Plan Review Details - Permit 20091341
Plan Review Stops For Permit 20091341
Review Stop G GAS REVIEW
Rev No 4 Status P Date 2020-10-09 Cont ID  
Sent By ccole Date 2020-10-09 Time 07:30 Rev Time 0.00
Received By ccole Date 2020-10-09 Time 07:29 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2020-10-08 Cont ID  
Sent By ccole Date 2020-10-08 Time 11:49 Rev Time 0.00
Received By ccole Date 2020-10-08 Time 09:09 Sent To  
Notes
2020-10-08 11:52:022ND REVIEW FBC-2017 RES.
 PERMIT- 20091341
 10/8/2020
  
 CODES IN EFFECT
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) CONCERNING THE GAS LINE RECONNECT: A) SHOW THE
 LOCATION OF THE NEW REGULATOR, INDICATE THE SELECTED
 MAKE AND MODEL, SHOW THE OUTLET PRESSURE, AND THE
 REQUIRED PIPE UNIONS WITHIN 1 FT. OF EITHER SIDE OF THE
 REGULATOR IF CONNECTED TO RIGID PIPING. SECTIONS
 G2421.1 & G2421.2 FBC RES. PLEASE NOTE REGULATOR SPECS
 ONSITE SHALL BE MARKED UP OR HIGHLIGHTED TO INDICATE
 INTERIOR OR EXTERIOR USE, INLET AND OUTLET PRESSURES,
 AND ORIFICE SIZES. PLEASE NIOTE THE GENERATOR SPECS
 INDICATE INPUT PRERSSURE OF 3.5- 7 IN.W.C.
  
 2)THE CONTRACTOR OR QUALIFIER WHO PREPARED THE GAS
 RISER DRAWING SHALL PROVIDE HIS/HER TITLE BLOCK AND
 SIGNATURE ON IT- SECTION 107.2.1 WPB, AND FLORIDA
 STATUTES 471.003(2)(H) & 471.025.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2020-10-06 Cont ID  
Sent By ccole Date 2020-10-06 Time 10:57 Rev Time 0.00
Received By ccole Date 2020-10-06 Time 10:04 Sent To  
Notes
2020-10-06 14:28:212ND REVIEW FBC-2017 RES.
 PERMIT- 20091341
 10/6/2020
  
 CODES IN EFFECT
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 COMMENTS FROM THE 1ST REVIEW LISTED BELOW STILL EXIST.
 NO CORRECTED PLANS OR COMMENT RESPONSES WERE UPLOADED
 FOR REVIEW.
  
 1) IT APPEARS THERE ARE TWO SEPARATE GENERATORS ON THE
 PROPERTY HOWEVER THE APPROVED PLANS UNDER THE PRIMARY
 PERMIT- 20080725 YOU HAVE LISTED ON YOUR APPLICATION
 SHOW A NEW (NOT A REPLACEMENT) 22 KW 327,000 BTUH
 GENERATOR LOCATED ON THE SOUTH SIDE OF THE HOUSE. THE
 SURVEY DRAWING YOU HAVE SUBMITTED INDICATES REPLACING A
 500,000 BTUH GENERATOR ON THE WEST SIDE OF THE
 PROPERTY. PLEASE NOTE THERE WERE NO GAS PIPING PLANS
 SUBMITTED AND NO GAS PERMIT ISSUED FOR THE GENERATOR
 UNDER PERMIT- 20080275, HOWEVER GAS PERMIT 07120106 WAS
 ISSUED FOR A 630,000 BTUH GENERATOR ON 02/04/2008. THIS
 GENERATOR APPEARS TO BE THE ONE THAT IS BEING REPLACED,
 HOWEVER THERE IS NO PERMIT ON FILE FOR REPLACEMENT OF
 THAT GENERATOR AND THE $1000.00 JOB VALUE LISTED ON
 YOUR APPLICATION IS A VERY LOW VALUE IF YOU ARE ALSO
 SUPPLYING THE GENERATOR. PLEASE PROVIDE A COPY OF A
 SIGNED CONTRACT AND/OR ESTIMATES OR INVOICES TO VERIFY
 THE TOTAL JOB COST INCLUDING LABOR, MATERIALS, THE
 GENERATOR, DESIGN FEES, AND SITE WORK- SECTION 109.3
 WPB.
  
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE 500,000
 BTUH GENERATOR- SECTION 107.2.1 WPB. THE SPECS SHALL BE
 MARKED UP TO SHOW THE BTUH CAPACITY OF THE GENERATOR,
 AND REQUIRED NATURAL GAS INPUT PRESSURE.
  
 3) GAS RISER:
  
 A) SHOW THE LOCATION OF THE NEW REGULATOR, INDICATE THE
 SELECTED MAKE AND MODEL, SHOW THE OUTLET PRESSURE, AND
 THE REQUIRED PIPE UNIONS WITHIN 1 FT. OF EITHER SIDE OF
 THE REGULATOR IF CONNECTED TO RIGID PIPING. SECTIONS
 G2421.1 & G2421.2 FBC RES. PLEASE NOTE REGULATOR SPECS
 ONSITE SHALL BE MARKED UP OR HIGHLIGHTED TO INDICATE
 INTERIOR OR EXTERIOR USE, INLET AND OUTLET PRESSURES,
 AND ORIFICE SIZES.
  
 B) SHOW THE LOCATION OF THE DRIP LEG- SECTION G2419.2
 FBC RES.
  
 C) INDICATE A TRACER WIRE WILL BE INSTALLED ADJACENT TO
 THE UG PE PIPING- SECTION G2415.17.3.
  
 3) SURVEY: SHOW THE GENERATOR CLEARANCES TO THE
 ADJACENT PROPERTY LINES AND THE BUILDING, AND
 MECHANICAL AIR INTAKES AND OPERABLE OPENINGS INTO THE
 BUILDING- SEC. 4.1.4 NFPA 37 AND SECTION R303.5.1 FBC
 RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-10-02 Cont ID  
Sent By ccole Date 2020-10-02 Time 12:03 Rev Time 0.00
Received By ccole Date 2020-10-02 Time 10:00 Sent To  
Notes
2020-10-02 12:04:091ST REVIEW FBC-2017 RES.
 PERMIT- 20091341
 10/2/2020
  
 CODES IN EFFECT
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IT APPEARS THERE ARE TWO SEPARATE GENERATORS ON THE
 PROPERTY HOWEVER THE APPROVED PLANS UNDER THE PRIMARY
 PERMIT- 20080725 YOU HAVE LISTED ON YOUR APPLICATION
 SHOW A NEW (NOT A REPLACEMENT) 22 KW 327,000 BTUH
 GENERATOR LOCATED ON THE SOUTH SIDE OF THE HOUSE. THE
 SURVEY DRAWING YOU HAVE SUBMITTED INDICATES REPLACING A
 500,000 BTUH GENERATOR ON THE WEST SIDE OF THE
 PROPERTY. PLEASE NOTE THERE WERE NO GAS PIPING PLANS
 SUBMITTED AND NO GAS PERMIT ISSUED FOR THE GENERATOR
 UNDER PERMIT- 20080275, HOWEVER GAS PERMIT 07120106 WAS
 ISSUED FOR A 630,000 BTUH GENERATOR ON 02/04/2008. THIS
 GENERATOR APPEARS TO BE THE ONE THAT IS BEING REPLACED,
 HOWEVER THERE IS NO PERMIT ON FILE FOR REPLACEMENT OF
 THAT GENERATOR AND THE $1000.00 JOB VALUE LISTED ON
 YOUR APPLICATION IS A VERY LOW VALUE IF YOU ARE ALSO
 SUPPLYING THE GENERATOR. PLEASE PROVIDE A COPY OF A
 SIGNED CONTRACT AND/OR ESTIMATES OR INVOICES TO VERIFY
 THE TOTAL JOB COST INCLUDING LABOR, MATERIALS, THE
 GENERATOR, DESIGN FEES, AND SITE WORK- SECTION 109.3
 WPB.
  
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE 500,000
 BTUH GENERATOR- SECTION 107.2.1 WPB. THE SPECS SHALL BE
 MARKED UP TO SHOW THE BTUH CAPACITY OF THE GENERATOR,
 AND REQUIRED NATURAL GAS INPUT PRESSURE.
  
 3) GAS RISER:
  
 A) SHOW THE LOCATION OF THE NEW REGULATOR, INDICATE THE
 SELECTED MAKE AND MODEL, SHOW THE OUTLET PRESSURE, AND
 THE REQUIRED PIPE UNIONS WITHIN 1 FT. OF EITHER SIDE OF
 THE REGULATOR IF CONNECTED TO RIGID PIPING. SECTIONS
 G2421.1 & G2421.2 FBC RES. PLEASE NOTE REGULATOR SPECS
 ONSITE SHALL BE MARKED UP OR HIGHLIGHTED TO INDICATE
 INTERIOR OR EXTERIOR USE, INLET AND OUTLET PRESSURES,
 AND ORIFICE SIZES.
  
 B) SHOW THE LOCATION OF THE DRIP LEG- SECTION G2419.2
 FBC RES.
  
 C) INDICATE A TRACER WIRE WILL BE INSTALLED ADJACENT TO
 THE UG PE PIPING- SECTION G2415.17.3.
  
 3) SURVEY: SHOW THE GENERATOR CLEARANCES TO THE
 ADJACENT PROPERTY LINES AND THE BUILDING, AND
 MECHANICAL AIR INTAKES AND OPERABLE OPENINGS INTO THE
 BUILDING- SEC. 4.1.4 NFPA 37 AND SECTION R303.5.1 FBC
 RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2020-10-08 Time   Rev Time 0.00
Received By lmarchan Date 2020-10-07 Time 15:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-10-06 Time   Rev Time 0.00
Received By lmarchan Date 2020-10-05 Time 16:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-10-02 Time   Rev Time 0.00
Received By lmarchan Date 2020-09-30 Time 14:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status N Date 2020-10-08 Cont ID  
Sent By ccole Date 2020-10-08 Time 11:47 Rev Time 0.00
Received By ccole Date 2020-10-08 Time 09:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-10-06 Cont ID  
Sent By ccole Date 2020-10-06 Time 10:57 Rev Time 0.00
Received By ccole Date 2020-10-06 Time 10:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-10-02 Cont ID  
Sent By ccole Date 2020-10-02 Time 12:06 Rev Time 0.00
Received By ccole Date 2020-10-02 Time 12:06 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2020-10-09 Cont ID  
Sent By ccole Date 2020-10-09 Time 07:30 Rev Time 0.00
Received By ccole Date 2020-10-09 Time 07:30 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2020-10-08 Cont ID  
Sent By ccole Date 2020-10-08 Time 11:48 Rev Time 0.00
Received By ccole Date 2020-10-08 Time 11:48 Sent To  
Notes
2020-10-08 11:48:44THE CONTRACTOR OR QUALIFIER WHO PREPARED THE GAS RISER
 DRAWING SHALL PROVIDE HIS/HER TITLE BLOCK AND SIGNATURE
 ON IT- SECTION 107.2.1 WPB, AND FLORIDA STATUTES
 471.003(2)(H) & 471.025.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-10-06 Cont ID  
Sent By ccole Date 2020-10-06 Time 10:57 Rev Time 0.00
Received By ccole Date 2020-10-06 Time 10:04 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-10-02 Cont ID  
Sent By ccole Date 2020-10-02 Time 12:08 Rev Time 0.00
Received By ccole Date 2020-10-02 Time 10:01 Sent To  
Notes
2020-10-02 12:09:38THE CONTRACTOR OR QUALIFIER WHO PREPARED THE GAS RISER
 DRAWING SHALL PROVIDE HIS/HER TITLE BLOCK AND SIGNATURE
 ON IT- SECTION 107.2.1 WPB, AND FLORIDA STATUTES
 471.003(2)(H) & 471.025.