Plan Review Details - Permit 20091056
Plan Review Stops For Permit 20091056
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-10-01 Time   Rev Time 0.00
Received By lmarchan Date 2020-09-30 Time 14:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-09-29 Time   Rev Time 0.00
Received By lmarchan Date 2020-09-28 Time 11:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-10-01 Cont ID  
Sent By ccole Date 2020-10-01 Time 15:44 Rev Time 0.00
Received By ccole Date 2020-10-01 Time 15:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-09-29 Cont ID  
Sent By ccole Date 2020-09-29 Time 14:47 Rev Time 0.00
Received By ccole Date 2020-09-29 Time 14:47 Sent To  
Notes
2020-09-29 14:48:011ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20091056
 9/29/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P101: REMOVE OR CORRECT THE ELECTRIC WATER
 HEATER LABELS ON THE PLAN UNDER THE PHOTO AND DETAIL.
 THE WH IS A GAS-FIRED TANKLESS WATER HEATER THAT WAS
 INSTALLED UNDER PERMIT- 20080653.
  
 2) P101: PROVIDE AN EQUIPMENT SCHEDULE FOR THE WATER
 HEATER INDICATING MAKE, MODEL NUMBER, AND EFFICIENCY
 RATING- SECTION 107.2.1 WPB & TABLE C404.2 FBC EC.
 PLEASE NOTE THE RHEEM MODEL SHOWN IN THE PHOTO DOES NOT
 MATCH THE NAVIEN MODEL NUMBER SHOWN ON THE GAS DRAWINGS
 UNDER PERMIT- 20080653- NAVIEN NPE-240 A. SUBMIT A
 MANUFACTURER?S PRODUCT SPEC SHEET AND INSTALLATION
 GUIDELINES FOR THE WATER HEATER SHOWING RECOMMENDED
 CLEARANCES FOR SERVICE ACCESS AND VENTING- SECTION
 624.1 FBC FG. PLEASE DO NOT SUBMIT THE ENTIRE INSTALL
 MANUAL JUST THE RELEVANT SHEETS. THE ENTIRE MANUAL
 SHALL BE ONSITE FOR INSPECTION.
  
 3) P101: REVISE THE WATER RISER TO MATCH WITH THE WATER
 PLAN- SECTION 107.2.1 WPB.
  
 4) P101: INDICATE HOW CONDENSATE FROM THE WATER HEATER
 WILL DISCHARGE TO AN APPROVED PLACE OF DISPOSAL-
 SECTION 307.2 FBC FG.
  
 5) P101: THE SANITARY RISER SHOWS TWO UNIDENTIFIED
 TRAPPED FIXTURES SHARING A COMMON VENT THAT ARE NOT
 SHOWN ON THE PLANS OR WATER RISER. PLEASE IDENTIFY AND
 SHOW THE LOCATIONS OF THE FIXTURES ON THE FLOOR PLAN OR
 CORRECT THE RISER- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-10-02 Cont ID  
Sent By lmarchan Date 2020-10-02 Time 15:44 Rev Time 0.00
Received By lmarchan Date 2020-10-02 Time 15:44 Sent To  
Notes
2020-10-02 15:44:44OK PER REVIEWER

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-10-01 Cont ID  
Sent By ccole Date 2020-10-01 Time 15:44 Rev Time 0.00
Received By ccole Date 2020-10-01 Time 15:07 Sent To  
Notes
2020-10-01 15:50:05SHEET P101: THE VALIDITY OF THE ELECTRONIC SIGNATURE
 AND SEAL COULD NOT BE VERIFIED USING THE ADOBE READER
 SYSTEM. THE PLAN APPEARS TO BE A PRINTED COPY OF THE
 SIGNED AND SEALED PLAN.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-09-29 Cont ID  
Sent By ccole Date 2020-09-29 Time 14:50 Rev Time 0.00
Received By ccole Date 2020-09-29 Time 07:12 Sent To  
Notes
2020-09-29 14:55:24SHEET P101: I COULD NOT VERIFY THE VALIDITY OF THE
 ARCHITECT'S ELECTRONIC SIGNATURE ON THE PLAN WHICH MAY
 BE EITHER BE A COPIED ELECTRONIC SEAL AND SIGNATURE, OR
 THE APPLICATION IS NOT COMPATIBLE WITH OUR SYSTEM USING
 ADOBE TO VERIFY.
 CCOLE- 9/29/2020