| 2020-10-20 10:31:39 | 1ST REVIEW FBC-2017 RES. FUEL GAS |
| | PERMIT- 20100167 |
| | 10/20/29 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) GAS RISER DRAWING: PROVIDE AN LP GAS RISER DRAWING |
| | SHOWING THE TYPES AND SIZES OF PIPING; TOTAL DEVELOPED |
| | LENGTH OF THE SYSTEM AND LENGTHS OF BRANCHES TO ALL NEW |
| | AND EXISTING LP APPLIANCES OR EQUIPMENT; TOTAL BTUH |
| | LOAD OF THE SYSTEM AND INDIVIDUAL LOADS OF APPLIANCES |
| | OR EQUIPMENT- SECTIONS G2412.3, G2412.4, G2413.2, |
| | G2413.4.1, G2413.4.2, G2412.3, G2412.4 FBC RES. |
| | |
| | A) SHOW THE LOCATIONS OF SHUTOFF VALVES, LOCATIONS AND |
| | MAKES AND MODELS OF REGULATORS INCLUDING INLET AND |
| | OUTLET PRESSURES, LOCATIONS OF UNIONS, RISERS AND FLEX |
| | CONNECTORS; AND A LIST OF GAS PIPE SIZING TABLES- |
| | SECTIONS G2420, G2421, & G2413.4(1)- G2413.4(21) FBC |
| | RES. PLEASE NOTE THE SUBMITTED PIPE SIZING TABLE IN THE |
| | GAS SUBMITTAL PACKAGE IS FOR NATURAL GAS. PLEASE SUBMIT |
| | LP PIPE SIZING TABLES. |
| | |
| | 2) PLEASE MARK UP THE SUBMITTED SURVEY TO SHOW THE |
| | LOCATION OF THE NEW LP TANK AND REQUIRED 10 FT. |
| | CLEARANCES DISTANCES FROM THE TANK TO THE BUILDING, AND |
| | ADJACENT PROPERTY LINES- TABLE 6.3.1.1 NFPA 58. PLEASE |
| | SHOW THE PIPING RUN ON THE SURVEY FROM THE TANK TO THE |
| | GENERATOR- SECTION 107.2.1 WPB. |
| | |
| | 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | 500-GALLON UG LP TANK SHOWING THE TANK AND DOME HAVE |
| | BEEN DESIGNED, FABRICATED, TESTED AND MARKED (STAMPED) |
| | IN ACCORDANCE WITH THE REGULATIONS AS REQUIRED BY THE |
| | REGULATORY AGENCIES AND COMPLIANCE STANDARDS LISTED IN |
| | SECTION 5.2.1.1 NFPA 58. |
| | |
| | 4) PROVIDE LP TANK INSTALLATION AS REQUIRED BY NFPA 58: |
| | |
| | A) ENGINEERING FOR ANCHORING THE TANK TO PREVENT |
| | FLOTATION, COLLAPSE, OR LATERAL MOVEMENT- SECTION |
| | 6.6.1.6. PLEASE INCLUDE A FRONT AND SIDE ELEVATION VIEW |
| | THAT SHOWS THE BURIAL DEPTH, ANCHORING BASE MATERIAL, |
| | AND THE TYPES, SIZES, AND NUMBERS OF ANCHORS, CABLES OR |
| | STRAPS, AND THE TYPE OF PROTECTIVE SLEEVES FOR THE |
| | CABLES OR STRAPS. |
| | |
| | B) SHOW HOW THE TANK WILL BE PROTECTED AGAINST |
| | CORROSION BY INSTALLATION OF A CATHODIC PROTECTION |
| | SYSTEM CONSISTING OF A SACRIFICIAL ANODE OR AN |
| | IMPRESSED CURRENT ANODE PER SECTIONS 5.2.1.11 & |
| | 6.6.6.1(I) NFPA 58. INDICATE THE TYPE OF PROTECTION AND |
| | HOW IT WILL BE TESTED- SECTION 6.17.1. |
| | |
| | 5) THE SURVEY HAS BEEN INCORRECTLY MARKED UP TO SHOW A |
| | 5 FT. CLEARANCE FOR THE GENERATOR TO WINDOWS AND DOORS, |
| | HOWEVER A 10 FT. CLEARANCE TO MECHANICAL AND GRAVITY |
| | AIR INTAKES IS REQUIRED PER SECTION R303.5.1 FBC RES- |
| | PLEASE CORRECT THE DRAWING. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |