| 2020-10-16 17:46:29 | 1ST REVIEW FBC-2017 RES. FUEL GAS |
| | PERMIT- 20100548 |
| | 10/16/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) GAS RISER DRAWING: REFER TO SECTIONS G2412.3, |
| | G2412.4, G2413.1, & G2413.2 FBC RES. FUEL GAS. A |
| | COMPLETE REVIEW OF THE NEW GAS PIPING TO THE GENERATOR |
| | CANNOT BE ACCOMPLISHED WITHOUT A COMPLETE RISER DRAWING |
| | THAT INCLUDES THE BRANCH LINE TO THE POOL HEATER, AND |
| | THE BRANCH LINE TO THE INTERIOR APPLIANCES. SHOW THE |
| | TOTAL LENGTHS OF THE BRANCHES, AND THE TOTAL DEVELOPED |
| | LENGTH OF THE SYSTEM FROM THE METER TO THE MOST REMOTE |
| | OUTLET. YOU ARE INDICATING THE WATER HEATER AT 30,000 |
| | BTUH, HOWEVER THE EXISTING WATER HEATER IS A 75 GALLON |
| | HEATER PER PERMIT 02050842. THE TYPICAL LOAD SHOULD BE |
| | AROUND 75,000 BTUH. PLEASE CORRECT THE LOADS ON THE |
| | DRAWING. PLEASE NOTE THAT ACCORDING TO THE PIPE SIZING |
| | TABLE 402.4(3) FBC FG THAT YOU ARE USING THE TOTAL |
| | DEVELOPED LENGTH OF THE SYSTEM SHALL NOT EXCEED 40 FT. |
| | FOR A 1 IN. PIPE SUPPLYING A TOTAL LOAD OF 826,000 |
| | BTUH. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |