| 2020-10-02 18:38:06 | 10/02/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. PLEASE NOTE THAT THIS BUILDING WAS CONSTRUCTED UNDER |
| | THE FAIR HOUSING ACT. PLEASE INDICATE ON PLANS WHICH |
| | DESIGN SPECIFICATION ( ?A? OR ?B? OF THE ACT) WAS USED |
| | IN THE ORIGINAL DESIGN OF THESE UNITS. THE ALTERATION |
| | THAT IS PROPOSED IN THE BATHROOM SHALL ALSO BE IN |
| | COMPLIANCE WITH THE FAIR HOUSING ACT. |
| | |
| | 2. PLEASE GIVE A NARRATIVE FOR THE SCOPE OF THE WORK |
| | BEING DONE PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 3. ALL INFORMATION, DRAWINGS, SPECIFICATIONS, AND |
| | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| | THE PERSON RESPONSIBLE FOR THE DESIGN PER THE WPB |
| | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 4. THE BATHROOM DOES NOT SHOW THE BATHING UNITS, ARE |
| | YOU GETTING RID OF THE TUB AND THERE SEEMS TO BE ONLY |
| | ONE LAVS IN THIS BATHROOM. IT IS UNCLEAR TO WHAT IS |
| | BEING DONE AND WHAT WAS THERE. IF THIS IS A B UNIT THE |
| | LAVE MUST HAVE THE TOP FIXTURE RIM IS A MAXIMUM OF 34 |
| | INCHES AFF, WITH THE APRON AT LEAST 27 INCHES AFF. |
| | |
| | 5. THE CLAIMED VALUE APPEARS TO BE UNDERESTIMATED ON |
| | THE APPLICATION, PLEASE PROVIDE A BONA FIDE SIGNED |
| | CONTRACT PER THE WPB AMENDMENTS TO THE FBC SEC. 109.3 |
| | BUILDING PERMIT VALUATIONS. |
| | |
| | 6. THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING |
| | OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA |
| | AND DOCUMENTS: A FLOOR PLAN AND DEMOLITION PER THE 2017 |
| | FBC WPB AMENDMENTS SEC. 107.3.5 MINIMUM PLAN REVIEW |
| | CRITERIA FOR BUILDINGS. |
| | |
| | 7. THE CITY OF WEST PALM BEACH BUILDING DEPARTMENT |
| | PROVIDES AN OPTION FOR THE CHANGING OF AN FHA |
| | COMPLIANCE STRUCTURE. THE OWNER AND DESIGNER OF RECORD |
| | ACKNOWLEDGE THAT THE PROPOSED BATHROOM DESIGN DOES NOT |
| | MEET THE REQUIREMENTS OF THE FAIR HOUSING ACCESSIBILITY |
| | GUIDELINES. THE OWNER AGREES TO REVERT THE UNIT BACK TO |
| | COMPLIANCE AT THE TIME OF SALE IF SO, REQUESTED BY THE |
| | BUYER. THIS WILL BE IN A LETTER TYPE FORMAT SIGNED AND |
| | NOTARIZED BY THE OWNER. WE PROVIDE A SAMPLE LETTER AND |
| | IT MUST BE SUBMITTED TO THE BUILDING DEPARTMENT OF THE |
| | CITY OF WPB. IF THIS OPTION IS CHOSEN, PLEASE SEND AN |
| | EMAIL TO [email protected] AND I WILL SEND A COPY OF THE |
| | FAIR HOUSING AFFIDAVIT. |
| | |
| | 8. THE WASHING MACHINE IS BEING ROTATED AND IT MUST |
| | HAVE THE SHUT OFF VALVES ACCESSIBLE WITHOUT MOVING THE |
| | UNIT AND WITHIN REACH PER THE 2017 FBC SEC. P 606.3 |
| | ACCESS TO VALVES. |
| | |
| | 9. A SUB PLUMBING PERMIT IS REQUIRED BY A LICENSED |
| | CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 105.1. |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |