| 2020-12-30 07:52:22 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20100364 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE MECHANICAL EQUIPMENT SIZING |
| | CALCULATIONS FOR THE UNIT ABOUT THE GARAGE AND THE UNIT |
| | SERVING BOTH FLOORS OF THE MAIN HOUSE. THE ORIGINAL |
| | APPROVED DRAWING INDICATES 2 3-TON UNITS FOR THE MAIN |
| | HOUSE. FBC EC R403.7 |
| | |
| | 2) PLEASE SHOW THE CONDENSATE DISPOSAL. FBC RES M1411.3 |
| | |
| | 3) PLEASE PROVIDE ENERGY SUBMITTAL FOR THE GARAGE. FBC |
| | EC 101.5.1.1.2 |
| | |
| | 4) PLEASE SHOW HOW THE CONDENSING UNITS WILL BE |
| | ANCHORED. FBC RES M1307.2 |
| | |
| | 5) PLEASE PROVIDE CFM?S OF THE HOOD AND THE REQUIRED |
| | CFM OF THE STOVE. FBC RES M1503.4 |
| | |
| | 6) PLEASE SHOW THE RETURN AIR PATH TO THE AHU IN THE |
| | MECHANICAL CLOSET, WHAT TYPE OF DOOR IS LOCATED AT THE |
| | CLOSET OPENING? FBC RES M1602.3 |
| | |
| | 7) SECOND FLOOR BATHROOM WILL NEED TO SHOW AN EXHAUST |
| | FAN IN THE SHOWER AREA. FBC RES TABLE M1507.4 |
| | |
| | 8) PLEASE PROVIDE A TITLE BLOCK ON THE DRAWING, THE |
| | DESIGNER OF DRAWING MUST PRINT AND SIGN THE DRAWING. |
| | FBC 107.2 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |