Plan Review Details - Permit 20090880
Plan Review Stops For Permit 20090880
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2021-01-05 Cont ID  
Sent By jwitmer Date 2021-01-05 Time 08:27 Rev Time 0.00
Received By jwitmer Date 2021-01-05 Time 07:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2020-12-14 Cont ID  
Sent By jwitmer Date 2020-12-14 Time 14:30 Rev Time 0.00
Received By jwitmer Date 2020-12-14 Time 13:30 Sent To  
Notes
2020-12-14 14:33:30WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20090880
 ADD: 600 S. DIXIE HWY.# 836
 CONT: JLC CUSTOM FLOORING & REMODELING
 TEL: BLANK
 E-MAIL: BLANK
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 4TH REVIEW
 DATE: MON. DEC. 14TH/2020
 ACTION: DENIED
  
 NOTICE ONLY: 4X FEE / NOTICE!!!!! FLORIDA STATUTE
 553.80(2)(B)
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
  
  
 1) 4TH REQUEST. SEMI -COMPLIED. UNDER THE HEADING OF
 TRADE : FLOORING.
 THE PERMIT APPLICATION STATES FOR THE 1ST TIME THE WORK
 TO BE COMPLETED UNDER THIS PERMIT IS PORCELIN FLOOR
 TILE AND UNDERLAYMENT. NEITHER THE FLOOR PLAN NOR
 APPLICATION INDICATE THE SQUARE FOOTAGE OF TILE TO BE
 INSTALLED.
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATIVE CODE SECTION 105.1
 REQUIRED.
  
 2A) SEMI-COMPLIED . IN SPEAKING WITH THE OWNERS
 PORCELIN TILE TO BE INSTALLED WITH WHISPER MAT CS BUT
 NOT ON THE PERMIT APPLICATION UNDER DESCRIPTION OF
 WORK. 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. THE
 SQUARE FOOTAGE IS NOT LISTED ON NEITHER THE APPLICATION
 NOR THE FLOOR PLAN. THE VALUE OF THIS PERMIT CANNOT BE
 DETERMINED WITHOUT THE SQUARE FOOTAGE OF THE FLOOR AREA
 TO HAVE PORCELAIN TILE INSTALLED. 109.3* BUILDING
 PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDERESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 2B) THIS REVIEW FOR THE 1ST TIME PICTURES WERE UPLOADED
 AND IN ONE PICTURE WHERE IT APPEARS THAT EITHER A TUB
 OR SHOWER WAS THE WALLS ARE STRIPED DOWN TO THE METAL
 STUDS, IS THIS WORK TO BE COMPLETED UNDER THIS PERMIT.
 NOTE THIS PERMIT IS FOR FLOOR ONLY NO WHERE ON THE
 APPLICATION IS THERE ANYTHING THING ABOUT CHANGING A
 TUB TO A SHOWER. THIS BUILDING WAS BUILT AFTER THE FAIR
 HOUSING ACT WENT INTO EFFECT AND NEEDS TO SHOW
 COMPLIANCE WITH FAIR HOUSING.
 FAIR HOUSING GUIDELINES. FAIR HOUSING ACT DESIGN AND
 CONSTRUCTION REQUIREMENTS. FOR PURPOSES OF THIS
 SECTION, A COVERED MULTIFAMILY DWELLING SHALL BE DEEMED
 TO BE DESIGNED AND CONSTRUCTED FOR FIRST OCCUPANCY ON
 OR BEFORE MARCH 13, 1991, IF THEY ARE OCCUPIED BY THAT
 DATE OR IF THE LAST BUILDING PERMIT OR RENEWAL THEREOF
 FOR THE COVERED MULTIFAMILY DWELLINGS IS ISSUED BY A
 STATE, COUNTY OR LOCAL GOVERNMENT ON OR BEFORE JANUARY
 13, 1990.
 FAIR HOUSING LETTER AS AN ALTERNATE METHOD. SEE LETTER:
 PROJECT ADDRESS: ______________________________________
 _____________________
 PERMIT NUMBER: ________________________
 THE OWNER AND DESIGNER OF RECORD ACKNOWLEDGE THAT THE
 PROPOSED BATHROOM DESIGN DOES NOT MEET THE REQUIREMENTS
 OF THE FAIR HOUSING ACCESSIBILITY GUIDELINES. THE OWNER
 AGREES TO REVERT THE UNIT BACK TO COMPLIANCE AT TIME OF
 SALE IF SO REQUESTED BY THE BUYER.
  
 SIGNATURE OF DESIGNER: ______________________________
 PRINTED NAME OF DESIGNER: ___________________________
  
 SIGNATURE OF OWNER: ________________________________
 PRINTED NAME OF OWNER: _____________________________
 NOTARY FOR OWNER?S SIGNATURE:
 STATE OF FLORIDA, COUNTY OF PALM BEACH
 THE FOREGOING INSTRUMENT WAS ACKNOWLEDGED BEFORE ME
 THIS _____ DAY OF ________, 20__ BY
 ___________________________ WHO IS PERSONALLY KNOWN TO
 ME OR WHO HAS PRODUCED: ___________________________ AS
 IDENTIFICATION AND WHO DID / DID NOT TAKE AN OATH.
 NOTARY SIGNATURE ___________________________________
 NOTARY PRINTED NAME ________________________________
  
 3) SEMI-COMPLIED. 4TH REQUEST. THE SITE PLAN
 (FLOORPLAN) FLOOR PLAN SUBMITTED PLEASE NOTE THE
 CONTRACTOR/ QUALIFIER FOR THE COMPANY MUST PRINT THEIR
 NAME, SIGN THEIR NAME AND LICENSE NUMBER TO THE FLOOR
 PLAN.
 THE CONTRACTOR ONLY PRINTED THEIR NAME.
 CERTIFICATION BY CONTRACTOR. 107.3.4.3 CERTIFICATION BY
 CONTRACTOR. PLEASE NOTE THE EXCEPTION TO ENGINEERED
 PLANS UNDER 471.003(H) ELECTRICAL/ PLUMBING/
 MECHANICAL, 481.229(1)(C) (BUILDING) REQUIRES THE
 CONTRACTOR FOR THAT TRADE THAT WILL BE LICENSED IN THAT
 TRADE, WILL ALSO BE THE CONTRACTOR THAT DESIGNS THE
 SYSTEM UNDER THAT TRADE. THE CONTRACTOR (QUALIFIER)
 THAT CREATED / DRAWN THE SET OF PLANS WILL NEED TO
 IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE
 PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR
 THE TRADE YOU ARE LICENSED IN AND PLANS DRAWN.
  
 4) COMPLIED. THIS SUBMITTAL WHISPER MAT CS UNDERLAYMENT
 WAS UPLOADED.
  
 5) NOTE ONLY!!! TO THE PERSON UPLOADING DOCUMENTS. EACH
 DOCUMENT SHOULD BE LOADED SEPARATELY INTO THE FILE
 FOLDER, AN EXAMPLE WOULD BE THE PERMIT APPLICATION,
 THEN THE FLOOR PLAN IN ON OTHER FOLDER, THEN THEN ANY
 OTHER DOCUMENTS EACH UPLOADED SEPARATELY THEN FINISH
 THE TASK TO NOTIFY THE LIBRARIAN THAT THE TASK IS
 COMPLETE.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2020-12-04 Cont ID  
Sent By jwitmer Date 2020-12-04 Time 09:48 Rev Time 0.00
Received By jwitmer Date 2020-12-04 Time 08:45 Sent To  
Notes
2020-12-04 09:48:16WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20090880
 ADD: 600 S. DIXIE HWY.# 836
 CONT: JLC CUSTOM FLOORING & REMODELING
 TEL: BLANK
 E-MAIL: BLANK
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: FRI. DEC. 04TH/2020
 ACTION: DENIED
  
 1)3RD REQUEST. SEMI -COMPLIED. UNDER THE HEADING OF
 TRADE : FLOORING.
 THE PERMIT APPLICATION IS BLANK AS TO THE CONTRACTOR
 CONTRACTED TO INSTALL THE FLOORING AND UNDERLAYMENT.
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATIVE CODE SECTION 105.1
 REQUIRED.
  
 2) SEMI-COMPLIED . UNDER THE HEADING OF TRADE:
 FLOORING. 2ND REQUEST. THE APPLICANT HAS NOT INDICATED
 ON THE PERMIT APPLICATION UNDER THE DESCRIPTION OF WORK
 WHAT TYPE OF WORK IS TO BE PREFORMED WITHIN THE SCOPE
 OF THIS PERMIT. IN SPEAKING WITH THE OWNERS PORCELIN
 TILE TO BE INSTALLED WITH WHISPER AT CS BUT NOT ON THE
 PERMIT APPLICATION UNDER DESCRIPTION OF WORK. 107.2.1.2
 ADDITIONAL INFORMATION IS REQUIRED.
  
 3) SEMI-COMPLIED. 2ND REQUEST. FOR THE FUTURE FLOOR
 PLAN TO BE SUBMITTED PLEASE NOTE THE CONTRACTOR/
 QUALIFIER FOR THE COMPANY MUST PRINT THEIR NAME, SIGN
 THEIR NAME AND LICENSE NUMBER TO THE FLOOR PLAN.
 THE CONTRACTOR ONLY PRINTED THEIR NAME.
 CERTIFICATION BY CONTRACTOR. 107.3.4.3 CERTIFICATION BY
 CONTRACTOR. PLEASE NOTE THE EXCEPTION TO ENGINEERED
 PLANS UNDER 471.003(H) ELECTRICAL/ PLUMBING/
 MECHANICAL, 481.229(1)(C) (BUILDING) REQUIRES THE
 CONTRACTOR FOR THAT TRADE THAT WILL BE LICENSED IN THAT
 TRADE, WILL ALSO BE THE CONTRACTOR THAT DESIGNS THE
 SYSTEM UNDER THAT TRADE. THE CONTRACTOR (QUALIFIER)
 THAT CREATED / DRAWN THE SET OF PLANS WILL NEED TO
 IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE
 PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR
 THE TRADE YOU ARE LICENSED IN AND PLANS DRAWN.
  
 4) COMPLIED. THIS SUBMITTAL WHISPER MAT CS UNDERLAYMENT
 WAS UPLOADED.
  
 5) TO THE PERSON UPLOADING DOCUMENTS. EACH DOCUMENT
 SHOULD BE LOADED SEPARATELY INTO THE FILE FOLDER, AN
 EXAMPLE WOULD BE THE PERMIT APPLICATION, THEN THE FLOOR
 PLAN IN ON OTHER FOLDER, THEN THEN ANY OTHER DOCUMENTS
 EACH UPLOADED SEPARATELY THEN FINISH THE TASK TO NOTIFY
 THE LIBRARIAN THAT THE TASK IS COMPLETE.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-11-28 Cont ID  
Sent By jwitmer Date 2020-11-28 Time 13:43 Rev Time 0.00
Received By jwitmer Date 2020-11-28 Time 13:27 Sent To  
Notes
2020-11-28 13:43:00WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20090880
 ADD: 600 S. DIXIE HWY.# 836
 CONT: JLC CUSTOM FLOORING & REMODELING
 TEL: BLANK
 E-MAIL: BLANK
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: SAT. NOV.28TH/2020
 ACTION: DENIED
  
 4X FEE / NOTICE!!!!! FLORIDA STATUTE 553.80(2)(B)
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
  
  
 1) 2ND REQUEST. THE PERMIT APPLICATION IS BLANK AS TO
 THE CONTRACTOR CONTRACTED TO INSTALL THE FLOORING AND
 UNDERLAYMENT.
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATIVE CODE SECTION 105.1
 REQUIRED.
  
 2) 2ND REQUEST. THE APPLICANT HAS NOT INDICATED ON THE
 PERMIT APPLICATION UNDER THE DESCRIPTION OF WORK WHAT
 TYPE OF WORK IS TO BE PREFORMED WITHIN THE SCOPE OF
 THIS PERMIT. FURTHERMORE, THERE WAS NO FLOOR PLAN AS TO
 WHERE THE WORK IS TO OCCUR. 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 3) 2ND REQUEST. FOR THE FUTURE FLOOR PLAN TO BE
 SUBMITTED PLEASE NOTE THE CONTRACTOR/ QUALIFIER FOR THE
 COMPANY MUST PRINT THEIR NAME, SIGN THEIR NAME AND
 LICENSE NUMBER TO THE FLOOR PLAN.
 CERTIFICATION BY CONTRACTOR. 107.3.4.3 CERTIFICATION BY
 CONTRACTOR. PLEASE NOTE THE EXCEPTION TO ENGINEERED
 PLANS UNDER 471.003(H) ELECTRICAL/ PLUMBING/
 MECHANICAL, 481.229(1)(C) (BUILDING) REQUIRES THE
 CONTRACTOR FOR THAT TRADE THAT WILL BE LICENSED IN THAT
 TRADE, WILL ALSO BE THE CONTRACTOR THAT DESIGNS THE
 SYSTEM UNDER THAT TRADE. THE CONTRACTOR (QUALIFIER)
 THAT CREATED / DRAWN THE SET OF PLANS WILL NEED TO
 IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE
 PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR
 THE TRADE YOU ARE LICENSED IN AND PLANS DRAWN.
  
 4) 2ND REQUEST.A SALES BROCHURE (PRODUCT DATA SHEET)
 FOR WHISPER MAT LVT(LUXURY VINYL TILE) WAS SUBMITTED
 FOR USE WITH LUXURY VINYL TILE. TO DATE THE CITY HAS
 NOT SEEN THIS PRODUCT WITH TESTING REPORTS.
 FLOOR INSULATION (FBC-B 2017)
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS SHOWING
 COMPLIANCE WITH:
  
 TYPE I AND II BUILDINGS
 4A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 4B) FBC-B 2017 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 4C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 LVT & LPT LUXURY VINYL TILE. FLOOR FINISH
 CLASSIFICATION AS REQUIRED IN SECTION 804.2
 CLASSIFICATION AND 804.3 TESTING AND IDENTIFICATION OF
 THE 2017 FBC-B.
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-11-11 Cont ID  
Sent By jwitmer Date 2020-11-11 Time 10:45 Rev Time 0.00
Received By jwitmer Date 2020-11-11 Time 10:13 Sent To  
Notes
2020-11-11 10:43:13WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20090880
 ADD: 600 S. DIXIE HWY.# 836
 CONT: JLC CUSTOM FLOORING & REMODELING
 TEL: BLANK
 E-MAIL: BLANK
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. NOV.11/2020
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION IS BLANK AS TO THE CONTRACTOR
 CONTRACTED TO INSTALL THE FLOORING AND UNDERLAYMENT.
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATIVE CODE SECTION 105.1
 REQUIRED.
  
 2) THE APPLICANT HAS NOT INDICATED ON THE PERMIT
 APPLICATION UNDER THE DESCRIPTION OF WORK WHAT TYPE OF
 WORK IS TO BE PREFORMED WITHIN THE SCOPE OF THIS
 PERMIT. FURTHERMORE, THERE WAS NO FLOOR PLAN AS TO
 WHERE THE WORK IS TO OCCUR. 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 3) FOR THE FUTURE FLOOR PLAN TO BE SUBMITTED PLEASE
 NOTE THE CONTRACTOR/ QUALIFIER FOR THE COMPANY MUST
 PRINT THEIR NAME, SIGN THEIR NAME AND LICENSE NUMBER TO
 THE FLOOR PLAN.
 CERTIFICATION BY CONTRACTOR. 107.3.4.3 CERTIFICATION BY
 CONTRACTOR. PLEASE NOTE THE EXCEPTION TO ENGINEERED
 PLANS UNDER 471.003(H) ELECTRICAL/ PLUMBING/
 MECHANICAL, 481.229(1)(C) (BUILDING) REQUIRES THE
 CONTRACTOR FOR THAT TRADE THAT WILL BE LICENSED IN THAT
 TRADE, WILL ALSO BE THE CONTRACTOR THAT DESIGNS THE
 SYSTEM UNDER THAT TRADE. THE CONTRACTOR (QUALIFIER)
 THAT CREATED / DRAWN THE SET OF PLANS WILL NEED TO
 IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE
 PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR
 THE TRADE YOU ARE LICENSED IN AND PLANS DRAWN.
  
 4) A SALES BROCHURE (PRODUCT DATA SHEET) FOR WHISPER
 MAT LVT(LUXURY VINYL TILE) WAS SUBMITTED FOR USE WITH
 LUXURY VINYL TILE. TO DATE THE CITY HAS NOT SEEN THIS
 PRODUCT WITH TESTING REPORTS.
 FLOOR INSULATION (FBC-B 2017)
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS SHOWING
 COMPLIANCE WITH:
  
 TYPE I AND II BUILDINGS
 4A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 4B) FBC-B 2017 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 4C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 LVT & LPT LUXURY VINYL TILE. FLOOR FINISH
 CLASSIFICATION AS REQUIRED IN SECTION 804.2
 CLASSIFICATION AND 804.3 TESTING AND IDENTIFICATION OF
 THE 2017 FBC-B.
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2021-01-05 Cont ID  
Sent By jwitmer Date 2021-01-05 Time 08:23 Rev Time 0.00
Received By jwitmer Date 2020-12-29 Time 08:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status F Date 2020-12-14 Cont ID  
Sent By jwitmer Date 2020-12-14 Time 14:37 Rev Time 0.00
Received By jwitmer Date 2020-12-08 Time 15:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-12-04 Cont ID  
Sent By jwitmer Date 2020-12-04 Time 09:51 Rev Time 0.00
Received By jwitmer Date 2020-12-03 Time 16:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-11-28 Cont ID  
Sent By jwitmer Date 2020-11-28 Time 13:44 Rev Time 0.00
Received By jwitmer Date 2020-11-23 Time 12:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-11-11 Cont ID  
Sent By jwitmer Date 2020-11-11 Time 10:46 Rev Time 0.00
Received By jwitmer Date 2020-11-03 Time 09:22 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2021-01-05 Cont ID  
Sent By jwitmer Date 2021-01-05 Time 08:24 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2020-12-14 Cont ID  
Sent By jwitmer Date 2020-12-14 Time 14:34 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2020-12-14 14:35:13. 4TH REQUEST. THE SITE PLAN (FLOORPLAN) FLOOR PLAN
 SUBMITTED PLEASE NOTE THE CONTRACTOR/ QUALIFIER FOR THE
 COMPANY MUST PRINT THEIR NAME, SIGN THEIR NAME AND
 LICENSE NUMBER TO THE FLOOR PLAN.
 THE CONTRACTOR ONLY PRINTED THEIR NAME.
 CERTIFICATION BY CONTRACTOR. 107.3.4.3 CERTIFICATION BY
 CONTRACTOR. PLEASE NOTE THE EXCEPTION TO ENGINEERED
 PLANS UNDER 471.003(H) ELECTRICAL/ PLUMBING/
 MECHANICAL, 481.229(1)(C) (BUILDING) REQUIRES THE
 CONTRACTOR FOR THAT TRADE THAT WILL BE LICENSED IN THAT
 TRADE, WILL ALSO BE THE CONTRACTOR THAT DESIGNS THE
 SYSTEM UNDER THAT TRADE. THE CONTRACTOR (QUALIFIER)
 THAT CREATED / DRAWN THE SET OF PLANS WILL NEED TO
 IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE
 PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR
 THE TRADE YOU ARE LICENSED IN AND PLANS DRAWN.
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2020-12-04 Cont ID  
Sent By jwitmer Date 2020-12-04 Time 09:50 Rev Time 0.00
Received By jwitmer Date 2020-12-04 Time 08:46 Sent To  
Notes
2020-12-04 09:50:333RD REQUEST. FOR THE FUTURE FLOOR PLAN TO BE SUBMITTED
 PLEASE NOTE THE CONTRACTOR/ QUALIFIER FOR THE COMPANY
 MUST PRINT THEIR NAME, SIGN THEIR NAME AND LICENSE
 NUMBER TO THE FLOOR PLAN.
 THE CONTRACTOR ONLY PRINTED THEIR NAME.
 CERTIFICATION BY CONTRACTOR. 107.3.4.3 CERTIFICATION BY
 CONTRACTOR. PLEASE NOTE THE EXCEPTION TO ENGINEERED
 PLANS UNDER 471.003(H) ELECTRICAL/ PLUMBING/
 MECHANICAL, 481.229(1)(C) (BUILDING) REQUIRES THE
 CONTRACTOR FOR THAT TRADE THAT WILL BE LICENSED IN THAT
 TRADE, WILL ALSO BE THE CONTRACTOR THAT DESIGNS THE
 SYSTEM UNDER THAT TRADE. THE CONTRACTOR (QUALIFIER)
 THAT CREATED / DRAWN THE SET OF PLANS WILL NEED TO
 IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE
 PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR
 THE TRADE YOU ARE LICENSED IN AND PLANS DRAWN.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-11-28 Cont ID  
Sent By jwitmer Date 2020-11-28 Time 13:44 Rev Time 0.00
Received By jwitmer Date 2020-11-28 Time 13:28 Sent To  
Notes
2020-11-28 13:44:23SEE BUILDING REVIEW NOTES.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-11-11 Cont ID  
Sent By jwitmer Date 2020-11-11 Time 10:45 Rev Time 0.00
Received By jwitmer Date 2020-11-11 Time 10:13 Sent To  
Notes
2020-11-11 10:45:56SEE BUILDING REVIEW.