| 2020-10-19 10:16:30 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | |
| | 1ST REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | |
| | 1.SEE PLAN SHEET A0: PER WPB FBC 107.2.1; A) ADD |
| | PLUMBING SHEET B) DELETE REFERENCE TO FLORIDA BUILDING |
| | CODE-RESIDENTIAL |
| | |
| | 2.PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE A |
| | PLUMBING DRAWING TO INCLUDE SANITARY AND WATER PLAN |
| | VIEW AND RISER DIAGRAMS SHOWING HOW NEW RELOCATED SINK |
| | IS TO CONNECT TO THE EXISTING SERVICES. |
| | |
| | 3.PLEASE NOTE WHEN DESIGNING THE WASTE AND VENT FOR THE |
| | RELOCATED SINK, PER FBC PL 918.3.1, IF AN AIR |
| | ADMITTANCE IS INCORPORATED INTO THE DESIGN AND THE |
| | HORIZONTAL BRANCH IS LOCATED MORE THAN FOUR BRANCH |
| | INTERVALS FROM THE TOP OF THE STACK, THE HORIZONTAL |
| | BRANCH SHALL BE PROVIDED WITH A RELIEF VENT THAT SHALL |
| | CONNECT TO A VENT STACK OR STACK VENT, OR EXTEND |
| | OUTDOORS TO THE OPEN AIR. THE RELIEF VENT SHALL CONNECT |
| | TO THE HORIZONTAL BRANCH DRAIN BETWEEN THE STACK AND |
| | THE MOST DOWNSTREAM FIXTURE DRAIN CONNECTED TO THE |
| | HORIZONTAL BRANCH DRAIN. THE RELIEF VENT SHALL BE SIZED |
| | IN ACCORDANCE WITH SECTION 906.2 AND INSTALLED IN |
| | ACCORDANCE WITH SECTION 905. THE RELIEF VENT SHALL BE |
| | PERMITTED TO SERVE AS THE VENT FOR OTHER FIXTURES. |
| | |
| | 4.IN ACCORDANCE WITH THE PROVISIONS OF WPB FBC 105.1, A |
| | PLUMBING SUB PERMIT IS REQUIRED. |
| | |
| | 5.PER WPB FBC 107.2.1, PROVIDE NOTE: PER FBC PL |
| | 802.1.6, DOMESTIC DISHWASHING MACHINES SHALL DISCHARGE |
| | INDIRECTLY THROUGH AN AIR GAP OR AIR BREAK INTO A WASTE |
| | RECEPTOR IN ACCORDANCE WITH SECTION 802.2, OR DISCHARGE |
| | INTO A WYE BRANCH FITTING ON THE TAILPIECE OF THE |
| | KITCHEN SINK OR THE DISHWASHER CONNECTION OF A FOOD |
| | WASTE DISPOSER. THE WASTE LINE OF A DOMESTIC |
| | DISHWASHING MACHINE DISCHARGING INTO A KITCHEN SINK |
| | TAILPIECE OR FOOD WASTE DISPOSER SHALL CONNECT TO A |
| | DECK-MOUNTED AIR GAP OR THE WASTE LINE SHALL RISE AND |
| | BE SECURELY FASTENED TO THE UNDERSIDE OF THE SINK RIM |
| | OR COUNTER. |
| | |
| | 6.PER WPB FBC 107.2.1, PROVIDE NOTE: PER FBC PL 604.9, |
| | A WATER-HAMMER ARRESTOR CONFORMING TO ASSE1010 SHALL BE |
| | INSTALLED ON THE HOT WATER SUPPLY TO THE DISHWASHER IN |
| | ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS. |
| | |
| | 7. REAL ESTATE RECORDS INDICATE THIS UNIT IS IN A |
| | THIRTY-TWO (32) STORY BUILDING. PER WPB FBC 107.2.1, |
| | PLEASE CONFIRM OR PROVIDE CORRECT INFORMATION AND |
| | PROVIDE THE FOLLOWING INFORMATION. IS THE UNIT ON THE |
| | GROUND LEVEL OR AN ELEVATED LEVEL. IS THE FLOOR A RATED |
| | FLOOR FOR FIRE? NOTE, IF ANT PLUMBING PIPE IS TO |
| | PENETRATE THE FLOOR AND IT IS A FIRE RATED FLOOR THEN A |
| | UL ASSEMBLY FOR FIRE SAFEING COMPLYING WITH FBC CHAPTER |
| | 7 IS REQUIRED. |
| | |
| | 8. FS471, DOCUMENTS PREPARED BY AN ENGINEER AND |
| | SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, |
| | DATED ORIGINALS. A SCAN OF A SIGNED PLAN IS NOT |
| | CONSIDERED AN ORIGINAL.SEE SIGNATURES REVIEW. |
| | ALL PLANS TO BE SIGNED AND SEALED BY THE DESIGNER AS |
| | REQUIRED BY FAC AND FS OR DIGITALLY SIGNED AND SEALED |
| | BY THE DESIGNER IN ACCORDANCE WITH FAC AND FS. |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | |