Plan Review Details - Permit 20090889
Plan Review Stops For Permit 20090889
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2021-01-07 Cont ID  
Sent By rmcphers Date 2021-01-07 Time 08:26 Rev Time 0.00
Received By rmcphers Date 2021-01-07 Time 08:26 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-10-26 Cont ID  
Sent By rmcphers Date 2020-10-26 Time 14:31 Rev Time 0.00
Received By rmcphers Date 2020-10-26 Time 14:30 Sent To  
Notes
2020-10-26 14:32:24PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-01-15 Cont ID  
Sent By rmcphers Date 2021-01-15 Time 10:13 Rev Time 0.00
Received By rmcphers Date 2021-01-15 Time 10:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-01-07 Cont ID  
Sent By rmcphers Date 2021-01-07 Time 08:18 Rev Time 0.00
Received By rmcphers Date 2021-01-06 Time 15:49 Sent To  
Notes
2021-01-07 08:11:56PUBLIX REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE COMPLETE COPIES OF THE MIAMI DADE OR
 FLORIDA STATE PRODUCT APPROVALS FOR THE NEW EXTERIOR
 DOORS.
 2) ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED
 APPROVED BY THE DESIGNER OF RECORD.
 3) WINDOW AND DOOR PRODUCT APPROVALS MAY BE DEFERRED
 SUBMITTALS BY LISTING ITEMS TO BE DEFERRED ON THE
 CONSTRUCTION DOCUMENTS - 107.3.4.1 DEFERRED SUBMITTALS.
 FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS
 ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE
 NOT SUBMITTED AT THE TIME OF THE APPLICATION AND THAT
 ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-10-26 Cont ID  
Sent By rmcphers Date 2020-10-26 Time 14:30 Rev Time 0.00
Received By rmcphers Date 2020-10-26 Time 13:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-01-11 Cont ID  
Sent By jleahy Date 2021-01-11 Time 13:53 Rev Time 0.00
Received By jleahy Date 2021-01-11 Time 13:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-10-28 Cont ID  
Sent By jleahy Date 2020-10-28 Time 09:55 Rev Time 0.00
Received By jleahy Date 2020-10-28 Time 09:41 Sent To  
Notes
***NONE***

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2020-10-28 Cont ID  
Sent By jleahy Date 2020-10-28 Time 09:55 Rev Time 0.00
Received By jleahy Date 2020-10-28 Time 09:55 Sent To  
Notes
2020-10-28 09:56:36LOW VOLTAGE DATA/PHONE, ENERGY MANAGEMENT JLEAHY

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-09-25 Cont ID  
Sent By pleduc Date 2020-09-25 Time   Rev Time 0.00
Received By pleduc Date 2020-09-25 Time 13:39 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2021-01-07 Cont ID  
Sent By lcrespo Date 2021-01-07 Time 11:42 Rev Time 0.00
Received By lcrespo Date 2021-01-07 Time 10:58 Sent To  
Notes
2021-01-07 11:42:3801/07/21 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-10-21 Cont ID  
Sent By jesmith Date 2020-10-21 Time 16:52 Rev Time 0.00
Received By jesmith Date 2020-10-21 Time 13:43 Sent To  
Notes
2020-10-21 14:58:08CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION; LEVEL 2
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 NFPA 54 = NATIONAL FUEL GAS CODE
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW
 GAS COMMENTS: DENIED
  
 1. RE: PM07.01, SECTION 2.4.2.1; INDOOR GAS FITTING
 SPECIFICATION IS CALLING FOR FORGED STEEL WELD
 FITTINGS. THIS IS A 3000# SOCKET WELD FITTING
 CONFORMING TO ASTM A-105. SECTION 2.4.1 GENERAL
 SPECIFICATION INDICATES MALLEABLE FITTINGS;
 ADDITIONALLY, FBC FG 403.4.2 REQUIRES STEEL PIPE TO
 CONFORM TO ASTM A53/A53M, A106 (SEAMLESS) OR ASME
 B36.10/10M, NOT A120. PER WPB FBC 107.2.1, CLARIFY.
  
 2.RE: PM07.01, SECTION 2.4.3; SHALL BE USED FOR
 UNDERGROUND ONLY "PLASTIC PIPE SHALL NOT BE USED WITHIN
 OR UNDER ANY BUILDING OR SLAB OR BE OPERATED AT
 PRESSURES GREATER THAN 100 PSIG FOR NATURAL GAS OR 30
 PSIG TO COMPLY WITH FBC FG 404.17.1."
  
 3.RE: PLAN SHEET P01.02. THERE ARE TWO (2) EXISTING GAS
 MAIN BRANCHES SUPPLIED BY WHAT APPEARS TO BE A NATURAL
 GAS METER (CFH BASED ON 0.5 INCH WC SG 0.6). ACCORDING
 TO PREVIOUS RECORD DRAWINGS (MASTER PERMIT #01080053
 LOCATED IN CITY OF WEST PALM BEACH'S FILENET WORKPLACE,
 SEE PLAN SHEETS P-1, P-2 AND P-6, ALL REV 2 DATED
 9/18/01) PLAN P-6/DETAIL 20, THE METER IS 2LB.AND DOES
 NOT SUPPLY THE EMERGENCY GENERATOR; P-6/DETAIL 20
 INDICATES THE IN-LINE REGULATOR SHOWN ON THE BRANCH TO
 THE BAKERY IS AN MP REGULATOR AND REDUCES THE PRESSURE
 AT THAT POINT FROM POUNDS TO INCHES. THE BRANCH TO THE
 EMERGENCY GENERATOR IS IDENTIFIED AS LP GAS AND PER
 (MASTER PERMIT #01080053) PLAN P-6/DETAIL 20, PLAN P-1
 AND PLAN P-2, ALL REV 2 DATED 9/18/01, IS ACTUALLY AN
 LP SYSTEM SUPPLIED BY A 120 GALLON PROPANE TANK. PER
 WPB FBC 107.2.1, NEW DRAWINGS SUBMITTED UNDER THIS
 PERMIT 20090889 SHALL BE CONSISTENT WITH THE OLDER
 RECORD DRAWINGS AS SHOWN ON MASTER PERMIT #01080053
 PLANS. SPECIFY TYPES OF GAS, NATURAL AND LP OF EACH
 SYSTEM, SHOW EXISTING LP TANK, CONFIRM THE DELIVERY
 PRESSURE OF THE SYSTEM(S), SHOW AND IDENTIFY MP
 REGULATORS WITH POUNDS TO INCHES PRESSURE REDUCTION AND
 CONFIRM THE DISTANCE FROM THE REGULATOR(S) TO THE
 FURTHEST CONNECTED APPLIANCE/EQUIPMENT IN THE
 SYSTEM(S). LIST THE BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM(S). REFER TO THE FBC FG
 SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4
 (37). PLEASE NOTE THAT IF MP REGULATORS ARE REQUIRED
 FOR THE APPLIANCES THAT THE DOWNSTREAM SIDE OF THE
 REGULATOR IS A SECOND SYSTEM AND ARE CONSIDERED A
 SEPARATE SYSTEM. PROVIDE THE TABLE FROM FBC FG
 APPLICABLE TO THE SIZING OF EACH SYSTEM. PROVIDE THE
 TOTAL BTUS FOR EACH SYSTEM.
  
 4.PER WPB FBC 107.2.1, PROVIDE NOTE REFERENCING
 SPECIFICATION SHEETS PM06.01 AND PM07.01, SECTION 22 40
 00 PLUMBING FOR ADDITIONAL SPECIFICATIONS
  
 5.PER WPB FBC 107.2.1, PROVIDE MANUFACTURER'S
 SPECIFICATION/INSTALLATION MANUAL FOR NEW LRO 2G5 70
 DOUBLE RACK OVEN TO VERIFY COMPLIANCE WITH STANDARDS
 NFPA 54, NFPA 58, AND FBC FG 402.2, AND 301.3.
  
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE SIGNED AND SEALED OR DIGITALLY SIGNED
 AND SEALED BY THE DESIGNER IN ACCORDANCE WITH FAC AND
 FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20090889 375 S ROSEMARY AVE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-01-14 Cont ID  
Sent By lcrespo Date 2021-01-14 Time 15:16 Rev Time 0.00
Received By lcrespo Date 2020-12-18 Time 16:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-10-28 Cont ID  
Sent By jleahy Date 2020-10-28 Time 11:15 Rev Time 0.00
Received By jleahy Date 2020-09-22 Time 10:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2020-10-15 Cont ID  
Sent By medwards Date 2020-10-15 Time 14:50 Rev Time 0.00
Received By medwards Date 2020-10-14 Time 15:24 Sent To  
Notes
2020-10-15 14:50:42APPROVED WITH PRIVISO
  
 ALL HOODS WILL REQUIRE A SEPERATE PERMIT AND REVIEW.
 ALL REFRIGERATION WILL REQUIRE A SEPERATE PERMIT AND
 REVIEW.

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-01-14 Cont ID  
Sent By lcrespo Date 2021-01-14 Time 15:05 Rev Time 0.00
Received By lcrespo Date 2021-01-07 Time 08:59 Sent To  
Notes
2021-01-14 15:05:4601/14/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  
2021-01-14 10:10:25 
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-10-26 Cont ID  
Sent By jesmith Date 2020-10-21 Time 16:52 Rev Time 0.00
Received By rmcphers Date 2020-10-19 Time 15:19 Sent To  
Notes
2020-10-21 14:48:09CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION; LEVEL 2
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 NFPA 54 = NATIONAL FUEL GAS CODE
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 1.RE: P01.01 NOTE WITH REFERENCE TO P04.01/DETAIL 6.
 A) NOTE CALLS FOR 1-1/4 INCH COPPER DRAINS/VENTS.
 DETAIL CALLS FOR CPVC 1-1/2 INCH DRAINS/VENTS. PER WPB
 FBC 107.2.1, CLARIFY.
 B) NOTE DIRECTS INSTALLER TO CONNECT TO THE NEAREST HUB
 DRAIN. NEITHER EXISTING (DEMO) OR NEW PLAN SHOWS A HUB
 DRAIN IN THE VICINITY OF THE EQUIPMENT. PER WPB FBC
 107.2.1, CLARIFY.
 C) PER WPB FBC 107.2.1, PROVIDE MANUFACTURER'S
 SPECIFICATION/INSTALLATION MANUAL FOR NEW ALTO SHAAM
 CTP720 E AND FOR EXISTING /RELOCATED CTP 10-10 E
 D) PER WPB FBC 107.2.1, PROVIDE MANUFACTURER'S
 SPECIFICATION FOR FLEXIBLE WATER CONNECTORS FOR
 FILTERED AND UNFILTERED WATER.
  
 2. P04.01/DETAIL 3 AND SPECIFICATION PM07.01, SECTION
 3.4.1.1 CONTRADICT EACH OTHER. PER WPB FBC 107.2.1,
 CLARIFY.
  
 3.PER WPB FBC 107.2.1, PROVIDE NOTE UNDER SPECIFICATION
 PM07.01, SECTION 3.5.1 STATING "PER FBC PL 705.6.3,
 SOLDER JOINTS SHALL BE MADE IN ACCORDANCE WITH THE
 METHODS OF ASTM B828. CUT TUBE ENDS SHALL BE REAMED TO
 THE FULL INSIDE DIAMETER OF THE TUBE END. ALL JOINT
 SURFACES SHALL BE CLEANED. A FLUX CONFORMING TO ASTM
 B813 SHALL BE APPLIED. THE JOINT SHALL BE SOLDERED WITH
 A SOLDER CONFORMING TO ASTM B32."
  
 4.PER WPB FBC 107.2.1, PROVIDE NOTE REFERENCING
 SPECIFICATION SHEETS PM06.01 AND PM07.01, SECTION 22 40
 00 PLUMBING FOR ADDITIONAL SPECIFICATIONS
  
 5.REGARDING THE ADDED HUB DRAIN FOR CD-1 CONNECTED TO
 THE GREASY WASTE, PER WPB FBC 107.2.1, PLEASE CLARIFY
 WHAT IS TO DISCHARGE INTO THE HUB DRAIN AND FROM WHAT
 EQUIPMENT. BASED UPON P04.01/DETAIL 3, IT APPEARS THAT
 THE HUB DRAIN IS TO RECEIVE CONDENSATION FROM A
 REFRIGERATED CASE; PLEASE NOTE PER FBC PL 1003.3.1
 GREASE INTERCEPTORS AND AUTOMATIC GREASE REMOVAL
 DEVICES SHALL RECEIVE WASTE ONLY FROM FIXTURES AND
 EQUIPMENT THAT ALLOW FATS, OILS OR GREASE TO BE
 DISCHARGED. PER WPB FBC 107.2.1, CLARIFY WHAT KIND OF
 WASTE IS TO BE DISCHARGED INTO THE REFERENCED HUB DRAIN
 AND IF SAID WASTE DOES NOT SATISFY THE REQUIREMENTS OF
 FBC PL 1003.3.1, THEN CONNECT TO SANITARY.
  
  
 END OF COMMENTS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE SIGNED AND SEALED OR DIGITALLY SIGNED
 AND SEALED BY THE DESIGNER IN ACCORDANCE WITH FAC AND
 FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20090889 375 S ROSEMARY AVE

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-01-12 Cont ID  
Sent By rmcphers Date 2021-01-07 Time 08:24 Rev Time 0.00
Received By rmcphers Date 2021-01-07 Time 08:24 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-10-20 Cont ID  
Sent By equinone Date 2020-10-20 Time 15:26 Rev Time 0.00
Received By equinone Date 2020-10-20 Time 15:26 Sent To  
Notes
2020-10-20 15:34:42ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
 SOME DRAWINGS (0126-BA01, 02-0848-PM01 AND OTHERS) ARE
 MISSING THE DIGITAL SIGNATURE OR IF PREPARED BY A PE
 ARE REQUIRED TO HAVE A THIRD PARTY CERTIFICATION.
  
 FS471, FS481, DOCUMENTS PREPARED BY AN ARCHITECT OR
 ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED, SEALED, DATED ORIGINALS. A SCAN OF A SIGNED
 PLAN IS NOT CONSIDERED AN ORIGINAL.
  
 EITHER EMAIL A DIGITALLY OR ELECTRONICALLY SIGNED PLAN
 TO ME, OR YOU CAN MAIL (OR DROP OFF) ONE ORIGINAL
 SIGNED AND SEALED PAPER ORIGINAL WITH A WET SIGNATURE
 TO:
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 DEVELOPMENT SERVICES
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
  
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS,
 561-805-6746.
  

Review Stop Z ZONING
Rev No 2 Status P Date 2020-12-29 Cont ID  
Sent By eschneid Date 2020-12-29 Time 10:50 Rev Time 0.50
Received By eschneid Date 2020-12-29 Time 09:02 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2020-10-06 Cont ID  
Sent By eschneid Date 2020-10-06 Time 11:17 Rev Time 0.50
Received By eschneid Date 2020-10-06 Time 10:51 Sent To  
Notes
2020-10-06 11:17:51FAILED
  
 1) THE PROPOSED INSTALLATION OF BOLLARDS ON THE OUTSIDE
 OF THE STORE REQUIRES A SURVEY TO BE PROVIDED.
 ADDITIONALLY, CITYPLACE RETAIL, LLC, NEEDS TO EITHER
 STAMP THE BOLLARD PLANS OR PROVIDE A LETTER APPROVING
 THE BOLLARD INSTALLATION. NOTE: YOU MAY CHOOSE TO
 SUBMIT THE BOLLARDS AS A SEPARATE BUILDING PERMIT.
  
 2) THE PLANS SHOW NEW CONDENSERS AND FANS ON THE ROOF.
 IN ACCORDANCE WITH THE CITYPLACE DRI, PLEASE PROVIDE
 VERIFICATION THAT ALL ROOFTOP MECHANICAL EQUIPMENT,
 INCLUDING BUT NOT LIMITED TO SUCH ITEMS AS PUBLIC AND
 PRIVATE UTILITY SERVICE CONNECTIONS; HEATING,
 VENTILATING, AND AIR CONDITIONING SYSTEMS;
 COMMUNICATIONS DEVICES; AND RELATED EQUIPMENT, SHALL BE
 SCREENED FROM PUBLIC VIEW THROUGH ANY COMBINATION OF
 LANDSCAPING, WALLS AND EQUIPMENT LOCATION. PLEASE
 PROVIDE PLANS OR OTHER EVIDENCE THAT THE NEW ROOFTOP
 MECHANICAL EQUIPMENT WILL BE SCREENED FROM PUBLIC VIEW.
 NOTE: THIS EXTERIOR WORK ALSO REQUIRES CITYPLACE
 RETAIL, LLC, SIGN OFF.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]