Plan Review Details - Permit 20091290
Plan Review Stops For Permit 20091290
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-12-08 Cont ID  
Sent By rmcdouga Date 2020-12-08 Time 09:17 Rev Time 0.00
Received By rmcdouga Date 2020-12-08 Time 08:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-11-04 Cont ID  
Sent By rmcdouga Date 2020-11-04 Time 15:31 Rev Time 0.00
Received By rmcdouga Date 2020-11-04 Time 14:43 Sent To  
Notes
2020-11-04 15:43:14PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE EXPOSURE CATEGORY IS STILL SPECIFIED AS C ON
 SHEET T-1 IN THE LOADING CRITERIA. THE DRAWINGS SPECIFY
 THAT THE EXPOSURE CATEGORY IS C. THIS PROJECT IS
 LOCATED IN EXPOSURE CATEGORY D. FBC 1609.4
  
 2) THIS ITEM HAS NOT BEEN FULLY ADDRESSED. ON SHEET
 C-5, SPECIFY THE REQUIRED EMBED DEPTH AND THE ANCHOR
 SPACING REQUIRED FOR ATTACHING THE THE UNISTRUT TO THE
 WALL OF THE BUILDING. CITY AMENDMENTS FBC 107.2.1
  
 3) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-10-14 Cont ID  
Sent By rmcdouga Date 2020-10-14 Time 14:00 Rev Time 0.00
Received By rmcdouga Date 2020-10-14 Time 12:41 Sent To  
Notes
2020-10-14 14:00:43PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE APPURTENANCE MOUNT MODIFICATION ANALYSIS STATES
 THAT IT WAS DONE IN ACCORDANCE WITH THE 2018
 INTERNATIONAL BUILDING CODE. THE 2018 IBC HAS NOT BE
 ADOPTED BY THE STATE OF FLORIDA AT THIS TIME. THE
 CURRENT CODE IS THE 2017 FLORIDA BUILDING CODE. PLEASE
 REVISE.
  
 2) THE DRAWINGS SPECIFY THAT THE EXPOSURE CATEGORY IS
 C. THIS PROJECT IS LOCATED IN EXPOSURE CATEGORY D. FBC
 1609.4
  
 3) ON DRAWING SHEET C-3, THE RRUS UNITS ARE SHOWN AS
 BEING RELOCATED TO UNISTRUT ATTACHED TO THE WALL OF THE
 BUILDING. PROVIDE ATTACHMENT DETAILS WITH THE REQUIRED
 NUMBER AND TYPES OF FASTENERS FOR ATTACHING THE
 UNISTRUT AND MOUNTING THE BOXES TO THE UNISTRUT. CITY
 AMENDMENTS FBC 107.2.1
  
 4) THE ENGINEER THAT DIGITALLY SIGNED AND SEALED THE
 APPURTENANCE MOUNT MODIFICATION ANALYSIS, SELF
 CERTIFIED HIS SIGNATURE. THE FLORIDA BOARD OF
 PROFESSIONAL ENGINEERS REQUIRES ENGINEERS TO HAVE A
 THIRD PARTY CERTIFICATION OF THEIR DIGITAL SIGNATURES.
  
 5) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-11-06 Cont ID  
Sent By equinone Date 2020-11-06 Time 10:56 Rev Time 0.00
Received By equinone Date 2020-11-06 Time 10:56 Sent To  
Notes
2020-11-06 10:57:27NO CHANGES TO ELECTRICAL DRAWINGS. PLANS STAMPED BY
 JAKE. EQ

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-10-08 Cont ID  
Sent By jleahy Date 2020-10-08 Time 09:56 Rev Time 0.00
Received By jleahy Date 2020-10-08 Time 09:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-12-08 Cont ID  
Sent By rmcdouga Date 2020-12-08 Time 09:17 Rev Time 0.00
Received By rmcdouga Date 2020-11-20 Time 15:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-11-16 Cont ID  
Sent By lmarchan Date 2020-11-16 Time 16:15 Rev Time 0.00
Received By lmarchan Date 2020-10-30 Time 10:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-10-14 Cont ID  
Sent By rmcdouga Date 2020-10-14 Time 14:01 Rev Time 0.00
Received By rmcdouga Date 2020-10-01 Time 10:52 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-12-08 Cont ID  
Sent By rmcdouga Date 2020-12-08 Time 09:17 Rev Time 0.00
Received By rmcdouga Date 2020-12-08 Time 09:17 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-11-04 Cont ID  
Sent By rmcdouga Date 2020-11-04 Time 15:43 Rev Time 0.00
Received By rmcdouga Date 2020-11-04 Time 14:43 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-10-14 Cont ID  
Sent By rmcdouga Date 2020-10-14 Time 14:01 Rev Time 0.00
Received By rmcdouga Date 2020-10-14 Time 12:41 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2020-12-02 Cont ID  
Sent By jroach Date 2020-12-02 Time 10:39 Rev Time 0.00
Received By jroach Date 2020-12-02 Time 10:38 Sent To  
Notes
2020-12-02 10:39:11PROVISO
  
 1. MEASURES TO PRESERVE REQUIRED EXISTING CONCEALMENT
 ELEMENTS, IF ANY, SHALL BE EMPLOYED, SUCH AS SCREENING
 OR PAINTING OF ADDED/RELOCATED EQUIPMENT TO MATCH THE
 BUILDING; AND
  
 2. THERE SHALL BE NO VISIBLE LOGOS OR MARKINGS OF ANY
 KIND ON VISUALLY EXPOSED AREAS; AND,
  
 3. THE APPLICANT SHALL MAINTAIN MARKINGS ON THE
 PENTHOUSE WHERE RF LEVELS EXCEED THE FCC MAXIMUM
 PERMITTED EXPOSURE LEVELS.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, PRINCIPAL
 PLANNER, AT [email protected] OR (561) 822-1448.

Review Stop Z ZONING
Rev No 2 Status P Date 2020-11-16 Cont ID  
Sent By jroach Date 2020-11-16 Time 16:07 Rev Time 0.00
Received By jroach Date 2020-11-16 Time 16:07 Sent To  
Notes
2020-11-16 16:07:51PROVISO
  
 1. MEASURES TO PRESERVE REQUIRED EXISTING CONCEALMENT
 ELEMENTS, IF ANY, SHALL BE EMPLOYED, SUCH AS SCREENING
 OR PAINTING OF ADDED/RELOCATED EQUIPMENT TO MATCH THE
 BUILDING; AND
  
 2. THERE SHALL BE NO VISIBLE LOGOS OR MARKINGS OF ANY
 KIND ON VISUALLY EXPOSED AREAS; AND,
  
 3. THE APPLICANT SHALL MAINTAIN MARKINGS ON THE
 PENTHOUSE WHERE RF LEVELS EXCEED THE FCC MAXIMUM
 PERMITTED EXPOSURE LEVELS.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, PRINCIPAL
 PLANNER, AT [email protected] OR (561) 822-1448.

Review Stop Z ZONING
Rev No 1 Status P Date 2020-10-08 Cont ID  
Sent By jroach Date 2020-10-08 Time 16:56 Rev Time 0.00
Received By jroach Date 2020-10-08 Time 16:51 Sent To  
Notes
2020-10-08 16:58:02PROVISO
  
 1. MEASURES TO PRESERVE REQUIRED EXISTING CONCEALMENT
 ELEMENTS, IF ANY, SHALL BE EMPLOYED, SUCH AS SCREENING
 OR PAINTING OF ADDED/RELOCATED EQUIPMENT TO MATCH THE
 BUILDING; AND
  
 2. THERE SHALL BE NO VISIBLE LOGOS OR MARKINGS OF ANY
 KIND ON VISUALLY EXPOSED AREAS; AND,
  
 3. THE APPLICANT SHALL MAINTAIN MARKINGS ON THE
 PENTHOUSE WHERE RF LEVELS EXCEED THE FCC MAXIMUM
 PERMITTED EXPOSURE LEVELS.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, PRINCIPAL
 PLANNER, AT [email protected] OR (561) 822-1448.