Plan Review Details - Permit 20100493
Plan Review Stops For Permit 20100493
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2020-11-20 Cont ID  
Sent By cpuell Date 2020-11-20 Time 16:07 Rev Time 0.00
Received By cpuell Date 2020-11-20 Time 16:07 Sent To  
Notes
***NONE***

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2020-10-09 Cont ID  
Sent By cpuell Date 2020-10-09 Time 14:12 Rev Time 0.00
Received By cpuell Date 2020-10-09 Time 14:12 Sent To  
Notes
2020-10-09 14:14:34PLEASE EMAIL [email protected] WITH A SITE PLAN SHOWING
 THE EXACT LOCATION OF THE MAIN ENTRANCE TO THE PROPOSED
 BUILDING, SO THAT AN ADDRESS CAN BE ESTABLISHED FOR THE
 PROPERTY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-01-04 Cont ID  
Sent By rmcdouga Date 2021-01-04 Time 12:40 Rev Time 0.00
Received By rmcdouga Date 2021-01-04 Time 12:32 Sent To  
Notes
2021-01-04 12:45:19THIS TEMPORARY CONSTRUCTION FENCE PERMIT IS FOR THE FPL
 UNDER GROUND WORK AND SOME DRAINAGE WORK. THE TEMPORARY
 CONSTRUCTION FENCE FOR THE BUILDING WILL BE SUBMITTED
 AT A LATER DATE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-10-29 Cont ID  
Sent By rmcdouga Date 2020-10-29 Time 11:29 Rev Time 0.00
Received By rmcdouga Date 2020-10-29 Time 11:29 Sent To  
Notes
2020-10-29 11:28:24PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SEE ZONING AND FIRE COMMENTS.
  
 2) THE MOT PLANS, ROW PERMITS AND SAFEGUARDS DURING
 CONSTRUCTION PLANS WILL NEED TO BE APPROVED BEFORE THE
 TEMPORARY FENCE PERMIT CAN BE APPROVED.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2021-01-05 Cont ID  
Sent By rrossano Date 2021-01-05 Time   Rev Time 0.00
Received By rrossano Date 2021-01-05 Time   Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-12-28 Cont ID  
Sent By pleduc Date 2020-12-28 Time   Rev Time 0.00
Received By pleduc Date 2020-12-28 Time 11:39 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-10-20 Cont ID  
Sent By pleduc Date 2020-10-20 Time   Rev Time 0.00
Received By pleduc Date 2020-10-20 Time 10:02 Sent To  
Notes
2020-10-20 10:19:58THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE DOES NOT APPEAR TO BE A GATED ACCESS ALONG
 BANYAN.
  
 DIXIE & BANYAN WILL BE THE MOST LIKELY ACCESS ROADWAY
 POINTS.
  
 PLEASE PROVIDE AN ACCESS GATE ALONG BANYAN.
  
  
  
 2) PLEASE ENSURE THAT EACH GATE ACCESS POINT IS
 PROVIDED WITH A KNOX PADLOCK,
  
 PROVIDE A NOTE OF ACKOWLEDGEMENT
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-01-05 Cont ID  
Sent By rmcdouga Date 2021-01-05 Time 08:12 Rev Time 0.00
Received By rmcdouga Date 2020-12-23 Time 17:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-10-29 Cont ID  
Sent By rmcdouga Date 2020-10-29 Time 11:29 Rev Time 0.00
Received By rmcdouga Date 2020-10-15 Time 16:17 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2020-10-29 Cont ID  
Sent By rmcdouga Date 2020-10-29 Time 11:29 Rev Time 0.00
Received By rmcdouga Date 2020-10-29 Time 11:29 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2021-01-04 Cont ID  
Sent By aaponte Date 2021-01-04 Time 10:05 Rev Time 0.00
Received By aaponte Date 2021-01-04 Time 10:05 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2020-10-21 Cont ID  
Sent By aaponte Date 2020-10-21 Time 10:36 Rev Time 0.00
Received By aaponte Date 2020-10-21 Time 10:36 Sent To  
Notes
2020-10-21 10:44:361. CONSTRUCTION FENCE PERMITS WILL NOT BE ISSUED UNTIL
 THE SITE IS CLOSE TO OBTAINING BUILDING PERMIT.
 PROPOSED PROJECT HAS NOT SUBMITTED FOR BUIDLING PERMIT
 YET.
 2. PLEASE EXPLAIN THE REASONING FOR THE PROPOSED FENCE
 LAYOUT (WITH A PORTION OF THE PARKING LOT REMAINING
 OUTSIDE FENCE).
 3. PRIOR TO THE ISSUANCE OF THE FIRST BUILDING PERMIT,
 THE APPLICANT SHALL PREPARE A CONSTRUCTION SITE
 SECURITY AND MANAGEMENT PLAN FOR APPROVAL BY THE CITY
 OF WEST PALM BEACH POLICE
 DEPARTMENT CPTED OFFICIAL. PLEASE CONTACT SETH BOXTON
 AT [email protected].
 4. STAFF RECOMMENDS THE CONSTRUCTION TEAM TO EVALUATE
 THE OPTIONS TO REDUCE AS MUCH AS POSSIBLE THE TIME THE
 SIDEWALK WILL BE CLOSED TO THE PUBLIC.
 FOR ADDTIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439
  