Plan Review Details - Permit 20100471
Plan Review Stops For Permit 20100471
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-10-19 Cont ID  
Sent By rmcdouga Date 2020-10-19 Time 10:37 Rev Time 0.00
Received By rmcdouga Date 2020-10-19 Time 10:37 Sent To  
Notes
2020-10-19 10:40:08PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-10-19 Cont ID  
Sent By rmcdouga Date 2020-10-19 Time 10:40 Rev Time 0.00
Received By rmcdouga Date 2020-10-19 Time 10:33 Sent To  
Notes
2020-10-19 10:47:46PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT A COPY OF THE CONTRACT WITH THE SCOPE OF WORK
 SPECIFIED. FBC 109.3 BUILDING PERMIT VALUATION. FOR
 PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS
 SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 2) THE DRYWALL THAT IS BEING REPLACED ON THE CORRIDOR
 WALLS AND CEILING IS PART OF FIRE RATED ASSEMBLIES.
 PROVIDE SIGNED AND SEALED DRAWINGS AND DETAILS FROM A
 FLORIDA LICENSED DESIGN PROFESSIONAL. PROVIDE WALL AND
 CEILING SECTIONS WITH THE LISTING DETAILS FOR THE FIRE
 RATED ASSEMBLY. FBC 107.2.1 - INFORMATION ON
 CONSTRUCTION DOCUMENTS. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-10-20 Cont ID  
Sent By pleduc Date 2020-10-20 Time   Rev Time 0.00
Received By pleduc Date 2020-10-20 Time 09:30 Sent To  
Notes
2020-10-20 09:35:32THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE INDICATIONS OF RATED WALL REMOVAL AND
 RE-CONSTRUCTION, HOWEVER THERE ARE NO DETAILS OF LISTED
 FIRE RATING DETAILS.
  
 PLEASE REVIEW AND PROVIDE.
  
  
 2) THERE ARE INDICATIONS OF REMOVAL OF CEILING AND WALL
 MATERIAL; HOWEVER, THERE ARE NO INDICATIONS OF ANY OF
 THIS WORK THAT MAY AFFECT FIRE SPRINKLER OR FIRE ALARM
 DEVICES.
  
 PLEASE PROVIDE DETAIL INVOLVING FIRE SPRINKLER HEADS.
  
 ANY WORK ON FIRE SPRINKLERS OR FIRE ALARM DEVICES,
 INCLUDING DEMO, SHALL BE DONE UNDER SEPARATE PERMIT AND
 SHOP DRAWINGS.
  
 PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGEMENT.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-10-20 Cont ID  
Sent By jleahy Date 2020-10-20 Time 11:22 Rev Time 0.00
Received By jleahy Date 2020-10-15 Time 13:22 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-10-19 Cont ID  
Sent By rmcdouga Date 2020-10-19 Time 10:48 Rev Time 0.00
Received By rmcdouga Date 2020-10-19 Time 10:48 Sent To  
Notes
2020-10-19 10:51:00ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO HAVE
 THE ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE
 THE OPTION TO SUBMIT THE SIGNED AND SEALED PAPER
 VERSION OF DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE
 BEEN APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE AND SEAL IS
 REQUIRED TO BE ON THE DRAWINGS. NO PHOTOCOPY OR OTHER
 FACSIMILES OF THE SIGNATURE ARE ACCEPTABLE. FS 471 &
 61G15
  
  