Plan Review Details - Permit 20091254
Plan Review Stops For Permit 20091254
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-10-30 Cont ID  
Sent By pvalenti Date 2020-10-30 Time 11:08 Rev Time 0.00
Received By pvalenti Date 2020-10-30 Time 11:07 Sent To  
Notes
2020-10-21 08:32:09PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
 FBC B 107:
  
 1) PLEASE PROVIDE A "BUILDING"SUB-PERMIT APPLICATION.
  
 2) PLEASE PROVIDE A FLOOR PLAN/SKETCH OF THE UNIT AND
 IDENTIFY THE AREA OF WORK INCLUDING MEASUREMENTS AND
 DETAILS.
  
 3) PLEASE SUBMIT THE FOLLOWING INFORMATION FOR THE NEW
 FLOORING:
 TWO COMPLETE COLLATED SETS OF ALL DOCUMENTS REQUIRED
  
 PLEASE NOTE THAT TEST REPORTS ARE REQUIRED -
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-10-21 Cont ID  
Sent By pvalenti Date 2020-10-21 Time 09:00 Rev Time 0.00
Received By pvalenti Date 2020-10-21 Time 09:00 Sent To  
Notes
2020-10-21 09:07:01 
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 1) FBC B 107, PROVIDE A "BUILDING" SUB-PERMIT
 APPLICATION.
  
 2) FBC B 107.2.1, PROVIDE A FLOOR PLAN/SKETCH OF THE
 UNIT SHOWING THE WORK TO BE PERFORMED INCLUDING THE
 LOCATIONS, MEASUREMENTS AND DETAILS.
  
 3) FBC B 107.2.1, PROVIDE THE FOLLOWING:
  
 PLEASE NOTE THAT TEST REPORTS ARE REQUIRED -
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL COMMENTS MAY
 RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-11-03 Cont ID  
Sent By lcrespo Date 2020-11-03 Time 10:33 Rev Time 0.00
Received By lcrespo Date 2020-10-23 Time 10:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-10-21 Cont ID  
Sent By lcrespo Date 2020-10-21 Time 11:47 Rev Time 0.00
Received By lcrespo Date 2020-10-08 Time 11:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-11-03 Cont ID  
Sent By lcrespo Date 2020-11-03 Time 10:32 Rev Time 0.00
Received By lcrespo Date 2020-11-02 Time 09:48 Sent To  
Notes
2020-11-03 10:33:4211/03/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-10-21 Cont ID  
Sent By lcrespo Date 2020-10-21 Time 11:46 Rev Time 0.00
Received By lcrespo Date 2020-10-21 Time 11:46 Sent To  
Notes
2020-10-21 11:47:4309/23/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. A BUILDING PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 2. PLEASE PROVIDE PLANS DRAWN IN DETAIL WITH THE SCOPE
 OF WORK AND PROVIDE ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS, AND ACCOMPANYING DATA THAT SHALL BEAR
 THE PRINTED NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN PER THE WPB AMENDMENTS TO
 THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 3. THIS BUILDING WAS CONSTRUCTED UNDER THE FAIR HOUSING
 ACT. PLEASE INDICATE ON PLANS WHICH DESIGN
 SPECIFICATION ( "A" OR "B" OF THE ACT) WAS USED IN THE
 ORIGINAL DESIGN OF THESE UNITS. TELL US WHICH USABLE
 BATHROOM IN THE DWELLING UNITS, THE ALTERATION THAT IS
 PROPOSED IN THE BATHROOM SHALL ALSO COMPLY WITH THE
 FAIR HOUSING ACT. IF THIS INFORMATION IS NOT AVAILABLE
 AND THE SCOPE OF WORK DOES NOT INVOLVE CHANGES TO FHA
 FOR EXAMPLE CHANGING A TUB TO A SHOWER IN A "B" TYPE
 BATHROOM THAT IS NOT ALLOWED. IT MAY BE DONE BUT THE
 HOMEOWNER WILL REQUIRE TO FILL OUT AND AFFIDAVIT SEE
 NEXT COMMENT.
  
 4. THE CITY OF WEST PALM BEACH BUILDING DEPARTMENT
 PROVIDES AN OPTION FOR THE CHANGING OF AN FHA
 COMPLIANCE STRUCTURE. THE OWNER AND DESIGNER OF RECORD
 ACKNOWLEDGE THAT THE PROPOSED BATHROOM DESIGN DOES NOT
 MEET THE REQUIREMENTS OF THE FAIR HOUSING ACCESSIBILITY
 GUIDELINES. THE OWNER AGREES TO REVERT THE UNIT BACK TO
 THE COMPLIANCE AT THE TIME OF SALE IF SO, REQUESTED BY
 THE BUYER. THIS WILL BE IN A LETTER TYPE FORMAT SIGNED
 AND NOTARIZED BY THE OWNER. WE PROVIDE A SAMPLE LETTER
 AND IT MUST BE SUBMITTED TO THE BUILDING DEPARTMENT OF
 THE CITY OF WPB. IF THIS OPTION IS CHOSEN, PLEASE SEND
 AN EMAIL TO [email protected] AND I WILL SEND A COPY OF
 THE FAIR HOUSING AFFIDAVIT.
  
 HTTPS://CODES.ICCSAFE.ORG/CATEGORY/FLORIDA?YEAR%5B%5D=C
 URRENT+ADOPTION&PAGE=1
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-10-30 Cont ID  
Sent By pvalenti Date 2020-10-30 Time 11:08 Rev Time 0.00
Received By pvalenti Date 2020-10-30 Time 11:08 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-10-21 Cont ID  
Sent By lcrespo Date 2020-10-21 Time 11:47 Rev Time 0.00
Received By lcrespo Date 2020-10-21 Time 11:47 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved