Plan Review Details - Permit 20100270
Plan Review Stops For Permit 20100270
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-12-17 Cont ID  
Sent By rmcphers Date 2020-12-17 Time 15:09 Rev Time 0.00
Received By rmcphers Date 2020-12-17 Time 15:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-12-14 Cont ID  
Sent By rmcphers Date 2020-12-14 Time 12:53 Rev Time 0.00
Received By rmcphers Date 2020-12-14 Time 12:53 Sent To  
Notes
2020-12-14 12:59:11INTERIOR REPAIRS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 2ND REVIEW
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW THE LOCATION OF THE REQUIRED SMOKE
 DETECTORS FBC R314.2.2 ALTERATIONS, REPAIRS AND
 ADDITIONS.
 WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS. R314.3 LOCATION.
 SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING
 LOCATIONS:
 1.IN EACH SLEEPING ROOM.
 2.OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE
 VICINITY OF THE BEDROOMS.
  
 2) IS THE INSULATION BEING REPLACED? IF SO SHOW THE
 INSULATION "R" VALUE - CAN COMPLY WITH FBC ENERGY 402.1
 (R30)
 3) PLEASE SHOW THE SIZE AND LOCATION OF THE ATTIC
 ACCESS TO COMPLY WITH FBC R807 (SHOW THE EXISTING
 LOCATION)

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-12-09 Cont ID  
Sent By rmcphers Date 2020-12-09 Time 13:41 Rev Time 0.00
Received By rmcphers Date 2020-12-09 Time 13:41 Sent To  
Notes
2020-12-09 14:01:48INTERIOR REPAIRS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW THE LOCATION OF THE REQUIRED SMOKE
 DETECTORS FBC R314.2.2 ALTERATIONS, REPAIRS AND
 ADDITIONS.
 WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS.
 2) IS THE INSULATION BEING REPLACED? IF SO SHOW THE
 INSULATION "R" VALUE CAN COMPLY WITH FBC ENERGY 402.1
 3) PLEASE SHOW THE SIZE AND LOCATION OF THE ATTIC
 ACCESS TO COMPLY WITH FBC R807 (SHOW THE EXISTING
 LOCATION)

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-12-11 Cont ID  
Sent By cthroop Date 2020-12-11 Time 16:37 Rev Time 0.00
Received By cthroop Date 2020-12-11 Time 16:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-12-09 Cont ID  
Sent By cthroop Date 2020-12-09 Time 11:25 Rev Time 0.00
Received By cthroop Date 2020-12-09 Time 10:56 Sent To  
Notes
2020-12-09 11:27:00PLAN REVIEW / ELECTRICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2014 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE AN ELECTRICAL PLAN. IDENTIFY LOCATION OF
 ELECTRICAL WORK.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-12-17 Cont ID  
Sent By rmcphers Date 2020-12-17 Time 15:14 Rev Time 0.00
Received By rmcphers Date 2020-12-16 Time 15:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-12-14 Cont ID  
Sent By rmcphers Date 2020-12-14 Time 12:59 Rev Time 0.00
Received By rmcphers Date 2020-12-09 Time 15:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-12-09 Cont ID  
Sent By rmcphers Date 2020-12-09 Time 14:01 Rev Time 0.00
Received By rmcphers Date 2020-12-01 Time 09:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-12-11 Cont ID  
Sent By cthroop Date 2020-12-11 Time 16:37 Rev Time 0.00
Received By cthroop Date 2020-12-11 Time 16:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-12-02 Cont ID  
Sent By cthroop Date 2020-12-02 Time 16:57 Rev Time 0.00
Received By cthroop Date 2020-12-02 Time 16:25 Sent To  
Notes
2020-12-02 16:59:49PLAN REVIEW / PLUMBING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2014 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE SHOWER PAN DETAIL.
  
 P2709.1 SHOWER PAN CONSTRUCTION. FBC 107.2.1
 WHERE A SHOWER RECEPTOR HAS A FINISHED CURB THRESHOLD,
 IT SHALL BE NOT LESS THAN 1 INCH (25 MM) BELOW THE
 SIDES AND BACK OF THE RECEPTOR. THE CURB SHALL BE NOT
 LESS THAN 2 INCHES (51 MM) AND NOT MORE THAN 9 INCHES
 (229 MM) DEEP WHEN MEASURED FROM THE TOP OF THE CURB TO
 THE TOP OF THE DRAIN. THE FINISHED FLOOR SHALL SLOPE
 UNIFORMLY TOWARD THE DRAIN NOT LESS THAN 1/4 UNIT
 VERTICAL IN 12 UNITS HORIZONTAL (2-PERCENT SLOPE) NOR
 MORE THAN 1/2 UNIT VERTICAL PER 12 UNITS HORIZONTAL
 (4-PERCENT SLOPE) AND FLOOR DRAINS SHALL BE FLANGED TO
 PROVIDE A WATER-TIGHT JOINT IN THE FLOOR.
  
 P2709.3 SHOWER PAN LINING INSTALLATION.
 LINING MATERIALS SHALL BE SLOPED ONE FOURTH UNIT
 VERTICAL IN 12 UNITS HORIZONTAL (2-PERCENT SLOPE) TO
 WEEP HOLES IN THE SUBDRAIN BY MEANS OF A SMOOTH,
 SOLIDLY FORMED SUBBASE, SHALL BE PROPERLY RECESSED AND
 FASTENED TO APPROVED BACKING SO AS NOT TO OCCUPY THE
 SPACE REQUIRED FOR THE WALL COVERING, AND SHALL NOT BE
 NAILED OR PERFORATED AT ANY POINT LESS THAN 1 INCH
 (25.4 MM) ABOVE THE FINISHED THRESHOLD.
  
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status N Date 2020-12-17 Cont ID  
Sent By rmcphers Date 2020-12-17 Time 15:10 Rev Time 0.00
Received By rmcphers Date 2020-12-17 Time 15:10 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2020-12-14 Cont ID  
Sent By rmcphers Date 2020-12-14 Time 12:59 Rev Time 0.00
Received By rmcphers Date 2020-12-14 Time 12:59 Sent To  
Notes
2020-12-11 16:38:05ELECTRICAL PLAN SIGNED BY CONTRACTOR. CT

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-12-02 Cont ID  
Sent By cthroop Date 2020-12-02 Time 16:29 Rev Time 0.00
Received By cthroop Date 2020-12-02 Time 16:28 Sent To  
Notes
2020-12-02 16:29:56PLAN REVIEW / SIGNATURES
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. DESIGNER SHALL PRINT NAME AND SIGN PLAN SHEETS.
  
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5), CHPT. 471, F.S. & 61G15 AND CHPT.
 481, F.S. & 61G1.
  
  