Plan Review Details - Permit 20100038
Plan Review Stops For Permit 20100038
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2020-10-20 Cont ID  
Sent By cpuell Date 2020-10-20 Time 16:04 Rev Time 0.00
Received By cpuell Date 2020-10-20 Time 16:04 Sent To  
Notes
***NONE***

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2020-10-13 Cont ID  
Sent By cpuell Date 2020-10-13 Time 12:27 Rev Time 0.00
Received By cpuell Date 2020-10-13 Time 12:27 Sent To  
Notes
2020-10-13 12:28:11PLEASE EMAIL A SITE PLAN SHOWING THE BUILDING TO BE
 DEMOLISHED TO [email protected]

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2020-10-21 Cont ID  
Sent By pvalenti Date 2020-10-21 Time 10:46 Rev Time 0.00
Received By pvalenti Date 2020-10-21 Time 10:45 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-10-17 Cont ID  
Sent By pvalenti Date 2020-10-17 Time 11:31 Rev Time 0.00
Received By pvalenti Date 2020-10-17 Time 11:27 Sent To  
Notes
2020-10-17 11:32:40PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 ASBESTOS REQUIREMENTS:
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-11-06 Cont ID  
Sent By pvalenti Date 2020-11-06 Time 09:55 Rev Time 0.00
Received By pvalenti Date 2020-11-06 Time 09:39 Sent To  
Notes
2020-11-06 10:09:14PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW APPROVED WITH PROVISO:
  
 ALL WORK PER CITY CODES IS SUBJECT TO FIELD INSPECTOR'S
 APPROVAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-10-28 Cont ID  
Sent By pvalenti Date 2020-10-28 Time 10:03 Rev Time 0.00
Received By pvalenti Date 2020-10-28 Time 09:55 Sent To  
Notes
2020-10-28 10:08:51PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 THE FOLLOWING ITEMS ARE REQUIRED PRIOR TO ISSUANCE OF A
 DEMO PERMIT PER FLORIDA BUILDING CODE, BUILDING 3303:
  
 3. UTILITY RELEASE ? CITY OF WEST PALM BEACH WATER
 DEPARTMENT, REQUEST FOR METER PULL, ON THEIR FORM
 "DEMOLITION APPLICATION"
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT?SERVICES/FORMS/B
 UILDING?PERMIT?FORMS
 IF A HYDRANT METER OR BACKFLOW PREVENTER IS DESIRED,
 THEN A PARTIAL RELEASE WILL BE NOTED ON THEIR FORM.
 FAX THE COMPLETED "DEMOLITION APPLICATION" FORM TO
 561?822?2183.
  
 4. SEWER LATERAL CAPPING PERMIT IS REQUIRED (SUBMIT
 APPLICATION TO BUILDING DIVISION); SCHEDULE A FINAL
 PLUMBING #703.
  
 8. PROVIDE A STORMWATER POLLUTION PREVENTION PLAN.
  
 BACKFLOW ? BEFORE SCHEDULING THE 703, THE BACKFLOW
 DEVICE NEEDS TO BE TESTED AND CERTIFIED BY THE CITY?S
 UTILITIES DEPT, 561?822?2244.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-10-17 Cont ID  
Sent By pvalenti Date 2020-10-17 Time 11:34 Rev Time 0.00
Received By pvalenti Date 2020-10-17 Time 11:27 Sent To  
Notes
2020-10-17 11:40:28PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 THE FOLLOWING ITEMS ARE REQUIRED PRIOR TO ISSUANCE OF A
 DEMO PERMIT PER FLORIDA BUILDING CODE, BUILDING 3303:
  
  
 3. UTILITY RELEASE - CITY OF WEST PALM BEACH WATER
 DEPARTMENT, REQUEST FOR METER PULL, ON THEIR FORM
 "DEMOLITION APPLICATION"
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
 IF A HYDRANT METER OR BACKFLOW PREVENTER IS DESIRED,
 THEN A PARTIAL RELEASE WILL BE NOTED ON THEIR FORM.
 FAX THE COMPLETED "DEMOLITION APPLICATION" FORM TO
 561-822-2183.
 4. SEWER LATERAL CAPPING PERMIT IS REQUIRED (SUBMIT
 APPLICATION TO BUILDING DIVISION); SCHEDULE A FINAL
 PLUMBING #703.
  
 6. COMPLETE THE DEMO DEBRIS FORM:
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
 IF THE FORM IS NOT AVAILABLE ONLINE, SEND A REQUEST FOR
 THE FORM TO [email protected].
 7. PROVIDE A SITE PLAN OR SURVEY SHOWING LOCATION OF
 THE STRUCTURE(S) TO BE DEMOLISHED, FBC 107.
 8. PROVIDE A STORMWATER POLLUTION PREVENTION PLAN.
 9. PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING
 ASBESTOS REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOSDEMOLITION-
 RENOVATION.HTML
 BACKFLOW - BEFORE SCHEDULING THE 703, THE BACKFLOW
 DEVICE NEEDS TO BE TESTED AND CERTIFIED BY THE CITY?S
 UTILITIES DEPT, 561-822-2244.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2020-11-06 Cont ID  
Sent By rrossano Date 2020-11-06 Time   Rev Time 0.00
Received By rrossano Date 2020-11-06 Time   Sent To I
Notes
2020-11-06 10:03:42PASSED WITH PROVISO: THERE ARE WATER AND SEWER LINES IN
 THE VICINITY OF THIS PROJECT. PER CHAPTER 556 OF THE
 FLORIDA STATE STATUTES, YOU MUST CALL 811 FOR UTILITY
 LOCATES AT LEAST TWO FULL BUSINESS DAYS IN ADVANCE OF
 ANY CONSTRUCTION OR DEMOLITION WORK. INFORMATION CAN BE
 FOUND HERE: HTTP://WWW.SUNSHINE811.COM/
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
 RICK ROSSANO
 PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1098
 FAX: (561) 494-1116
 MOBILE: (561) 246-9525
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2020-10-27 Cont ID  
Sent By rrossano Date 2020-10-27 Time   Rev Time  
Received By rrossano Date 2020-10-27 Time   Sent To  
Notes
2020-10-27 13:17:25PLEASE ADDRESS BUILDING COMMENTS.

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2020-11-06 Cont ID  
Sent By aborngra Date 2020-11-06 Time 07:59 Rev Time 0.00
Received By aborngra Date 2020-11-06 Time 07:59 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2020-10-21 Cont ID  
Sent By aborngra Date 2020-10-21 Time 09:48 Rev Time 0.00
Received By aborngra Date 2020-10-21 Time 09:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-11-06 Cont ID  
Sent By ccarvaja Date 2020-11-06 Time 09:33 Rev Time 0.00
Received By ccarvaja Date 2020-11-03 Time 09:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-11-02 Cont ID  
Sent By lmarchan Date 2020-11-02 Time 16:04 Rev Time 0.00
Received By lmarchan Date 2020-10-14 Time 10:56 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2020-10-17 Cont ID  
Sent By pvalenti Date 2020-10-17 Time 11:44 Rev Time 0.00
Received By pvalenti Date 2020-10-17 Time 11:27 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2020-11-02 Cont ID  
Sent By ajones Date 2020-11-02 Time 15:45 Rev Time 0.00
Received By ajones Date 2020-11-02 Time 15:45 Sent To  
Notes
***NONE***