Plan Review Details - Permit 20100525
Plan Review Stops For Permit 20100525
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-12-03 Cont ID  
Sent By jgomez Date 2020-12-03 Time 17:29 Rev Time 0.00
Received By jgomez Date 2020-12-03 Time 15:36 Sent To  
Notes
2020-12-03 15:45:05BUILDING REVIEW APPROVED WITH PROVISO:
 1- PER EMAIL WITH JOHN ANNUNZIATA (JCA MANAGEMENT LLC)
 THE GARAGE WORK WAS EXCLUDED FROM THE SCOPE OF WORK OF
 THIS PERMIT APPLICATION. WORK WILL BE SUBMITTED UNDER A
 SEPARATE PERMIT APPLICATION AND PLANS.
  
 2-PROVIDE PRODUCT APPROVAL FOR:
 INSWING DOOR AS SHOWN ON PLANS FOR PARLOR, LIVING ROOM
 AND OFFICE AREAS. NOA 20-0427.05 SUBMITTED IS ONLY FOR
 OUTSWING DOORS.
  
 3-ARCHITECT TO REVIEW/APPROVE IN WRITING ABOVE PRODUCT
 APPROVAL.
  
  
 *******************************************************
 ******************************
  
 THU 12/3/2020 3:35 PM
 JOHN ANNUNZIATA
 JCA MANAGEMENT LLC
 (561)827-9599
  
 YES, LET'S VOID ALL THE GARAGE WORK AND CALL FOR A
 SEPARATE PERMIT PLEASE.
  
 ON THU, DEC 3, 2020 AT 3:24 PM JULIO GOMEZ
  WROTE:
 GOOD AFTERNOON MR. ANNUNZIATA,
 IF YOU WANT I CAN VOID ALL THE WORK IN THE GARAGE IN
 DRAWING A1.1 AND CALL FOR A SEPARATE PERMIT. THIS WAY I
 CAN APPROVE THE BUILDING REVIEW STOP. KEEP IN MIND THAT
 YOU STILL NEED THE HISTORIC REVIEW APPROVED.
 THANK YOU.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-12-01 Cont ID  
Sent By jgomez Date 2020-12-01 Time 11:10 Rev Time 0.00
Received By jgomez Date 2020-11-30 Time 17:26 Sent To  
Notes
2020-12-01 11:11:26RESIDENTIAL (R3) SECOND BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE.
  
  
 1-SHEET S1.1: GARAGE FLOOR PLAN:
 A)PROVIDE COMPLETE OPENING FRAMING DETAIL FOR NEW
 OVERHEAD GARAGE DOOR AND NEW FRENCH DOORS IN THE GUEST
 SUITE. HEADER DETAIL ON SAME SHEET IS INCOMPLETE. IT
 DOESN'T SPECIFY ALL FRAMING MEMBERS SIZES AND
 CONNECTORS. PROVIDE COMPLETE INFORMATION. SEC. 504 AND
 SEC. 506 FBC-EXISTING BUILDING. SEC. R601.2
 FBC-RESIDENTIAL.
  
 RESPONSE:
 HEADER DETAIL STILL INCOMPLETE. IT DOESN'T SHOW HOW THE
 LOADS ARE TRANSFERRED AS REQUIRED BY SEC. R601.2
 FBC-RESIDENTIAL. IT DOESN'T SPECIFY HOW THE 2X4 STUDS
 ARE FASTENED TO TRANSFER THE LOADS TO THE FLOOR AND
 CONSEQUENTLY TO THE FOOTING. THEE IS NOT CONNECTION
 SPECIFIED AT THE BOTTOM. ALSO, PROVIDE SPECIFIC
 SPECIFICATIONS FOR ALL THE STRAPS CONNECTING THE
 RAFTERS AND THE STUDS TO THE HEADER. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 B) OK
  
 2- REQUIRED HEATING. SEC. R303.10 FBC-RESIDENTIAL.
 SPECIFY HOW PROVIDING HEAT TO THE NEW GUEST SUITE.
 SEC. 504 AND SEC. 506 FBC-EXISTING BUILDING.
  
 RESPONSE:
 ARCHITECT'S RESPONSE LETTER STATES THAT "NO NEW GUEST
 SUITE- ALL EXISTING ROOMS, ONLY LABEL CHANGE".
 ACCORDING TO CITY RECORDS AND PALM BEACH PROPERTY
 APPRAISER, THIS STRUCTURE IS A GARAGE. THERE ARE NO
 CITY RECORDS FOR THE CONVERSION OF GARAGE TO ANY OTHER
 USE. THEREFORE, THIS IS CONSIDERED A PARTIAL CHANGE OF
 USE WHERE HALF OF THE GARAGE IS CHANGED TO LIVABLE
 SPACE. "ONLY A LABEL CHANGE" DOESN'T MAKE IT COMPLAINT.
 THAT IS WHY ALL THE COMMENTS ARE BASED ON THE PROPOSED
 USE. NEED TO SHOW COMPLIANCE WITH THE HEATING
 REQUIREMENTS.
  
 NEW COMMENT:
 PLANS WERE REVISED. NEW GARAGE FLOOR PLAN SHOWS A DOOR
 LEADING FROM THE GARAGE TO THE GUEST SUITE. THIS IS NOT
 ALLOWED. SEC. R302.5.1 FBC-RESIDENTIAL. REVISE AS
 REQUIRED.
  
  
 3- PLEASE SUBMIT A SEPARATE PERMIT APPLICATION FOR THE
 SEPARATE GARAGE/GUEST SUITE BUILDING. SAME PLANS CAN BE
 USED. SEPARATE PERMIT APPLICATIONS HELP TO COORDINATE
 INSPECTIONS FOR EACH BUILDING AND TO FACILITATE RECORDS
 RETENTION. SEC. 107.2.1.3 CITY AMENDMENTS.
 NOTE: PLEASE CONTACT ME TO EXPLAIN THIS. I CAN MAKE A
 COPY OF THE PERMIT APPLICATION TO GENERATE A NEW PERMIT
 NUMBER.
 THE IMPORTANT ISSUE OVER HERE IS FOR CONTRACTOR TO BE
 AWARE THAT THERE IS A SEPARATE PERMIT NUMBER FOR EACH
 STRUCTURE. THIS IS IMPORTANT WHEN CALLING FOR
 INSPECTIONS.
  
 RESPONSE:
 ARCHITECT'S RESPONSE LETTER STATES THAT "OWNER DELETED
 ALL WORK IN THE GARAGE (EXCEPT NEW OH DOOR ON THE NORTH
 ELEVATION)".
 A SEPARATE PERMIT APPLICATION STILL REQUIRED. THERE IS
 A PARTIAL CHANGE OF USE IN THIS STRUCTURE. SEE RESPONSE
 TO COMMENT #2 ABOVE.
  
 4- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL):
  
 A)OK
  
 B)OVERHEAD GARAGE DOOR.
 (NOT SUBMITTED YET)
  
 C)INSWING DOOR AS SHOWN ON PLANS FOR PARLOR, LIVING
 ROOM AND OFFICE AREAS. NOA 20-0427.05 SUBMITTED IS ONLY
 FOR OUTSWING DOORS.
  
 5- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS
 NOTE: COORDINATE ALSO WITH DOOR SCHEDULE ON SHEET A1.1.
 NOA'S TO MATCH NOA'S SUBMITTED TO AVOID
 CONFLICTS/DELAYS.
  
 6- OK
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-10-28 Cont ID  
Sent By jgomez Date 2020-10-28 Time 16:03 Rev Time 0.00
Received By jgomez Date 2020-10-28 Time 13:42 Sent To  
Notes
2020-10-28 16:04:35RESIDENTIAL (R3) BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
  
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR
 TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME
 OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
  
  
 NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE.
  
 1-SHEET S1.1: GARAGE FLOOR PLAN:
 A)PROVIDE COMPLETE OPENING FRAMING DETAIL FOR NEW
 OVERHEAD GARAGE DOOR AND NEW FRENCH DOORS IN THE GUEST
 SUITE. HEADER DETAIL ON SAME SHEET IS INCOMPLETE. IT
 DOESN'T SPECIFY ALL FRAMING MEMBERS SIZES AND
 CONNECTORS. PROVIDE COMPLETE INFORMATION. SEC. 504 AND
 SEC. 506 FBC-EXISTING BUILDING. SEC. R601.2
 FBC-RESIDENTIAL.
  
 B) PROVIDE INFILL FRAMING DETAIL FOR EXTERIOR WALL
 OPENINGS TO BE CLOSED.
 SPECIFY ALL FRAMING MEMBERS SIZES AND CONNECTORS,
 SHEATHING, INSULATION, FINISHES, ETC. SEC. 504 AND SEC.
 506 FBC-EXISTING BUILDING. SEC. R601.2 FBC-RESIDENTIAL.
  
 2- REQUIRED HEATING. SEC. R303.10 FBC-RESIDENTIAL.
 SPECIFY HOW PROVIDING HEAT TO THE NEW GUEST SUITE.
 SEC. 504 AND SEC. 506 FBC-EXISTING BUILDING.
  
 3- PLEASE SUBMIT A SEPARATE PERMIT APPLICATION FOR THE
 SEPARATE GARAGE/GUEST SUITE BUILDING. SAME PLANS CAN BE
 USED. SEPARATE PERMIT APPLICATIONS HELP TO COORDINATE
 INSPECTIONS FOR EACH BUILDING AND TO FACILITATE RECORDS
 RETENTION. SEC. 107.2.1.3 CITY AMENDMENTS.
 NOTE: PLEASE CONTACT ME TO EXPLAIN THIS. I CAN MAKE A
 COPY OF THE PERMIT APPLICATION TO GENERATE A NEW PERMIT
 NUMBER.
 THE IMPORTANT ISSUE OVER HERE IS FOR CONTRACTOR TO BE
 AWARE THAT THERE IS A SEPARATE PERMIT NUMBER FOR EACH
 STRUCTURE. THIS IS IMPORTANT WHEN CALLING FOR
 INSPECTIONS.
  
 4- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL):
  
 A)PVC DOUBLE HUNG WINDOWS NOA 17-0630.10 SUBMITTED
 EXPIRED ON SEPTEMBER 17,2020. NEED CURRENT PRODUCT
 APPROVAL.
  
 B)OVERHEAD GARAGE DOOR.
  
 5- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS
 NOTE: COORDINATE ALSO WITH DOOR SCHEDULE ON SHEET A1.1.
 NOA'S TO MATCH NOA'S SUBMITTED TO AVOID
 CONFLICTS/DELAYS.
  
 6- SCOPE OF WORK IS NOT CLEAR.
 ARE ALL THE WINDOWS AND ALL EXTERIOR DOORS GOING TO BE
 REPLACED OR NOT. FLOOR PLANS ON SHEET A1.1 SHOW THEM AS
 EXISTING (EX.) AND THERE IS NO INDICATION THAT THESE
 DOORS/WINDOWS ARE GOING TO BE REPLACED. BUT, ON THE
 OTHER HAND THERE ARE WINDOWS AND DOORS SKETCHES AND
 SCHEDULES SUBMITTED UNDER THE SUPPORTING DOCUMENTS.
 PLEASE CLARIFY/REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-10-24 Cont ID  
Sent By fgiaquin Date 2020-10-24 Time 11:02 Rev Time 0.00
Received By fgiaquin Date 2020-10-24 Time 09:25 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2020-12-11 Cont ID  
Sent By fmittner Date 2020-12-11 Time 11:08 Rev Time 0.00
Received By fmittner Date 2020-12-11 Time 11:08 Sent To  
Notes
2020-12-11 11:10:04WHITE FRAMES

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2020-10-29 Cont ID  
Sent By fmittner Date 2020-10-29 Time 14:54 Rev Time 0.00
Received By fmittner Date 2020-10-29 Time 14:54 Sent To  
Notes
2020-10-29 15:00:16WINDOW CHART PROPOSES 1/1 DOUBLE HUNG BUT CURRENT AND
 HISTORIC GRID PATTERN IS 6/1.
  
 QUESTIONS, CONTACT:
 FRIEDERIKE MITTNER, CITY HISTORIC PRESERVATION PLANNER
 (561) 822-1457 OR [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-12-16 Cont ID  
Sent By lmarchan Date 2020-12-16 Time 08:24 Rev Time 0.00
Received By lmarchan Date 2020-11-24 Time 15:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-11-03 Cont ID  
Sent By jleahy Date 2020-11-03 Time 06:56 Rev Time 0.00
Received By jleahy Date 2020-10-15 Time 06:59 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2020-12-03 Cont ID  
Sent By jgomez Date 2020-12-03 Time 18:14 Rev Time 0.00
Received By jgomez Date 2020-12-03 Time 18:05 Sent To  
Notes
2020-12-03 18:14:41NOTE:
 THIS PERMIT APPLICATION EXCLUDES THE ALTERATION WORK TO
 BE DONE IN THE GARAGE (GUEST SUITE). IMPACT FEES
 ASSESSMENT WILL BE REQUIRED WHEN CONTRACTOR SUBMITS
 SEPARATE PERMIT APPLICATION FOR GARAGE ALTERATION. JG.
  
  
  
 IMPACT FEES - DIGITAL SUBMITTALS
  
 PLANS SHOW A GARAGE WITH A GUEST SUITE. PLANS NEED TO
 BE REVIEWED BY PALM BEACH COUNTY FOR IMPACT FEE
 ASSESSMENT.
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-10-28 Cont ID  
Sent By jgomez Date 2020-10-28 Time 15:13 Rev Time 0.00
Received By jgomez Date 2020-10-28 Time 15:12 Sent To  
Notes
2020-10-28 15:16:16IMPACT FEES - DIGITAL SUBMITTALS
  
 PLANS SHOW A GARAGE WITH A GUEST SUITE. PLANS NEED TO
 BE REVIEWED BY PALM BEACH COUNTY FOR IMPACT FEE
 ASSESSMENT.
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-11-25 Cont ID  
Sent By ccole Date 2020-11-25 Time 15:59 Rev Time 0.00
Received By ccole Date 2020-11-25 Time 15:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-10-20 Cont ID  
Sent By ccole Date 2020-10-20 Time 12:11 Rev Time 0.00
Received By ccole Date 2020-10-20 Time 10:41 Sent To  
Notes
2020-10-20 12:14:531ST REVIEW FBC-2017 RES.
 PERMIT-20100525
 10/20/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P1.1: PLEASE PROVIDE A PLUMBING SCOPE OF WORK
 OUTLINE ON THE PLAN. IT APPEARS A NEW LAUNDRY ROOM AND
 BATHROOM ARE BEING CONSTRUCTED, AND FIXTURES ARE BEING
 REPLACED IN EXISTING BATHROOMS ETC. PLEASE CLARIFY BY
 PROVIDING AN ITEMIZED LIST OF PROPOSED WORK- SECTION
 107.2.1 WPB.
  
 2) SHEET P1.1: PROVIDE SANITARY RISER DRAWINGS FOR THE
 WASHING MACHINE IN THE MAIN HOUSE, AND THE LAVATORY IN
 THE GUEST SUITE- SECTION 107.3.5.3 WPB.
  
 3) P1.1: SHOW CLEANOUTS AT THE BASE OF THE STACKS
 SERVING THE NEW 2ND FLOOR BATHROOM AND THE WASHING
 MACHINE- SECTION P3005.2.4 FBC RES.
  
 4) P1.1 PROVIDE AN EQUIPMENT SCHEDULE FOR THE WATER
 HEATER AND SUBMIT MANUFACTURER'S SPECIFICATIONS- TABLE
 C404.2 FBC EC AND G2448.1 FBC RES. PLEASE NOTE A
 SEPARATE PERMIT IS REQUIRED FOR THE GAS PIPING
 INSTALLATION TO THE WATER HEATER AND ALL OTHER GAS
 FIRED APPLIANCES- SECTION 107.2.1 WPB.
  
 5) P1.1: PROVIDE GAS VENTING DIAGRAM FOR THE WATER
 HEATER SHOWING THE TYPE AND SIZE OF VENT PIPE, THE
 TOTAL RUN LENGTH OF THE VENTING AND TERMINATION HEIGHT
 ABOVE THE ROOF- SECTION G2448.1 AND G2426 FBC RES.
 PLEASE NOTE THE VENTING PLAN CAN BE SUBMITTED WITH THE
 SEPARATE GAS PLANS.
  
 6) P1.1: PROVIDE A WATER RISER DRAWING SHOWING THE NEW
 WATER SUPPLY LINES TO THE REFRIGERATOR AND POT FILLER-
 SECTION 107.3.5.3 WPB. SHOW ON THE RISER THE POINTS OF
 CONNECTIONS FOR NEW DISTRIBUTION LINES FROM THE WATER
 HEATER, AND THE LOCATIONS OF REQUIRED WATER HAMMER
 ARRESTORS AND BACKFLOW PREVENTERS FOR THE NEW SUPPLY
 LINES- SECTIONS P2902.3 & P2903.5 FBC RES.
  
 7) P1.1: INDICATE THE HOT WATER PIPING WILL BE
 INSULATED WITH MINIMUM R3 PIPE INSULATION- SECTION
 R403.5.3 FBC EC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-12-01 Cont ID  
Sent By jgomez Date 2020-12-01 Time 11:15 Rev Time 0.00
Received By jgomez Date 2020-12-01 Time 11:13 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-10-28 Cont ID  
Sent By jgomez Date 2020-10-28 Time 15:09 Rev Time 0.00
Received By jgomez Date 2020-10-28 Time 15:09 Sent To  
Notes
2020-10-28 15:12:421- DRAWINGS A1.1 AND S1.1 ARE MISSING THE ARCHITECT'S
 DIGITAL SIGNATURE.
 PLANS NEED TO HAVE ARCHITECT'S ORIGINAL SEAL AND
 SIGNATURE WHEN SUBMITTING DOCUMENTS FOR PUBLIC RECORDS
 AS REQUIRED BY 61G1-16.003 FAC. PLANS WERE SUBMITTED
 ELECTRONICALLY. ARCHITECT TO PROVIDE PLANS WITH DIGITAL
 SIGNATURE OR PROVIDE HARD COPY PLANS WITH THE ORIGINAL
 SEAL AND SIGNATURE.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2020-10-29 Cont ID  
Sent By fmittner Date 2020-10-29 Time 14:54 Rev Time 0.00
Received By fmittner Date 2020-10-29 Time 14:54 Sent To  
Notes
***NONE***