Plan Review Details - Permit 20091250
Plan Review Stops For Permit 20091250
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2020-11-27 Cont ID  
Sent By jwitmer Date 2020-11-27 Time 09:35 Rev Time 0.00
Received By jwitmer Date 2020-11-27 Time 09:32 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2020-11-19 Cont ID  
Sent By jwitmer Date 2020-11-19 Time 11:22 Rev Time 0.00
Received By jwitmer Date 2020-11-19 Time 11:16 Sent To  
Notes
2020-11-19 11:21:58COMMERCIAL ASBESTOS
  
 TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-10-18 Cont ID  
Sent By jwitmer Date 2020-10-18 Time 16:04 Rev Time 0.00
Received By jwitmer Date 2020-10-18 Time 14:46 Sent To  
Notes
2020-10-18 16:03:36COMMERCIAL ASBESTOS
  
 TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2021-01-09 Cont ID  
Sent By pvalenti Date 2021-01-09 Time 10:43 Rev Time 0.00
Received By pvalenti Date 2021-01-09 Time 09:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2020-12-15 Cont ID  
Sent By jwitmer Date 2020-12-15 Time 10:56 Rev Time 0.00
Received By jwitmer Date 2020-12-14 Time 12:01 Sent To  
Notes
2020-12-15 10:52:16WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20091250
 ADD: 4400 N. CONGRESS AVE. SUITE: 100
 CONT: BERG CONSTRUCTION
 TEL: 561-339-7827
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 4TH REVIEW
 DATE: TUES. DEC. 15TH/2020
 ACTION: DENIED
 1) COMPLIED.
  
 2A) 4TH ROUND COMMENTS.SAME COMMENT. THE DESIGNER OF
 RECORD STATES EACH RESTROOM IS FULLY ACCESSIBLE (115)
 WITH THE FOLLOWING EXCEPTION 116, 131, & 132. THIS
 MEANS THAT IN THE OPINION OF THE DESIGNER OF RECORD
 RESTROOM 115 IS FULLY COMPLIANT WITH THE 2017
 FBC-ACCESSIBILITY CODE.
 TO VERIFY THE DIMENSIONS IN RESTROOM 115 WE USUALLY SEE
 AN OVERALL BACKWALL WALL MEASUREMENT. THAT HAS NOT
 OCCURRED. THE LAST CONVERSATION WITH THE DESIGNER HE
 WAS GOING TO HAVE THE CONTRACTOR GO OUT TO THE JOBSITE
 AND MEASURE THE BACK WALL TO SEE WHAT THE ACTUAL FINISH
 MEASUREMENT IS. THIS REVIEW THERE IS STILL NO BACK WALL
 MEASUREMENT. IN THE PROJECT DOX PROGRAM THERE IS A
 MEASURING TOOL. WE HAVE TO CALIBRATE THE PLAN TO A
 GIVEN MEASUREMENT THEN WE CAN DETERMINE SIZE (LENGTH)
 OF VARIOUS COMPONENTS. TO CALIBRATE THIS PLAN, WE TOOK
 THE 2-FOOT 4-INCH MEASUREMENT BETWEEN RESTROOM 115 AND
 116. WE THEN TOOK THE CALIBRATED BACK WALL MEASUREMENT
 OF RESTROOM 115 AND DETERMINED THE BACK-WALL LENGTH TO
 BE 6 FEET 8 INCHES. WITH THAT MEASUREMENT YOU CANNOT
 GET THE REQUIRED 60 INCHES FROM THE ADJACENT SIDEWALL
 OF THE WATERCLOSET TO THE ADJACENT LAVATORY. IN
 MEASURING THE CLEAR FLOOR SPACE FOR THE WATER CLOSET
 THE REQUIRED 60 INCHES CLEAR FLOOR SPACE WAS NOT
 MEASURED CORRECTLY, (604.3.1. SIZE. CLEARANCE AROUND A
 WATER CLOSET SHALL BE 60 INCHES MINIMUM MEASURED
 PERPENDICULAR FROM THE SIDE WALL AND 56 INCHES MINIMUM
 PERPENDICULAR FROM THE REAR WALL. NOTE THE MINIMUM BACK
 WALL MEASUREMENT SHOULD BE 7-FOOT 1 INCH. THE 60-INCH
 MEASUREMENT IS TAKEN PERPENDICULAR FROM THE BACK WALL.
 THIS REVIEW I?VE SPOKEN TO MY SUPERVISOR ABOUT THIS
 PLAN WE BOTH VIEWED THE PLAN AND DISPROPORTION CAST
 LETTER. ALL HAVE CONCERNED THAT THE BACK-WALL
 MEASUREMENT HAS TO BE KNOWN TO KNOW HOW THE FUNDS ARE
 GOING TO BE SPENT IN THE EVENT OF DISPROPORTIONATE COST
 OCCURS.
  
  
 SEMI-COMPLIED. IN THE PASR THE DESIGN PROFESSIONAL DID
 CONTACT ME BY PHONE TO DISCUSS THIS PROJECT. I DID
 STATE THAT THE 20% DISPROPORTIONAT COST ($7,000.00
 DOLLARS) WOULD NEED TO BE SPENT IN EITHER ONE UNISEX
 RESTROOM AND IF THAT COULD NOT BE COMPLETED FOR
 $7,000.00 DOLLARS IT WOULD NEED A LETTER STATING AS
 SUCH FOR THAT DOLLAR AMOUNT AND IN THAT LETTER SHOW
 WHERE THE $7,000.00 DOLLARS IS GOING TO BE SPENT.
  
 1ST ROUND OF COMMENTS. SHEET A.1.1SHOWING 4 RESTROOMS
 AND NONE ARE SHOWN TO BE ACCESSIBLE RESTROOMS, NOT EVEN
 A SINGLE UNISEX RESTROOM.
 PLEASE REVIEW IN THE 2017 FBC-ACCESSIBILITY CODE
 CHAPTER 2 SCOPING REQUIREMENTS SECTION 213.2 FOR TOILET
 ROOMS AND BATHING ROOMS AND EXCEPTION 2 AND 4.
  
 2B) THE PLANS INDICATE THIS ALTERATION IS DECLARED AS A
 LEVEL II ALTERATION. EXISTING BLDG. CODE-
 ACCESSIBILITY. UNDER THE 2017 EXISTING BUILDING CODE
 LEVEL II ALTERATIONS, SECTION 806.1 A BUILDING,
 FACILITY, OR ELEMENT THAT IS ALTERED SHALL COMPLY WITH
 THE PROVISIONS OF THE FLORIDA BUILDING CODE-
 ACCESSIBILITY. IN THE ACCESSIBILITY CODE FOR
 ALTERATIONS YOU ARE REFERRED TO SECTION 202.4.1
 DISPROPORTIONATE COST AND 202.4.2 ACCESSIBLE FEATURES
 IN THE EVENT OF DISPROPORTIONALITY.
  
 THE CONTRACT VALUE FOR THIS JOB AS STATED IS $35,000.00
 DOLLARS. FLORIDA ACCESSIBILITY CODE SECTION:
 DISPROPORTIONATE COST 202.4.1. PLEASE REVIEW HOW YOU
 ARE TO MEET DISPROPORTIONATE COST. EITHER THE
 CONTRACTOR OR THE DESIGNER OF RECORD ON THEIR
 LETTERHEAD NEED TO SHOW HOW THEY ARE GOING TO SPEND UP
 TO THE 20% DISPROPORTIONATE FUNDS($35,000.00X0.20=
 $7,000.00) LISTED FOR EACH ELEMENT WHERE THE FUNDS ARE
 BEING SPENT AND IN THE ORDER LISTED IN SECTION 202.4.1
 DISPROPORTIONATE COST OF THE 2017 ACCESSIBILITY CODE.
  
 202.4.1. DISPROPORTIONATE COST. ALTERATIONS MADE TO
 PROVIDE AN ACCESSIBLE PATH OF TRAVEL TO THE ALTERED
 AREA WILL BE DEEMED DISPROPORTIONATE TO THE OVERALL
 ALTERATION WHEN THE COST EXCEEDS 20% OF THE COST OF THE
 ALTERATION TO THE PRIMARY FUNCTION AREA. COST THAT MAY
 BE COUNTED AS EXPENDITURES REQUIRED TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL MAY INCLUDE: (I) COST
 ASSOCIATED WITH PROVIDING AN ACCESSIBLE ENTRANCE AND AN
 ACCESSIBLE ROUT TO THE ALTERED AREA; (II) COST
 ASSOCIATED WITH MAKING RESTROOMS ACCESSIBLE, SUCH AS
 INSTALLING GRAB BARS, ENLARGING TOILET STALLS,
 INSULATING PIPES, OR INSTALLING ACCESSIBLE FAUCET
 CONTROLS; (III) COST ASSOCIATED WITH PROVIDING
 ACCESSIBLE TELEPHONES, SUCH AS RELOCATING THE TELEPHONE
 TO AN ACCESSIBLE HEIGHT, INSTALLING AMPLIFICATION
 DEVICES, OR INSTALLING A TEXT TELEPHONE (TTY); (IV)
 COST ASSOCIATED WITH RELOCATING AN ACCESSIBLE DRINKING
 FOUNTAIN.
 IF IN THE EVENT THE CONTRACTOR REACHES DISPROPORTION
 COST, THEN ON THEIR LETTERHEAD AGAIN THEY MUST SHOW
 WHERE UP TO $7,000.00 DOLLARS WILL BE SPENT IN
 ACCESSIBLE UPGRADES. IN REVIEWING THIS PLAN, IT WOULD
 APPEAR THE FUNDS WOULD BE SPENT IN CREATING A UNISEX
 RESTROOM.
 12/15/2020 WHEN REVIEWING THE LETTER FOR PROVING
 DISPROPORTIONATE COST THE WORDING FOR THE DOOR/
 HARDWARE IS NOT CLEAR. ARE 31 DOORS BEING CHANGED OUT
 WITH LEVER HARDWARE EACH DOOR AT A COST OF $167.00 PER
 DOOR, COST OF LABOR FOR INSTALLATION AND MATERIALS,
 DOOR FRAME AND HARDWARE FOR THIS PRICE. WE NEED TO SEE
 A COST BREAKDOWN FOR THE WHOLE JOB FROM THE CONTRACTOR
 SHOWING THIS FIGURE WAS NOT INCLUDED IN THE PRICE OF
 THE CONTRACT. WE ALSO NEED TO SEE THAT THE ACCESSIBLE
 HIGH-LOW DRINKING FOUNTAIN WAS NOT IN THE ORIGINAL
 CONTRACT VALUE. THAT THE ACCESSIBLE UPGRADES ARE TRULY
 OVER AND ABOVE THE CONTRACT VALUE.
  
 2B) COMPLIED, SHEET A3.1 DETAIL 4 SHOWS A DIFFERENT
 STYLE DRINKING FOUNTAIN THEN BEFORE.
  
 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2020-11-27 Cont ID  
Sent By jwitmer Date 2020-11-27 Time 10:17 Rev Time 0.00
Received By jwitmer Date 2020-11-27 Time 09:32 Sent To  
Notes
2020-11-27 10:16:14WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20091250
 ADD: 4400 N. CONGRESS AVE. SUITE: 100
 CONT: BERG CONSTRUCTION
 TEL: 561-339-7827
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: FRI. NOV. 27TH/2020
 ACTION: DENIED
 1) COMPLIED.
  
 2A) 3RD ROUND COMMENTS. THE DESIGNER OF RECORD STATES
 EACH RESTROOM IS FULLY ACCESSIBLE WITH THE FOLLOWING
 EXCEPTION 116,131,& 132. THIS MEANS THAT IN THE OPINION
 OF THE DESIGNER OF RECORD RESTROOM 115 IS FULLY
 COMPLIANT WITH THE 2017 FBC-ACCESSIBILITY CODE.
 TO VERIFY THE DIMENSIONS IN RESTROOM 115 WE USUALLY SEE
 AN OVERALL BACKWALL WALL MEASUREMENT. THAT HAS NOT
 OCCURRED. IN THE PROJECT DOX PROGRAM THERE IS A
 MEASURING TOOL. WE HAVETO CALIBRATE THE PLAN TO A GIVEN
 MEASUREMENT THEN WE CAN DETERMINE SIZE (LENGTH) OF
 VARIOUS COMPONENTS. TO CALIBRATE THIS PLAN WE TOOK THE
 2 FOOT 4 INCH MEASUREMENT BETWEEN RESTROOM 115 AND 116.
 WE THEN TOOK THE CALIBRATED BACK WALL MEASUREMENT OF
 RESTROOM 115 AND DETERMINED THE BACK WALL LENGTH TO BE
 6FEET 8 INCHES. WITH THAT MEASUREMENT YOU CAN NOT GET
 THE REQUIRED 60 INCHES FROM THE ADJACENT SIDEWALL OF
 THE WATERCLOSET TO THE ADJACENT LAVATORY. IN MEASURING
 THE CLEAR FLOOR SPACE FOR THE WATER CLOSET THE REQUIRED
 60 INCHES CLEAR FLOOR SPACE WAS NOT MEASURED CORRECTLY,
 (604.3.1. SIZE. CLEARANCE AROUND A WATER CLOSET SHALL
 BE 60 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE
 SIDE WALL AND 56 INCHES MINIMUM PERPENDICULAR FROM THE
 REAR WALL. NOTE THE MINIMUM BACK WALL MEASUREMENT
 SHOULD BE 7-FOOT 1 INCH). THE 60 INCH MEASUREMENT IS
 TAKEN PERPENDICULAR FROM THE BACK WALL.
  
  
 SEMI-COMPLIED. IN THE PASR THE DESIGN PROFESSIONAL DID
 CONTACT ME BY PHONE TO DISCUSS THIS PROJECT. I DID
 STATE THAT THE 20% DISPROPORTIONAT COST ($7,000.00
 DOLLARS) WOULD NEED TO BE SPENT IN EITHER ONE UNISEX
 RESTROOM AND IF THAT COULD NOT BE COMPLETED FOR
 $7,000.00 DOLLARS IT WOULD NEED A LETTER STATING AS
 SUCH FOR THAT DOLLAR AMOUNT AND IN THAT LETTER SHOW
 WHERE THE $7,000.00 DOLLARS IS GOING TO BE SPENT. THIS
 LETTER IS NOT TO BE PART OF THE PLAN REVIEW COMMENTS
 BUT ON THEIR LETTERHEAD AND LOADED AS A SEPARATE
 DOCUMENT IN THE FILE FOLDER. THANK YOU FOR YOUR HELP IN
 THIS MATTER..
  
 1ST ROUND OF COMMENTS. SHEET A.1.1SHOWING 4 RESTROOMS
 AND NONE ARE SHOWN TO BE ACCESSIBLE RESTROOMS, NOT EVEN
 A SINGLE UNISEX RESTROOM.
 PLEASE REVIEW IN THE 2017 FBC-ACCESSIBILITY CODE
 CHAPTER 2 SCOPING REQUIREMENTS SECTION 213.2 FOR TOILET
 ROOMS AND BATHING ROOMS AND EXCEPTION 2 AND 4.
  
 2B) THE PLANS INDICATE THIS ALTERATION IS DECLARED AS A
 LEVEL II ALTERATION. EXISTING BLDG. CODE-
 ACCESSIBILITY. UNDER THE 2017 EXISTING BUILDING CODE
 LEVEL II ALTERATIONS, SECTION 806.1 A BUILDING,
 FACILITY, OR ELEMENT THAT IS ALTERED SHALL COMPLY WITH
 THE PROVISIONS OF THE FLORIDA BUILDING CODE-
 ACCESSIBILITY. IN THE ACCESSIBILITY CODE FOR
 ALTERATIONS YOU ARE REFERRED TO SECTION 202.4.1
 DISPROPORTIONATE COST AND 202.4.2 ACCESSIBLE FEATURES
 IN THE EVENT OF DISPROPORTIONALITY.
  
 THE CONTRACT VALUE FOR THIS JOB AS STATED IS $35,000.00
 DOLLARS. FLORIDA ACCESSIBILITY CODE SECTION:
 DISPROPORTIONATE COST 202.4.1. PLEASE REVIEW HOW YOU
 ARE TO MEET DISPROPORTIONATE COST. EITHER THE
 CONTRACTOR OR THE DESIGNER OF RECORD ON THEIR
 LETTERHEAD NEED TO SHOW HOW THEY ARE GOING TO SPEND UP
 TO THE 20% DISPROPORTIONATE FUNDS($35,000.00X0.20=
 $7,000.00) LISTED FOR EACH ELEMENT WHERE THE FUNDS ARE
 BEING SPENT AND IN THE ORDER LISTED IN SECTION 202.4.1
 DISPROPORTIONATE COST OF THE 2017 ACCESSIBILITY CODE.
  
 202.4.1. DISPROPORTIONATE COST. ALTERATIONS MADE TO
 PROVIDE AN ACCESSIBLE PATH OF TRAVEL TO THE ALTERED
 AREA WILL BE DEEMED DISPROPORTIONATE TO THE OVERALL
 ALTERATION WHEN THE COST EXCEEDS 20% OF THE COST OF THE
 ALTERATION TO THE PRIMARY FUNCTION AREA. COST THAT MAY
 BE COUNTED AS EXPENDITURES REQUIRED TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL MAY INCLUDE: (I) COST
 ASSOCIATED WITH PROVIDING AN ACCESSIBLE ENTRANCE AND AN
 ACCESSIBLE ROUT TO THE ALTERED AREA; (II) COST
 ASSOCIATED WITH MAKING RESTROOMS ACCESSIBLE, SUCH AS
 INSTALLING GRAB BARS, ENLARGING TOILET STALLS,
 INSULATING PIPES, OR INSTALLING ACCESSIBLE FAUCET
 CONTROLS; (III) COST ASSOCIATED WITH PROVIDING
 ACCESSIBLE TELEPHONES, SUCH AS RELOCATING THE TELEPHONE
 TO AN ACCESSIBLE HEIGHT, INSTALLING AMPLIFICATION
 DEVICES, OR INSTALLING A TEXT TELEPHONE (TTY); (IV)
 COST ASSOCIATED WITH RELOCATING AN ACCESSIBLE DRINKING
 FOUNTAIN.
 IF IN THE EVENT THE CONTRACTOR REACHES DISPROPORTION
 COST THEN ON THEIR LETTERHEAD AGAIN THEY MUST SHOW
 WHERE UP TO $7,000.00 DOLLARS WILL BE SPENT IN
 ACCESSIBLE UPGRADES. IN REVIEWING THIS PLAN IT WOULD
 APPEAR THE FUNDS WOULD BE SPENT IN CREATING A UNISEX
 RESTROOM.
  
 2B) NEW COMMENT. SHEET A3.1 DETAIL 4 DOES SHOW THE HIGH
 LOW DRINKING FOUNTAIN AND WITH THIS TYPE OF DRINKING
 FOUNTAIN THE LOW DRINKING FOUNTAIN MEETS THE PROTRUDING
 OBJECT REQUIREMENTS BUT AS SHOWN IF WALKING DOWN THE
 CORRIDOR FROM THE RIGHT THE BOTTOM OF THE UPPER
 DRINKING FOUNTAIN IS HIGHER THAN 27 INCHES AND NOT
 MEETING THE REQUIREMENTS OF THE 2017 FBC-ACCESSIBILITY
 CODE SECTION PROTRUDING OBJECTS 307.2 PROTRUSION LIMITS
 307.2. OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES
 AND NOT MORE THAN 80 INCHES ABOVE THE FLOOR SHALL NOT
 PROTRUDE MORE THAN 4 INCHES HORIZONTALLY INTO THE
 CIRCULATION PATH.
  
 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-11-19 Cont ID  
Sent By jwitmer Date 2020-11-19 Time 11:59 Rev Time 0.00
Received By jwitmer Date 2020-11-19 Time 11:17 Sent To  
Notes
2020-11-19 11:59:26WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20091250
 ADD: 4400 N. CONGRESS AVE. SUITE: 100
 CONT: BERG CONSTRUCTION
 TEL: 561-339-7827
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURS. NOV. 19TH/2020
 ACTION: DENIED
 1) COMPLIED.
  
 2A) SEMI-COMPLIED. IN THE PASR THE DESIGN PROFESSIONAL
 DID CONTACT ME BY PHONE TO DISCUSS THIS PROJECT. I DID
 STATE THAT THE 20% DISPROPORTIONAT COST ($7,000.00
 DOLLARS) WOULD NEED TO BE SPENT IN EITHER ONE UNISEX
 RESTROOM AND IF THAT COULD NOT BE COMPLETED FOR
 $7,000.00 DOLLARS IT WOULD NEED A LETTER STATING AS
 SUCH FOR THAT DOLLAR AMOUNT AND IN THAT LETTER SHOW
 WHERE THE $7,000.00 DOLLARS IS GOING TO BE SPENT. THIS
 LETTER IS NOT TO BE PART OF THE PLAN REVIEW COMMENTS
 BUT ON THEIR LETTERHEAD AND LOADED AS A SEPARATE
 DOCUMENT IN THE FILE FOLDER. THANK YOU FOR YOUR HELP IN
 THIS MATTER..
  
 1ST ROUND OF COMMENTS. SHEET A.1.1SHOWING 4 RESTROOMS
 AND NONE ARE SHOWN TO BE ACCESSIBLE RESTROOMS, NOT EVEN
 A SINGLE UNISEX RESTROOM.
 PLEASE REVIEW IN THE 2017 FBC-ACCESSIBILITY CODE
 CHAPTER 2 SCOPING REQUIREMENTS SECTION 213.2 FOR TOILET
 ROOMS AND BATHING ROOMS AND EXCEPTION 2 AND 4.
  
 2B) THE PLANS INDICATE THIS ALTERATION IS DECLARED AS A
 LEVEL II ALTERATION. EXISTING BLDG. CODE-
 ACCESSIBILITY. UNDER THE 2017 EXISTING BUILDING CODE
 LEVEL II ALTERATIONS, SECTION 806.1 A BUILDING,
 FACILITY, OR ELEMENT THAT IS ALTERED SHALL COMPLY WITH
 THE PROVISIONS OF THE FLORIDA BUILDING CODE-
 ACCESSIBILITY. IN THE ACCESSIBILITY CODE FOR
 ALTERATIONS YOU ARE REFERRED TO SECTION 202.4.1
 DISPROPORTIONATE COST AND 202.4.2 ACCESSIBLE FEATURES
 IN THE EVENT OF DISPROPORTIONALITY.
  
 THE CONTRACT VALUE FOR THIS JOB AS STATED IS $35,000.00
 DOLLARS. FLORIDA ACCESSIBILITY CODE SECTION:
 DISPROPORTIONATE COST 202.4.1. PLEASE REVIEW HOW YOU
 ARE TO MEET DISPROPORTIONATE COST. EITHER THE
 CONTRACTOR OR THE DESIGNER OF RECORD ON THEIR
 LETTERHEAD NEED TO SHOW HOW THEY ARE GOING TO SPEND UP
 TO THE 20% DISPROPORTIONATE FUNDS($35,000.00X0.20=
 $7,000.00) LISTED FOR EACH ELEMENT WHERE THE FUNDS ARE
 BEING SPENT AND IN THE ORDER LISTED IN SECTION 202.4.1
 DISPROPORTIONATE COST OF THE 2017 ACCESSIBILITY CODE.
  
 202.4.1. DISPROPORTIONATE COST. ALTERATIONS MADE TO
 PROVIDE AN ACCESSIBLE PATH OF TRAVEL TO THE ALTERED
 AREA WILL BE DEEMED DISPROPORTIONATE TO THE OVERALL
 ALTERATION WHEN THE COST EXCEEDS 20% OF THE COST OF THE
 ALTERATION TO THE PRIMARY FUNCTION AREA. COST THAT MAY
 BE COUNTED AS EXPENDITURES REQUIRED TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL MAY INCLUDE: (I) COST
 ASSOCIATED WITH PROVIDING AN ACCESSIBLE ENTRANCE AND AN
 ACCESSIBLE ROUT TO THE ALTERED AREA; (II) COST
 ASSOCIATED WITH MAKING RESTROOMS ACCESSIBLE, SUCH AS
 INSTALLING GRAB BARS, ENLARGING TOILET STALLS,
 INSULATING PIPES, OR INSTALLING ACCESSIBLE FAUCET
 CONTROLS; (III) COST ASSOCIATED WITH PROVIDING
 ACCESSIBLE TELEPHONES, SUCH AS RELOCATING THE TELEPHONE
 TO AN ACCESSIBLE HEIGHT, INSTALLING AMPLIFICATION
 DEVICES, OR INSTALLING A TEXT TELEPHONE (TTY); (IV)
 COST ASSOCIATED WITH RELOCATING AN ACCESSIBLE DRINKING
 FOUNTAIN.
 IF IN THE EVENT THE CONTRACTOR REACHES DISPROPORTION
 COST THEN ON THEIR LETTERHEAD AGAIN THEY MUST SHOW
 WHERE UP TO $7,000.00 DOLLARS WILL BE SPENT IN
 ACCESSIBLE UPGRADES. IN REVIEWING THIS PLAN IT WOULD
 APPEAR THE FUNDS WOULD BE SPENT IN CREATING A UNISEX
 RESTROOM.
  
 2B) NEW COMMENT. SHEET A3.1 DETAIL 4 DOES SHOW THE HIGH
 LOW DRINKING FOUNTAIN AND WITH THIS TYPE OF DRINKING
 FOUNTAIN THE LOW DRINKING FOUNTAIN MEETS THE PROTRUDING
 OBJECT REQUIREMENTS BUT AS SHOWN IF WALKING DOWN THE
 CORRIDOR FROM THE RIGHT THE BOTTOM OF THE UPPER
 DRINKING FOUNTAIN IS HIGHER THAN 27 INCHES AND NOT
 MEETING THE REQUIREMENTS OF THE 2017 FBC-ACCESSIBILITY
 CODE SECTION PROTRUDING OBJECTS 307.2 PROTRUSION LIMITS
 307.2. OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES
 AND NOT MORE THAN 80 INCHES ABOVE THE FLOOR SHALL NOT
 PROTRUDE MORE THAN 4 INCHES HORIZONTALLY INTO THE
 CIRCULATION PATH.
  
 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-10-18 Cont ID  
Sent By jwitmer Date 2020-10-18 Time 16:05 Rev Time 0.00
Received By jwitmer Date 2020-10-18 Time 14:46 Sent To  
Notes
2020-10-18 16:05:11WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20091250
 ADD: 4400 N. CONGRESS AVE. SUITE: 100
 CONT: BERG CONSTRUCTION
 TEL: 561-339-7827
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SUN. OCT. 18TH/2020
 ACTION: DENIED
 1) SHEET A1.1 SHOWS 4 RESTROOMS. RESTROOMS 115 & 116
 STATE THE ARE EXISTING, RESTROOMS 131 & 132 HAVE NOT
 DECLARED IF THEY ARE EXISTING OR NEW? 2017 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATIVE CODE SECTION 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 2A) SHEET A.1.1SHOWING 4 RESTROOMS AND NONE ARE SHOWN
 TO BE ACCESSIBLE RESTROOMS, NOT EVEN A SINGLE UNISEX
 RESTROOM.
 PLEASE REVIEW IN THE 2017 FBC-ACCESSIBILITY CODE
 CHAPTER 2 SCOPING REQUIREMENTS SECTION 213.2 FOR TOILET
 ROOMS AND BATHING ROOMS AND EXCEPTION 2 AND 4.
  
 2B) THE PLANS INDICATE THIS ALTERATION IS DECLARED AS A
 LEVEL II ALTERATION. EXISTING BLDG. CODE-
 ACCESSIBILITY. UNDER THE 2017 EXISTING BUILDING CODE
 LEVEL II ALTERATIONS, SECTION 806.1 A BUILDING,
 FACILITY, OR ELEMENT THAT IS ALTERED SHALL COMPLY WITH
 THE PROVISIONS OF THE FLORIDA BUILDING CODE-
 ACCESSIBILITY. IN THE ACCESSIBILITY CODE FOR
 ALTERATIONS YOU ARE REFERRED TO SECTION 202.4.1
 DISPROPORTIONATE COST AND 202.4.2 ACCESSIBLE FEATURES
 IN THE EVENT OF DISPROPORTIONALITY.
  
 THE CONTRACT VALUE FOR THIS JOB AS STATED IS $35,000.00
 DOLLARS. FLORIDA ACCESSIBILITY CODE SECTION:
 DISPROPORTIONATE COST 202.4.1. PLEASE REVIEW HOW YOU
 ARE TO MEET DISPROPORTIONATE COST. EITHER THE
 CONTRACTOR OR THE DESIGNER OF RECORD ON THEIR
 LETTERHEAD NEED TO SHOW HOW THEY ARE GOING TO SPEND UP
 TO THE 20% DISPROPORTIONATE FUNDS($35,000.00X0.20=
 $7,000.00) LISTED FOR EACH ELEMENT WHERE THE FUNDS ARE
 BEING SPENT AND IN THE ORDER LISTED IN SECTION 202.4.1
 DISPROPORTIONATE COST OF THE 2017 ACCESSIBILITY CODE.
  
 202.4.1. DISPROPORTIONATE COST. ALTERATIONS MADE TO
 PROVIDE AN ACCESSIBLE PATH OF TRAVEL TO THE ALTERED
 AREA WILL BE DEEMED DISPROPORTIONATE TO THE OVERALL
 ALTERATION WHEN THE COST EXCEEDS 20% OF THE COST OF THE
 ALTERATION TO THE PRIMARY FUNCTION AREA. COST THAT MAY
 BE COUNTED AS EXPENDITURES REQUIRED TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL MAY INCLUDE: (I) COST
 ASSOCIATED WITH PROVIDING AN ACCESSIBLE ENTRANCE AND AN
 ACCESSIBLE ROUT TO THE ALTERED AREA; (II) COST
 ASSOCIATED WITH MAKING RESTROOMS ACCESSIBLE, SUCH AS
 INSTALLING GRAB BARS, ENLARGING TOILET STALLS,
 INSULATING PIPES, OR INSTALLING ACCESSIBLE FAUCET
 CONTROLS; (III) COST ASSOCIATED WITH PROVIDING
 ACCESSIBLE TELEPHONES, SUCH AS RELOCATING THE TELEPHONE
 TO AN ACCESSIBLE HEIGHT, INSTALLING AMPLIFICATION
 DEVICES, OR INSTALLING A TEXT TELEPHONE (TTY); (IV)
 COST ASSOCIATED WITH RELOCATING AN ACCESSIBLE DRINKING
 FOUNTAIN.
 IF IN THE EVENT THE CONTRACTOR REACHES DISPROPORTION
 COST THEN ON THEIR LETTERHEAD AGAIN THEY MUST SHOW
 WHERE UP TO $7,000.00 DOLLARS WILL BE SPENT IN
 ACCESSIBLE UPGRADES. IN REVIEWING THIS PLAN IT WOULD
 APPEAR THE FUNDS WOULD BE SPENT IN CREATING A UNISEX
 RESTROOM.
  
 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-12-04 Cont ID  
Sent By equinone Date 2020-12-04 Time 09:26 Rev Time 0.00
Received By equinone Date 2020-12-04 Time 09:26 Sent To  
Notes
2020-12-04 09:26:44SEE SIGNATURE COMMENTS

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-11-23 Cont ID  
Sent By equinone Date 2020-11-23 Time 08:25 Rev Time 0.00
Received By equinone Date 2020-11-23 Time 08:25 Sent To  
Notes
2020-11-23 08:26:02ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED,
  
 PLAN REVIEW COMMENT RESPONSES SIGNED MAKES REFERENCE TO
 A REVISED EP-1 SUBMITTED ADDRESING THE COMMENTS FROM
 REVIEW NO. 1. HOWEVER, IT SEEMS THAT THE REVISED EP-1
 HAS NOT BEEN UPLOADED YET. THE PREVIOUS COMMENTS STILL
 NEED TO BE ADDRESSED.
  
 PREVIOUS COMMENTS BELOW:
  
 AHUS AND HPS:
  
 1) INDICATE LOCATION OF EQUIPMENT AND DISCONNECTING
 MEANS ON ELECTRICAL DRAWINGS AND CIRCUIT NUMBER AND
 PANEL.
 2) SPECIFY SIZE OF CONDUCTORS FEEDING EACH UNIT.
 INCLUDE GROUNDING EQUIPMENT CONDUCTOR (NEC 440)
 3) PROVIDE REQUIRED 125-VOLT, SINGLE-PHASE, 15 OR 20
 AMPS RATED RECEPTACLE WITHIN 25 FEET OF EACH UNIT AS
 PER NEC 210-63. IF UNITS ARE LOCATED IN ROOFTOPS
 RECEPTABLE MUST BE GFCI TYPE (NEC 210-8 B(3)
  
 PANELS C AND D:
  
 4) INDICATE LOCATION ON ELECTRICAL DRAWINGS
  
 SIGNATURE:
  
 5) SEE SIGNATURE COMMENTS FOR ALL DRAWINGS (DIGITAL
 SIGNATURE IS REQUIRED).
  
 FS471, FS481, DOCUMENTS PREPARED BY AN ARCHITECT OR
 ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED, SEALED, DATED ORIGINALS. A SCAN OF A SIGNED
 PLAN IS NOT CONSIDERED AN ORIGINAL.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-10-29 Cont ID  
Sent By equinone Date 2020-10-29 Time 14:49 Rev Time 0.00
Received By equinone Date 2020-10-29 Time 14:48 Sent To  
Notes
2020-10-29 15:23:18ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED,
 SEE COMMENTS BELOW
  
 AHUS AND HPS:
  
 1) INDICATE LOCATION OF EQUIPMENT AND DISCONNECTING
 MEANS ON ELECTRICAL DRAWINGS AND CIRCUIT NUMBER AND
 PANEL.
 2) SPECIFY SIZE OF CONDUCTORS FEEDING EACH UNIT.
 INCLUDE GROUNDING EQUIPMENT CONDUCTOR (NEC 440)
 3) PROVIDE REQUIRED 125-VOLT, SINGLE-PHASE, 15 OR 20
 AMPS RATED RECEPTACLE WITHIN 25 FEET OF EACH UNIT AS
 PER NEC 210-63. IF UNITS ARE LOCATED IN ROOFTOPS
 RECEPTABLE MUST BE GFCI TYPE (NEC 210-8 B(3)
  
 PANELS C AND D:
  
 4) INDICATE LOCATION ON ELECTRICAL DRAWINGS
  
 SIGNATURE:
  
 5) SEE SIGNATURE COMMENTS FOR ALL DRAWINGS (DIGITAL
 SIGNATURE IS REQUIRED).
  
 FS471, FS481, DOCUMENTS PREPARED BY AN ARCHITECT OR
 ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED, SEALED, DATED ORIGINALS. A SCAN OF A SIGNED
 PLAN IS NOT CONSIDERED AN ORIGINAL.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2020-11-24 Cont ID  
Sent By pleduc Date 2020-11-24 Time   Rev Time 0.00
Received By pleduc Date 2020-11-24 Time 12:40 Sent To  
Notes
2020-11-24 12:42:34FIRE PROVISO:
  
 ANY FIRE ALARM WORK, INCLUDING DEMO, SHALL BE UNDER
 SEPARATE PERMIT AND SHOPR DRAWINGS
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-11-16 Cont ID  
Sent By pleduc Date 2020-11-16 Time   Rev Time 0.00
Received By pleduc Date 2020-11-16 Time 15:51 Sent To  
Notes
2020-11-16 15:52:11FIRE PROVISO:
  
 ANY FIRE ALARM WORK, INCLUDING DEMO, SHALL BE UNDER
 SEPARATE PERMIT AND SHOPR DRAWINGS
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-10-19 Cont ID  
Sent By pleduc Date 2020-10-19 Time   Rev Time 0.00
Received By pleduc Date 2020-10-16 Time 16:28 Sent To  
Notes
2020-10-19 16:47:13FIRE PROVISO:
  
 ANY FIRE ALARM WORK, INCLUDING DEMO, SHALL BE UNDER
 SEPARATE PERMIT AND SHOPR DRAWINGS
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2021-01-19 Cont ID  
Sent By pvalenti Date 2021-01-19 Time 06:54 Rev Time 0.00
Received By pvalenti Date 2021-01-13 Time 15:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date   Cont ID  
Sent By   Date 2021-01-13 Time   Rev Time 0.00
Received By ccarvaja Date 2021-01-07 Time 18:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2021-01-07 Cont ID  
Sent By jleahy Date 2021-01-07 Time 10:02 Rev Time 0.00
Received By jleahy Date 2021-01-07 Time 10:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2020-12-18 Time   Rev Time 0.00
Received By ccarvaja Date 2020-12-11 Time 18:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-12-04 Cont ID  
Sent By equinone Date 2020-12-04 Time 09:27 Rev Time 0.00
Received By equinone Date 2020-11-23 Time 15:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-11-23 Cont ID  
Sent By equinone Date 2020-11-23 Time 08:29 Rev Time 0.00
Received By equinone Date 2020-11-13 Time 10:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-10-29 Cont ID  
Sent By jleahy Date 2020-10-29 Time 17:16 Rev Time 0.00
Received By jleahy Date 2020-10-14 Time 16:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2020-12-16 Cont ID  
Sent By medwards Date 2020-12-16 Time 17:34 Rev Time 0.00
Received By medwards Date 2020-12-16 Time 17:34 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2020-11-25 Cont ID  
Sent By medwards Date 2020-11-25 Time 10:52 Rev Time 0.00
Received By medwards Date 2020-11-25 Time 10:52 Sent To  
Notes
2020-11-25 10:52:461ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20091250
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) 3RD TIME ASKING FOR THE OUTDOOR AIR CALCULATIONS.
 PLEASE PROVIDE OUTDOOR AIR CALCULATIONS FOR EACH USE OF
 SPACE IN THIS TENANT SPACE I.E. CONFERENCE ROOMS, MAIN
 ENTRY LOBBY, OFFICES SPACES, RECEPTION AREAS. FBC M
 TABLE 403.3.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2020-11-16 Cont ID  
Sent By medwards Date 2020-11-16 Time 09:40 Rev Time 0.00
Received By medwards Date 2020-11-16 Time 09:16 Sent To  
Notes
2020-11-16 09:40:592ND REVIEW FBC-2017 MECHANICAL
 PERMIT- 20091250
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 CAN NOT COMPLETE SECOND CYCLE REVIEW:
  
 1) THERE IS NO REVISED M-1 SHEET SUBMITTED IN THE
 SECOND CYCLE SET OF DOCUMENTS.
  
 2) THERE IS NO HEAT LOAD AND ENERGY CALCULATION FORMS
 SUBMITTED IN THIS SECOND CYCLE SET OF DOCUMENTS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-10-16 Cont ID  
Sent By medwards Date 2020-10-16 Time 14:46 Rev Time 0.00
Received By medwards Date 2020-10-16 Time 14:46 Sent To  
Notes
2020-10-16 14:48:101ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20091250
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE OUTSIDE AIR CALCULATIONS. FBC M TABLE
 403.3.1.1
  
 2) PLEASE PROVIDE AN OCCUPANT LOAD FOR THIS PROJECT.
 FBC M TABLE 403.3.1.1
  
 3) PLEASE PROVIDE A SCOPE OF WORK FOR THE MECHANICAL
 SYSTEMS. FBC 107.2.1
  
 4) PLEASE PROVIDE A DEMO SHEET FOR THE MECHANICAL
 SYSTEMS. FBC 107.2.1
  
 5) IF THIS IS ALL NEW UNITS, PLEASE PROVIDE
 CALCULATIONS FOR HEATING AND COOLING LOADS. FBC EC
 C403.2.1
  
 6) PLEASE SHOW THE LOCATION OF THE OUTSIDE AIR DUCT
 TERMINATIONS. PROVIDE A ROOF DETAIL SHEET TO VERIFY ALL
 CLEARANCES ARE MET. FBC M 401.4
  
 7) PLEASE SHOW THE TERMINATION LOCATION FOR THE
 BATHROOM EXHAUST FANS. FBC M 501.3
  
 8) PLEASE SHOW THE CFM?S THAT AHU-3 IS SUPPLYING TO THE
 RECEPTION AREA. FBC107.2.1
  
 9) PLEASE SHOW THE LOCATION OF THE CONDENSING UNITS.
 FBC 107.2.1
  
 10) PLEASE SHOW WHERE THE CONDENSATION FOR EACH OF THE
 AHU?S WILL BE DISPOSED. THERE IS NO PLUMBING SHEET
 ATTACHED TO THIS PROJECT. FBC M 307.2.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 5 Status P Date 2021-01-13 Cont ID  
Sent By ccole Date 2021-01-13 Time 13:20 Rev Time 0.00
Received By ccole Date 2021-01-13 Time 13:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2020-12-18 Cont ID  
Sent By ccole Date 2020-12-18 Time 10:42 Rev Time 0.00
Received By ccole Date 2020-12-18 Time 09:49 Sent To  
Notes
2020-12-18 10:42:504TH REVIEW FBC-2017 PLUMBING
 PERMIT- 20091250
 12/18/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 COMMENT #3 LISTED BELOW FROM THE PREVIOUS REVIEW STILL
 EXISTS.
  
 3) FAILED. SHEET MP: THE DRINKING FOUNTAIN DRAIN CANNOT
 CONNECT TO THE HORIZONTAL WET VENT OF THE BATHROOM
 FIXTURES PER SECTION 912.1 FBC P. THE DRAIN SHALL
 CONNECT DOWNSTREAM OF THE WET VENT AND BE INDIVIDUALLY
 VENTED. THE REVISED MP-1 IS STILL SHOWING THE DRINKING
 FOUNTAIN DRAIN CONNECTING INT THE WET VENT OF THE
 ADJACENT BATHROOM.
  
 6) PASSED. 4TH REQUEST FOR A PLUMBING SUB-PERMIT
 APPLICATION- SECTION 105.1 WPB. PLEASE NOTE THE
 APPLICATION CAN BE SUBMITTED AFTER THE MAIN PERMIT
 ISSUANCE HOWEVER NO PLUMBING DEMOLITION OR REWORK WORK
 SHALL COMMENCE UNTIL THE SUB-PERMIT IS ISSUED.
  
 NEW COMMENT.
 FINAL APPROVAL OF THE PLUMBING PLANS IS CONTINGENT ON A
 PASSED BUILDING PLAN REVIEW. PLEASE REVIEW BUILDING
 COMMENTS CONCERNING DISPROPORTIONATE COSTS AND
 ACCESSIBLE BATHROOM COMPLIANCE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2020-11-24 Cont ID  
Sent By ccole Date 2020-11-24 Time 10:26 Rev Time 0.00
Received By ccole Date 2020-11-24 Time 09:13 Sent To  
Notes
2020-11-24 10:26:483RD REVIEW FBC-2017 PLUMBING
 PERMIT- 20091250
 11/24/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS A1.1 & A3.1: AS PREVIOUSLY NOTED THE DRINKING
 FOUNTAIN IS PROTRUDING INTO THE INTO THE CIRCULATION
 PATH WHICH IS NOT ALLOWED PER SECTION 307.2 FBC ACC.
  
 2) PLEASE PROVIDE AN EQUIPMENT SCHEDULE FOR THE
 DRINKING FOUNTAIN INDICATING THE MAKE AND MODEL OF THE
 UNIT- SECTION 410.1 FBC P.
  
 3) SHEET MP: THE DRINKING FOUNTAIN DRAIN CANNOT CONNECT
 TO THE HORIZONTAL WET VENT OF THE BATHROOM FIXTURES PER
 SECTION 912.1 FBC P. THE DRAIN SHALL CONNECT DOWNSTREAM
 OF THE WET VENT AND BE INDIVIDUALLY VENTED.
  
 4) MP: PROVIDE A WATER HAMMER ARRESTOR FOR THE WATER
 SUPPLY LINE TO THE DRINKING FOUNTAIN- SECTION 604.9 FBC
 P.
  
 5) 3RD REQUEST FOR A SLAB REPAIR FOR THE NEW PLUMBING
 DRAIN INSTALLATION - SECTION 107.2.1 WPB.
  
 6) 3RD REQUEST FOR A PLUMBING SUB-PERMIT APPLICATION-
 SECTION 105.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-11-17 Cont ID  
Sent By ccole Date 2020-11-17 Time 09:12 Rev Time 0.00
Received By ccole Date 2020-11-17 Time 07:21 Sent To  
Notes
2020-11-17 09:13:182ND REVIEW FBC-2017 PLUMBING
 PERMIT- 20091250
 11/17/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 THE NEW PLAN SHEET MP1 WAS NOT UPLOADED FOR REVIEW. THE
 COMMENTS FROM THE 1ST REVIEW LISTED BELOW ARE MARKED AS
 PASSED OR FAILED. SOME NOTES HAVE BEEN ADDED TO FAILED
 COMMENTS.
  
 1) FAILED- NO PLANS SUBMITTED. REFER TO SECTION
 107.3.5.1.1 AMENDMENTS TO THE FBC-17 AND PROVIDE
 PLUMBING PLANS INCLUDING:
 A) FAILED. SCOPE OF WORK OUTLINE.
 B) FAILED. SANITARY AND WATER RISER DRAWINGS FOR
 INSTALLATION OF THE NEW DRINKING FOUNTAINS.
 C) FAILED. PLUMBING FIXTURE CALCULATIONS- TABLE 403.3
 FBC P. INDICATE THE REQUIRED AND PROVIDED NUMBER OF
 FIXTURES PER THE TABLE.
 D) FAILED. REFER TO SECTIONS 306, 307, AND 602 FBC ACC
 AND PROVIDE DRINKING FOUNTAIN INSTALLATION DETAILS AND
 ELEVATION VIEWS SHOWING KNEE AND TOE CLEARANCES, SPOUT
 HEIGHTS, AND SPOUT LOCATIONS. INDICATE HOW THE
 FOUNTAINS WILL BE IN COMPLIANCE WITH SECTION 307.2-
 PROTRUDING OBJECTS INTO THE CIRCULATION PATH. THE
 DETAIL ON SHEET A3.1 IS INCOMPLETE- REFER TO FIGURES
 306.2, 307.2, & 602.5 FBC ACC. IT APPEARS A
 BARRIER-FREE TYPE DRINKING FOUNTAIN IS PROPOSED WHICH
 NEEDS TO BE INSTALLED IN A RECESSED NICHE TO BE IN
 COMPLIANCE WITH SECTION 307.2 FOR PROTRUDING OBJECTS
 INTO THE CIRCULATION PATH.
  
 2) FAILED. PROVIDE A SLAB REPAIR DETAIL- SECTION
 107.2.1 WPB.
  
 3) PASSED. SHEET A1.1: LABEL THE TOILET ROOMS 131 AND
 132 AS EITHER NEW OR EXISTING- SECTION 107.2.1 WPB.
  
 4) FAILED. PROVIDE A PLUMBING SUB-PERMIT APPLICATION-
 SECTION 105.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-10-23 Cont ID  
Sent By ccole Date 2020-10-23 Time 17:33 Rev Time 0.00
Received By ccole Date 2020-10-23 Time 17:08 Sent To  
Notes
2020-10-23 17:33:391ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20091250
 10/23/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REFER TO SECTION 107.3.5.1.1 AMENDMENTS TO THE
 FBC-17 AND PROVIDE PLUMBING PLANS INCLUDING:
  
 A) SCOPE OF WORK OUTLINE.
  
 B) SANITARY AND WATER RISER DRAWINGS FOR INSTALLATION
 OF THE NEW DRINKING FOUNTAINS.
  
 C) PLUMBING FIXTURE CALCULATIONS- TABLE 403.3 FBC P.
 INDICATE THE REQUIRED AND PROVIDED NUMBER OF FIXTURES
 PER THE TABLE.
  
 D) REFER TO SECTIONS 306, 307, AND 602 FBC ACC AND
 PROVIDE DRINKING FOUNTAIN INSTALLATION DETAILS AND
 ELEVATION VIEWS SHOWING KNEE AND TOE CLEARANCES, SPOUT
 HEIGHTS, AND SPOUT LOCATIONS. INDICATE HOW THE
 FOUNTAINS WILL BE IN COMPLIANCE WITH SECTION 307.2-
 PROTRUDING OBJECTS INTO THE CIRCULATION PATH.
  
 2) PROVIDE A SLAB REPAIR DETAIL- SECTION 107.2.1 WPB.
  
 3) SHEET A1.1: LABEL THE TOILET ROOMS 131 AND 132 AS
 EITHER NEW OR EXISTING- SECTION 107.2.1 WPB.
  
 4) PROVIDE A PLUMBING SUB-PERMIT APPLICATION- SECTION
 105.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status P Date 2021-01-19 Cont ID  
Sent By medwards Date 2021-01-19 Time 06:54 Rev Time 0.00
Received By pvalenti Date 2021-01-19 Time 06:54 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status F Date 2021-01-09 Cont ID  
Sent By pvalenti Date 2021-01-09 Time 11:06 Rev Time 0.00
Received By pvalenti Date 2021-01-09 Time 09:26 Sent To  
Notes
2021-01-09 11:11:50PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 SIGNATURE REVIEW DENIED:
  
 THE FOLLOWING SHEETS NEED TO BE SIGNED & SEALED BY
 DESIGN PROFESSIONAL: A-2.1, A-4.1, A-4.2, CS-1.1, LP-1,
 LS-1.1 & N1.1.
  
 FS 471/FS 481 DOCUMENTS PREPARED BY AN
 ENGINEER/ARCHITECT AND SUBMITTED FOR PUBLIC RECORD ARE
 TO BE SIGNED, SEALED & DATED ORIGINALS. A SCAN OF A
 SIGNED/SEALED PLAN IS NOT CONSIDERED AN ORIGINAL.
 UPLOAD TO PROJECT DOX DIGITALLY SIGNED (THIRD PARTY
 VERIFIED) PLANS OR YOU CAN MAIL SIGNED/SEALED PAPER
 ORIGINALS TO:
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER II
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 FEEL FREE TO CONTACT ME AT 561 805 6673.
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2020-12-16 Cont ID  
Sent By medwards Date 2020-12-16 Time 17:32 Rev Time 0.00
Received By medwards Date 2020-12-16 Time 17:31 Sent To  
Notes
2020-12-16 17:33:42DESIGNER OF DRAWINGS MUST DIGITALLY SIGN AND SEAL EACH
 SHEET.
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2020-11-25 Cont ID  
Sent By medwards Date 2020-11-25 Time 10:56 Rev Time 0.00
Received By medwards Date 2020-11-25 Time 10:55 Sent To  
Notes
2020-11-25 10:56:253RD REQUEST:
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-11-16 Cont ID  
Sent By medwards Date 2020-11-16 Time 09:41 Rev Time 0.00
Received By medwards Date 2020-11-16 Time 09:41 Sent To  
Notes
2020-11-16 09:42:362ND REQUEST:
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-10-16 Cont ID  
Sent By medwards Date 2020-10-16 Time 14:50 Rev Time 0.00
Received By medwards Date 2020-10-16 Time 14:50 Sent To  
Notes
2020-10-16 14:51:04PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  