| 2020-10-27 15:39:27 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20100241 |
| | ADD: 1801 S. FLAGLER DR. # 1406 |
| | CONT: SHUTTER UP |
| | TEL: 561-588-2623 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. OCT. 27TH/2020 |
| | ACTION: DENIED |
| | |
| | 1) THE SUBMITTED FLOOR PLAN IS NOT DESIGNED BY A DESIGN |
| | PROFESSIONAL(ARCHITECT OR ENGINEER) BUT BY THE |
| | CONTRACTOR. THE CONTRACTOR NEEDS TO TAKE OWNERSHIP OF |
| | THE FLOORPLAN AND THE DESIGN PRESSURE SHEET. |
| | |
| | CERTIFICATION BY CONTRACTOR. 107.3.4.3 CERTIFICATION BY |
| | CONTRACTOR. PLEASE NOTE THE EXCEPTION TO ENGINEERED |
| | PLANS UNDER 471.003(H) ELECTRICAL/ PLUMBING/ |
| | MECHANICAL, 481.229(1)(C) (BUILDING) REQUIRES THE |
| | CONTRACTOR FOR THAT TRADE THAT WILL BE LICENSED IN THAT |
| | TRADE, WILL ALSO BE THE CONTRACTOR THAT DESIGNS THE |
| | SYSTEM UNDER THAT TRADE. THE CONTRACTOR (QUALIFIER) |
| | THAT CREATED / DRAWN THE SET OF PLANS WILL NEED TO |
| | IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE |
| | PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR |
| | THE TRADE YOU ARE LICENSED IN ON YOUR PLANS AND DESIGN |
| | PRESSURE CALCULATIONS. |
| | |
| | 2) PLEASE NOTE THE DESIGN PRESSURE CALCULATIONS |
| | SUBMITTED INDICATE YOU ARE TAKING PRESSURES FOR AN |
| | INTERIOR WALL ZONE4. |
| | WHAT THE CONTRACTOR DID NOT INCLUDE IN THIS SUBMITTAL |
| | IS A OVERALL FLOOR PLAN FOR THIS FLOOR AND THE LOCATION |
| | OF THE UNIT WITHIN THE FOOTPRINT OF THE BUILDING, THIS |
| | WILL ALLOW US TO DETERMINE IF THE LOCATION FOR ZONE 4 |
| | IS ACCURATE. 107.2.1.2. ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 3) THE DESIGN PRESSURE CALCULATIONS SUBMITTED: |
| | 3A) THE SUBMITTED DESIGN PRESSURE CALCULATION BUILDING |
| | INFORMATION NEEDS TO BE CORRECTED TO AN EXPOSURE D AND |
| | WIND ZONE 170 VULT. 2017 FBC-B 1609 & ASCE 7-10. |
| | |
| | 3B) BOTH THE 2017 FBC-B AND ASCE TABLE GO TO 60 FT WHEN |
| | YOU USE THE HEIGHT AND EXPOSURE ADJUSTMENT |
| | COEFFICIENTS. ABOVE 60 FEET YOU WILL NEED TO HAVE |
| | ENGINEERING SHEETS FOR THE CORRECT EXPOSURE AND HEIGHT |
| | OF THE BUILDING. THESE SHEETS NEED TO HAVE EITHER A |
| | SIGNED AND SEALED ORIGINAL SHEET OR DIGITALLY SIGNED |
| | AND SEALED SHEET. IN BOTH CASES THE PRESSURE DESIGN |
| | SHEET NEEDS TO BE UPLOADED INTO THE PLAN FILE TO ENABLE |
| | US TO VERIFY THE DIGITAL SIGNATURE. DIGITAL SIGNATURES |
| | NEED TO STAY IN AN ELECTRONIC FORMAT NOT DOWNLOADED |
| | BEFORE OUR REVIEW. NEGATIVE PRESSURES ARE TAKIN FROM |
| | THE BUILDING HEIGHT AND POSITIVE PRESSURES ARE TAKEN |
| | FROM GRADE TO THE FLOOR HEIGHT IN WHICH YOU ARE |
| | WORKING. |
| | |
| | 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 |
| | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |