Plan Review Details - Permit 20100237
Plan Review Stops For Permit 20100237
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2020-11-16 Cont ID  
Sent By cpuell Date 2020-11-16 Time 14:35 Rev Time 0.00
Received By cpuell Date 2020-11-16 Time 14:35 Sent To  
Notes
2020-11-16 14:35:45NEW OFFICE SPACE WILL HAVE THE ADDRESS OF 1380 CLARE
 AVE

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2020-11-05 Cont ID  
Sent By cpuell Date 2020-11-05 Time 09:32 Rev Time 0.00
Received By cpuell Date 2020-11-05 Time 09:32 Sent To  
Notes
2020-11-05 09:33:18IS NEW ENTRANCE FOR A NEW SUITE? PLEASE EMAIL A SITE
 PLAN, AERIAL OR SURVEY SHOWING THE EXACT LOCATION OF
 THE WORK BEING DONE. PLEASE EMAIL INFO TO
 [email protected]

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2020-11-28 Cont ID  
Sent By pvalenti Date 2020-11-28 Time 10:19 Rev Time 0.00
Received By pvalenti Date 2020-11-28 Time 10:00 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2020-11-16 Cont ID  
Sent By pvalenti Date 2020-11-16 Time 13:00 Rev Time 0.00
Received By pvalenti Date 2020-11-16 Time 12:59 Sent To  
Notes
2020-11-16 13:03:10PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561?805?6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 PLEASE SUBMIT YOUR ASBESTOS ACKNOWLEDGEMENT LETTER AS
 NOTED BELOW:
 ASBESTOS REQUIREMENTS:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS?AND?SERVICE
 S/ENVIRONMENTAL?HEALTH/AIR?QUALITY/ASBESTOS?DEMOLITION?
 RENOVATION.HTML
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-11-05 Cont ID  
Sent By pvalenti Date 2020-11-05 Time 07:10 Rev Time 0.00
Received By pvalenti Date 2020-11-05 Time 06:07 Sent To  
Notes
2020-11-05 07:11:42PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 ASBESTOS REQUIREMENTS:
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-11-28 Cont ID  
Sent By pvalenti Date 2020-11-28 Time 10:15 Rev Time 0.00
Received By pvalenti Date 2020-11-28 Time 10:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-11-05 Cont ID  
Sent By pvalenti Date 2020-11-05 Time 07:27 Rev Time 0.00
Received By pvalenti Date 2020-11-05 Time 06:07 Sent To  
Notes
2020-11-05 08:10:08PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 1) FBC B 107.2.1, PLEASE PROVIDE PRODUCT APPROVALS FOR
 WINDOWS AND DOOR TO BE INSTALLED.
 2) FBC B 107.2.1, PLEASE PROVIDE FASTENER/CONNECTION
 DETAILS FOR NEW 16 GAGE METAL STUD MATERIAL AT DOOR
 HEADER AREA.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-11-24 Cont ID  
Sent By pleduc Date 2020-11-24 Time   Rev Time 0.00
Received By pleduc Date 2020-11-24 Time 12:50 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-11-05 Cont ID  
Sent By pleduc Date 2020-11-05 Time   Rev Time 0.00
Received By pleduc Date 2020-11-05 Time 11:22 Sent To  
Notes
2020-11-05 11:36:14THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS NO INDICATION OF A DOOR SCHEDULE INCLUDING
 HANDLE TYPE, AND LOCK/LATCH.
  
 PER NFPA 101, CH 7, MEANS OF EGRESS
  
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM
 THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED.
 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY
 TO DOOR
 LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER EXPOSURE TO
 ELEVATED
 TEMPERATURE IN ACCORDANCE WITH THE LISTING, BASED ON
 LABORATORY
 FIRE TEST PROCEDURES.
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A
 TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM
 THE EGRESS
 SIDE.
  
 7.2.1.5.10* A LATCH OR OTHER FASTENING DEVICE ON A DOOR
 LEAF SHALL
 BE PROVIDED WITH A RELEASING DEVICE THAT HAS AN OBVIOUS
 METHOD OF
 OPERATION AND THAT IS READILY OPERATED UNDER ALL
 LIGHTING CONDITIONS.
 7.2.1.5.10.1 THE RELEASING MECHANISM FOR ANY LATCH
 SHALL BE
 LOCATED AS FOLLOWS:
 (1) NOT LESS THAN 34 IN. (865 MM) ABOVE THE FINISHED
 FLOOR FOR
 OTHER THAN EXISTING INSTALLATIONS
 (2) NOT MORE THAN 48 IN. (1220 MM) ABOVE THE FINISHED
 FLOOR
 7.2.1.5.10.2 THE RELEASING MECHANISM SHALL OPEN THE
 DOOR LEAF
 WITH NOT MORE THAN ONE RELEASING OPERATION, UNLESS
 OTHERWISE
 SPECIFIED IN 7.2.1.5.10.3, 7.2.1.5.10.4, OR
 7.2.1.5.10.6.
  
 PLEASE PROVIDE DETAILS IN COMPLIANCE WITH THE ABOVE.
  
  
 2) THERE ARE NO INDICATIONS OF AN INTERIOR EXT SIGN.
  
 PER NFPA 101, CH 7
  
 7.10.1.2 EXITS.
 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS
 THAT OBVIOUSLY
 AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED
 BY AN APPROVED
 SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT
 ACCESS.
  
 PLEASE PROVIDE IF APPLICABLE, PROVIDE JUSTIFICATION IF
 NONE INSTALLED.
  
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-12-10 Cont ID  
Sent By lmarchan Date 2020-12-10 Time 11:23 Rev Time 0.00
Received By lmarchan Date 2020-11-23 Time 16:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-11-21 Cont ID  
Sent By lmarchan Date 2020-11-21 Time 07:04 Rev Time 0.00
Received By lmarchan Date 2020-11-03 Time 09:07 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status P Date 2021-03-17 Cont ID  
Sent By shill Date 2021-03-17 Time 12:38 Rev Time 0.00
Received By shill Date 2021-03-17 Time 12:37 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-11-28 Cont ID  
Sent By pvalenti Date 2020-11-28 Time 10:19 Rev Time 0.00
Received By pvalenti Date 2020-11-28 Time 09:59 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-11-05 Cont ID  
Sent By pvalenti Date 2020-11-05 Time 07:13 Rev Time 0.00
Received By pvalenti Date 2020-11-05 Time 06:07 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2020-12-08 Cont ID  
Sent By kalexand Date 2020-12-08 Time 11:06 Rev Time 0.00
Received By kalexand Date 2020-12-08 Time 11:06 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2020-11-20 Cont ID  
Sent By kalexand Date 2020-11-20 Time 16:51 Rev Time 0.00
Received By kalexand Date 2020-11-20 Time 16:51 Sent To I
Notes
***NONE***