Plan Review Details - Permit 20091175
Plan Review Stops For Permit 20091175
Review Stop AD ADDRESSING
Rev No 4 Status P Date 2021-02-05 Cont ID  
Sent By cpuell Date 2021-02-05 Time 15:21 Rev Time 0.00
Received By cpuell Date 2021-02-05 Time 15:21 Sent To  
Notes
2021-02-05 15:22:11BOTH BUILDINGS ON PARCEL CHANGES, NEW CONFIGURATION 419
 LYTLE ST (FRONT BLDG) 421 LYTLE ST (REAR BUILDING)

Review Stop AD ADDRESSING
Rev No 3 Status F Date 2021-02-05 Cont ID  
Sent By cpuell Date 2021-02-05 Time 09:49 Rev Time 0.00
Received By cpuell Date 2021-02-05 Time 09:49 Sent To  
Notes
2021-02-05 09:50:00ADDRESSING OPTIONS GIVEN, WAITING ON REPRESENTATIVES TO
 CONFIRM NEW ADDRESSES.

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2021-02-03 Cont ID  
Sent By cpuell Date 2021-02-03 Time 12:32 Rev Time 0.00
Received By cpuell Date 2021-02-03 Time 12:32 Sent To  
Notes
2021-02-03 12:33:14WAITING ON ZONING TO APPROVE THE PROJECT BEFORE ISSUING
 A NEW ADDRESS, PLEASE EMAIL [email protected] WHEN IT IS
 APPROVED BY ZONING.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2020-12-28 Cont ID  
Sent By cpuell Date 2020-12-28 Time 12:04 Rev Time 0.00
Received By cpuell Date 2020-12-28 Time 12:04 Sent To  
Notes
2020-12-28 12:05:282ND UNIT NOT ALLOWED PER ZONING, IF THAT CHANGES PLEASE
 REACH OUT TO [email protected] TO ESTABLISH AN ADDRESS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2021-02-05 Cont ID  
Sent By pvalenti Date 2021-02-05 Time 08:50 Rev Time 0.00
Received By pvalenti Date 2021-02-05 Time 08:40 Sent To  
Notes
2021-02-05 08:54:29PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW:
  
 APPROVED

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2020-12-23 Cont ID  
Sent By pvalenti Date 2020-12-23 Time 11:20 Rev Time 0.00
Received By pvalenti Date 2020-12-23 Time 10:47 Sent To  
Notes
2020-12-23 11:27:09PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 1.) FBC B 107.2.5, PLEASE PROVIDE A SITE-PLAN
 (INCLUDING THE PROPOSED PARKING AREA IF APPLICABLE)
 COMPLETE WITH SET-BACK & DISTANCE MEASUREMENTS.
  
  
 NOTE: PERMIT CAN NOT BE APPROVED WITHOUT PASSING THE
 ZONING & ADDRESSING ALL PLAN REVIEWS. INCLUDING
 COMMENTS FROM ZONING & COMMENTS FROM ADDRESSING.
  
 ALL REQUIRED SUB-PERMITS ( MECHANICAL, ELECTRIC &
 PLUMBING) WILL HAVE TO BE SUBMITTED PRIOR TO APPROVAL
 OF MASTER PERMIT OR ADDITIONAL FEES FOR SUB-PERMITS
 WILL BE REQUIRED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL COMMENTS WILL
 RESULT IN NEW PLAN REVIEW COMMENTS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-11-23 Cont ID  
Sent By pvalenti Date 2020-11-23 Time 09:30 Rev Time 0.00
Received By pvalenti Date 2020-11-23 Time 09:30 Sent To  
Notes
2020-11-23 09:34:19PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW FAILED:
  
 FBC B 107.2.1, PLEASE PROVIDE A RESPONSE LETTER WITH
 THE CHANGES MADE FOR THE INSULATION TO BE USED AS THIS
 IS STILL NOT CLEAR AS TO WHAT IS INTENDED FOR USE. SEE
 THE NOTES BELOW:
  
 1) ON PLAN SHEET A.2 (SHOWS R?19 WITH 1" SPACE FOR
 CROSS VENTILLATION).
 2) FBC ENERGY CONSERVATION PAGE R?56 PRESCRIPTIVE
 REQUIREMENTS (SHOWS CLIMATE ZONE 1, R?30).
 3) FBC ENERGY CONSERVATION PAGE R?56 INSTALLED VALUES
 (SHOWS R?20 SPRAY FOAM).
 4) FBC ENERGY EFFICIENCY RESIDENTIAL PERFORMANCE
 METHOD, PAGE 3, CEILING INSULATION TYPE (SHOWS BLOWN).

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-09-30 Cont ID  
Sent By pvalenti Date 2020-09-30 Time 10:41 Rev Time 0.00
Received By pvalenti Date 2020-09-30 Time 08:50 Sent To  
Notes
2020-09-30 11:12:09PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 FBC B 107.2.1, THE ROOF INSULATION REQUIREMENTS ARE NOT
 CLEAR. PLEASE PROVIDE CLARIFICATION:
  
 1) ON PLAN SHEET A.2 (SHOWS R-19 WITH 1" SPACE FOR
 CROSS VENTILLATION).
 2) FBC ENERGY CONSERVATION PAGE R-56 PRESCRIPTIVE
 REQUIREMENTS (SHOWS CLIMATE ZONE 1, R-30).
 3) FBC ENERGY CONSERVATION PAGE R-56 INSTALLED VALUES
 (SHOWS R-20 SPRAY FOAM).
 4) FBC ENERGY EFFICIENCY RESIDENTIAL PERFORMANCE
 METHOD, PAGE 3, CEILING INSULATION TYPE (SHOWS BLOWN).

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2021-02-24 Cont ID  
Sent By equinone Date 2021-02-24 Time 13:51 Rev Time 0.00
Received By equinone Date 2021-02-24 Time 13:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2021-02-05 Cont ID  
Sent By equinone Date 2021-02-05 Time 14:28 Rev Time 0.00
Received By equinone Date 2021-02-05 Time 09:46 Sent To  
Notes
2021-02-05 14:46:30CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED.
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1) SHEET A.1 (PROPOSED PLAN VIEW) AND E.1 -- A.1 SHOWS
 THREE METERS WHILE RISER DIAGRAM AND POWER LAYOUT ON
 E.1 SHOWS ONLY TWO. PLEASE EXPLAIN AND CORRECT
 DISCREPANCIES. FBC 107
 2) ELECTRICAL DRAWINGS FOR OTHER UNIT (PERMIT 20121069)
 SHOWS THREE PANELS ON RISER DIAGRAM WHILE THIS PERMIT
 ONLY SHOWS TWO PANELS. PLEASE EXPLAIN AND CORRECT
 DISCREPANCIES.IF ONLY TWO PANELS AND TWO METERS, PERMIT
 20121069 WILL NEED TO BE REVISED AS WELL.
 3) SHEET E.1: LOAD CALCULATIONS ARE FOR THREE PANELS
 (A, B, AND C) WHILE RISER DIAGRAM ONLY SHOWS TWO
 PANELS. PLEASE UPDATE LOAD CALCULATIONS FOR ENTIRE
 SERVICE AS WELL AS SEPARATE PANELS (A AND B IF ONLY TWO
 PANELS WILL BE USED). FBC 107
 4) PLEASE SPECIFY AIC RATINGS FOR SERVICE DISCONNECTS
 AND PANELS A AND B
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-11-30 Cont ID  
Sent By equinone Date 2020-11-30 Time 11:36 Rev Time 0.00
Received By equinone Date 2020-11-30 Time 11:36 Sent To  
Notes
2020-11-30 11:52:37PLEASE SEE SIGNATURE COMMENTS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-10-07 Cont ID  
Sent By jleahy Date 2020-10-07 Time 14:12 Rev Time 0.00
Received By jleahy Date 2020-10-07 Time 14:07 Sent To  
Notes
2020-10-07 16:01:57ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 RISER SHOWS 2/0S IN MAST PLEASE SUBMIT A LOAD
 CALCULATION FOR THESE 2/0S.
  
 PLAN SHOWS PANEL IN THIS BUILDING, IS IT REMOTE FROM
 SERVICE IF SO PLEASE ESTABLISH GROUNDING ELECTRODE
 SYSTEM AT THIS BUILDING 250.32(A)

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2021-02-24 Cont ID  
Sent By equinone Date 2021-02-24 Time 14:19 Rev Time 0.00
Received By pvalenti Date 2021-01-25 Time 10:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-01-08 Cont ID  
Sent By lcrespo Date 2021-01-08 Time 10:16 Rev Time 0.00
Received By lcrespo Date 2021-01-07 Time 10:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-12-23 Cont ID  
Sent By jleahy Date 2020-12-23 Time 11:34 Rev Time 0.00
Received By jleahy Date 2020-12-23 Time 10:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-12-28 Cont ID  
Sent By pvalenti Date 2020-12-28 Time 12:04 Rev Time  
Received By cpuell Date 2020-11-18 Time 16:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-10-31 Cont ID  
Sent By cpuell Date 2020-10-31 Time 18:46 Rev Time 0.00
Received By cpuell Date 2020-09-30 Time 07:09 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2021-03-08 Cont ID  
Sent By lmarchan Date 2021-03-08 Time 09:21 Rev Time 0.00
Received By lmarchan Date 2021-03-02 Time 11:13 Sent To  
Notes
2021-03-08 09:21:47RECEIPT MU-2021-10064 - $0.00
2021-03-02 11:13:133/2/21 EMAILED IMPACT OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-09-30 Cont ID  
Sent By pvalenti Date 2020-09-30 Time 07:05 Rev Time 0.00
Received By pvalenti Date 2020-09-30 Time 07:05 Sent To  
Notes
2020-09-30 07:07:04PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 IMPACT FEES - DIGITAL SUBMITTALS
  
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-11-19 Cont ID  
Sent By medwards Date 2020-11-19 Time 08:10 Rev Time 0.00
Received By medwards Date 2020-11-19 Time 08:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-09-30 Cont ID  
Sent By pvalenti Date 2020-09-30 Time 11:33 Rev Time 0.00
Received By pvalenti Date 2020-09-30 Time 09:06 Sent To  
Notes
2020-09-30 10:16:18PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 MECHANICAL REVIEW DENIED:
  
 FBC RM TABLE M1506.2, THE BATHROOM EXHAUST DUCT NEEDS
 TO BE CHANGED FROM 3" TO 4" DIAMETER AND THE BATHROOM
 EXHAUST FANS NEED TO MOVE A HIGHER CFM THAN 50 CFM. 70
 CFM FANS WITH 4" DUCTS SHOULD MEET THE REQUIREMENTS FOR
 A 50 CFM SYSTEM PER FBC RM TABLE M1506.2.

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-01-08 Cont ID  
Sent By lcrespo Date 2021-01-08 Time 10:16 Rev Time 0.00
Received By lcrespo Date 2021-01-08 Time 10:11 Sent To  
Notes
2021-01-08 10:17:2701/08/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-11-19 Cont ID  
Sent By ccole Date 2020-11-19 Time 15:57 Rev Time 0.00
Received By ccole Date 2020-11-19 Time 15:30 Sent To  
Notes
2020-11-19 16:10:281ST REVIEW FBC-2017 RES.
 PERMIT- 20091175
 11/19/20
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P1/M1: THE RISER DRAWING AND THE PLUMBING PLAN
 DO NOT MATCH. THE RISER SHOWS A DOUBLE LAV SINK, THE
 PLAN SHOWS A SINGLE. THE RISER SHOWS A WASHING MACHINE,
 THE PLAN DOES NOT SHOW A WASHING MACHINE.
  
 2) P1/M1: PROVIDE THE EFFICIENCY RATINGS OF THE NEW
 TANKLESS WATER HEATERS, AND ENTER THE DATA IN THE
 ENERGY COMPLIANCE FORM R405-2017.
  
 3) PROVIDE A PLUMBING SUB-PERMIT APPLICATION- SECTION
 105.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2020-10-02 Cont ID  
Sent By ccole Date 2020-10-02 Time 15:08 Rev Time 0.00
Received By ccole Date 2020-10-02 Time 13:52 Sent To  
Notes
2020-10-02 15:09:53A PLUMBING SUB-PERMIT IS REQUIRED AND SHALL BE ONSITE
 PRIOR TO COMMENCEMENT OF PLUMBING WORK.

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status N Date 2020-12-23 Cont ID  
Sent By pvalenti Date 2020-12-23 Time 10:51 Rev Time 0.00
Received By pvalenti Date 2020-12-23 Time 10:46 Sent To  
Notes
2020-12-23 10:55:10PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 ROOFING REVIEW NOT REQUIRED AS THIS STRUCTURE IS HAVING
 NO NEW ROOFING WORK.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2020-11-23 Cont ID  
Sent By pvalenti Date 2020-11-23 Time 09:39 Rev Time 0.00
Received By pvalenti Date 2020-11-23 Time 09:39 Sent To  
Notes
2020-11-23 09:44:00PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561?805?6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 2ND ROOFING REVIEW DENIED:
  
 FBC B 107, PLEASE PROVEDE THE PRODUCT APPROVAL FOR THE
 ROOFING MATERIALS TO BE USED. AS PER PLAN SHEET S.2, IT
 APPEARS THAT THE INTENDED PRODUCT APPROVAL IS NOA #
 16?0413.06. THIS NOA NEEDS TO BE SUBMITTED WITH THE
 SELECTED OPTION IDENTIFIED
 (MARKED/CIRCLED/HIGHLIGHTED). THE OPTION SELECTED MUST
 MEET THE WINDLOAD PRESSURES REQUIRED.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2020-09-30 Cont ID  
Sent By pvalenti Date 2020-09-30 Time 13:08 Rev Time 0.00
Received By pvalenti Date 2020-09-30 Time 09:50 Sent To  
Notes
2020-09-30 13:13:49PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 ROOFING REVIEW DENIED:
  
 FBC B 107, PLEASE PROVEDE THE PRODUCT APPROVAL FOR THE
 ROOFING MATERIALS TO BE USED. AS PER PLAN SHEET S.2, IT
 APPEARS THAT THE INTENDED PRODUCT APPROVAL IS NOA #
 16-0413.06. THIS NOA NEEDS TO BE SUBMITTED WITH THE
 SELECTED OPTION IDENTIFIED
 (MARKED/CIRCLED/HIGHLIGHTED). THE OPTION SELECTED MUST
 MEET THE WINDLOAD PRESSURES REQUIRED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2021-02-24 Cont ID  
Sent By equinone Date 2021-02-24 Time 13:54 Rev Time 0.00
Received By equinone Date 2021-02-24 Time 13:54 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-02-05 Cont ID  
Sent By pvalenti Date 2021-02-05 Time 09:33 Rev Time 0.00
Received By pvalenti Date 2021-02-05 Time 09:29 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-12-23 Cont ID  
Sent By pvalenti Date 2020-12-23 Time 11:16 Rev Time 0.00
Received By pvalenti Date 2020-12-23 Time 10:48 Sent To  
Notes
2020-12-23 11:34:38PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 SIGNATURE REVIEW APPROVED BY ORIGINAL PAPER
 SIGNED/SEALED PLANS.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-11-18 Cont ID  
Sent By medwards Date 2020-11-18 Time 17:22 Rev Time 0.00
Received By medwards Date 2020-11-18 Time 17:22 Sent To  
Notes
2020-11-18 17:23:32DRAWINGS WERE NOT SIGNED OR SEALED, ROUTED TO THE
 LIBRARY. ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-09-30 Cont ID  
Sent By pvalenti Date 2020-09-30 Time 07:07 Rev Time 0.00
Received By pvalenti Date 2020-09-30 Time 07:07 Sent To  
Notes
2020-09-30 07:09:19PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 SIGNATURE REVIEW APPROVED BY THE ORIGINAL SIGNED/SEALED
 PAPER PLANS.

Review Stop Z ZONING
Rev No 5 Status P Date 2021-02-04 Cont ID  
Sent By ajones Date 2021-02-04 Time 15:26 Rev Time 0.00
Received By ajones Date 2021-02-04 Time 15:26 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status F Date 2021-02-03 Cont ID  
Sent By kalexand Date 2021-02-03 Time 10:26 Rev Time 0.00
Received By kalexand Date 2021-02-03 Time 10:26 Sent To I
Notes
2021-02-03 10:34:44ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW:
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. A LEVEL 1 SITE PLAN APPROVAL IS REQUIRED PRIOR TO
 ISSUANCE OF BUILDING PERMITS. PURSUANT TO ZLDR SEC.
 94-514(1): EXPANSION OR EXTENSION. THE AREA OCCUPIED BY
 A NONCONFORMING USE SHALL NOT BE ENLARGED OR EXPANDED
 BEYOND THE AREA THAT WAS LAWFUL AT THE TIME THE USE
 BECAME NONCONFORMING. HOWEVER, ANY LEGAL NONCONFORMING
 USE MAY BE EXTENDED WITHIN THE BUILDING IN WHICH IT IS
 LOCATED WITH THE APPROVAL OF A LEVEL I SITE PLAN, BUT
 THE BUILDING SHALL NOT BE EXPANDED TO ALLOW AN
 EXPANSION OF THE USE. NO ADDITIONAL SITE FEATURES SHALL
 BE ALLOWED UNLESS SUCH FEATURES REDUCE THE
 NON-CONFORMITY.
  
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD
 LIKE TO RESUBMIT ELECTRONICALLY, EMAIL
 [email protected] AND REQUEST TO HAVE YOUR
 PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOG
 IN INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL.
 PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU
 ARE FINISHED UPLOADING.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 KIZZI ALEXANDRE, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1442
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 3 Status F Date 2021-01-06 Cont ID  
Sent By kalexand Date 2021-01-06 Time 08:27 Rev Time 0.00
Received By kalexand Date 2021-01-06 Time 08:27 Sent To I
Notes
2021-01-06 08:32:36ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW:
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. ACCESSORY DWELLING UNIT NOT PERMITTED IN
 SINGLE-FAMILY LOW DENSITY (SF7) ZONING DISTRICTS.
 PURSUANT TO ZLDR SEC. 94-303 ACCESSORY APARTMENTS ARE
 ONLY PERMITTED IN SINGLE-FAMILY HIGH-DENSITY (SF14)
 RESIDENTIAL ZONING DISTRICTS.
 THE FIRST ACCESSORY UNIT (LISTED ON THE PLANS AS
 ?EXIST. UNIT #2?) IS PERMITTED AS IT IS A LEGAL
 NONCONFORMING USE IN THE SINGLE-FAMILY LOW-DENSITY
 (SF7) ZONING DISTRICT. CONVERTING THE GARAGE PORTION OF
 THE STRUCTURE INTO A THIRD UNIT IS NOT PERMITTED.
  
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD
 LIKE TO RESUBMIT ELECTRONICALLY, EMAIL
 [email protected] AND REQUEST TO HAVE YOUR
 PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOG
 IN INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL.
 PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU
 ARE FINISHED UPLOADING.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 KIZZI ALEXANDRE, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1442
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 2 Status F Date 2020-12-22 Cont ID  
Sent By kalexand Date 2020-12-22 Time 13:47 Rev Time 0.00
Received By kalexand Date 2020-12-22 Time 13:47 Sent To I
Notes
2020-12-22 15:00:19ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW:
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. ACCESSORY DWELLING UNIT NOT PERMITTED IN
 SINGLE-FAMILY LOW DENSITY (SF7) ZONING DISTRICTS.
 PURSUANT TO ZLDR SEC. 94-303 ACCESSORY APARTMENTS ARE
 ONLY PERMITTED IN SINGLE-FAMILY HIGH-DENSITY (SF14)
 RESIDENTIAL ZONING DISTRICTS.
 THE FIRST ACCESSORY UNIT IS CONSIDERED A LEGAL
 NONCONFORMING USE WITHIN THIS DISTRICT; YOU MAY NOT
 INCREASE THE NONCONFORMITY OF ANY STRUCTURE. PURSUANT
 TP ZLDR SEC. 94-515 ANY NONCONFORMING STRUCTURE MAY BE
 ALTERED TO DECREASE ITS NONCONFORMITY, OR INCREASE ITS
 COMPLIANCE, WITH THE CURRENT REGULATIONS.
  
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD
 LIKE TO RESUBMIT ELECTRONICALLY, EMAIL
 [email protected] AND REQUEST TO HAVE YOUR
 PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOG
 IN INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL.
 PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU
 ARE FINISHED UPLOADING.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 KIZZI ALEXANDRE, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1442
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  
  
  
  
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2020-10-30 Cont ID  
Sent By kalexand Date 2020-10-30 Time 11:35 Rev Time 0.00
Received By kalexand Date 2020-10-30 Time 11:35 Sent To I
Notes
2020-10-30 11:46:38ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW:
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PROVIDE SURVEY INDICATING SETBACKS FROM PROPERTY
 LINES.
  
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD
 LIKE TO RESUBMIT ELECTRONICALLY, EMAIL
 [email protected] AND REQUEST TO HAVE YOUR
 PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOG
 IN INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL.
 PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU
 ARE FINISHED UPLOADING.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 KIZZI ALEXANDRE, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION