Plan Review Details - Permit 20091183
Plan Review Stops For Permit 20091183
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2020-10-09 Cont ID  
Sent By cpuell Date 2020-10-09 Time 10:32 Rev Time 0.00
Received By cpuell Date 2020-10-09 Time 10:32 Sent To  
Notes
***NONE***

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2020-10-06 Cont ID  
Sent By cpuell Date 2020-10-06 Time 14:35 Rev Time 0.00
Received By cpuell Date 2020-10-06 Time 14:33 Sent To  
Notes
2020-10-06 14:35:42PLEASE REACH OUT TO [email protected] TO DISCUSS STUDIO
 ADDRESSES.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2020-10-08 Cont ID  
Sent By rmcphers Date 2020-10-08 Time 07:46 Rev Time 0.00
Received By rmcphers Date 2020-10-08 Time 07:46 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-10-06 Cont ID  
Sent By rmcphers Date 2020-10-06 Time 13:48 Rev Time 0.00
Received By rmcphers Date 2020-10-06 Time 13:48 Sent To  
Notes
2020-10-06 13:49:39PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-10-19 Cont ID  
Sent By rmcphers Date 2020-10-19 Time 14:38 Rev Time 0.00
Received By rmcphers Date 2020-10-19 Time 14:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-10-08 Cont ID  
Sent By rmcphers Date 2020-10-08 Time 07:46 Rev Time 0.00
Received By rmcphers Date 2020-10-08 Time 07:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-10-06 Cont ID  
Sent By rmcphers Date 2020-10-06 Time 13:46 Rev Time 0.00
Received By rmcphers Date 2020-10-06 Time 13:31 Sent To  
Notes
2020-10-06 13:46:03BUSINESS RENOVATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) DRAWING A2.1 MIRROR NOTE SAYS 40" TO THE BOTTOM OF
 THE EDGE (SHOULD SAY BOTTOM EDGE OF THE REFLECTION) FBC
 ACCESSIBILITY 603.3MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
 2) SHOW RESTROOM BASE BOARD (CANNOT BE WOOD) TO COMPLY
 WITH FBC 1210.2.1 FLOORS AND WALL BASES.
 IN OTHER THAN DWELLING UNITS, TOILET, BATHING AND
 SHOWER ROOM FLOOR FINISH MATERIALS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE. THE INTERSECTIONS OF SUCH
 FLOORS WITH WALLS SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT VERTICAL BASE THAT EXTENDS UPWARD ONTO THE
 WALLS NOT LESS THAN 4 INCHES (102 MM).
 3) SHOW THE GRAB BAR HEIGHTS TO COMPLY WITH FBC 609.4
 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE,

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-10-08 Cont ID  
Sent By jleahy Date 2020-10-08 Time 07:35 Rev Time 0.00
Received By jleahy Date 2020-10-08 Time 07:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-09-29 Cont ID  
Sent By jleahy Date 2020-09-29 Time 07:52 Rev Time 0.00
Received By jleahy Date 2020-09-29 Time 07:47 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-10-16 Cont ID  
Sent By pleduc Date 2020-10-16 Time   Rev Time 0.00
Received By pleduc Date 2020-10-16 Time 16:47 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-09-29 Cont ID  
Sent By pleduc Date 2020-09-29 Time   Rev Time 0.00
Received By pleduc Date 2020-09-29 Time 13:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-10-19 Cont ID  
Sent By rmcphers Date 2020-10-19 Time 14:39 Rev Time 0.00
Received By rmcphers Date 2020-10-15 Time 15:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-10-08 Time   Rev Time 0.00
Received By lmarchan Date 2020-10-07 Time 16:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-10-06 Cont ID  
Sent By cpuell Date 2020-10-06 Time 14:35 Rev Time 0.00
Received By cpuell Date 2020-09-28 Time 07:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2020-10-27 Cont ID  
Sent By hmoser Date 2020-10-27 Time 11:40 Rev Time 0.00
Received By hmoser Date 2020-10-27 Time 11:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2020-10-16 Cont ID  
Sent By ccole Date 2020-10-16 Time 10:09 Rev Time 0.00
Received By ccole Date 2020-10-16 Time 09:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-10-08 Cont ID  
Sent By ccole Date 2020-10-08 Time 10:48 Rev Time 0.00
Received By ccole Date 2020-10-08 Time 09:08 Sent To  
Notes
2020-10-08 10:48:572ND REVIEW FBC-2017 PLUMBING
 PERMIT- 20091183
 10/8/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 THE COMMENTS LISTED BELOW FROM THE 1ST REVIEW STILL
 HAVE NOT BEEN ADDRESSED. NOTES IN CAP LETTERS HAVE BEEN
 ADDED TO EACH COMMENT- PLEASE COMPLY.
  
 1) PROVIDE PLUMBING PLANS AND SPECIFICATIONS. PLEASE
 INCLUDE A SANITARY AND WATER RISER, AND PLUMBING
 FIXTURE AND DEVICE SCHEDULE. SHOW THE POINTS OF
 CONNECTIONS TO THE EXISTING WATER DISTRIBUTION AND
 SANITARY DRAINAGE SYSTEMS- SECTION 107.3.5.1.3 WPB
 AMENDMENTS. THIS IS A SEPARATE PERMIT AND NOT A
 REVISION TO THE PREVIOUSLY ISSUED PLANS UNDER PERMITS
 16090622 & 19061299. COMPLETE PLUMBING PLANS AND
 SPECIFICATIONS ARE REQUIRED INCLUDING THE REQUESTED
 RISER DRAWINGS; FIXTURE CALCULATIONS; FIXTURE,
 EQUIPMENT, AND DEVICE SCHEDULES; PIPING AND INSULATION
 SPECIFCATIONS ETC. THE RECORDED PLANS ON FILE FOR
 PERMIT- 16090622 SHOWS ONLY SANITARY DRAINAGE CLEANOUT
 STUB-UPS, AND A WATER SUPPLY SHUT OFF VALVE AT EACH
 RESTROOM LOCATION. RECORDED PLANS FOR PERMIT 19061299
 DO NOT SHOW ANY PLUMBING WORK IN THE C BUILDING.
 PLEASE NOTE THE PLUMBING PLANS FOR PERMIT 16090622 SHOW
 PLUMBING STUBS FOR THE RESTROOMS IN STUDIO'S C6 AND C9
 WHICH APPEAR TO HAVE BEEN ELIMINATED, AND A NEW
 ACCESSIBLE COUNTER AND SINK TO BE INSTALLED. PLEASE
 PROVIDE ARCHITECTUAL DETAILS FOR INSTALLATION OF THE
 COUNTER AND SINK TO MEET COMPLIANCE WITH SECTIONS
 606.2, 305, 306, 308, & 309 FBC ACC. PLEASE PROVIDE
 RISER DRAWINGS AND ADD THE SINK TO THE FIXTURE
 SCHEDULE.
  
 2) INDICATE HOW THE REQUIRED TEMPERED WATER WILL BE
 PROVIDED TO THE LAVATORIES PER SECTION 416.5 FBC P, AND
 SHOW THE SOURCE OF REQUIRED HOT WATER- SECTION 607.1.
 PLEASE SEE NOTES ADDED TO COMMENT #1 ABOVE. THE
 SELECTED WATER HEATER SHALL BE EQUIPPED WITH AN ASSE
 1070 WATER TEMPERATURE LIMITING DEVICE THAT LIMITS THE
 WATER TEMPERATURE TO 110 DEGREES F, OR APPROVED MIXING
 VALVES SHALL BE INSTALLED- SECTION 607.1.2 FBC P.
  
 3) A2.1: ACCESSIBILITY CORRECTIONS NEEDED PER THE FBC
 ACC:
 D) KNEE AND TOE CLEARANCES FOR THE LAVATORY NOT SHOWN-
 SECTIONS 306 AND 606.2. NOT PROVIDED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB.
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-09-30 Cont ID  
Sent By ccole Date 2020-09-30 Time 10:03 Rev Time 0.00
Received By ccole Date 2020-09-30 Time 07:29 Sent To  
Notes
2020-09-30 10:09:561ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20091183
 9/30/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE PLUMBING PLANS AND SPECIFICATIONS. PLEASE
 INCLUDE A SANITARY AND WATER RISER, AND PLUMBING
 FIXTURE AND DEVICE SCHEDULE. SHOW THE POINTS OF
 CONNECTIONS TO THE EXISTING WATER DISTRIBUTION AND
 SANITARY DRAINAGE SYSTEMS- SECTION 107.3.5.1.3 WPB
 AMENDMENTS.
  
 2) INDICATE HOW THE REQUIRED TEMPERED WATER WILL BE
 PROVIDED TO THE LAVATORIES PER SECTION 416.5 FBC P, AND
 SHOW THE SOURCE OF REQUIRED HOT WATER- SECTION 607.1.
  
 3) A2.1: ACCESSIBILITY CORRECTIONS NEEDED PER THE FBC
 ACC:
  
 A) THE MOUNTING HEIGHTS OF THE GRAB BARS IS NOT SHOWN.
 THE HEIGHTS SHALL BE IN COMPLIANCE WITH- SECTION 609.4.
 PLEASE SEE FIGURE 604.5.2 FOR LOCATION OF REAR GRAB BAR
 BEHIND THE WATER CLOSET.
  
 B) LOCATION OF THE WATER CLOSET FLUSH CONTROL NOT
 SHOWN- SECTION 604.6.
  
 C) THE 40" HEIGHT OF THE MIRROR SHALL BE MEASURED FROM
 THE FINISHED FLOOR TO THE REFLECTIVE SURFACE- SECTION
 603.3.
  
 D) KNEE AND TOE CLEARANCES FOR THE LAVATORY NOT SHOWN-
 SECTIONS 306 AND 606.2.
  
 4) A2.1: PLEASE REFER TO SECTION 310.3 FBC P: THE
 INTERIOR WALL FINISH IN THE RESTROOM SHALL BE IN
 ACCORDANCE WITH SECTION 1210.2.2 WALLS AND PARTITIONS.
 WALLS AND PARTITIONS WITHIN 2 FEET OF SERVICE SINKS,
 URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS THAN 4
 FEET ABOVE THE FLOOR, AND EXCEPT FOR STRUCTURAL
 ELEMENTS, THE MATERIALS USED IN SUCH WALLS SHALL BE OF
 A TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE.
 EXCEPTION: THIS SECTION DOES NOT APPLY TO THE FOLLOWING
 BUILDINGS AND SPACES:
 1. DWELLING UNITS AND SLEEPING UNITS.
 2. TOILET ROOMS THAT ARE NOT ACCESSIBLE TO THE PUBLIC
 AND THAT HAVE NOT MORE THAN ONE WATER CLOSET.
  
 THE PLAN IS INDICATING EPOXY- PAINTED DRYWALL, HOWEVER
 IF THE RESTROOM IS OPEN TO THE PUBLIC THEN
 EPOXY-PAINTED DRYWALL DOES NOT MEET COMPLIANCE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-10-19 Cont ID  
Sent By rmcphers Date 2020-10-19 Time 14:39 Rev Time 0.00
Received By rmcphers Date 2020-10-19 Time 14:39 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-10-08 Cont ID  
Sent By shill Date 2020-10-08 Time 06:37 Rev Time 0.00
Received By shill Date 2020-10-08 Time 06:37 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-10-06 Cont ID  
Sent By rmcphers Date 2020-10-06 Time 13:48 Rev Time 0.00
Received By rmcphers Date 2020-10-06 Time 13:48 Sent To  
Notes
***NONE***