| 2020-10-08 10:48:57 | 2ND REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20091183 |
| | 10/8/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | THE COMMENTS LISTED BELOW FROM THE 1ST REVIEW STILL |
| | HAVE NOT BEEN ADDRESSED. NOTES IN CAP LETTERS HAVE BEEN |
| | ADDED TO EACH COMMENT- PLEASE COMPLY. |
| | |
| | 1) PROVIDE PLUMBING PLANS AND SPECIFICATIONS. PLEASE |
| | INCLUDE A SANITARY AND WATER RISER, AND PLUMBING |
| | FIXTURE AND DEVICE SCHEDULE. SHOW THE POINTS OF |
| | CONNECTIONS TO THE EXISTING WATER DISTRIBUTION AND |
| | SANITARY DRAINAGE SYSTEMS- SECTION 107.3.5.1.3 WPB |
| | AMENDMENTS. THIS IS A SEPARATE PERMIT AND NOT A |
| | REVISION TO THE PREVIOUSLY ISSUED PLANS UNDER PERMITS |
| | 16090622 & 19061299. COMPLETE PLUMBING PLANS AND |
| | SPECIFICATIONS ARE REQUIRED INCLUDING THE REQUESTED |
| | RISER DRAWINGS; FIXTURE CALCULATIONS; FIXTURE, |
| | EQUIPMENT, AND DEVICE SCHEDULES; PIPING AND INSULATION |
| | SPECIFCATIONS ETC. THE RECORDED PLANS ON FILE FOR |
| | PERMIT- 16090622 SHOWS ONLY SANITARY DRAINAGE CLEANOUT |
| | STUB-UPS, AND A WATER SUPPLY SHUT OFF VALVE AT EACH |
| | RESTROOM LOCATION. RECORDED PLANS FOR PERMIT 19061299 |
| | DO NOT SHOW ANY PLUMBING WORK IN THE C BUILDING. |
| | PLEASE NOTE THE PLUMBING PLANS FOR PERMIT 16090622 SHOW |
| | PLUMBING STUBS FOR THE RESTROOMS IN STUDIO'S C6 AND C9 |
| | WHICH APPEAR TO HAVE BEEN ELIMINATED, AND A NEW |
| | ACCESSIBLE COUNTER AND SINK TO BE INSTALLED. PLEASE |
| | PROVIDE ARCHITECTUAL DETAILS FOR INSTALLATION OF THE |
| | COUNTER AND SINK TO MEET COMPLIANCE WITH SECTIONS |
| | 606.2, 305, 306, 308, & 309 FBC ACC. PLEASE PROVIDE |
| | RISER DRAWINGS AND ADD THE SINK TO THE FIXTURE |
| | SCHEDULE. |
| | |
| | 2) INDICATE HOW THE REQUIRED TEMPERED WATER WILL BE |
| | PROVIDED TO THE LAVATORIES PER SECTION 416.5 FBC P, AND |
| | SHOW THE SOURCE OF REQUIRED HOT WATER- SECTION 607.1. |
| | PLEASE SEE NOTES ADDED TO COMMENT #1 ABOVE. THE |
| | SELECTED WATER HEATER SHALL BE EQUIPPED WITH AN ASSE |
| | 1070 WATER TEMPERATURE LIMITING DEVICE THAT LIMITS THE |
| | WATER TEMPERATURE TO 110 DEGREES F, OR APPROVED MIXING |
| | VALVES SHALL BE INSTALLED- SECTION 607.1.2 FBC P. |
| | |
| | 3) A2.1: ACCESSIBILITY CORRECTIONS NEEDED PER THE FBC |
| | ACC: |
| | D) KNEE AND TOE CLEARANCES FOR THE LAVATORY NOT SHOWN- |
| | SECTIONS 306 AND 606.2. NOT PROVIDED. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |