| 2020-10-18 16:57:28 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20100238 |
| | ADD: 1411 N. FLAGLER DR. SUITE: 3902 |
| | CONT: TBD/ TO BE DETERMINED |
| | TEL: ???? |
| | E-MAIL: DOREEN @CDHAIRARCHITECT.COM |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: SUN. OCT. 18TH/2020 |
| | ACTION: DENIED |
| | |
| | 1) PLEASE NOTE IN THE FILE FOLDER THERE ARE TO FILES |
| | LABELED PERMIT APPLICATION EACH 2 PAGES, BUT THEY ARE |
| | BLANK. PERMIT LISTED NOW AS CONTRACTOR: TO BE |
| | DETERMINED. |
| | |
| | 2) SHEET A.210 THE DEMO FLOOR PLAN ALSO SHOWS THE |
| | PROPOSED FLOOR PLAN AS WELL. THE UNISEX RESTROOM |
| | ENLARGED FLOOR PLAN ALSO ON THIS PAGE. AS SHOWN THE |
| | INSWING DOOR CROSSES OVER THE REQUIRED CLEAR FLOOR |
| | SPACE FOR BOTH THE LAV AND WATER CLOSET SEE 2017 |
| | FBC-ACCESS. CODE 603.2.3. DOORS SHALL NOT SWING INTO |
| | THE CLEAR FLOOR SPACE OR CLEARANCES REQUIRED FOR ANY |
| | FIXTURE. DOORS SHALL BE PERMITTED TO SWING INTO THE |
| | REQUIRED TURNING SPACE. PLEASE SEE EXCEPTION 2. WHERE |
| | TOILET ROOMS ARE FOR INDIVIDUAL USE AND A CLEAR FLOORS |
| | SPACE COMPLYING WITH 305.3 IS PROVIDED WITHIN THE ROOM |
| | BEYOND THE ARC OF THE DOOR SWING. WHAT IS MISSING IS |
| | THE REQUIRED 30X48 INCH CLEAR FLOOR SPACE BEYOND THE |
| | ARC OF THE DOOR. USUALLY AT A 45% ANGLE TO THE DOOR |
| | ENTRANCE. |
| | |
| | 3) SHEET A310 ACCESSIBILITY RESTROOM WALL DETAILS, THE |
| | TOILET PAPER DISPENSER IS MISSING THE DIMENSION FROM |
| | THE FRONT OF THE WATER CLOSET TO THE CENTERLINE OF THE |
| | DISPENSER. TOILET PAPER DISPENSERS. 604.7. THE TOILET |
| | PAPER DISPENSER SHALL COMPLY WITH 309.4 AND SHALL BE 7 |
| | INCHES MINIMUM TO 9 INCHES MAXIMUM IN FRONT OF THE |
| | WATER CLOSET MEASURED TO THE CENTERLINE OF THE |
| | DISPENSER. |
| | |
| | 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 |
| | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |