Plan Review Details - Permit 20100209
Plan Review Stops For Permit 20100209
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2021-01-08 Cont ID  
Sent By cpuell Date 2021-01-08 Time 11:45 Rev Time 0.00
Received By cpuell Date 2021-01-08 Time 11:45 Sent To  
Notes
2021-01-08 11:46:49212 E LAKEWOOD RD TO REMAIN FOR FRONT PROPERTY AND
 CASITA (NOT A LEGAL UNIT)

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2020-12-17 Cont ID  
Sent By cpuell Date 2020-12-17 Time 09:33 Rev Time 0.00
Received By cpuell Date 2020-12-17 Time 09:33 Sent To  
Notes
2020-12-17 09:34:15APPLICANT HAS NOT REACHED OUT YET, COMMENTS STILL
 STAND:
 PLEASE REACH OUT TO [email protected] TO DISCUSS
 ADDRESSING OPTIONS, PREVIOUSLY THERE WERE 2 ADDRESSES
 ON THE PARCEL, HOWEVER ONE WAS A 1/2 ADDRESS WHICH IS
 NO LONGER ALLOWED. I WOULD ALSO LIKE TO CHANGE THE
 ADDRESS TO FALL IN LINE WITH THE CITY ROAD CENTERPOINT.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2020-10-08 Cont ID  
Sent By cpuell Date 2020-10-08 Time 10:42 Rev Time 0.00
Received By cpuell Date 2020-10-08 Time 10:40 Sent To  
Notes
2020-10-08 10:42:11PLEASE REACH OUT TO [email protected] TO DISCUSS
 ADDRESSING OPTIONS, PREVIOUSLY THERE WERE 2 ADDRESSES
 ON THE PARCEL, HOWEVER ONE WAS A 1/2 ADDRESS WHICH IS
 NO LONGER ALLOWED. I WOULD ALSO LIKE TO CHANGE THE
 ADDRESS TO FALL IN LINE WITH THE CITY ROAD CENTERPOINT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-12-21 Cont ID  
Sent By jgomez Date 2020-12-21 Time 14:17 Rev Time 0.00
Received By jgomez Date 2020-12-21 Time 13:31 Sent To  
Notes
2020-12-21 13:31:3112/18/2020 TALKED TO SOFIA SCIALLA (CONTRACTOR). SHE
 SAID OK TO PASS BUILDING REVIEW WITH PROVISO. JG.
  
 BUILDING REVIEW APPROVED WITH PROVISO:
 1-THERE ARE 2 SEPARATE PERMIT APPLICATIONS:
 MAIN HOUSE 20100209 AND GUEST CASITA 20120600. ALL
 SUBPERMITS TO REFERENCE BOTH PERMIT NUMBERS.
  
 2- ENERGY CALCULATIONS:
 A)PROVIDE SEPARATE ENERGY CALCULATIONS FOR THE GUEST
 CASITA. SEC. R101.3 FBC-ENERGY CONSERVATION.
 B)ENERGY CALCULATIONS SUBMITTED. NEED INFORMATION ON
 TOP OF FORM: OWNER, BUILDER, PERMIT OFFICE AND
 JURISDICTION NUMBER 604700.
 C)REVISE A/C AREA. MAIN HOUSE AND GUEST CASITA AREA TO
 BE DONE ON SEPARATE FORMS FOR EACH BUILDING.
 D)REVISE WALL TYPE IN ITEM #9 ON PAGE 1 OF 6. ACCORDING
 TO PLANS THESE ARE WOOD BEARING WALLS.
 E)PAGE 2 OF 6 SHOWS A KITCHEN IN-THE GUEST CASITA.
 THERE IS NOT KITCHEN IN THE GUEST CASITA.
 F)REVISE/CLARIFY DOORS INFORMATION ON PAGE 4 OF 6.
 WHERE IS THE 6 X 8 WOOD DOOR BY THE KITCHEN ZONE. ALSO,
 WHERE ARE THE OTHER TWO WOOD DOORS?. NOTE: GLAZING IN
 DOORS NEEDS TO BE INCLUDED IN THE WINDOW GLAZING AREA.
 G)PROVIDE THE NAME OF PERSON GENERATING THE REPORT AS
 REQUIRED BY SEC. R405.4.2.1 FBC- ENERGY CONSERVATION.
 H)REVISE WINDOWS OVERHANG SEPARATION TO MATCH PLANS.
  
 3-AS DISCUSSED W/ SOFIA SCIALLA, RESUBMIT PRODUCT
 APPROVALS (EXCEPT FOR ROOFING PRODUCT APPROVALS).
 COORDINATE WITH ENGINEER'S LETTER, AND PRODUCT
 APPROVALS LISTED ON THE PRODUCT APPROVAL SCHEDULE ON
 SHEET 3 OF 10.
  
 4-PROVIDE ICC EVALUATION REPORT FOR THE ICYNENE
 INSULATION REVIEWED/APPROVED BY THE DESIGNER OF RECORD.
  
 5-HANDRAILS AND GUARDRAILS DEFERRED SUBMITTAL: PROVIDE
 SHOP DRAWINGS REVIEWED BY THE DESIGN PROFESSIONAL OF
 RECORD.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-12-11 Cont ID  
Sent By jgomez Date 2020-12-11 Time 17:58 Rev Time 0.00
Received By jgomez Date 2020-12-11 Time 14:42 Sent To  
Notes
2020-12-11 18:00:03RESIDENTIAL (R3) SECOND BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 ******NOTE:
 SINCE THERE ARE TWO SEPARATE BUILDINGS IN THIS
 PROPERTY, THEN A SEPARATE PERMIT APPLICATION WILL BE
 REQUIRED FOR EACH EACH BUILDING. ONE FOR THE MAIN HOUSE
 AND ONE FOR THE GUEST CASITA.
 I GENERATED A NEW PERMIT NUMBER 20120600 FOR THE GUEST
 CASITA USING THE SAME APPLICATION SUBMITTED FOR THE
 MAIN HOUSE. GUEST CASITA APPLICATION WAS UPLOADED T
 PROJECTDOX. SAME PLANS CAN BE USED. I WILL CONTACT
 CONTRACTOR TO CLARIFY/COORDINATE.
 SEPARATE PERMIT APPLICATIONS HELP TO COORDINATE
 INSPECTIONS FOR EACH BUILDING AND TO FACILITATE RECORDS
 KEEPING. SEC. 107.2.1.3 CITY AMENDMENTS.
  
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO IF SURVEY
 OR SITE PLAN IS PROVIDED SHOWING THE BUILDINGS
 SETBACKS.
  
 PROVISO MEANS CONTRACTOR WILL SUBMIT REQUIRED
 INFORMATION AFTER THE PERMIT IS ISSUED BUT BEFORE
 INSPECTIONS TO AVOID CONFLICTS/DELAYS. REVISION FEES
 MAY APPLY. CONTRACTOR TO ADVICE IF PROVISO OPTION IS
 PREFERRED AT THIS TIME OR IF RE-SUBMITTING REQUIRED
 INFORMATION BEFORE PERMIT ISSUANCE.
  
  
  
  
 ORIGINAL COMMENT:
 1-PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 R101.5.1 FBC-ENERGY CONSERVATION.
 NOTE: PLEASE MAKE SURE FORMS ARE PROPERLY SIGNED BY ALL
 REQUIRED PARTIES, INCLUDING THE OWNER OR LEGALLY
 AUTHORIZED AGENT.
  
 RESPONSE:
 ENERGY CALCULATIONS SUBMITTED:
 A)THERE ARE TWO SEPARATE BUILDINGS IN THIS PROPERTY.
 MAIN HOUSE AND GUEST CASITA. NEED A SEPARATE ENERGY
 CALCULATIONS FOR EACH BUILDING.
 SEC. R101.2 FBC-ENERGY CONSERVATION. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 B)PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER, BUILDER AND PERMIT OFFICE AND
 JURISDICTION NUMBER (THIS JURISDICTION IS 604700) .
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 C)REVISE A/C AREA. MAIN HOUSE AND GUEST CASITA AREA TO
 BE DONE ON SEPARATE FORMS FOR EACH BUILDING.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 D)REVISE WALL TYPE IN ITEM #9 ON PAGE 1 OF 6. ACCORDING
 TO PLANS THESE ARE WOOD BEARING WALLS. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 E)PAGE 2 OF 6 SHOWS A KITCHEN IN-THE GUEST CASITA.
 THERE IS NOT KITCHEN IN THE GUEST CASITA. REVISE THIS
 WHEN DOING GUEST CASITA ON SEPARATE FORM.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 F)REVISE/CLARIFY DOORS INFORMATION ON PAGE 4 OF 6.
 WHERE IS THE 6 X 8 WOOD DOOR BY THE KITCHEN ZONE. SEE
 PLANS AND PRODUCT APPROVALS AND REVISE AS REQUIRED.
 ALSO, WHERE ARE THE OTHER TWO WOOD DOORS?. NOTE:
 GLAZING IN DOORS NEEDS TO BE INCLUDED IN THE WINDOW
 GLAZING AREA. SEE SEC. R405.5.3 FBC-ENERGY
 CONSERVATION).
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 G)PROVIDE THE NAME OF PERSON PERFORMING THE ANALYSIS
 AND GENERATING THE REPORT AS REQUIRED BY SEC.
 R405.4.2.1 FBC- ENERGY CONSERVATION.
  
 H)REVISE WINDOWS OVERHANG SEPARATION TO MATCH PLANS.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 ORIGINAL COMMENT:
 2- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 R401.3 FBC-RESIDENTIAL.
 SEC. 107.2.5 CITY AMENDMENTS.
 SEC. 110.9 CITY AMENDMENTS.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED. PROVIDE COMPLETE SITE
 PLAN DRAWN TO SCALE SHOWING THE BUILDINGS AND PROPOSED
 DRAINAGE. ALSO, SHOW THE DISTANCES FROM LOT LINES, ETC.
 SEE SEC. 107.2.5 CITY AMENDMENTS.
  
 3- OK
 4- OK
 5-OK
  
 6-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL):
  
 RESPONSE:
 PRODUCT APPROVALS NEED TO BE COORDINATED. PRODUCT
 APPROVALS UPLOADED TO PROJECTDOX AND PRODUCT APPROVALS
 LISTED ON THE SEPARATE ENGINEER'S LETTER (PRODUCT
 APPROVAL) AND PRODUCT APPROVALS LISTED ON THE PRODUCT
 APPROVAL SCHEDULE ON SHEET 3 OF 10 DON'T MATCH.
 PLEASE COORDINATE ALL PRODUCT APPROVALS, PRODUCT
 APPROVALS NUMBERS, ETC AND RESUBMIT. NOTE: TO AVOID
 CONFLICTS/DELAYS THIS CAN BE DONE LATER AFTER THE
 PERMIT IS ISSUED. NO PLAN REVIEW FEE FOR THIS. ALSO,
 SEE COMMENT BELOW FOR GARAGE DOOR.
  
 ******GARAGE DOOR NOA 20-0107.06 SUBMITTED. DOESN'T
 MEET THE DESIGN PRESSURES CALCULATED BY THE ENGINEER OF
 RECROD AND NOA DOESN'TMATCH ONE SPECIFIED ON THE
 PRODUCT APPROVAL SCHEDULE ON SHEET 3 OF 10.
  
 ***DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS
  
 7-HOUSE IS DESIGNED WITH UNVENTED ATTIC. DESIGNER OF
 RECORD IS SPECIFYING ICYNENE SPRAY INSULATION. PROVIDE
 ICC EVALUATION REPORT FOR THE ICYNENE INSULATION TO
 VERIFY COMPLIANCE WITH SEC. R316 FBC-RESIDENTIAL.
 NOTE: DESIGNER OF RECORD TO REVIEW AND APPROVE THE
 REPORT IN WRITING PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 RESPONSE:
 NO SUBMITTED. NOTE: THIS MAY BE SUBMITTED LATER AS A
 DEFERRED SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR
 TO INSTALLATION TO AVOID CONFLICTS/DELAYS.
  
 8-PROVISO: HANDRAILS AND GUARDRAILS DEFERRED SUBMITTAL:
 PROVIDE SHOP DRAWINGS REVIEWED BY THE DESIGN
 PROFESSIONAL OF RECORD PRIOR TO INSTALLATION TO AVOID
 CONFLICTS/DELAYS.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-10-27 Cont ID  
Sent By jgomez Date 2020-10-27 Time 09:37 Rev Time 0.00
Received By jgomez Date 2020-10-26 Time 11:25 Sent To  
Notes
2020-10-27 09:38:48RESIDENTIAL (R3) BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1-PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 R101.5.1 FBC-ENERGY CONSERVATION.
 NOTE: PLEASE MAKE SURE FORMS ARE PROPERLY SIGNED BY ALL
 REQUIRED PARTIES, INCLUDING THE OWNER OR LEGALLY
 AUTHORIZED AGENT.
  
 2- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 R401.3 FBC-RESIDENTIAL.
 SEC. 107.2.5 CITY AMENDMENTS.
 SEC. 110.9 CITY AMENDMENTS.
  
 3- ENGINEERING CRITERIA ON SHEET 2 OF 10:
 A)ACCORDING TO SEC. R301.2.1.4.3 FBC-RESIDENTIAL THIS
 BUILDING IS LOCATED IN EXPOSURE "D" NOT "C". REVISE AS
 REQUIRED AND REVISE THE COMPONENTS AND CLADDING DESIGN
 PRESSURES ACCORDINGLY.
  
 B)DESIGN LOADS SPECIFY A FLOOR LIVE/DEAD LOAD OF
 100PSF. CLEARLY IDENTIFY THE SECOND FLOOR LIVE LOAD AND
 DEAD LOAD FOR WHICH FLOOR TRUSSES ARE DESIGNED. SEC.
 107.2.1 CITY AMENDMENTS.
  
 C) DESIGN LOADS SPECIFY A ROOF LIVE/DEAD LOAD OF 45PSF.
 CLEARLY IDENTIFY THE ROOF LIVE LOAD AND DEAD LOAD FOR
 WHICH ROOF TRUSSES ARE DESIGNED, INCLUDING THE ATTIC
 LIVE LOADS WITH STORAGE. SEC. 107.2.1 CITY AMENDMENTS
 AND TABLE R301.5 FBC-RESIDENTIAL.
  
 4- SHEET 7 OF 10:
 A) PROVIDE DETAIL SHOWING HOW THE TWO FLOOR GIRDER
 TRUSSES ARE CONNECTED TO THE THE WALL WHEN THEY MEET AT
 THE INTERSECTION BETWEEN THE KITCHEN AREA AND THE
 MORNING ROOM. SEC. 107.2.1.2 CITY AMENDMENTS.
  
 B) CLARIFY SPACING OF FLOOR TRUSSES SHOWN ON THE FLOOR
 FRAMING PLAN. THERE IS A NOTE SPECIFYING 24" FLOOR
 TRUSSES @ 24" O.C, BUT TRUSSES ABOVE OFFICE AND GREAT
 ROOM ARE SHOWN WHAT LOOKS TO BE 16" O.C. SPACING, WHILE
 OTHER FLOOR TRUSSES ARE SHOWN WHAT LOOKS TO BE 24"
 O.C.. REVISE/ CLARIFY AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 5-SPECIFY THE SIZE OF THE ATTIC ACCESS SHOWN ON THE
 GUEST CASITA, TWO CAR GARAGES IN THE MAIN HOUSE AND IN
 SECOND FLOOR OF MAIN HOUSE.
 SEC. R807 FBC-RESIDENTIAL.
  
 6-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL):
  
 A) FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY
 IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 B) ROOF TILE AND CLEARLY SPECIFY ROOF TILE FASTENING
 METHOD AS REQUIRED BY CITY POLICY FOR ALL ROOFING
 PERMITS. FOR MECHANICALLY ATTACHED TILE PROVIDE
 COMPLETE TILE FASTENING INFORMATION.
  
 C)ROOF TILE ADHESIVE IF SELECTED AS THE FASTENING
 METHOD. CLEARLY IDENTIFY PADDY SIZE.
  
 D)GARAGE OVERHEAD DOOR. NOA 17-1018.12 SUBMITTED
 EXPIRED ON JULY 21, 2020. NEED CURRENT ONE.
  
 E)DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS
  
 7-HOUSE IS DESIGNED WITH UNVENTED ATTIC. DESIGNER OF
 RECORD IS SPECIFYING ICYNENE SPRAY INSULATION. PROVIDE
 ICC EVALUATION REPORT FOR THE ICYNENE INSULATION TO
 VERIFY COMPLIANCE WITH SEC. R316 FBC-RESIDENTIAL.
 NOTE: DESIGNER OF RECORD TO REVIEW AND APPROVE THE
 REPORT IN WRITING PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 8-HANDRAILS AND GUARDRAILS DEFERRED SUBMITTAL: PROVIDE
 SHOP DRAWINGS REVIEWED BY THE DESIGN PROFESSIONAL OF
 RECORD PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-02-03 Cont ID  
Sent By fgiaquin Date 2021-02-03 Time 21:08 Rev Time 0.00
Received By fgiaquin Date 2021-02-03 Time 20:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-12-15 Cont ID  
Sent By equinone Date 2020-12-15 Time 09:18 Rev Time 0.00
Received By equinone Date 2020-12-15 Time 09:18 Sent To  
Notes
2020-12-15 09:29:43CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
  
 ELECTRICAL REVIEW STATUS: FAILED, SEE COMMENTS BELOW.
  
 FROM PREVIOUS COMMENTS:
  
 1. CANNOT DE-RATE SERVICE ENTRANCE CONDUCTOR SIZES WHEN
 MORE THAN ONE PANEL SERVES A DWELLING. NEC 310.15 (B)
 (7) (1) NEC 230.23(A). SIZE 3/0 IS REQUIRED FOR 200AMP
 SERVICE ENTRANCE CONDUCTORS AND 1/0 IS REQUIRED FOR
 150AMP SERVICE ENTRANCE CONDUCTORS
  
 THE 150 AMPS SERVICE WAS CHANGED TO 200 AMPS AND IT
 WILL ALSO REQUIRE A SIZE 3/0 SERVICE ENTRANCE
 CONDUCTOR. PLEASE CORRECT.
  
 NEW COMMENTS:
  
 2. A NEW STEAM UNIT WAS ADDED TO PLANS. THE STEAM UNIT
 SPECS INDICATES A 7.2 KW/31AMPS LOAD WITH A 40 AMPS
 FUSE, BUT PANEL SCHEDULE SHOWS A 12KW LOAD WITH 50 AMPS
 BREAKER. PLEASE CORRECT DISCREPANCIES.
  
 3. PLEASE SHOW CIRCUIT AND DISCONNECT FOR STEAM UNIT ON
 POWER PLAN
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-10-26 Cont ID  
Sent By fgiaquin Date 2020-10-26 Time 22:24 Rev Time 0.00
Received By fgiaquin Date 2020-10-26 Time 21:41 Sent To  
Notes
2020-10-26 22:24:54ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. CANNOT DE-RATE SERVICE ENTRANCE CONDUCTOR SIZES WHEN
 MORE THAN ONE PANEL SERVES A DWELLING. NEC 310.15 (B)
 (7) (1) NEC 230.23(A)
  
 3/0 IS REQUIRED FOR 200AMP SERVICE ENTRANCE CONDUCTORS
 AND 1/0 IS REQUIRED FOR 150AMP SERVICE ENTRANCE
 CONDUCTORS
  
 2. "OPTIONAL" GENERATOR MUST BE REMOVED FROM PLANS. IF
 AND WHEN A GENERATOR IS INSTALLED IT IS REQUIRED TO BE
 INSTALLED WITH A SEPARATE STAND ALONE PERMIT. FBC 105.1
 FBC 107.2.1
  
 3. ELECTRICAL NOTE #8 DOES NOT LIST LAUNDRY ROOMS FOR
 AFCI PROTECTION. PROVIDE CORRECTION. NEC210.12A
  
 4. ALARMS OUTSIDE OF BEDROOMS MUST BE SMOKE/CARBON
 ALARMS WHEN THE HOME HAS A GAS APPLIANCE, FIREPLACE, OR
 ATTACHED GARAGE PER FBC RE 314 &315 PROVIDE CORRECTION.
  
 5. PROVIDE NOTE ON PLAN ALL LOW VOLTAGE SYSTEMS WILL
 REQUIRE A SEPARATE PERMIT. FBC 107.2.1
  
 6. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
  
  
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2021-02-03 Cont ID  
Sent By ccole Date 2021-02-03 Time 15:34 Rev Time 0.00
Received By ccole Date 2021-02-03 Time 13:49 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2021-01-06 Cont ID  
Sent By ccole Date 2021-01-06 Time 17:46 Rev Time 0.00
Received By ccole Date 2021-01-06 Time 17:46 Sent To  
Notes
2021-01-06 17:47:162ND REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20100209
 1/6/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED. A COMPLETE REVIEW OF THE
 GAS PLANS WAS NOT COMPLETED AT THIS TIME DUE A LACK OF
 INFORMATION PROVIDED ON THE PLANS. PLEASE REVIEW THE
 COMMENTS BELOW AND RESUBMIT COMPLIANT PLANS AND
 SPECIFICATIONS.
  
 1) SHEET 10 GAS RISER CORRECTIONS- FBC-17 RES. FUEL
 GAS:
 A) PROVIDE THE DELIVERY PRESSURE AT THE METER- G2413.1.
 B) CORRECT THE TOTAL BTU LOAD TO 1020 K- SECTION
 G2413.2.
 C) PROVIDE THE TYPES AND SIZES OF BRANCH PIPING TO THE
 TANKLESS WATER HEATERS AND THE RANGE- G2413.4.1 &
 G2413.4.2.
 D) LIST THE PIPE SIZING TABLES USED TO DESIGN THE
 SYSTEM- G2413.3 & G2413.4.
  
 2) LIST THE MAKES AND MODELS OF THE WATER HEATERS AND
 SUBMIT MANUFACTURER'S SPECIFICATIONS- G2448.1. THE
 SPECS AND INSTALL MANUALS MAY BE DEFERRED AND SUBMITTED
 AT A LATER DATE, BUT ALL SPECS AND INSTALL MANUALS
 SHALL BE ONSITE AT TIME OF INSPECTION- SECTIONS 107.2.1
 AND 107.3.4.1 WPB.
  
 3) LIST THE MAKES AND MODELS OF THE FIREPLACE, FIREPIT,
 POOL HEATER, DRYER, RANGE, AND BBQ GRILL ON THE PLAN
 AND SUBMIT MANUFACTURER'S SPECIFICATIONS. PLEASE NOTE
 THE SPECS AND INSTALL MANUALS MAY BE DEFERRED AND
 SUBMITTED AT A LATER DATE, BUT ALL SPECS AND INSTALL
 MANUALS SHALL BE ONSITE AT TIME OF INSPECTION- SECTIONS
 107.2.1 AND 107.3.4.1 WPB.
  
 4) SUBMIT MARKED UP OR HIGHLIGHTED REGULATOR SPECS
 SHOWING THE SELECTED MODELS, THE MAX INLET AND OUTLET
 SIZES AND PRESSURES AND ORIFICE SIZES. THE SPECS MAY BE
 DEFERRED AND BE ONSITE FOR INSPECTION.
  
 5) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE GAS
 RANGE AND THE FIREPLACE AND SHOW HOW THE AIR IS BEING
 PROVIDED- SECTION G2407.1.
  
 6) PROVIDE MAKEUP AIR CALCULATIONS FOR THE DRYER AND
 SHOW HOW THE AIR IS BEING PROVIDED- G2439.5.
  
 7) PROVIDE A VENTING DIAGRAM FOR THE FIREPLACE SHOWING
 THE TYPE AND SIZE OF VENT FLUE, VENT RUN, AND
 TERMINATION LOCATION- G2427.8(3).
  
 8) PLEASE SHOW THE LOCATION OF THE FIREPIT ON THE FLOOR
 PLAN DRAWINGS- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-01-06 Cont ID  
Sent By ccole Date 2020-10-22 Time 12:45 Rev Time 0.00
Received By ccole Date 2020-10-22 Time 10:04 Sent To  
Notes
2021-01-06 17:52:391ST REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20100209
 10/22/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED. A COMPLETE REVIEW OF THE
 GAS PLANS WAS NOT COMPLETED AT THIS TIME DUE A LACK OF
 INFORMATION PROVIDED ON THE PLANS. PLEASE REVIEW THE
 COMMENTS BELOW AND RESUBMIT COMPLIANT PLANS AND
 SPECIFICATIONS.
  
 1) SHEET 10 GAS RISER CORRECTIONS- FBC-17 RES. FUEL
 GAS:
 A) PROVIDE THE DELIVERY PRESSURE AT THE METER- G2413.1.
 B) CORRECT THE TOTAL BTU LOAD TO 1020 K- SECTION
 G2413.2.
 C) PROVIDE THE TYPES AND SIZES OF BRANCH PIPING TO THE
 TANKLESS WATER HEATERS AND THE RANGE- G2413.4.1 &
 G2413.4.2.
 D) LIST THE PIPE SIZING TABLES USED TO DESIGN THE
 SYSTEM- G2413.3 & G2413.4.
  
 2) LIST THE MAKES AND MODELS OF THE WATER HEATERS AND
 SUBMIT MANUFACTURER'S SPECIFICATIONS- G2448.1. THE
 SPECS AND INSTALL MANUALS MAY BE DEFERRED AND SUBMITTED
 AT A LATER DATE, BUT ALL SPECS AND INSTALL MANUALS
 SHALL BE ONSITE AT TIME OF INSPECTION- SECTIONS 107.2.1
 AND 107.3.4.1 WPB.
  
 3) LIST THE MAKES AND MODELS OF THE FIREPLACE, FIREPIT,
 POOL HEATER, DRYER, RANGE, AND BBQ GRILL ON THE PLAN
 AND SUBMIT MANUFACTURER'S SPECIFICATIONS. PLEASE NOTE
 THE SPECS AND INSTALL MANUALS MAY BE DEFERRED AND
 SUBMITTED AT A LATER DATE, BUT ALL SPECS AND INSTALL
 MANUALS SHALL BE ONSITE AT TIME OF INSPECTION- SECTIONS
 107.2.1 AND 107.3.4.1 WPB.
  
 4) SUBMIT MARKED UP OR HIGHLIGHTED REGULATOR SPECS
 SHOWING THE SELECTED MODELS, THE MAX INLET AND OUTLET
 SIZES AND PRESSURES AND ORIFICE SIZES. THE SPECS MAY BE
 DEFERRED AND BE ONSITE FOR INSPECTION.
  
 5) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE GAS
 RANGE AND THE FIREPLACE AND SHOW HOW THE AIR IS BEING
 PROVIDED- SECTION G2407.1.
  
 6) PROVIDE MAKEUP AIR CALCULATIONS FOR THE DRYER AND
 SHOW HOW THE AIR IS BEING PROVIDED- G2439.5.
  
 7) PROVIDE A VENTING DIAGRAM FOR THE FIREPLACE SHOWING
 THE TYPE AND SIZE OF VENT FLUE, VENT RUN, AND
 TERMINATION LOCATION- G2427.8(3).
  
 8) PLEASE SHOW THE LOCATION OF THE FIREPIT ON THE FLOOR
 PLAN DRAWINGS- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-02-03 Cont ID  
Sent By fgiaquin Date 2021-02-03 Time 21:09 Rev Time 0.00
Received By fgiaquin Date 2021-01-27 Time 09:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-01-15 Cont ID  
Sent By lmarchan Date 2021-01-15 Time 15:07 Rev Time 0.00
Received By lmarchan Date 2020-12-01 Time 10:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-11-15 Cont ID  
Sent By cpuell Date 2020-11-15 Time 18:38 Rev Time 0.00
Received By cpuell Date 2020-10-08 Time 07:31 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2021-02-01 Cont ID  
Sent By lmarchan Date 2021-02-01 Time 09:16 Rev Time 0.00
Received By lmarchan Date 2021-01-15 Time 15:07 Sent To  
Notes
2021-02-01 09:17:04MU-2021-4071 - $0.00 DUE
2021-01-15 15:07:481/15/21 EMALED IMPACT OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-10-27 Cont ID  
Sent By jgomez Date 2020-10-27 Time 09:40 Rev Time 0.00
Received By jgomez Date 2020-10-27 Time 09:40 Sent To  
Notes
2020-10-27 09:41:03 
 IMPACT FEES - DIGITAL SUBMITTALS
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2021-02-01 Cont ID  
Sent By medwards Date 2021-02-01 Time 16:53 Rev Time 0.00
Received By medwards Date 2021-02-01 Time 16:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2020-12-05 Cont ID  
Sent By medwards Date 2020-12-05 Time 10:55 Rev Time 0.00
Received By medwards Date 2020-12-05 Time 10:37 Sent To  
Notes
2020-12-05 10:57:051ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20100209
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 PLEASE RESPOND TO THE PREVIOUS REVIEW COMMENTS 4 AND 6.
  
 4) PLEASE PROVIDE DETAILS FOR SECURING THE CONDENSING
 UNITS. FBC RES M1307.2
  
 6) PLEASE SHOW ON MECHANICAL DRAWING THE CONDENSATE
 DISPOSAL LOCATION. FBC RES M1411.3
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-10-14 Cont ID  
Sent By medwards Date 2020-10-14 Time 14:10 Rev Time 0.00
Received By medwards Date 2020-10-14 Time 13:38 Sent To  
Notes
2020-10-14 14:10:301ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20100209
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 COULD NOT DO A MECHANICAL REVIEW AS THERE WAS NO
 MECHANICAL INFORMATION SUBMITTED IN THIS SUBMITTAL.
  
 1) PLEASE PROVIDE CODE COMPLIANT MECHANICAL DRAWINGS
 FOR THIS NEW RESIDENCE. FBC 107.2.1
  
 2) PLEASE PROVIDE ENERGY CALCULATIONS. FBC EC
 101.5.1.1.2
  
 3) PLEASE PROVIDE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FBC EC R403.7
  
 4) PLEASE PROVIDE DETAILS FOR SECURING THE CONDENSING
 UNITS. FBC RES M1307.2
  
 5) PLEASE PROVIDE DETAILS OF THE RETURN AIR BALANCING
 ON THE DRAWINGS. FBC RES M1602.3
  
 6) PLEASE SHOW ON MECHANICAL DRAWING THE CONDENSATE
 DISPOSAL LOCATION. FBC RES M1411.3
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-02-03 Cont ID  
Sent By ccole Date 2021-02-03 Time 15:34 Rev Time 0.00
Received By ccole Date 2021-02-03 Time 13:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-12-09 Cont ID  
Sent By ccole Date 2020-12-09 Time 17:38 Rev Time 0.00
Received By ccole Date 2020-12-09 Time 17:38 Sent To  
Notes
2020-12-09 17:39:052ND REVIEW FBC-2017 RES. PLUMBING
 PERMIT- 20100209
 12/9/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS 10A & 10B: THE NEW WATER RISERS SHOW 3/8 IN.
 FIXTURE SUPPLY PIPES TO THE 1ST FLOOR SINKS, WASHING
 MACHINE, AND THE 2ND FLOOR BATHTUB, SHOWERS, AND SINKS.
 PLEASE REFER TO SECTIONS P2601.1 P2903.8.2 FBC RES, AND
 TABLE 604.5 FBC P AND PROVIDE MIN. 1/2 IN. SUPPLY PIPES
 TO THE FIXTURES.
  
 2) SHEETS 10,10A, & 10B: BASED ON THE NEW NOTES
 CONCERNING THE HOT WATER SYSTEM IT APPEARS A
 RECIRCULATING PUMP WILL BE INSTALLED. ARE THE TANKLESS
 WATER HEATERS EQUIPPED WITH RECIRCULATION PUMPS OR WILL
 A SEPARATE PUMP BE INSTALLED? PLEASE PROVIDE ADDITIONAL
 INFORMATION AND DETAILS- SECTION 107.2.1 WPB. PLEASE
 REVISE THE NOTES TO INDICATE THE APPLICABLE CODE
 SECTIONS FROM THE FBC RES AND FBC EC.
  
 3) COMMENT #5 FROM THE 1ST REVIEW CONCERNING THE HOT
 WATER SYSTEM PARTIALLY ADDRESSED. PLEASE PROVIDE WATER
 HEATER EQUIPMENT SCHEDULES THAT INCLUDE THE EFFICIENCY
 RATINGS ON THE PLAN AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS- SECTIONS P2801.3 & G2448.1 FBC RES.
  
 4) SHEET 10: 2ND REQUEST TO SHOW A TWO-WAY CLEANOUT
 WILL BE INSTALLED AT THE BUILDING DRAIN/SEWER PIPE
 JUNCTIONS- SECTION P3005.2.8 FBC RES.
  
 5) SHEET 10: AS PREVIOUSLY NOTED A SEPARATE PERMIT AND
 PLANS ARE REQUIRED FOR THE GAS PIPING INSTALLATIONS-
 SECTIONS 105.1 & 107.2.1 WPB. A COMPLETE REVIEW OF THE
 REQUIRED GAS PIPING SYSTEMS, THE APPLIANCES AND
 GENERATOR SHOWN ON THE PLAN, AND THE REQUIRED
 COMBUSTION AIR AND VENTING PLANS WILL NOT BE PERFORMED
 UNDER THIS PERMIT.
  
 6) 2ND REQUEST FOR A PLUMBING SUB-PERMIT- SECTION 105.1
 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-10-22 Cont ID  
Sent By ccole Date 2020-10-22 Time 12:42 Rev Time 0.00
Received By ccole Date 2020-10-22 Time 09:48 Sent To  
Notes
2020-10-22 12:43:071ST REVIEW FBC-2017 RES. PLUMBING
 PERMIT- 20100209
 10/22/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SUBMIT A PLUMBING SUB-PERMIT APPLICATION- SECTION
 105.1 WPB.
  
 2) PLEASE NOTE A SEPARATE PERMIT AND PLANS ARE REQUIRED
 FOR THE GAS PIPING INSTALLATIONS- SECTIONS 105.1 &
 107.2.1 WPB. A COMPLETE REVIEW OF THE REQUIRED GAS
 PIPING SYSTEMS, THE APPLIANCES AND GENERATOR SHOWN ON
 THE PLAN, AND THE REQUIRED COMBUSTION AIR AND VENTING
 PLANS WILL NOT BE PERFORMED UNDER THIS PERMIT.
  
 3) PLEASE PROVIDE A PLUMBING FLOOR PLAN AND SITE
 DRAWING SHOWING THE SANITARY DRAINAGE AND WATER
 DISTRIBUTION PIPING LAYOUTS INCLUDING THE LOCATIONS OF
 THE WATER METER, MAIN SHUTOFFS VALVES FOR THE MAIN
 HOUSE AND GUEST HOUSE, LOCATIONS OF BACKFLOW PREVENTERS
 FOR THE MAIN POTABLE WATER SUPPLY SYSTEMS, AND AT WATER
 SUPPLY CONNECTIONS TO IRRIGATION SYSTEMS AND POOL
 EQUIPMENT, AND LOCATIONS OF HOSE BIBS- SECTION 107.2.1
 WPB AND SECTIONS P2902.1, P2902.1, P2903.1 & P2903.9
 FBC RES. PLEASE PROVIDE COMPLETE PLUMBING NOTES
 INDICATING AT A MINIMUM THE TYPES OF PIPING MATERIALS,
 FIXTURE SHUTOFF VALVES, INDIVIDUAL BATHTUB AND SHOWER
 VALVES, AND PIPE INSULATIONS TO BE INSTALLED ETC.-
 P2609 FBC RES.
  
 4) SHEET 10 SANITARY RISER:
  
 A) SHOW THE REQUIRED 3 IN. FIXTURE BRANCH DRAINS AND
 STACKS FOR THE WASHING MACHINES- SECTION 406.2 FBC P.
  
 B) SHOW THE REQUIRED CLEANOUTS AT THE BASES OF THE 3
 VERTICAL STACKS- SECTION P3005.2.4 FBC RES.
  
 C) THE WATER CLOSET IN THE ENSUITE BATHROOM WILL
 REQUIRE AN INDIVIDUAL VENT BECAUSE IT IS NOT PART OF
 THE BATHROOM WET VENT- NOT MORE THAN ONE WET-VENTED
 FIXTURE DRAIN SHALL DISCHARGE UPSTREAM OF THE
 DRY-VENTED FIXTURE DRAIN CONNECTION- SECTION P3108.2.1
 FBC RES.
  
 D) SHOW THE DISHWASHER DRAIN CONNECTION- SECTION
 P2717.2 FBC RES.
  
 E) PROVIDE A CLEANOUT AT THE JUNCTION OF THE GUEST
 HOUSE BUILDING DRAIN AND BUILDING SEWER- SECTION
 P3005.2.3 FBC RES. SHOW A TWO-WAY CLEANOUT WILL BE
 INSTALLED BUILDING DRAIN/SEWER PIPE JUNCTIONS- SECTION
 P3005.2.8 FBC RES.
  
 F) SHOW THE LOCATION OF THE CLEANOUT FOR THE OUTDOOR
 PATIO SINK- SECTION P3003.5.2.
  
 G) IT APPEARS THAT THE DRAIN AND VENT FOR ONE OF THE
 KITCHEN ISLAND SINKS IS MISSING FROM THE DRAWING-
 SECTION 107.2.1 WPB.
  
 5) INDICATE HOW HOT WATER WILL BE PROVIDED TO THE
 FIXTURES- SECTION P2801.1 FBC RES. PROVIDE A FLOOR PLAN
 DRAWING SHOWING THE LOCATIONS OF THE WATER HEATERS.
 PROVIDE EQUIPMENT SCHEDULES ON THE PLAN AND SUBMIT
 MANUFACTURER?S SPECIFICATIONS- SECTIONS P2801.3 &
 G2448.1 FBC RES. IT APPEARS FROM THE ELECTRICAL
 DRAWINGS THAN GAS-FIRED TANKLESS WATER HEATERS WILL BE
 INSTALLED. PLEASE PROVIDE PIPING DIAGRAMS FOR THE
 UNITS.
  
 6) PROVIDE A WATER RISER DRAWING PER SECTION 107.2.3.2
 WPB. SHOW PIPE SIZES AND LOCATIONS OF SHUTOFF VALVES,
 BACKFLOW PREVENTERS, WATER HAMMER ARRESTORS ETC. PLEASE
 NOTE THAT WATER HAMMERS ARE REQUIRED FOR SUPPLY LINES
 TO THE WASHING MACHINES, DISHWASHERS AND ICE MAKERS-
 SECTION P2903.5 FBC RES. BACKFLOW PREVENTERS ARE
 REQUIRED FOR SUPPLY LINES TO THE STEAM UNIT AND ICE
 MAKERS- SECTION P2902.3. THE SUPPLY LINE DISHWASHER
 SHALL BE PROTECTED AGAINST BACKFLOW BY AN AIR GAP OR
 BACKFLOW PREVENTER- SECTION P2717.1.
  
 7) INDICATE HOW WATER UNDERGROUND PIPING AND PIPING
 PENETRATING CONCRETE SLABS WILL BE PROTECTED AGAIN
 CORROSION- SECTION P2603.3.
  
 8) PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN FOR THE
 STEAM UNIT AND SUBMIT THE MANUFACTURER'S SPECIFICATIONS
 AND INSTALLATION MANUAL - SECTION M1307.1 FBC RES.
  
 9) INDICATE HOW CONDENSATE FROM THE STEAM UNIT AND ICE
 MAKER WILL BE DRAINED AND DISPOSED. SHOW THE TYPE AND
 SIZE OF PIPING, PIPING RUNS, AND DISCHARGE LOCATIONS-
 SECTION 314 FBC P.
  
 10) PROVIDE ENLARGED SHOWER RECESS AND SHOWER PAN
 DETAILS- SECTIONS P2709.1 & P2709.2 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status P Date 2021-02-05 Cont ID  
Sent By rgathrig Date 2021-02-05 Time 08:43 Rev Time 0.00
Received By rgathrig Date 2021-02-05 Time 08:43 Sent To  
Notes
2021-02-05 08:45:25APPROVED, PRIVATE PROVIDER INSPECTIONS ONLY
  
 PLANNING AND BUILDING CONSULTANTS, LLC
  
 APPROVED
  
 RICHARD GATHRIGHT
 ASSISTANT BUILDING OFICIAL
 561 805 6679

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2020-12-17 Cont ID  
Sent By jgomez Date 2020-12-17 Time 10:43 Rev Time 0.00
Received By jgomez Date 2020-12-17 Time 10:41 Sent To  
Notes
2020-12-17 10:44:051- ROOF TILE FL7473-R8
 2- ROOF TILE ADHESIVE FL 6332-R8
 3- MODIFIED BITUMEN FL16709-R6
 4- METAL CHANNEL FL5374-R5

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2020-10-27 Cont ID  
Sent By jgomez Date 2020-10-27 Time 09:41 Rev Time 0.00
Received By jgomez Date 2020-10-27 Time 09:41 Sent To  
Notes
2020-10-27 09:43:131-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL):
  
 A) FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY
 IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 B) ROOF TILE AND CLEARLY SPECIFY ROOF TILE FASTENING
 METHOD AS REQUIRED BY CITY POLICY FOR ALL ROOFING
 PERMITS. FOR MECHANICALLY ATTACHED TILE PROVIDE
 COMPLETE TILE FASTENING INFORMATION.
  
 C)ROOF TILE ADHESIVE IF SELECTED AS THE FASTENING
 METHOD. CLEARLY IDENTIFY PADDY SIZE.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-02-03 Cont ID  
Sent By fgiaquin Date 2021-02-03 Time 21:09 Rev Time 0.00
Received By fgiaquin Date 2021-02-03 Time 21:09 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-12-09 Cont ID  
Sent By jgomez Date 2020-12-09 Time 17:31 Rev Time 0.00
Received By jgomez Date 2020-12-09 Time 17:23 Sent To  
Notes
2020-12-09 17:31:42SOIL TEST REPORT WITH ENGINEER'S ORIGINAL
 SEAL/SIGNATURE. JG.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-10-27 Cont ID  
Sent By equinone Date 2020-10-27 Time 09:43 Rev Time 0.00
Received By jgomez Date 2020-10-27 Time 09:43 Sent To  
Notes
2020-10-27 09:51:531-SOIL TEST REPORT NEED TO HAVE THE ENGINEER'S ORIGINAL
 SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 471 F.S. WHEN
 SUBMITTING DOCUMENTS FOR PUBLIC RECORDS.
 PLEASE UPLOAD TO PROJECTDOX SOIL TEST REPORT WITH
 ENGINEER'S DIGITAL SIGNATURE OR PROVIDE HARD COPY OF
 SOIL TEST REPORT L WITH ENGINEER'S ORIGINAL SEAL AND
 SIGNATURE.
  
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2021-01-15 Cont ID  
Sent By kalexand Date 2021-01-15 Time 12:24 Rev Time 0.00
Received By kalexand Date 2021-01-15 Time 12:24 Sent To I
Notes
2021-01-15 12:26:04ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW:
 ________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. PROVIDE THE TOTAL HEIGHT OF THE PROPOSED HOME ON AN
 ELEVATION PLAN. PURSUANT TO THE ZLDR, SECTION 94-611,
 HEIGHT SHALL BE MEASURED AS THE VERTICAL DISTANCE FROM
 THE AVERAGE ELEVATION OF THE FINISHED GRADE OF THE
 BUILDING TO THE HIGHEST POINT OF THE TOP OF THE
 STRUCTURE OF A FLAT ROOF, OR TO THE DECK LINE OF A
 MANSARD ROOF, OR TO THE MEAN HEIGHT LEVEL BETWEEN EAVES
 AND RIDGE FOR GABLE, HIP, AND GAMBREL ROOFS.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 KIZZI ALEXANDRE, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1442
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status F Date 2020-11-13 Cont ID  
Sent By kalexand Date 2020-11-13 Time 15:33 Rev Time 0.00
Received By kalexand Date 2020-11-13 Time 15:33 Sent To I
Notes
2020-11-13 15:39:21ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW:
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. INDICATE PRINCIPAL STRUCTURE SETBACKS TO ALL
 PROPERTY LINES. NOTE: CITY OF WEST PALM BEACH ZONING
 AND LAND DEVELOPMENT REGULATIONS (ZLDR), SECTION 94-72:
 SINGLE FAMILY LOW DENSITY (SF7) RESIDENTIAL DISTRICT -
 MINIMUM SETBACKS FOR PRINCIPAL BUILDING ARE AS FOLLOWS:
  
 A. FRONT: 25 FEET
  
 B. CORNER: 12.5 FEET
  
 C. REAR: 15 FEET OR TEN PERCENT OF DEPTH, WHICHEVER IS
 LESS;
  
 D. SIDE: FIVE FEET MINIMUM, 15 FEET TOTAL.
  
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD
 LIKE TO RESUBMIT ELECTRONICALLY, EMAIL
 [email protected] AND REQUEST TO HAVE YOUR
 PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOG
 IN INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL.
 PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU
 ARE FINISHED UPLOADING.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 KIZZI ALEXANDRE, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1442
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved