS. FINAL BUILDING PERMIT VALUATION SHALL BE SET
 BY THE BUILDING OFFICIAL.
  
 SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE
 REQUIRED FOR:
 LIGHT POLES/SITE LIGHTING
 FIRE ALARM
 FIRE SPRINKLER
 LOW VOLTAGE
 ACCESS
 LANDSCAPING
 IRRIGATION
 PARKING LOT
 SWIMMING POOLS
 GENERATORS
 ALL OTHER ITEMS OTHER THAN BMEP
  
 16) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-11-17 Cont ID  
Sent By rmcdouga Date 2020-11-17 Time 12:02 Rev Time 0.00
Received By rmcdouga Date 2020-11-17 Time 07:13 Sent To  
Notes
2020-11-16 10:55:35PLAN
 REVIEW COMMENTS
  
 CLUBHOUSE
 A-3 OCCUPANCY
 TYPE V-B, UN-SPRINKLERED
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) ACCORDING TO THE FLOOD INSURANCE RATE MAP WHICH WAS
 ADOPTED ON OCTOBER 5, 2017 AND IS APPLICABLE TO THIS
 PROJECT, THE STRUCTURE IS IN AN AE FLOOD ZONE WHICH IS
 A SPECIAL FLOOD HAZARD AREA. THE FLOOD ZONE IS AE AND
 THE BFE IS 14' NAVD88. THE REQUIRED DFE IS 16' NAVD88.
 THE BUILDING AND ALL OF THE EEQUIPMENT SERVICING IT ARE
 REQUIRED TO BE AT OR ABOVE THE DFE, 16' NAVD88. AS OF
 OCTOBER 5TH, 2017, THE CITY HAS ADOPTED NEW FLOOD
 INSURANCE RATE MAPS WHICH USE NAVD 88 AS THE VERTICAL
 DATUM. THE CITY ALSO ADOPTED A 2' FREEBOARD WHICH
 REQUIRES THE FINISH FLOOR AND EQUIPMENT TO BE A MINIMUM
 OF TWO FEET ABOVE THE BFE. SPECIFY ALL ELEVATIONS IN
 NAVD 88. THREE ELEVATION CERTIFICATES ARE REQUIRED TO
 BE SUBMITTED. 1) A PRE-CONSTRUCTION ELEVATION
 CERTIFICATE BASED ON THE CONSTRUCTION PLANS IS REQUIRED
 BEFORE THE PERMIT IS ISSUED. 2) A BUILDING UNDER
 CONSTRUCTION ELEVATION CERTIFICATE WHEN FIRST FLOOR
 SLABS ARE POURED. 3) A FINISHED CONSTRUCTION ELEVATION
 WHEN THE JOB IS COMPLETE INCLUDING LANDSCAPING. THE
 FINAL ELEVATION CERTIFICATE IS REQUIRED TO BE SUBMITTED
 AND APPROVED BEFORE THE C.O. WILL BE ISSUED.
  
 2) SPECIFY THE FINISH FLOOR ELEVATION ON THE
 ARCHITECTURAL PLANS. FBC 107.2.1
  
 3) THE LIFE SAFETY LEGEND ON SHEET CH-LS-0.1 HAS THE
 TRAVEL DISTANCE AS 200' FOR PROTECTED WITH AUTOMATIC
 FIRE SPRINKLERS. FBC TBL 1017.2 HAS 200' FOR
 NON-SPRINKLERED AND THIS BUILDING IS NOT SPRINKLERED.
 PLEASE CORRECT.
  
 4) THE EXIT ACCESS TRAVEL DISTANCE FROM THE WORK ROOM
 SHOULD BE SHOWN FROM THE MOST REMOTE CORNER OF THE
 STORAGE ROOM. FBC 1017.3 MEASUREMENT. EXIT ACCESS
 TRAVEL DISTANCE SHALL BE MEASURED FROM THE MOST REMOTE
 POINT WITHIN A STORY ALONG THE NATURAL AND UNOBSTRUCTED
 PATH OF HORIZONTAL AND VERTICAL EGRESS TRAVEL TO THE
 ENTRANCE TO AN EXIT.
  
 5) ON SHEET CH-LS-0.1, THE OCCUPANCY SEPARATION
 REQUIREMENTS SPECIFY FBC TBL. 508.4. THIS TABLE IS FOR
 SEPARATED OCCUPANCIES. SINCE YOU DO NOT SPECIFY AND
 FIRE RATED WALLS ON THE PLANS, IT APPEARS THAT YOU WISH
 TO USE NON-SEPARATED OCCUPANCIES. THE SECTION THAT
 WOULD APPLY TO THIS PROJECT WOULD BE FBC 508.3 FOR
 NON-SEPARATED OCCUPANCIES.
  
 6) THE BUILDING SECTIONS ON SHEET CH-2.2 ARE
 INCORRECTLY TAGGED AS BEING ON SHEET CH-3.2. THESE
 SECTION ARE ACTUALLY ON SHEET CH-3.3. PLEASE CORRECT.
  
 7) PLEASE SHOW THE WHEEL CHAIR TURNING RADIUS SPACE IN
 THE BATHROOMS. FBC ACCESSIBILITY 304.3
  
 8) SHOW THE REQUIRED ACCESSIBLE ACCESS TO THE EXERCISE
 EQUIPMENT. FBC ACCESSIBILITY 1004.1 CLEAR FLOOR SPACE.
 EXERCISE MACHINES AND EQUIPMENT SHALL HAVE A CLEAR
 FLOOR SPACE COMPLYING WITH 305 POSITIONED FOR TRANSFER
 OR FOR USE BY AN INDIVIDUAL SEATED IN A WHEELCHAIR.
 CLEAR FLOOR OR GROUND SPACES REQUIRED AT EXERCISE
 MACHINES AND EQUIPMENT SHALL BE PERMITTED TO OVERLAP.
  
 9) THE DOOR TO THE WORK ROOM DOES NOT APPEAR TO HAVE
 THE REQUIRED MINIMUM 18" ON THE PULL SIDE. FBC
 ACCESSIBILITY 404.2.4.1 SWINGING DOORS AND GATES SHALL
 HAVE MANEUVERING CLEARANCES COMPLYING WITH TABLE
 404.2.4.1.
  
 10) SHOW COMPLIANCE WITH FBC 1210.2.2 WALLS AND
 PARTITIONS. WALLS AND PARTITIONS WITHIN 2 FEET (610 MM)
 OF SERVICE SINKS, URINALS AND WATER CLOSETS SHALL HAVE
 A SMOOTH, HARD, NONABSORBENT SURFACE, TO A HEIGHT OF
 NOT LESS THAN 4 FEET (1219 MM) ABOVE THE FLOOR, AND
 EXCEPT FOR STRUCTURAL ELEMENTS, THE MATERIALS USED IN
 SUCH WALLS SHALL BE OF A TYPE THAT IS NOT ADVERSELY
 AFFECTED BY MOISTURE.
  
 11) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT
 ROOFING MATERIALS, WINDOWS (GLASS TYPES), STRUCTURAL
 MULLIONS AND EXTERIOR DOOR TYPES. THESE ITEMS CAN BE
 DEFERRED IF REQUESTED, HOWEVER, THE DOCUMENTS MUST BE
 SUBMITTED AND APPROVED BY THE BUILDING DEPARTMENT
 BEFORE THEY CAN BE INSTALLED. ONLY ONE SET IS REQUIRED
 TO BE UPLOADED FOR ELECTRONICALLY SUBMITTED DOCUMENTS.
  
 12) FBC 107.3.4 SUBMIT TRUSS DRAWINGS, TRUSS LAYOUT
 PLANS, AND SHOP DRAWINGS FROM OTHER DELEGATE ENGINEERS
 FOR REVIEW.
  
 13) FBC 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES
 OF THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS
 THOSE PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT
 THE TIME OF THE APPLICATION AND THAT ARE TO BE
 SUBMITTED TO THE BUILDING OFFICIAL WITHIN A SPECIFIED
 PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE
 PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR
 DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING
 OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE
 IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING.
 THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED
 UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN
 APPROVED BY THE BUILDING OFFICIAL.
  
 14) ART IN PUBLIC PLACES
 THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES
 ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR
 NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT
 APPLICATION WAS SUBMITTED AFTER 6/29/14, AND THE TOTAL
 PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $750,000 WILL NEED TO COMPLY WITH THIS ORDINANCE.
 PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND
 CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V,
 ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION
 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL
 PROJECT CONSTRUCTION COST.
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
 FOR INFORMATION PLEASE CONTACT: MS. SYBILLE WELTER, ART
 IN PUBLIC PLACES COORDINATOR AT 822-1515 OR E-MAIL:
 [email protected]
  
 15) IN ORDER TO AVOID PAYING DOUBLE, PLEASE PROVIDE A
 COST BREAK DOWN FOR THE ITEMS INCLUDED WITH THIS PERMIT
 THAT DO NOT REQUIRE SEPARATE PERMITS AND FEES. FBC
 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE
 REQUIRED FOR:
 LIGHT POLES/SITE LIGHTING
 FIRE ALARM
 FIRE SPRINKLER
 LOW VOLTAGE
 ACCESS
 LANDSCAPING
 IRRIGATION
 PARKING LOT
 SWIMMING POOLS
 GENERATORS
 ALL OTHER ITEMS OTHER THAN BMEP
  
 16) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2021-03-24 Cont ID  
Sent By jleahy Date 2021-03-24 Time 07:58 Rev Time 0.00
Received By jleahy Date 2021-03-24 Time 07:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2021-03-22 Cont ID  
Sent By equinone Date 2021-03-22 Time 10:59 Rev Time 0.00
Received By equinone Date 2021-03-22 Time 10:21 Sent To  
Notes
2021-03-22 11:04:23CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 NEW COMMENT:
  
 1) NEW SHEET CH -0.0 INDEX OF DRAWINGS: NEWLY REVISED
 SHEET LISTS TWO ADDITIONAL ELECTRICAL DRAWINGS (E-1.0,
 E-1-1) THAT HAVE NOT BEEN UPLOADED. PLEASE CLARIFY AND
 UPLOAD MISSING DRAWINGS IF NEEDED.
  
 RESPONSE NARRATIVE FROM 3/11/2021 INDICATES THAT COVER
 SHEET HAS BEEN CORRECTED AND THAT E.1.0 HAS BEEN
 REMOVED AND A NEW E1.-1 HAS BEEN UPLOADED AS PART OF
 THE NEW SUBMITAL. THE E.1-1 DRAWING IS STILL MISSING (I
 COULD NOT FIND IT). PLEASE CLARIFY OR UPLOAD THE E.1-1
 DRAWING THAT IS MISSING.
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
  
 ENRIQUE QUINONEZ P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2021-02-08 Cont ID  
Sent By equinone Date 2021-02-08 Time 14:28 Rev Time 0.00
Received By equinone Date 2021-02-08 Time 09:44 Sent To  
Notes
2021-02-08 14:28:41CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 NEW COMMENT:
  
 1) NEW SHEET CH -0.0 INDEX OF DRAWINGS: NEWLY REVISED
 SHEET LISTS TWO ADDITIONAL ELECTRICAL DRAWINGS (E-1.0,
 E-1-1) THAT HAVE NOT BEEN UPLOADED. PLEASE CLARIFY AND
 UPLOAD MISSING DRAWINGS IF NEEDED.
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
  
 ENRIQUE QUINONEZ P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-11-25 Cont ID  
Sent By equinone Date 2020-11-25 Time 16:51 Rev Time 0.00
Received By equinone Date 2020-11-25 Time 15:39 Sent To  
Notes
2020-11-25 16:51:38CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED.
  
 1) PLEASE SHOW LOCATION OF PANEL M. IS THIS PANEL
 WITHIN THE CLUBHOUSE OR LOCATED DETACHED FROM THE
 STRUCTURE? FCB 107
 2) GROUNDING ELECTRODE CONDUCTOR FROM METER TO PANEL CH
 IS TOO SMALL. IT SHOULD BE BASED ON THE EQUIVALENT SIZE
 OF 1000 KCMIL (2 SETS OF 4#500 KCMIL AL), TABLE 250.66
 NEC
 3) RISER DIAGRAM SHOWS PANEL M WITH A GROUND CONNECTED
 TO THE GROUNDING SYSTEM FOR MAIN SERVICE. IF PANEL M IS
 LOCATED ON A DETACHED STRUCTURE, THEN IT NEEDS TO BE
 GROUNDED AS PER NEC 250.32 WITH ITS OWN GROUNDING
 ELECTRODE AND GROUNDING ELECTRODE CONDUCTOR. IF PANEL M
 IS LOCATED WITHIN THE CLUBHOUSE STRUCTURE IT NEEDS TO
 BE GROUNDED WITH AN EQUIPMENT GROUNDING CONDUCTOR AS
 PART OF THE FEEDER FROM PANEL CH. NEC TABLE 250.66, NEC
 250.32.
 4) PLEASE SHOW FEEDER SIZE (INCLUDE GROUNDING EQUIPMENT
 CONDUCTOR) FROM PANEL CH TO PANEL M. FCB 107
 5) PANEL M IS SHOWN AS MLO ON PANEL SCHEDULE, BUT RISER
 DIAGRAM INDICATES A 200 A MCB. PLEASE CORRECT
 DISCREPANCIES. FCB 107
 6) PANEL SCHEDULE CH DOES NOT HAVE INFORMATION ON
 BREAKER SIZE AND FEEDER FOR PANEL M AND THIS
 INFORMATION IS NOT PROVIDED ON RISER DIAGRAM. FCB 107
 7) PANEL CH: PLEASE INCLUDE WIRE (INCLUDING GROUNDING
 EQUIPMENT CONDUCTOR), CONDUIT SIZES, BREAKER SIZES FOR
 ALL CH UNITS. CONDUCTORS CAN BE INDICATED ON POWER PLAN
 IF MORE CONVENIENT. FCB 107
 8) PANEL SCHEDULE M: PLEASE INCLUDE WIRE AND CONDUIT
 SIZES (INCLUDING GROUNDING EQUIPMENT CONDUCTOR) FOR ALL
 AC AND CU UNITS. CONDUCTORS CAN BE INDICATED ON POWER
 PLAN TOO IF MORE CONVENIENT. FCB 107
 9) PLEASE SUBMIT SHORT CIRCUIT CALCULATIONS AND
 AVAILABLE FAULT CURRENTS FOR PANELS CH AND M NEC 110.24
 10) PANEL SCHEDULE M HAS A NOTE SHOWING A PANEL PV
 CALCULATION. THIS PANEL IS NOT SHOWN ANYWHERE ELSE AND
 IS NOT PART OF THE RISER DIAGRAM. THIS LOAD IS NOT
 INCLUDED IN ANY OF THE LOAD CALCULATIONS EITHER. PLEASE
 CLARIFY. FCB 107
 11) PLEASE SEE COMMENTS FROM BUILDING REVIEWER
 REGARDING STRUCTURE BEING ON A SPECIAL FLOOD ZONE AND
 REQUIREMENTS FOR EQUIPMENT LOCATION.
  
  
 END OF COMMENTS.
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 SINCERELY,
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2020-11-05 Cont ID  
Sent By rrossano Date 2020-11-05 Time   Rev Time  
Received By rrossano Date 2020-11-05 Time   Sent To  
Notes
2020-11-05 08:18:31ONSITE UTILITIES ARE PRIVATE. REVIEWING OVERALL
 ENGINEERING SUBMITTAL E20080019.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2021-03-16 Cont ID  
Sent By pleduc Date 2021-03-16 Time   Rev Time 0.00
Received By pleduc Date 2021-03-16 Time 10:13 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-01-25 Cont ID  
Sent By pleduc Date 2021-01-25 Time   Rev Time 0.00
Received By pleduc Date 2021-01-25 Time 12:57 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-11-18 Cont ID  
Sent By pleduc Date 2020-11-18 Time   Rev Time 0.00
Received By pleduc Date 2020-11-18 Time 13:31 Sent To  
Notes
2020-11-18 13:32:38FIRE PROVISO:
  
 ALL UNDERGROUND FIRE LINES SHALL BE INSTALLED UNDER
 SEPARATE PERMIT AND SHOP DRAWINGS PER NFPA 24
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-03-24 Cont ID  
Sent By lmarchan Date 2021-03-24 Time 13:59 Rev Time 0.00
Received By lmarchan Date 2021-03-12 Time 15:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-02-25 Cont ID  
Sent By lcrespo Date 2021-02-25 Time 14:44 Rev Time 0.00
Received By lcrespo Date 2021-01-20 Time 10:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-12-11 Cont ID  
Sent By cpuell Date 2020-12-11 Time 14:59 Rev Time 0.00
Received By cpuell Date 2020-10-23 Time 15:50 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2021-04-15 Cont ID  
Sent By lmarchan Date 2021-04-15 Time 15:21 Rev Time 0.00
Received By lmarchan Date 2021-03-24 Time 13:59 Sent To  
Notes
2021-03-25 11:18:47RECEIPT MU-2021-16220 - $5751.15 - PAID
2021-03-24 13:59:263/24/21 EMAILED IMPACT OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-11-16 Cont ID  
Sent By rmcdouga Date 2020-11-16 Time 10:41 Rev Time 0.00
Received By rmcdouga Date 2020-11-16 Time 10:39 Sent To  
Notes
2020-11-16 10:41:32PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2021-03-23 Cont ID  
Sent By medwards Date 2021-03-23 Time 09:08 Rev Time 0.00
Received By medwards Date 2021-03-23 Time 09:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-02-05 Cont ID  
Sent By medwards Date 2021-02-05 Time 13:37 Rev Time 0.00
Received By medwards Date 2021-02-05 Time 10:57 Sent To  
Notes
2021-02-05 13:38:122ND REVIEW FBC-2020 MECHANICAL
 PERMIT-20100729
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2020
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2020
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) FBC M 403.3.1.1 TELLS US THAT WE MUST USE TABLE
 403.3.1.1 AND NOT THE OCCUPANT COUNT FOUND ON THE
 ARCHITECTURAL SHEETS. PLEASE SUBMIT OUTDOOR AIR
 CALCULATIONS BASED ON THE USE OF SPACE AND TABLE
 403.3.1.1. PLEASE IDENTIFY OCCUPANCY CLASSIFICATION FOR
 EACH USE OF SPACE INCLUDING THE THEATER. THE
 CALCULATIONS SUBMITTED IN THIS CYCLE WERE BASED ON THE
 OCCUPANT COUNT FROM THE ARCHITECTURAL SHEETS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-11-10 Cont ID  
Sent By medwards Date 2020-11-10 Time 12:55 Rev Time 0.00
Received By medwards Date 2020-11-10 Time 10:38 Sent To  
Notes
2020-11-10 12:55:501ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20100729
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE IDENTIFY THE ROOM NAMES THAT ARE USED FOR THE
 OUTDOOR AIR CALCULATIONS FOR AC-FIT1 & FIT2. PLEASE
 CALCULATE THE OUTDOOR AREA FOR THE WEIGHT ROOM AND
 AEROBICS ROOM USING THE NUMBERS PROVIDED UNDER (SPORTS
 AND AMUSEMENT) FBC M TABLE 403.3.1.1
  
 2) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS FOR THE
 ENTIRE BUILDING, PROVIDE OUTDOOR AIR CALCULATIONS BASED
 ON THE USE OF SPACE IN THIS BUILDING. FBC M TABLE
 403.3.1.1
  
 3) AC CLUB-2; SHEET MCH-3 INDICATES THE TOTAL AIR
 SUPPLY IS 1400 CFM. SHEET MCH-1 INDICATES THE TOTAL
 CFM?S IS 1,835. PLEASE SHOW WHERE THE DIFFERENCES ARE.
 FBC EC M403.2
  
 4) AC CLUB-1; SHEET MCH-3 INDICATES THE TOTAL AIR
 SUPPLY IS 1400 CFM. SHEET MCH-1 INDICATES THE TOTAL
 CFM?S IS 1800. PLEASE SHOW WHERE THE DIFFERENCES ARE.
 FBC EC M403.2
  
 5) SHEET MCH-1; UNITS AC-1 AND AC-CLUB2 APPEAR TO HAVE
 A RETURN COMING FROM THE A/V CLOSET. PLEASE SHOW HOW
 THIS WOULD MEET FBC M 601.5 (7)
  
 6) SHEET MCH-3 INDICATES THAT EF-1 HAS A TOTAL EXHAUST
 CFM RATE OF 50 AND IS CONTROLLED BY A LIGHT SWITCH.
 THIS WOULD NOT COMPLY WITH FBC M TABLE 403.3.1.1 (NOTE
 E)
  
 7) SHEET MCH-1 PLEASE SHOW CFM?S FOR THE SUPPLY AIR IN
 THE A/V CLOSET. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 3 Status P Date 2021-03-19 Cont ID  
Sent By rmcdouga Date 2021-03-19 Time 14:21 Rev Time 0.00
Received By rmcdouga Date 2021-03-19 Time 14:21 Sent To  
Notes
2021-03-19 14:26:03THE PRE-CONSTRUCTION E.C. HAS BEEN ELECTRONICALLY
 SUBMITTED, REVIEWED AND APPROVED. THE UNDER
 CONSTRUCTION AND FINAL ELEVATION CERTIFICATES WILL NEED
 TO BE SUBMITTED AND APPROVED.

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status F Date 2021-02-17 Cont ID  
Sent By rmcdouga Date 2021-02-17 Time 08:31 Rev Time 0.00
Received By rmcdouga Date 2021-02-17 Time 08:31 Sent To  
Notes
2021-02-17 08:31:25THIS PROJECT IS LOCATED IN A SPECIAL FLOOD HAZARD AREA
 (SFHA), FLOOD ZONE AE. SEE BUILDING REVIEW COMMENTS FOR
 ADDITIONAL INFORMATION.

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2020-11-16 Cont ID  
Sent By rmcdouga Date 2020-11-16 Time 10:54 Rev Time 0.00
Received By rmcdouga Date 2020-11-16 Time 10:54 Sent To  
Notes
2020-11-16 10:59:21THIS PROJECT IS LOCATED IN A SPECIAL FLOOD HAZARD AREA
 (SFHA), FLOOD ZONE AE. SEE BUILDING REVIEW COMMENTS FOR
 ADDITIONAL INFORMATION.

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-03-19 Cont ID  
Sent By lcrespo Date 2021-03-19 Time 15:20 Rev Time 0.00
Received By lcrespo Date 2021-03-19 Time 14:25 Sent To  
Notes
2021-03-19 15:21:0503/19/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-02-25 Cont ID  
Sent By lcrespo Date 2021-02-25 Time 14:41 Rev Time 0.00
Received By lcrespo Date 2021-02-25 Time 12:44 Sent To  
Notes
2021-02-25 14:43:0102/25/21 2ND PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET CH-5.1;
  
 A) PLEASE PROVIDE DIMENSIONS FOR ALL FIXTURE CLEARANCES
 PER WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 B) DONE.
  
 C) DONE.
  
 D) THE LAV ON THE OPEN FLOOR NEEDS TO SHOW THE CLEAR
 FLOOR SPACE NEEDS TO SHOW A FORWARD APPROACH PER THE
 2017 FBC SEC. ACC 602.2 CLEAR FLOOR SPACE.
  
 E) DONE, NEEDS DIMENSIONS PLEASE,
  
 F) DONE.
  
 G) DONE.
  
 H) NEW, PLEASE REMOVE THE HASH LINE ON THE RESTROOM AND
 DRINKING FOUNTAIN OF THE CLEAR FLOOR SPACE FOR CLARITY
 PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 I) TOILET ARE DIMENSIONS? AS 1'-6" PLEASE ADD TO IT THE
 1'- 4" DIMENSION PER THE 2017 FLORIDA ACC.
  
 2. DONE.
  
 3. DONE.
  
 4. DONE.
  
 5. ON SHEET PCH-2:
  
 A) PLEASE PROVIDE THE SIZE OF THE JANITORS SINK UNDER
 SLAB WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 B) DONE.
  
 C) DONE, THE INLINE VACUUM BREAKER IS SHOW UNDERGROUND
 AND IT NEED TO BE ACCESSIBLE.
  
 D) DONE.
  
 E) PLEASE ADD TO DETAIL THAT VALVES SHALL COMPLY WITH
 ASSE 1070 OR CSA B125.3 PER THE 2017 FBC SEC. 416.5
 TEMPERED WATER FOR PUBLIC HAND-WASHING FACILITIES.
  
 F) PLEASE SHOW SHUT OFF VALVE ON ISOMETRIC PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-12-01 Cont ID  
Sent By lcrespo Date 2020-12-01 Time 18:04 Rev Time 0.00
Received By lcrespo Date 2020-11-04 Time 11:06 Sent To  
Notes
2020-12-02 11:26:1812/01/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET CH-5.1;
 A) PLEASE GIVE DIMENSIONS FOR FIXTURE CLEARANCES PER
 FLORIDA BUILDING CODE AND FLORIDA ACCESSIBILITY CODE.
  
 B) THE GRAB BARS ARE SHOWN 36? TO CENTER AND THEY NEED
 TO BE 36? TO TOP OF THE GRIPPING SURFACE PER THE 2017
 FBC ACC SEC. 609.4.
  
 C) THE DETAIL ON THE ACCESSIBILITY LEGEND FOR THE
 MIRROR SHOWS IT TO THE BOTTOM AND IT NEEDS TO BE TO THE
 REFLECTIVE BOTTOM EDGE PER THE 2017 FBC ACC SEC. 603.3.
  
 D) THE LAV ON THE OPEN FLOOR NEEDS TO SHOW THE CLEAR
 FLOOR SPACE OF 30? X 48? PER THE 2017 FBC SEC. ACC
 305.3.
  
 E) THE DRINKING FOUNTAIN NEEDS TO SHOW THE CLEAR FLOOR
 SPACE OF 30? X 48? PER THE 2017 FBC SEC. ACC 305.3.
  
 F) PLEASE SHOW DETAIL FOR CLEAR FLOOR SPACE IN THE
 KITCHEN AREA OF 30? X 48? PER THE 2017 FBC SEC. ACC
 305.3.
  
 G) PLEASE SHOW THAT THE SERVICE SINK (MOP SINK)
 SURROUNDING THE WALL HAS A NON-ABSORBENT SURFACE IN
 ACCORDANCE WITH THE 2017 FBC BUILDING SEC. 1210.2.2.
 PLEASE MAKE A NOTE ON THIS SHEET.
  
 2. ON SHEET A10.1 PLEASE REMOVE SHOWERS CLEAR FLOOR
 SPACE NOT USED IN THIS BUILDING AND ANY OTHER DETAILS
 THAT DO NOT APPLY TO THIS BUILDING PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION.
  
 3. ON SHEET PCH-1 AND PCH-2 PLEASE SHOW TRAP PRIMER AND
 GIVE REFERENCE TO THE PAGE IF DETAIL IS AVAILABLE PER
 THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 4. PLEASE PROVIDE MANUFACTURE SPECIFICATION FOR
 TANK-LESS HEATER PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 5. ON SHEET PCH-2:
 A) PLEASE PROVIDE HOT AND WATER TO THE MOP SINK ON THE
 ISOMERIC PER THE 201 FBC SEC. P 607.4.
  
 B) PLEASE SHOW SIZING FOR ALL WATER LINE RISER AND
 LABEL ALL AIR ARRESTORS PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.5.1.3 (13) COMMERCIAL PLUMBING.
  
 C) WATER RAN UNDERGROUND NEED TO BE INSULATED WITH A
 MINIMUM R-3 PER THE 2017 FBC SEC. RE 403.5.3.
  
 D) ICEMAKER NOT SHOWN ON ISOMETRIC PLEASE SHOW A
 SHUT-OFF VALVE AND IT SHALL BE EQUIPPED WITH AN IN-LINE
 VACUUM BREAKER THAT COMPLIES WITH ASSE 1024 PER THE
 2017 FBC SEC. 608.13.10.
  
 E) PLEASE SHOW ON LAVS A TEMPERING DEVICE THAT CONFORMS
 TO ASSE 1070 OR CSA B125.3 PER THE 2017 FBC SEC. 416.5
 TEMPERED WATER FOR PUBLIC HAND-WASHING FACILITIES.
  
 F) DUE TO THE LOCATION OF THE HOSE BIBBS IN BATHROOMS,
 A SHUT OFF VALVE IS RECOMMENDED BUT NOT REQUIRED FOR
 MAINTENANCE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2021-02-17 Cont ID  
Sent By rmcdouga Date 2021-02-17 Time 08:32 Rev Time 0.00
Received By rmcdouga Date 2021-02-17 Time 08:31 Sent To  
Notes
2021-02-17 08:33:27ROOFING PRODUCT APPROVALS ARE BEING DEFERRED. THEY ARE
 REQUIRED TO BE SUBMITTED AND APPROVED BEFORE THE
 ROOFING SUB-PERMIT IS ISSUED.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2020-11-16 Cont ID  
Sent By rmcdouga Date 2020-11-16 Time 10:56 Rev Time 0.00
Received By rmcdouga Date 2020-11-16 Time 10:40 Sent To  
Notes
2020-11-16 10:42:18NO PRODUCT APPROVALS WERE SUBMITTED FOR THE ROOFING
 MATERIALS.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-03-19 Cont ID  
Sent By rmcdouga Date 2021-03-19 Time 14:33 Rev Time 0.00
Received By rmcdouga Date 2021-03-19 Time 14:33 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-02-05 Cont ID  
Sent By medwards Date 2021-02-05 Time 14:03 Rev Time 0.00
Received By medwards Date 2021-02-05 Time 13:38 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-11-10 Cont ID  
Sent By medwards Date 2020-11-10 Time 14:22 Rev Time 0.00
Received By medwards Date 2020-11-10 Time 10:56 Sent To  
Notes
2020-11-10 14:27:21DESIGNERS MUST PROVIDE DIGITALLY SIGNED AND SEALED
 DRAWINGS FOR THE FOLLOWING SHEETS: SOIL REPORT, SURVEY,
 COVER SHEET, C-107, C-171, C-172, C-173
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop Z ZONING
Rev No 3 Status P Date 2021-03-24 Cont ID  
Sent By jroach Date 2021-03-24 Time 11:43 Rev Time 0.00
Received By jroach Date 2021-03-24 Time 11:38 Sent To  
Notes
2021-03-24 11:43:28ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 03.24.2021
 PERMIT NO.: 20100729
 ________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. THE SCOPE OF THIS PERMIT REVIEW IS LIMITED TO THE
 ?CLUBHOUSE? ONLY. SEPARATE PERMITS REQUIRED FOR ALL
 OTHER BUILDINGS, SURROUNDING SITE WORK, FENCING,
 LANDSCAPING, IRRIGATION, ETC.
  
 2. THE BROADSTONE LAKESIDE RESIDENTIAL PLANNED
 DEVELOPMENT SHALL BE SUBJECT TO ALL DEVELOPMENT ORDER
 CONDITIONS AS OUTLINED IN RESOLUTION NO. 106-20, AND AS
 MAY BE AMENDED. ALL CONDITIONS OF APPROVAL IMPOSED BY
 RESOLUTION NO. 106-20, AS AMENDED, SHALL BE ADDRESSED
 WITHIN THE APPROPRIATE SPECIFIED TIMEFRAMES.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 2 Status F Date 2021-02-05 Cont ID  
Sent By jroach Date 2021-02-05 Time 11:46 Rev Time 0.00
Received By jroach Date 2021-02-05 Time 11:46 Sent To  
Notes
2021-02-05 11:46:44ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 02.05.2021
 PERMIT NO.: 20100729
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. [ SATISFIED ] - ALL LANDSCAPE PLANS, ETC. SHALL BE
 REMOVED FROM THE BUILDING PERMIT SUBMITTAL AND
 SUBMITTED AS PART OF SEPARATE PERMIT APPLICATIONS. THE
 ONLY PLANS THAT SHOULD BE SUBMITTED WITH THIS PERMIT
 APPLICATION ARE THOSE THAT ARE NECESSARY FOR THE REVIEW
 AND ISSUANCE OF THIS PERMIT. ALL PLANS ASSOCIATED WITH
 SEPARATE PERMITS SHOULD BE REMOVED FROM THE SUBMITTAL.
  
 2. [ NOT SATISFIED ] - AS MODIFICATIONS HAVE BEEN MADE
 SINCE ADOPTION OF THE DEVELOPMENT ORDER (RESOLUTION NO.
 106-20), A MINOR AMENDMENT SHALL BE SUBMITTED TO AND
 APPROVED BY THE DEVELOPMENT SERVICES DEPARTMENT ?
 PLANNING DIVISION. THIS IS WITH THE ASSUMPTION AND
 FUTURE CONFIRMATION THAT NONE OF THE CHANGES TRIGGER
 THE THRESHOLD FOR A MAJOR AMENDMENT, AS SPECIFIED IN
 THE CITY?S ZONING AND LAND DEVELOPMENT REGULATIONS.
  
 3. [ SATISFIED ] - PURSUANT TO RESOLUTION NO. 106-20,
 PRIOR TO THE ISSUANCE OF ANY BUILDING PERMIT:
  
 3.1. [ SATISFIED ] - THE DEVELOPER SHALL PAY TO THE
 CITY OF WEST PALM BEACH A CONTRIBUTION IN THE AMOUNT OF
 $30,000 TOWARD TO COST OF A SAFETY STUDY FOR VILLAGE
 BOULEVARD.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT - PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2020-12-11 Cont ID  
Sent By jroach Date 2020-12-11 Time 13:31 Rev Time 0.00
Received By jroach Date 2020-12-11 Time 13:31 Sent To  
Notes
2020-12-11 13:37:16ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 12.11.2020
 PERMIT NO.: 20100729
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. ALL LANDSCAPE PLANS, ETC. SHALL BE REMOVED FROM THE
 BUILDING PERMIT SUBMITTAL AND SUBMITTED AS PART OF
 SEPARATE PERMIT APPLICATIONS. THE ONLY PLANS THAT
 SHOULD BE SUBMITTED WITH THIS PERMIT APPLICATION ARE
 THOSE THAT ARE NECESSARY FOR THE REVIEW AND ISSUANCE OF
 THIS PERMIT. ALL PLANS ASSOCIATED WITH SEPARATE PERMITS
 SHOULD BE REMOVED FROM THE SUBMITTAL.
  
 2. AS MODIFICATIONS HAVE BEEN MADE SINCE ADOPTION OF
 THE DEVELOPMENT ORDER (RESOLUTION NO. 106-20), A MINOR
 AMENDMENT SHALL BE SUBMITTED TO AND APPROVED BY THE
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION.
 THIS IS WITH THE ASSUMPTION AND FUTURE CONFIRMATION
 THAT NONE OF THE CHANGES TRIGGER THE THRESHOLD FOR A
 MAJOR AMENDMENT, AS SPECIFIED IN THE CITY?S ZONING AND
 LAND DEVELOPMENT REGULATIONS.
  
 3. PURSUANT TO RESOLUTION NO. 106-20, PRIOR TO THE
 ISSUANCE OF ANY BUILDING PERMIT:
  
 3.1. THE DEVELOPER SHALL PAY TO THE CITY OF WEST PALM
 BEACH A CONTRIBUTION IN THE AMOUNT OF $30,000 TOWARD TO
 COST OF A SAFETY STUDY FOR VILLAGE BOULEVARD.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  