Plan Review Details - Permit 20100363
Plan Review Stops For Permit 20100363
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2021-01-05 Cont ID  
Sent By cpuell Date 2021-01-05 Time 16:30 Rev Time 0.00
Received By cpuell Date 2021-01-05 Time 16:30 Sent To  
Notes
2021-01-05 16:31:087038 OKEECHOBEE BLVD

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2020-11-29 Cont ID  
Sent By cpuell Date 2020-11-29 Time 08:39 Rev Time 0.00
Received By cpuell Date 2020-11-29 Time 08:39 Sent To  
Notes
2020-11-29 08:39:44PLEASE EMAIL [email protected], WITH A SITE PLAN SHOWING
 THE EXACTLY LOCATION OF THE STORE GREAT GREEK WILL BE
 LOCATED, WHILE I HAVE NO ISSUES WITH 7038 OKEECHOBEE
 BLVD THE ADDRESS IS NOT CURRENTLY IN ANY DATABASE IN
 OUR SYSTEM, I NEED THE SITEPLAN SO I CAN ENTER THE GIS
 COORDINATES AND CREATE THE ADDRESS IN THE CITY'S AND
 COUNTY'S DATABASES.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status N Date 2020-10-20 Cont ID  
Sent By jwitmer Date 2020-10-20 Time 19:16 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2020-10-20 19:17:18FIRST TENANT BUILDOUT SHEEL BUILDING PERMIT 19081537.
 JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-02-17 Cont ID  
Sent By jwitmer Date 2021-02-17 Time 11:28 Rev Time 0.00
Received By jwitmer Date 2021-02-17 Time 10:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-01-07 Cont ID  
Sent By jwitmer Date 2021-01-07 Time 09:14 Rev Time 0.00
Received By jwitmer Date 2021-01-07 Time 08:16 Sent To  
Notes
2021-01-07 09:06:15WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20100367
 ADD: 7032 OKEECHOBEE BLVD.
 CONT: TBD/ TO BE DETERMINED
 TEL: ???
 E-MAIL: [email protected] / DAVID NITECKI
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURS. JAN. 07TH/2021
 ACTION: DENIED
  
 1) COMPLIED.
  
 2) 2ND REQUEST. THE INTERIOR LIGHTING COMPLIANCE
 CERTIFICATE INDICATE IT IS FOR THE GREAT GREEK.
 CONSTRUCTION SITE LISTED AS:
 2121 VISTA PARKWAY
 WEST PALM BEACH, FL.
 VISTA PARKWAY IS IN PALM BEACH COUNTY, NOT IN THE CITY
 OF WEST PALM BEACH. CORRECT THE ADDRESS.
  
 3) COMPLIED.
  
 4) THE K1-0 EQ & FURNITURE PLAN:
  
 4A) SEMI-COMPLIED. 2ND REQUEST. $ ACCESSIBLE SEATS ARE
 SHOWN AT THE SAME TABLE, THEY D0 NOT SHOW DISPERSION.
 THE FURNITURE FLOOR PLAN SHOWS 62 SEATS AND ONLY ONE
 ACCESSIBLE SEAT SYMBOL. 2017 FBC-ACCESS. CODE 226.1
 WHERE DINING SURFACES ARE PROVIDED FOR THE CONSUMPTION
 OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE SEATING
 SPACES AND STANDING SPACES AT THE DINING SURFACES SHALL
 COMPLY WITH 902. 62X 0.05= 4 ACCESSIBLE SEATS.
  
 4B)2ND REQUEST. 226.2 DISPERSION. DINING SURFACES ARE
 REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES. WILL THERE BE ADDITIONAL OUTSIDE SEASONAL
 SEATING?
  
 4C) COMPLIED, RESPONSE INDICATES NO SEASONAL (EXTERIOR)
 DINING.
  
 4D) 2ND REQUEST. 902.1 .DINING SURFACES AND WORK
 SURFACES SHALL COMPLY WITH 902.2 AND 902.3. ADVISORY
 902.1 GENERAL. DINING SURFACES INCLUDE, BUT ARE NOT
 LIMITED TO, BARS, TABLES, LUNCH COUNTERS, AND BOOTHS
  
 4D)(1) 2ND REQUEST. 902.2 CLEAR FLOOR OR GROUND SPACE.
 A CLEAR FLOOR SPACE COMPLYING WITH 305 POSITIONED FOR A
 FORWARD APPROACH SHALL BE PROVIDED. KNEE AND TOE
 CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
  
 4D)(2) 2ND REQUEST. 902.3 HEIGHT. THE TOPS OF DINING
 SURFACES AND WORK SURFACES SHALL BE 28 INCHES MINIMUM
 AND 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 5) COMPLIED. ROOFTOP EQUIPMENT ARE BEING PROVIDED UNDER
 SEPARATE PERMIT. PERMIT # 20100804 APPLIED FOR BY
 LANDLORD?S ARCHITECT.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-10-20 Cont ID  
Sent By jwitmer Date 2020-10-20 Time 19:18 Rev Time 0.00
Received By jwitmer Date 2020-10-20 Time 16:15 Sent To  
Notes
2020-10-20 16:23:18WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20100367
 ADD: 7000 OKEECHOBEE BLVD. (SUITE: 7038) SUITE NUMBER
 NEEDS TO BE ADDED TO PLAN.
 CONT: TBD/ TO BE DETERMINED
 TEL: ???
 E-MAIL: [email protected] / DAVID NITECKI
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. OCT. 20/2020
 ACTION: DENIED
  
 1) SHEET G1-01 PROJECT INFO & CODE:
 1A) THE KEY PLAN INDICATES THE GREAT GREEK RESTAURANT
 IS TAKING ONLY PART OF BUILDING ADDRESSED AS 7000
 OKEECHOBEE BLVD. WILL NEED A TENANT ADDRESS., SUITE
 NUMBER.
 2017 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED.
 2017 FBC-B 501.2 ADDRESS IDENTIFICATION. NEW AND
 EXISTING BUILDINGS SHALL BE PROVIDED WITH APPROVED
 ADDRESS IDENTIFICATION.
  
 1B) UNDER THE HEADING OF THE CODE MATRIX THE PLANS
 STATE THE CONSTRUCTION TYPE AS III-B. THE PLANS ARE
 SILENT AS IF THE BUILDING IS FIRE SPRINKLERED OR NOT?
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 1C) UNDER THE CODE MATRIX INTERIOR FINISHES THE EDITION
 OF THE CODE IS LISTED AS THE 2020 FBC. PLEASE NOTE WE
 ARE CURRENTLY UNDER THE 6TH EDITION OF THE FLORIDA
 BUILDING CODE 2017.
  
 1D) THE NOTE STATES TO MEET ALL REQUIREMENTS OF THE
 AMERICANS DISABILITY ACT, STATE OF FLORIDA CODE AND
 ICC/ANSI 117.1A THE MOST RESTRICTIVE REQUIREMENT SHALL
 GOVERN. PLEASE NOTE THE STATE OF FLORIDA HAS ADOPTED
 THE 2017 FBC-ACCESSIBILITY CODE WHICH HAS BEEN BLESSED
 BY THE DEPARTMENT OF JUSTICE. OUR CODE SECTIONS WILL
 REFERENCE THE 2017 FLORIDA ACCESSIBILITY CODE.
  
 2) THE INTERIOR LIGHTING COMPLIANCE CERTIFICATE
 INDICATE IT IS FOR THE GREAT GREEK. CONSTRUCTION SITE
 LISTED AS:
 2121 VISTA PARKWAY
 WEST PALM BEACH, FL.
 VISTA PARKWAY IS IN PALM BEACH COUNTY, NOT IN THE CITY
 OF WEST PALM BEACH. CORRECT THE ADDRESS.
  
 3) SHEET A5-10:
 3A) PLEASE REVIEW HOW THE HEIGHT OF THE WATER CLOSET
 GRAB BARS ARE DIMENSIONED FOR HEIGHT FROM FINISH FLOOR.
 2017 FBC-ACCESSIBILITY CODE SECTION 609.4 POSITION OF
 GRAB BARS. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE, NOT CENTERLINE.
 3B) DETAIL 6 DOES NOT SHOW THE LAVATORY PIPES WITH
 INSULATION. 2017 FBC-ACCESS. CODE SECTION 606.5 EXPOSED
 PIPES AND SURFACES. WATER SUPPLY & DRAINPIPES UNDER
 LAVATORIES AND SINKS SHALL BE INSULATED OR OTHERWISE
 CONFIGURED TO PROTECT AGAINST CONTACT.
 4) THE K1-0 EQ & FURNITURE PLAN:
 4A) THE FURNITURE FLOOR PLAN SHOWS 62 SEATS AND ONLY
 ONE ACCESSIBLE SEAT SYMBOL. 2017 FBC-ACCESS. CODE 226.1
 WHERE DINING SURFACES ARE PROVIDED FOR THE CONSUMPTION
 OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE SEATING
 SPACES AND STANDING SPACES AT THE DINING SURFACES SHALL
 COMPLY WITH 902. 62X 0.05= 4 ACCESSIBLE SEATS.
  
 4B) 226.2 DISPERSION. DINING SURFACES ARE REQUIRED TO
 COMPLY WITH 902 SHALL BE DISPERSED THROUGHOUT THE SPACE
 OR FACILITY CONTAINING DINING SURFACES. WILL THERE BE
 ADDITIONAL OUTSIDE SEASONAL SEATING?
  
 4C) 206.2.5 206.2.5 RESTAURANTS AND CAFETERIAS. IN
 RESTAURANTS AND CAFETERIAS, AN ACCESSIBLE ROUTE SHALL
 BE PROVIDED TO ALL DINING AREAS, INCLUDING RAISED OR
 SUNKEN DINING AREAS, AND OUTDOOR DINING AREAS.
  
 4D) 902.1 .DINING SURFACES AND WORK SURFACES SHALL
 COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL.
 DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS,
 TABLES, LUNCH COUNTERS, AND BOOTHS
  
 4D)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 4D)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
 5) THE MECHANICAL ROOF TOP PLAN KEY NOTES:
 5A KEY NOTE 1 STATES FURNISH AND INSTALL ROOFTOP UNITS
 RTU 1 & 2 VERIFY WITH LANDLORD REPRESENTATIVE AND
 STRUCTURAL DRAWINGS. THE ORIGINAL SHELL BUILDING PERMIT
 # 19081537 SHEET 15/63 STATES RTU # 1 & 2 ROOF OPENING
 FRAMING BY OTHERS UNDER SEPARATE PERMIT. THESE PLANS
 ALSO SHOW STEEL BAR JOIST AND METAL B DECKING.
 5A)(1) PROVIDE ADDITIONAL STRUCTURAL PLANS FOR THE
 RE-INFORCEMENT OF BAR JOIST FOR POINT LOADING, PROVIDE
 THE STEEL INFILL FRAMING FOR THE FUTURE RTU?S UNITS.
 PROVIDE ANCHORAGE FOR THE STEEL FRAMING, THE CURB TO
 THE STEEL FRAMING AND THE ANCHORAGE OF THE RTU TO THE
 ROOF CURB.
 2017 FBC-M- 301.15 WIND RESISTANCE.
 MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE
 EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO
 RESIST THE WIND PRESSURES DETERMINED IN ACCORDANCE WITH
 THE FLORIDA BUILDING CODE, BUILDING.
 FBC-B-1609.6.4.4.1 COMPONENTS AND CLADDING. WIND
 PRESSURE FOR EACH COMPONENT OR CLADDING ELEMENT IS TO
 BE DESIGNED FOR WIND PRESSURES COMPONENTS AND
 ATTACHMENTS.
 LATERAL FORCE-RESISTING SYSTEM. FOR ALL ROOF TOP
 EQUIPMENT, CURBS, FANS OR A/C STANDS, AND OR VENTS,
 DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL
 AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE.
 2017 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
  
  
 5B) KEY NOTE 2 STATES PROVIDE ROOF MOUNTED EXHAUST FANS
 EF 1 & 2 WITH MANUFACTURES APPROVED ROOF CURB. PROVIDE
 ADDITIONAL STRUCTURAL PLANS FOR THE RE-INFORCEMENT OF
 BAR JOIST FOR POINT LOADING, PROVIDE THE STEEL INFILL
 FRAMING FOR THE FUTURE RTU?S UNITS. PROVIDE ANCHORAGE
 FOR THE STEEL FRAMING, THE CURB TO THE STEEL FRAMING
 AND THE ANCHORAGE OF THE RTU TO THE ROOF CURB.
 2017 FBC-M- 301.15 WIND RESISTANCE.
 MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE
 EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO
 RESIST THE WIND PRESSURES DETERMINED IN ACCORDANCE WITH
 THE FLORIDA BUILDING CODE, BUILDING.
 FBC-B-1609.6.4.4.1 COMPONENTS AND CLADDING. WIND
 PRESSURE FOR EACH COMPONENT OR CLADDING ELEMENT IS TO
 BE DESIGNED FOR WIND PRESSURES COMPONENTS AND
 ATTACHMENTS.
 LATERAL FORCE-RESISTING SYSTEM. FOR ALL ROOF TOP
 EQUIPMENT, CURBS, FANS OR A/C STANDS, AND OR VENTS,
 DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL
 AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE.
 2017 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
 5C) WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS
 REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION FOR FIELD WIELDING, ON THE JOB-SITE
 WIELDING. THIRD PARTY CERTIFICATION WILL BE REQUIRED.
 REPORTS SUBMITTED TO BUILDING INSPECTOR AT TIME OF
 FRAMING INSPECTION.
 2017 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT
 561-805-6666.
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-02-23 Cont ID  
Sent By equinone Date 2021-02-23 Time 11:09 Rev Time 0.00
Received By equinone Date 2021-02-23 Time 11:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-01-21 Cont ID  
Sent By equinone Date 2021-01-21 Time 14:36 Rev Time 0.00
Received By equinone Date 2021-01-21 Time 11:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-11-19 Cont ID  
Sent By equinone Date 2020-11-19 Time 14:39 Rev Time 0.00
Received By equinone Date 2020-11-19 Time 14:39 Sent To  
Notes
2020-11-19 14:40:12CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED.
  
 1) ELECTRICAL ROOF PLAN SHOWS CIRCUIT PP 27,29,31 FOR
 RTU#1 SIZED AS 3#8, 1#10 GND (DOES NOT MEET AMPACITY
 REQUIRED) WHILE NOTE 10 SPECIFIES 3#3, 1#8 CONDUCTOR
 WITH 100 A SWITCH. PANEL PP SHOWS THIS CIRCUIT WITH AN
 80 AMPS BREAKER. PLEASE CORRECT WITH PROPER CONDUCTOR
 SIZE AND MAKE INFORMATION CONSISTENT.
 2) ALL COMMERCIAL KITCHEN RECEPTACLES MUST HAVE GFCI
 PROTECTION. DEFINITION OF KITCHEN INCLUDES FOOD
 PREPARATION AREAS. PLEASE PROVIDE GFCI PROTECTION FOR
 RECEPTACLES IN FOOD PREPARATION AREA (PP-59). NEC 100,
 NEC 210.8 (B)(2).
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 SINCERELY,
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-10-22 Cont ID  
Sent By pleduc Date 2020-10-22 Time   Rev Time 0.00
Received By pleduc Date 2020-10-22 Time 11:04 Sent To  
Notes
2020-10-22 12:40:48FIRE PROVISO:
  
 THE HOOD AND FIRE SUPRESSION SYSTEMS SHALL BE SUBMITTED
 UNDER SEPARATE PERMITS AND SEPARATE SHOP DRAWINGS
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2021-02-17 Cont ID  
Sent By tklarge Date 2021-02-17 Time 12:56 Rev Time 0.00
Received By tklarge Date 2021-02-17 Time 10:49 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2021-02-04 Cont ID  
Sent By tklarge Date 2021-02-04 Time 10:15 Rev Time 0.00
Received By tklarge Date 2021-02-04 Time 10:15 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-11-22 Cont ID  
Sent By tklarge Date 2020-11-22 Time 08:27 Rev Time 0.00
Received By tklarge Date 2020-11-22 Time 07:55 Sent To  
Notes
2020-11-22 08:27:081) SUBMIT COPIES OF THE MANUFACTURER'S SPECIFICATION
 SHEETS FOR ALL GAS EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND FBC-2017 FUEL GAS CODE
 SEC. 402.2, AND 301.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1,
 2) SHT. P3-01 - KEYNOTE #1 STATES THE LP GAS DEMAND IS
 1182 MBH BUT THE GAS LOAD SUMMARY TABLE SHOWS 812 MBH.
 CLARIFY.
 3) SHT. P3-01 - THE GAS LOAD SUMMARY TABLE INDICATES
 LIQUID PROPANE GAS BUT THE TABLE ALSO REFERSS TO
 NATURAL GAS. CLARIFY.
 4) SHT. P3-01 - THE GAS LOAD SUMMARY TABLE NOTES THE
 TOTAL DEVELOPED LENGTH AS 82 FEET BUT KEYNOTE #1 STATES
 THE DEVELOPED LENGTH IS 126 FEET.THE PLANS FOR PERMIT
 APPLICATION #20100804 FOR THIS SAME SPACE SHOW THE
 DEVELOPED LENGTH AS 75 FEET.CLARIFY.
 5) SHT. P4-01 - THE GAS RISER REFERENCES SIZING TABLE
 402.4(26) FROM THE FUEL GAS CODE. THIS TABLE IS FOR A
 10 PSI SYSTEM BUT THE PLAN REFERS TO AN 11 INCH WATER
 COLUMN PRESSURE. CLARIFY. NOTE: A COMPREHENSIVE GAS
 REVIEW COUD NOT BE DONE AT THIS TIME DDUE TO THE WRONG
 SIZING TABLE REFERENCED ON THE PLANS.
 6) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED.WPB
 AMEND. TO FBC SEC. 107.2.1.
 7) SUBMIT DETAILS FOR THE ANCHORING OF THE GAS PIPING
 ON THE ROOF.GAS PIPING INSTALLED ON THE ROOF SHALL
 OMPLY WITH FBC-FUEL GAS SEC.404.9.
 8) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE GAS
 APPLIANCES. 2017 FBC-FUEL GAS SEC. 304.1. WHERE
 COMBUSTION AIR IS PROVIDED BY THE BUILDING?S MECHANICAL
 VENTILATION SYSTEM, THE SYSTEM SHALL PROVIDE THE
 SPECIFIED COMBUSTION AIR RATE IN ADDITION TO THE
 REQUIRED VENTILATION AIR. 2017 FBC-FUEL GAS
 SEC.304.9.3.
 9) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR. 2017 FBC-FUEL GAS
 SEC.409.4.
 10) SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE PRESSURE REGULATORS.
 REGULATORS INSTALLED ON THE EXTERIOR OF THE BUILDING
 SHALL BE APPROVED FOR OUTDOOR INSTALLATION. IDENTIFY ON
 THE SPECIFICATION SHEETS WHICH MODEL REGULATOR IS BEING
 INSTALLED AND THE ORIFICE SIZE TO ENSURE THE REGULATOR
 CAN ACCOMMODATE THE BTU LOAD THROUGH THE REGULATOR.2017
 FGC SEC.410.1, 2017 FBC-RES. SEC. G2421.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-02-24 Cont ID  
Sent By equinone Date 2021-02-24 Time 10:03 Rev Time 0.00
Received By medwards Date 2021-02-09 Time 11:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-02-08 Cont ID  
Sent By cpuell Date 2021-02-08 Time 12:06 Rev Time 0.00
Received By cpuell Date 2021-01-04 Time 14:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-11-23 Cont ID  
Sent By lmarchan Date 2020-11-23 Time 07:37 Rev Time 0.00
Received By lmarchan Date 2020-10-19 Time 08:16 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2021-02-24 Cont ID  
Sent By medwards Date 2021-02-24 Time 10:02 Rev Time 0.00
Received By medwards Date 2021-02-24 Time 10:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-01-14 Cont ID  
Sent By medwards Date 2021-01-14 Time 10:17 Rev Time 0.00
Received By medwards Date 2021-01-14 Time 10:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-11-05 Cont ID  
Sent By medwards Date 2020-11-05 Time 15:21 Rev Time 0.00
Received By medwards Date 2020-11-05 Time 13:33 Sent To  
Notes
2020-11-05 15:22:311ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20100363
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE CALCULATIONS FOR THE HEATING AND
 COOLING LOADS. FBC EC C403.2.1
  
 2) HOODS AND REFRIGERATION EQUIPMENT(COOLER/FREEZER)
 WILL BE SEPARATE SUBMITTALS WITH THEIR OWN PERMITS AND
 REVIEWS
  
 3) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS FOR THIS
 PROJECT. FBC M TABLE 403.3.1.1
  
 4) PLEASE SHOW ROOF ACCESS. FBC M 306.5
  
 5) PLEASE SHOW THAT EQUIPMENT ON THE ROOF MEETS FBC M
 304.11
  
 6) PLEASE REMOVE THE HOOD DRAWINGS AS THEY WILL BE
 REQUIRED TO HAVE A SUB PERMIT AND SEPARATE REVIEW. FBC
 107.2
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-02-17 Cont ID  
Sent By tklarge Date 2021-02-17 Time 12:57 Rev Time 0.00
Received By tklarge Date 2021-02-17 Time 10:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-02-08 Cont ID  
Sent By tklarge Date 2021-02-08 Time 06:30 Rev Time 0.00
Received By tklarge Date 2021-02-03 Time 03:10 Sent To  
Notes
2021-02-05 05:17:541) THE ADDRESS ON THE PERMIT APPLICATION IS STILL
 INCORRECT. THE PLANS NOTE "7038 OKEECHOBEE BLVD." AND
 THE PERMIT APPLICATION NOTES THE ADDRESS AS 7032
 OKEECHOBEE BLVD. SUBMIT A CORRECTED PERMIT APPLICATION
 WITH THE CORRECT ADDRESS WWHICCH IS 7038 OKEECHOBEE
 BLVD. WPB AMEND. TO FBC SEC. 105.3.
 2) THE PLUMBING PLANS SHALL BE DIGITALLY SIGNED AND
 SEALED IN ACCORDANCE WITH FL. ADMIN. CODE RULE
 61G1-16.005 (ARCHITECTS) AND 61G15-23.004, 61G15-23.005
 (ENGINEERS).
 3) THE DISHWASHER IS SHOWN AS ITEM D-5 ON SHT.K1-01 AND
 LISTED AS ITEM D-5 ON SHT. SHT.K1-02 BUT LISTED AS G-7
 ON SHT.P2-01 AND P4-01. ITEM D-5 IS NOT LISTED ON THE
 KITCHEN EQUIPMMENT SCHEDULE ON SHT.P2-01. SHT.K1-02
 LISTS ITEM G-7 AS A SPARE.CLARIFY.
 4) SHT.P2-01 - THE DISHWASHER APPEARS TO BE LOCATED IN
 FRONT A FUTURE LOCATION OF A 200 AMP ELECTRICAL PANEL.
 PLEASE REVIEW AS THIS COULD BE A FUTURE ELECTRICAL CODE
 VIOLATION FOR WORKING CLEARANCES FOR THE ELECTRIC
 PANEL.
 5) SHT. K1-01 - ITEM B8 HAS AN ARROW POINTING TO AN
 OPEN SPACE. NO ITEM IS SHOWN. ITEM B9 IS NOT SHOWN ON
 THE FLOOR PLAN. CLARIFY.
 6) SHT.P5-01 - THE 3- COMP WAREWASH SINK DETAIL APPEARS
 TO SHOW TEMPERED WATER TO THE SINK.THE SINK SHALL BE
 EQUIPPED WITH HOT WATER PER FBC-PLUMBING SEC.607.1.
 7) SHT. P5-01 - WATER HETER DETAILS REFER TO SHT P1-01
 - THIS SHEET IS NOT LISTED IN THE NAMING CONVENTIONS OF
 THE UPLOADED PLANS.THIS SHEET IS LISTED AS P0-01.
 PLEASE CORRECT.
 8) HOT WATER SHALL BE SUPPLIED TO THE HAND SINKS IN THE
 FOOD PREP AREA PER FBC-PLUMBING SEC. 607.1.
 9) SHT. P2-01 - GREASE INTERCEPTOR SIZING CALCULATIONS
 - THE CALCULATIONS SHOW 50 SEATS BUT DOES NOT APPEAR TO
 INCLUDE THE SEATING IN THE DINING BOOTHS OPPOSITE THE
 SEATS. THESE SEATS MUST BE INCLUDED IN THE CALCULATIONS
 AND ALSO IN THE TOTAL OCCUPANT LOAD SHOWN ON SHT.G1-01.
 10) SHT. P2-01 - GREASE INTERCEPTOR SIZING CALCULATIONS
 - THE CALCULATIONS SHOW THE NUMBER OF HOURS OPEN AS 1.5
 LISTED UNDER ITEM #3 AND SHOWN AS 12 HOURS IN THE
 EQUATION. CLARIFY.
 11) IN WORKING THE GREASE INTERCEPTOR EQUATION AS
 LISTED IN FL. ADMIN. CODE RULE 64E-6, MY CALCULATIONS
 SHOW 750 GALLONS. THE MINIMUM VOLUME SHALL BE 750
 GALLONS. FL. ADMIN. CODE RULE 64E-6.013 (7) (D).
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-11-22 Cont ID  
Sent By tklarge Date 2020-11-22 Time 07:55 Rev Time 0.00
Received By tklarge Date 2020-11-05 Time 05:46 Sent To  
Notes
2020-11-13 11:56:561) THIS PLAN SHOWS THE ADDRESS OF THE SPACE AS 7000
 OKEECHOBEE BLVD. BUT PERMIT APPLICATION # 20100804
 SHOWS THE ADDRESS FOR THIS SAME SPACE AS 7038
 OKEECHOBEE BLVD.PROVIDE THE CORRECT ADDRESS AND BAY
 SPACE NUMBER FOR THIS SPACE.WPB AMEND. TO FBC SEC.
 107.2.1.
 2) SHT. G1-01 NOTES THE SQUARE FOOTAGE OF THIS SPACE AS
 1846 SQUARE FEET WITH 64 OCUPANTS AND PERMIT
 APPLICATION #20100804 SHOWS THE SQUARE FOOTAGE FOR THIS
 SPACE AS 2000 SQUARE FEET WITH 45 OCCUPANTS AND THE
 ORIGINAL SHELL PERMIT #19090177 SHOWS THE SQUARE
 FOOTAGE FOR THIS SAME SPACE AS 1383 SQUARE FEET.
 CLARIFY.
 3) SHT. G1-01 - PLUMBING SYSTEMS TABLE - CALLS OUT THE
 2020 FLORIDA PLUMBING CODE. THE CODE IN EFFECT IS THE
 2017 EDITION OF THE FLORIDA PLUMBING CODE. REVISE THE
 NOTE.
 4) G1-03 - ACCESSIBILITY NOTES - NOTE #25 - THE TOILET
 PAPER DISPENSER SHALL BE LOCATED A MINIMUM OF 7 INCHES
 AND A MAXIMUM OF 9 INCHES IN FRONT OF THE WATER CLOSET
 MEASURED TO THE CENTERLINE OF THE DISPENSER. REVISE THE
 NOTE. FBC-ACCESS. SEC.604.9.6.
 5) . A2-10 - KEYNOTES - THE PLANS SHOW A KEYNOTE #8 AT
 THE MOP SINK BUT THERE IS NO KEYNOTE #8 LISTED IN THE
 KEYNOTES. THIS APPEARS TO BE A TYPO.CLAIFY.
 6) SHT. A5-10 - DETAIL #6 - KNEE CLEARANCE UNDER THE
 LAVATORY SHALL BE 8 INCHES DEEP MINIMUM AT 27 INCHES
 ABOVE THE FINISH FLOOR. SHOW THIS ON THE PLANS.
 FBC-ACCESS. SC. 306.3.3.
 7) INDICATE ON THE PLANS IF THERE WILL BE ANY OUTDOOR
 SEATING. IF SO, THESE SEATS MUST BE ADDED TO THE TOTAL
 OCCUPANT LOAD WHICH MAY INCREASE THE REQUIRED PLUMBING
 FIXTURE COUNT.
 8)SHT. A5-10 - THE PLANS SHOW THE GRAB BARS MEASURED TO
 THE CENTERLINE OF THE BAR. GRAB BARS SHALL BE MEASURED
 TO THE TOP OF THE GRIPPING SURFACE PER FBC-ACCESS.
 SEC.609.4.
 9)SHT.A5-10 - THE PLAN SHOWS GRAB BARS INSTALLED IN THE
 VERTICAL POSITION. FBC-ACCESS. SEC. 609.4 REQUIRES GRAB
 BARS TO BE INSTALLED IN A HORIZONTAL POSITION. THERE IS
 NO EXCEPTION ALLOWING GRAB BARS TO BE INSTALLED IN A
 VERTICAL POSITION.
 10) SHT. A2-11 - SHOW THE INSIDE CLEAR DIMENSIONS OF
 THE TOILET ROOMS ( LENGTH X WIDTH).
 11) SHOW THE DIMENSIONS (L X W) OF THE CLEAR FLOOR
 SPACES FOR THE PLUMBING FIXTURES IN THE TOILET
 ROOM.COMPLY WITH FBC-ACCESS. SECS.604.3 & 606.2.
 12) SHT. A5- DETAIL #6 - THE HEIGHT OF THE TOILET
 APPEARS TO BE MEASURED TO THE TOP OF THE TOILET BOWL.
 THE HEIGHT SHALL BE MEASURED TO THE TOP OF THE SEAT PER
 FBC-ACCESS. SEC.604.4.
 13) A BACKFLOW PREVENTION DEVICE IS REQUIRED ON THE
 WATER FILTRATION SYSTEM. FBC-PLUMBING SEC.608.3, TABLEE
 608.1.
 14) SUBMIT DETAILS ON THE WATER FILTRATION SYSTEM. WPB
 AMEND. TO FBC SEC. 107.2.1.
 15) SHT. K1-01 - SHOW THE LOCATION OF THE DISHWASHER ON
 THE PLANS (ITEM D5).
 16) P0 - 01 - MATERIALS AND PERFORMANCE - NOTE #9 -
 PIPE SLEEVES SHALL BE TWO SIZES GREATER THAN THE PIPE.
 FBC-PLUMBING SEC. 305.3. NOTE: THE SHEET SHOULD BE
 NAMED AS P1-01, NOT P0-01..
 17) SHT. P2-01 - THE DISHWASHER (ITEM G7) IS NOT LISTED
 ON THE KITCHEN EQUIPMENT SCHEDULE ON SHT. K1-01 OR
 K1-02. CLARIFY.
 18) SHT.P2-01 - KEYNOTE #4 - CONDENSATE SHALL NOT BE
 DISCHARGED TO THE SANITARY OR GREASE WASTE SYSTEM.
 FBC-PLUMBING SEC.1003.2, CITY OF WPB CODE OF ORDINANCES
 CHAPT. 90, ART.III, SEC.90-126 (B)(5).
 19) SHT. P3-01 - KEYNOTE #7 REFERS TO AN EXISTING 1
 INCH WATER LINE BUT TABLE TO CALCULATE WATER FIXTURE
 UNITS CALLS OUT A 1 1/2 INCH PIPE SIZE.CLARIFY.
 20) SHT. P4-01 - SIZE ALL OF THE VENTS AND DRAIN LINES
 ON THE SANITARY RISER. COMPLY WITH FBC-PLUMBING SEC.906
 & TABLE 906.1.
 21) SHT. P4-01 - IDENTIFY THE HOT & COLD WATER DROPS O
 THE WATER HEATER ON THE WATER RISER AND LABEL THE
 EXISTING WATER LINE COMING INTO THE BUILDING AS SUCH.
 22) SHT. P4-01 - THE GREASE WASTE RISER SHOWS FIXTURE
 D5. THIS FIXTURE IS NOT LISTED ON ANY FIXTURE SCHEDULE.
 CLARIFY.
 23) SHT. P4-01 - THE HOT WATERFOR FIXTURE H1.1 APPEARS
 TO BE CONNETED TO THE RECIRCULATION LINE AND NOT THE
 HOT WATER LINE. CLARIFY.
 24) SHT. P5-01 - 3 COMPARTMENT SINK DETAIL - EACH WELL
 OF A MULTIPLE - COMPARTMENT SINK SHALL DISCHARGE
 INDEPENDENTLY TO A WASTE RECEPTOR.FBC-PLUMBING
 SEC.802.1.1.
 25) HOT WATER SHALL B SUPPLIED TO ALL SINKS IN THE FOOD
 PREP AREA AND TO THE MOP SINK. FBC-PLUMMBING SEC.607.1.
 26) THERMOSTATIC MIXING VALVES SHALL OMPLY WITH ASSE
 1070. FFBC-PLUMBING SEC. 607.1.2.
 27) SHT. P5-01 - SHOW THE SIZE OF THE EXPANSION TANL ON
 THE WATER HEATER DETAIL.
 28) PROVIDE A CLEAR DETAIL OF THE METHOD OF SECURING
 THE WATER HEATER. THE SUPPLIED DETAILS ARE UNCLEAR.HOW
 IS THE EMT WITH FLATTENED EDGES BEING USED? THE PLAN
 SHOWS AN 8 INCH MINIMUM AND 24 INCH MAXIMUM FOR
 SOMETHING. THE DETAILS SRE VAGUE. CLARIFY.FBC-PLUMBING
 SEC. 308.4.
 29) THE WATER HEATER APPEARS TO BE LOCATED ABOVE THE
 MOP SINK.PROVIDE COMPLETE DETAILS FOR THE
 SHELF/PLATFORM, TYPE AND SIZE OF CONNECTIONS TO THE
 SHELF/PLATFORM AND TO THE BUILDING STRUCTURE, PROVIDE
 CLEARANCES FOR MAINTENANCE AND REPLACEMENT IN
 ACCORDANCE WITH FBC-PLUMBING SEC.502.5.
 30) SHT. P5-01 - THERE IS A NOTE AT THE WATER HEATER
 DETAIL THAT REFERS TO SHT. MPE-02. THERE IS NO SUCH
 DRAWING IN THIS SUBMITTAL. CLARIFY.
 31) SIZE ALL SECTIONS OF THE WATER RISER. WPB AMEND. TO
 FBC SEC. 107.2.1.
 32) SUBMIT SIZING CALCULATIONS FOR THE GREASE
 INTERCEPTOR. CALCULATIONS WERE NOT SUBMITTED UNDER THE
 SHELL PERMIT #19090177. FBC-PLUMBING SEC. 1003.2.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-02-23 Cont ID  
Sent By equinone Date 2021-02-23 Time 11:10 Rev Time 0.00
Received By equinone Date 2021-02-23 Time 11:10 Sent To  
Notes
2021-02-17 12:58:09PLUMBING SHEETS OK. T.LARGE

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-01-21 Cont ID  
Sent By equinone Date 2021-01-21 Time 14:37 Rev Time 0.00
Received By equinone Date 2021-01-21 Time 14:37 Sent To  
Notes
2021-01-21 14:38:50ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
 FS471, FS481, DOCUMENTS PREPARED BY AN ARCHITECT OR
 ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED, SEALED, DATED ORIGINALS. A SCAN OF A SIGNED
 PLAN IS NOT CONSIDERED AN ORIGINAL.
  
 EITHER UPLOAD A DIGITALLY OR ELECTRONICALLY SIGNED PLAN
 TO ME, OR YOU DROP ONE ORIGINAL SIGNED AND SEALED PAPER
 ORIGINAL WITH A WET SIGNATURE.
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 DEVELOPMENT SERVICES
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
  
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS,
 561-805-6746.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-10-20 Cont ID  
Sent By equinone Date 2020-10-20 Time 15:57 Rev Time 0.00
Received By equinone Date 2020-10-20 Time 15:57 Sent To  
Notes
2020-10-20 15:57:55ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
 FS471, FS481, DOCUMENTS PREPARED BY AN ARCHITECT OR
 ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED, SEALED, DATED ORIGINALS. A SCAN OF A SIGNED
 PLAN IS NOT CONSIDERED AN ORIGINAL.
  
 EITHER EMAIL A DIGITALLY OR ELECTRONICALLY SIGNED PLAN
 TO ME, OR YOU CAN MAIL (OR DROP OFF) ONE ORIGINAL
 SIGNED AND SEALED PAPER ORIGINAL WITH A WET SIGNATURE
 TO:
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 DEVELOPMENT SERVICES
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
  
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS,
 561-805-6746.
  