| 2020-10-06 14:28:21 | 2ND REVIEW FBC-2017 RES. |
| | PERMIT- 20091341 |
| | 10/6/2020 |
| | |
| | CODES IN EFFECT |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | COMMENTS FROM THE 1ST REVIEW LISTED BELOW STILL EXIST. |
| | NO CORRECTED PLANS OR COMMENT RESPONSES WERE UPLOADED |
| | FOR REVIEW. |
| | |
| | 1) IT APPEARS THERE ARE TWO SEPARATE GENERATORS ON THE |
| | PROPERTY HOWEVER THE APPROVED PLANS UNDER THE PRIMARY |
| | PERMIT- 20080725 YOU HAVE LISTED ON YOUR APPLICATION |
| | SHOW A NEW (NOT A REPLACEMENT) 22 KW 327,000 BTUH |
| | GENERATOR LOCATED ON THE SOUTH SIDE OF THE HOUSE. THE |
| | SURVEY DRAWING YOU HAVE SUBMITTED INDICATES REPLACING A |
| | 500,000 BTUH GENERATOR ON THE WEST SIDE OF THE |
| | PROPERTY. PLEASE NOTE THERE WERE NO GAS PIPING PLANS |
| | SUBMITTED AND NO GAS PERMIT ISSUED FOR THE GENERATOR |
| | UNDER PERMIT- 20080275, HOWEVER GAS PERMIT 07120106 WAS |
| | ISSUED FOR A 630,000 BTUH GENERATOR ON 02/04/2008. THIS |
| | GENERATOR APPEARS TO BE THE ONE THAT IS BEING REPLACED, |
| | HOWEVER THERE IS NO PERMIT ON FILE FOR REPLACEMENT OF |
| | THAT GENERATOR AND THE $1000.00 JOB VALUE LISTED ON |
| | YOUR APPLICATION IS A VERY LOW VALUE IF YOU ARE ALSO |
| | SUPPLYING THE GENERATOR. PLEASE PROVIDE A COPY OF A |
| | SIGNED CONTRACT AND/OR ESTIMATES OR INVOICES TO VERIFY |
| | THE TOTAL JOB COST INCLUDING LABOR, MATERIALS, THE |
| | GENERATOR, DESIGN FEES, AND SITE WORK- SECTION 109.3 |
| | WPB. |
| | |
| | 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE 500,000 |
| | BTUH GENERATOR- SECTION 107.2.1 WPB. THE SPECS SHALL BE |
| | MARKED UP TO SHOW THE BTUH CAPACITY OF THE GENERATOR, |
| | AND REQUIRED NATURAL GAS INPUT PRESSURE. |
| | |
| | 3) GAS RISER: |
| | |
| | A) SHOW THE LOCATION OF THE NEW REGULATOR, INDICATE THE |
| | SELECTED MAKE AND MODEL, SHOW THE OUTLET PRESSURE, AND |
| | THE REQUIRED PIPE UNIONS WITHIN 1 FT. OF EITHER SIDE OF |
| | THE REGULATOR IF CONNECTED TO RIGID PIPING. SECTIONS |
| | G2421.1 & G2421.2 FBC RES. PLEASE NOTE REGULATOR SPECS |
| | ONSITE SHALL BE MARKED UP OR HIGHLIGHTED TO INDICATE |
| | INTERIOR OR EXTERIOR USE, INLET AND OUTLET PRESSURES, |
| | AND ORIFICE SIZES. |
| | |
| | B) SHOW THE LOCATION OF THE DRIP LEG- SECTION G2419.2 |
| | FBC RES. |
| | |
| | C) INDICATE A TRACER WIRE WILL BE INSTALLED ADJACENT TO |
| | THE UG PE PIPING- SECTION G2415.17.3. |
| | |
| | 3) SURVEY: SHOW THE GENERATOR CLEARANCES TO THE |
| | ADJACENT PROPERTY LINES AND THE BUILDING, AND |
| | MECHANICAL AIR INTAKES AND OPERABLE OPENINGS INTO THE |
| | BUILDING- SEC. 4.1.4 NFPA 37 AND SECTION R303.5.1 FBC |
| | RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |