Plan Review Details - Permit 20090848
| Plan Review Stops For Permit 20090848 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
2 |
Status |
P |
Date |
2021-01-19 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2021-01-19 |
Time |
10:45 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2021-01-19 |
Time |
10:45 |
Sent To |
|
|
| Notes |
| 2021-01-19 10:46:40 | NEW HOTEL WILL HAVE ADDRESS OF 1221 BELVEDERE RD |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
F |
Date |
2020-10-16 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2020-10-16 |
Time |
15:13 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2020-10-16 |
Time |
15:13 |
Sent To |
|
|
| Notes |
| 2020-10-16 15:15:29 | PLEASE EMAIL [email protected] A SITE PLAN AND FIRST FLOOR | | | PLAN CLEARLY MARKING THE MAIN ENTRANCE TO THE PROPERTY. |
|
|
| Review Stop |
AIPP |
ART IN PUBLIC PLACES |
| Rev No |
4 |
Status |
P |
Date |
2021-05-26 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2021-05-26 |
Time |
10:53 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2021-05-26 |
Time |
10:53 |
Sent To |
|
|
| Notes |
| 2021-05-26 10:54:25 | AIPP SATIFIED PER E-MAIL ON 5/26/21 FORM S.W. | | | PLEASE RELEASE THE CO HOLD ON PERMIT #20090848 AD1 PB2 | | | AIRPORT HOTELS 1301 BELVEDERE ROAD, THEY HAVE SATISFIED | | | THE PUBLIC ART REQUIREMENT. |
|
|
| Review Stop |
AIPP |
ART IN PUBLIC PLACES |
| Rev No |
3 |
Status |
F |
Date |
2021-03-30 |
|
|
Cont ID |
|
| Sent By |
scwelter |
Date |
2021-03-30 |
Time |
15:18 |
Rev Time |
0.00 |
| Received By |
scwelter |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
AIPP |
ART IN PUBLIC PLACES |
| Rev No |
2 |
Status |
F |
Date |
2021-03-05 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2021-03-05 |
Time |
11:21 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2021-03-05 |
Time |
11:21 |
Sent To |
|
|
| Notes |
| 2021-03-05 11:27:18 | A HOLD HAS BEEN PLACED ON THE C.O. HOWEVER, BEFORE THE | | | PERMIT IS ISSUED YOU ARE REQUIRED TO CONTACT SYBILLIE | | | WELTER AND FILE AN APPLICATION FOR ART IN PUBLIC | | | PLACES. HER PHONE NUMBER IS 561-822-1521 AND HER EMAIL | | | IS [email protected]. |
|
|
| Review Stop |
AIPP |
ART IN PUBLIC PLACES |
| Rev No |
1 |
Status |
F |
Date |
2020-11-02 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2020-11-02 |
Time |
07:35 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2020-11-02 |
Time |
07:35 |
Sent To |
|
|
| Notes |
| 2020-11-02 07:36:08 | THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES | | | ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR | | | NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT | | | APPLICATION WAS SUBMITTED AFTER 6/29/14, AND THE TOTAL | | | PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN | | | $750,000 WILL NEED TO COMPLY WITH THIS ORDINANCE. | | | PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND | | | CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V, | | | ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION | | | 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL | | | PROJECT CONSTRUCTION COST. | | | PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE | | | V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND | | | NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO | | | THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE | | | PROJECTS. | | | FOR INFORMATION PLEASE CONTACT: MS. SYBILLE WELTER, ART | | | IN PUBLIC PLACES COORDINATOR AT 822-1521 OR E-MAIL: | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2021-10-12 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2021-10-12 |
Time |
17:00 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2021-10-07 |
Time |
09:44 |
Sent To |
|
|
| Notes |
| 2021-10-12 15:55:09 | PLAN | | | REVIEW COMMENTS | | | | | | 5TH REVIEW | | | FBC SIXTH EDITION (2017) & CITY OF W.P.B. CHAPTER 1 | | | AMENDMENTS | | | CITY ORDINANCES | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | NEW 4 STORY HOTEL | | | TYPE II-B CONSTRUCTION | | | R-1 OCCUPANCY TYPE | | | FLOOD ZONE AE, BFE 12.7' NAVD88 (DFE 14.7' NAVD 88 | | | INCLUDES 2' FREEBOARD) | | | | | | 1) COMPLIED. | | | | | | 2) COMPLIED. | | | | | | 3) PARTIALLY COMPLIED. THE BUILDING OFFICIAL, ROBERT | | | BROWN, HAS CONDITIONALLY AGREED TO ACCEPT THE OPTION TO | | | ENCLOSE THE WINDOW OPENINGS THAT EXCEED THE AMOUNT OF | | | ALLOWABLE OPENINGS BASED ON THE FIRE SEPARATION | | | DISTANCE TO THE RE-PLATTED PROPERTY LINE IN THE | | | EXISTING HOTEL. THE CONDITIONS ARE THAT A HOLD WILL BE | | | PLACED ON THE PROPOSED HOTEL'S C.O. UNTIL THE ALLOWABLE | | | OPENINGS ISSUE IS RESOLVED AND THE PROPOSED WORK TO | | | ENCLOSE THE WINDOW OPENINGS IS REQUIRED TO BE SHOWN ON | | | THE REMODEL PLANS FOR THE EXISTING HOTEL LOCATED AT | | | 1301 BELVEDERE RD. UNDER PERMIT #20120964. | | | | | | 4) NOT COMPLIED. [BARRIER AND MOT PLANS STILL HAVE NOT | | | BEEN SUBMITTED.](NO PLANS FOR THIS HAVE BEEN | | | SUBMITTED.) SHOW COMPLIANCE WITH FBC CHAPTER 33 FOR | | | SAFEGUARDS DURING CONSTRUCTION. SUBMIT BARRIER AND MOT | | | PLANS. | | | | | | 5) PROVISO. PRODUCT APPROVALS TO BE DEFERRED. THERE IS | | | A LIST OF PRODUCT APPROVALS TO BE DEFERRED ON SHEET | | | A011. DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE | | | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN | | | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD | | | THEM TO THE BUILDING OFFICIAL WITH A NOTATION | | | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE | | | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO | | | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL | | | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED | | | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING | | | OFFICIAL. | | | | | | 6) PROVISO. NOTED ON THE PLANS. | | | SEPARATE PERMITS, PLANS AND FEES WILL BE REQUIRED FOR | | | THE FOLLOWING: | | | LIGHT POLES/SITE LIGHTING | | | FIRE ALARM | | | FIRE SPRINKLER | | | LOW VOLTAGE | | | ACCESS | | | LANDSCAPING | | | IRRIGATION | | | PARKING LOT | | | DUMPSTER ENCLOSURE | | | SITE WALLS | | | ALL OTHER ITEMS OTHER THAN BMEP | | | | | | 7) NOTE: A SEPARATE SUB-PERMIT IS REQUIRED FOR ROOFING. | | | | | | 8) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A | | | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE | | | CITY RE-SUBMITTAL FORM. | | | | | | 9) COMPLIED. | | | | | | 10) NEW COMMENT. THE PRODUCT APPROVAL THAT WAS | | | SUBMITTED FOR THE ROOF HATCH, NOA NO. 18-0110.05, HAS | | | NOT BEEN REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD. FBC 107. FBC 107.3.4 - PROVIDE TWO | | | SETS OF PRODUCT APPROVALS FOR THOSE PRODUCTS WHICH ARE | | | REGULATED BY FAC 61G20-3.001 PER FLORIDA STATUTE | | | 553.842 (5) THAT HAVE BEEN REVIEWED AND APPROVED IN | | | WRITING BY THE DESIGNER OF RECORD. PROVIDE TWO COMPLETE | | | PRODUCT APPROVALS WITH FL OR NOA NUMBERS INCLUDING | | | INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES | | | FOR EACH OF THE DIFFERENT ROOFING MATERIALS, WINDOW | | | (GLASS TYPES), STRUCTURAL MULLIONS AND EXTERIOR DOOR | | | TYPES. THESE ITEMS CAN BE DEFERRED IF REQUESTED, | | | HOWEVER, THE DOCUMENTS MUST BE SUBMITTED AND APPROVED | | | BY THE BUILDING DEPARTMENT BEFORE THEY CAN BE | | | INSTALLED. ONLY ONE SET IS REQUIRED TO BE UPLOADED FOR | | | ELECTRONICALLY SUBMITTED DOCUMENTS. | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2021-06-29 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2021-06-29 |
Time |
15:15 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2021-06-28 |
Time |
14:02 |
Sent To |
|
|
| Notes |
| 2021-06-29 14:20:21 | PLAN | | | REVIEW COMMENTS | | | | | | 4TH REVIEW | | | FBC SIXTH EDITION (2017) & CITY OF W.P.B. CHAPTER 1 | | | AMENDMENTS | | | CITY ORDINANCES | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | NEW 4 STORY HOTEL | | | TYPE II-B CONSTRUCTION | | | R-1 OCCUPANCY TYPE | | | FLOOD ZONE AE, BFE 12.7' NAVD88 (DFE 14.7' NAVD 88 | | | INCLUDES 2' FREEBOARD) | | | | | | NOTE: THE NUMBERING IS OFF ON THE RESPONSES STARTING AT | | | NUMBER 17. THE RESPONSE FOR #17 IS ACTUALLY FOR COMMENT | | | # 18 AND SO ON. | | | | | | 1) THE PRE-CONSTRUCTION ELEVATION CERTIFICATE HAS | | | ERRORS. THE LATITUDE AND LONGITUDE ARE REVERSED ON THE | | | CERTIFICATE (IE. THE LONGITUDE IS IN THE SPACE FOR | | | LATITUDE AND THE LATITUDE IS IN THE SPACE FOR | | | LONGITUDE). THE NORTH AND WEST DESIGNATIONS WERE NOT | | | SPECIFIED FOR LONGITUDE AND LATITUDE. NOTE: THE | | | COORDINATES ARE REQUIRED TO BE WITHIN 66 FEET OF THE | | | MAIN BUILDING ENTRANCE. [PREVIOUS COMMENT #2. THE NOT | | | COMPLIED.] [PRECONSTRUCTION ELEVATION CERTIFICATE WAS | | | NOT SUBMITTED.] (THE PERMIT CAN NOT BE ISSUED UNTIL A | | | PRE-CONSTRUCTION ELEVATION CERTIFICATE HAS BEEN | | | SUBMITTED AND APPROVED.) THIS PROJECT IS LOCATED IN A | | | SPECIAL FLOOD HAZARD AREA (AE FLOOD ZONE). SEE NFIP | | | REVIEW COMMENTS. | | | | | | 2) ENGINEERING APPROVAL IS REQUIRED. [PREVIOUS COMMENT | | | #3. NOT COMPLIED.] [SEE ENGINEERING COMMENT THAT STATES | | | SITE PLAN HAS NOT BEEN APPROVED](THE PERMIT CAN NOT BE | | | ISSUED UNTIL MINOR LOT SUBDIVISION HAS BEEN APPROVED.) | | | THE SITE PLAN SHOWS A PROPERTY LINE THAT IS PART OF | | | ANOTHER PARCEL ON THE PALM BEACH COUNTY PROPERTY | | | APPRAISER'S WEB SITE. PROVIDE A COPY OF THE RECORDED | | | PLAT FOR THIS LOT DIVISION. FBC 107.2 | | | | | | 3) SITE PLANS WERE SUBMITTED FOR REFERENCE. A REVIEW OF | | | THESE DOCUMENTS, PREVIOUS COMMENT #4, HAS RESULTED IN | | | THE FOLLOWING ADDITIONAL COMMENTS. | | | A) SHOW HOW THE EXISTING HOTEL WILL COMPLY WITH FBC | | | 705.8 MAXIMUM AREA OF EXTERIOR WALL OPENINGS BASED ON | | | FIRE SEPARATION DISTANCE TO THE PROPOSED PARCEL LINE | | | BETWEEN THE TWO BUILDINGS. | | | B) THE PLANS SPECIFY (5) ACCESSIBLE PARKING SPACES. FBC | | | ACCESSIBILITY 208.2 REQUIRES (9) ACCESSIBILE SPACES FOR | | | PARKING FACILITIES WITH 401 - 500 SPACES AND (8) | | | ACCESSIBILE SPACES FOR PARKING FACILITIES WITH 301 - | | | 400 SPACES. THE ACTUAL NUMBER WILL DEPEND ON THE TOTAL | | | NUMBER OF SPACES IF THE WAVIER THAT YOU HAVE REQUESTED | | | IS GRANTED OR NOT. FBC ACCESSIBILITY 208.2.4 REQUIRES | | | (2) OF THE ACCESSIBILE SPACES TO BE VAN PARKING SPACES. | | | (ONE FOR EVERY SIX OR FRACTION OF SIX ACCESSIBLE | | | SPACES.) | | | | | | 4) PREVIOUS COMMENT #6. NOT COMPLIED. [BARRIER AND MOT | | | PLANS STILL HAVE NOT BEEN SUBMITTED.](NO PLANS FOR THIS | | | HAS BEEN SUBMITTED.) SHOW COMPLIANCE WITH FBC CHAPTER | | | 33 FOR SAFEGUARDS DURING CONSTRUCTION. SUBMIT BARRIER | | | AND MOT PLANS. | | | | | | 5) PROVISO. PRODUCT APPROVALS TO BE DEFERRED. THERE IS | | | A LIST OF PRODUCT APPROVALS TO BE DEFERRED ON SHEET | | | A011. DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE | | | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN | | | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD | | | THEM TO THE BUILDING OFFICIAL WITH A NOTATION | | | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE | | | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO | | | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL | | | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED | | | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING | | | OFFICIAL. | | | | | | 6) PROVISO. NOTED ON THE PLANS. | | | SEPARATE PERMITS, PLANS AND FEES WILL BE REQUIRED FOR | | | THE FOLLOWING: | | | LIGHT POLES/SITE LIGHTING | | | FIRE ALARM | | | FIRE SPRINKLER | | | LOW VOLTAGE | | | ACCESS | | | LANDSCAPING | | | IRRIGATION | | | PARKING LOT | | | DUMPSTER ENCLOSURE | | | SITE WALLS | | | ALL OTHER ITEMS OTHER THAN BMEP | | | | | | 7) NOTE: A SEPARATE SUB-PERMIT IS REQUIRED FOR ROOFING. | | | | | | 8) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A | | | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE | | | CITY RE-SUBMITTAL FORM. | | | | | | 9) [PREVIOUS COMMENT #23.] NOT COMPLIED. [SEE THE | | | MARKUP CLOUDS AT MISSING PRESSURES ON PAGES 096-S200 | | | AND 097-S201. ALSO SEE THE MARKUPS ON PAGE 100-S204 | | | GRIDLINES 1 AND 6 WHICH ARE EXTERIOR WALL ELEVATIONS.] | | | NEW COMMENT: SOME OF THE COMPONENT AND CLADDING | | | PRESSURES AND NEGATIVE SIGNS ARE MISSING FROM THE | | | ELEVATIONS ON THE STRUCTURAL DRAWINGS. FBC 107.2.1 & | | | 1609 | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2021-03-08 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2021-03-08 |
Time |
09:55 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2021-03-05 |
Time |
08:50 |
Sent To |
|
|
| Notes |
| 2021-03-05 11:27:49 | PLAN | | | REVIEW COMMENTS | | | | | | 3RD REVIEW | | | FBC SIXTH EDITION (2017) & CITY OF W.P.B. CHAPTER 1 | | | AMENDMENTS | | | CITY ORDINANCES | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | NEW 4 STORY HOTEL | | | TYPE II-B CONSTRUCTION | | | R-1 OCCUPANCY TYPE | | | FLOOD ZONE AE, BFE 12.7' NAVD88 (DFE 14.7' NAVD 88 | | | INCLUDES 2' FREEBOARD) | | | | | | NOTE: THE NUMBERING IS OFF ON THE RESPONSES STARTING AT | | | NUMBER 17. THE RESPONSE FOR #17 IS ACTUALLY FOR COMMENT | | | # 18 AND SO ON. | | | | | | 1) COMPLIED. | | | | | | 2) NOT COMPLIED. [PRECONSTRUCTION ELEVATION CERTIFICATE | | | WAS NOT SUBMITTED.] (THE PERMIT CAN NOT BE ISSUED UNTIL | | | A PRE-CONSTRUCTION ELEVATION CERTIFICATE HAS BEEN | | | SUBMITTED AND APPROVED.) THIS PROJECT IS LOCATED IN A | | | SPECIAL FLOOD HAZARD AREA (AE FLOOD ZONE). SEE NFIP | | | REVIEW COMMENTS. | | | | | | 3) NOT COMPLIED. [SEE ENGINEERING COMMENT THAT STATES | | | SITE PLAN HAS NOT BEEN APPROVED](THE PERMIT CAN NOT BE | | | ISSUED UNTIL MINOR LOT SUBDIVISION HAS BEEN APPROVED.) | | | THE SITE PLAN SHOWS A PROPERTY LINE THAT IS PART OF | | | ANOTHER PARCEL ON THE PALM BEACH COUNTY PROPERTY | | | APPRAISER'S WEB SITE. PROVIDE A COPY OF THE RECORDED | | | PLAT FOR THIS LOT DIVISION. FBC 107.2 | | | | | | 4) NOT COMPLIED. [THE REQUESTED DETAILED SITE PLAN | | | NEEDS TO BE SUBMITTED WITH THE DOCUMENTS FOR THIS | | | PERMIT.] (NO DETAILED SITE PLAN WITH REQUESTED | | | INFORMATION WAS SUBMITTED. ALL ELEVATIONS ARE REQUIRED | | | TO BE IN NAVD 88.) FBC 107.2.5 SITE PLAN. THE | | | CONSTRUCTION DOCUMENTS SUBMITTED WITH THE APPLICATION | | | FOR PERMIT SHALL BE ACCOMPANIED BY A SITE PLAN SHOWING | | | TO SCALE THE SIZE AND LOCATION OF NEW CONSTRUCTION AND | | | EXISTING STRUCTURES ON THE SITE, DISTANCES FROM LOT | | | LINES, THE ESTABLISHED STREET GRADES AND THE PROPOSED | | | FINISHED GRADES AND, AS APPLICABLE, FLOOD HAZARD AREAS, | | | FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT SHALL BE | | | DRAWN IN ACCORDANCE WITH AN ACCURATE BOUNDARY LINE | | | SURVEY. PROVIDE SITE PLAN WITH ELEVATIONS OF THE | | | BUILDING, PARKING LOT, ACCESSIBLE PARKING, ACCESSIBLE | | | ROUTES, ETC. | | | | | | 5) NOT COMPLIED. [ENGINEERING HAS NOT APPROVED THE SITE | | | PLAN.] (NO CIVIL PLANS WERE SUBMITTED.) SHOW COMPLIANCE | | | WITH FBC 110.9 IMPACT OF CONSTRUCTION. ALL CONSTRUCTION | | | ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A | | | MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF | | | ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO | | | AFFECT SAID PROPERTY PURSUANT TO A CONSENT GRANTED BY | | | THE APPLICABLE PROPERTY OWNER, UNDER TERMS OR | | | CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY OWNER. | | | THIS INCLUDES, BUT IS NOT LIMITED TO, THE CONTROL OF | | | DUST, NOISE, WATER OR DRAINAGE RUN-OFFS, DEBRIS, AND | | | THE STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION | | | ACTIVITY SHALL NOT ADVERSELY IMPACT LEGAL HISTORIC | | | SURFACE WATER DRAINAGE FLOWS SERVING ADJACENT | | | PROPERTIES, AND MAY REQUIRE SPECIAL DRAINAGE DESIGN | | | COMPLYING WITH ENGINEERING STANDARDS TO PRESERVE THE | | | POSITIVE DRAINAGE PATTERNS OF THE AFFECTED SITES. | | | ACCORDINGLY, DEVELOPERS, CONTRACTORS AND OWNERS OF ALL | | | NEW RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, | | | POOLS, PATIOS, DRIVEWAYS, DECKS OR SIMILAR ITEMS, ON | | | EXISTING PROPERTIES RESULTING IN A SIGNIFICANT DECREASE | | | OF PERMEABLE LAND AREA ON ANY PARCEL OR HAS ALTERED THE | | | DRAINAGE FLOW ON THE DEVELOPED PROPERTY SHALL, AS A | | | PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED | | | DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS | | | PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A | | | CERTIFICATION FROM A LICENSED PROFESSIONAL SHALL BE | | | SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL | | | OF THE FINAL INSPECTION. | | | | | | 6) NOT COMPLIED. [BARRIER AND MOT PLANS STILL HAVE NOT | | | BEEN SUBMITTED.](NO PLANS FOR THIS HAS BEEN SUBMITTED.) | | | SHOW COMPLIANCE WITH FBC CHAPTER 33 FOR SAFEGUARDS | | | DURING CONSTRUCTION. SUBMIT BARRIER AND MOT PLANS. | | | | | | 7) COMPLIED. | | | | | | 8) COMPLIED. | | | | | | 9) COMPLIED. | | | | | | 10) COMPLIED. | | | | | | 11) NOT COMPLIED. [THE REQUEST TO DEFER PRODUCT | | | APPROVALS IS NOT CLEAR. THE REQUEST FOR THE PRODUCT | | | APPROVALS AND OTHER ITEMS TO BE DEFERRED IS REQUIRED TO | | | BE ON THE PLANS WITH THE ITEMS LISTED OR THEY WILL NEED | | | TO BE SUBMITTED AND APPROVED BEFORE THE PERMIT IS | | | ISSUED.] (PRODUCT APPROVALS TO BE DEFERRED. THERE IS A | | | LIST OF PRODUCT APPROVALS ON SHEET A011.) THE CITY | | | AMENDMENTS REQUIRES THAT PRODUCT APPROVALS ARE TO BE | | | SUBMITTED FOR APPROVAL AFTER THEY HAVE BEEN REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR | | | THE PROJECT. FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT | | | APPROVALS FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC | | | 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE | | | BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER | | | OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH | | | FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS | | | AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT | | | ROOFING MATERIALS, WINDOWS (GLASS TYPES), STRUCTURAL | | | MULLIONS, STORE FRONTS, EXTERIOR DOORS, ETC. THESE | | | ITEMS CAN BE DEFERRED IF REQUESTED, HOWEVER, THE | | | DOCUMENTS MUST BE SUBMITTED AND APPROVED BY THE | | | BUILDING DEPARTMENT BEFORE THEY CAN BE INSTALLED. ONLY | | | ONE SET IS REQUIRED TO BE UPLOADED FOR ELECTRONICALLY | | | SUBMITTED DOCUMENTS. | | | FBC 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF | | | THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE | | | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE | | | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO | | | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. | | | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR | | | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED | | | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST | | | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS | | | FOR REVIEW BY THE BUILDING OFFICIAL. THE REGISTERED | | | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST | | | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS | | | FOR REVIEW BY THE BUILDING OFFICIAL. SHOP DRAWINGS AND | | | CALCULATIONS FROM DELEGATE ENGINEERS SHOULD BE INCLUDED | | | ON THE LIST. | | | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE | | | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN | | | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD | | | THEM TO THE BUILDING OFFICIAL WITH A NOTATION | | | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE | | | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO | | | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL | | | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED | | | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING | | | OFFICIAL. | | | | | | 12) NOT COMPLIED. [THIS IS REQUIRED TO BE ON DOCUMENTS | | | FOR THIS PERMIT.] (ELEVATIONS TO BE IN NAVD 88.) | | | PROVIDE THE FLOOR ELEVATIONS ON THE FLOOR PLAN OF THE | | | GROUND FLOOR, THE BUILDING ELEVATIONS AND BUILDING | | | SECTIONS. FBC 107.2 | | | | | | 13) PROVISO. NOTED ON THE PLANS. | | | SEPARATE PERMITS, PLANS AND FEES WILL BE REQUIRED FOR | | | THE FOLLOWING: | | | LIGHT POLES/SITE LIGHTING | | | FIRE ALARM | | | FIRE SPRINKLER | | | LOW VOLTAGE | | | ACCESS | | | LANDSCAPING | | | IRRIGATION | | | PARKING LOT | | | DUMPSTER ENCLOSURE | | | SITE WALLS | | | ALL OTHER ITEMS OTHER THAN BMEP | | | | | | 14) PROVISO. PRODUCT APPROVALS FOR THE ROOFING | | | MATERIALS TO BE APPROVED BY THE DESIGNER OF RECORD, | | | SUBMITTED AND APPROVED BY THE BUILDING DEPARTMENT | | | BEFORE THE ROOFING PERMIT IS ISSUED. A SEPARATE SUB- | | | PERMIT AND APPLICATION IS REQUIRED FOR ROOFING. | | | | | | 15) COMPLIED. | | | | | | 16) COMPLIED. | | | | | | 17) COMPLIED. | | | | | | 18) NOT COMPLIED. [NONE OF THE REQUESTED INFORMATION | | | HAS BEEN PROVIDED FOR THIS PERMIT.] (SHEET A100, THE | | | SITE PLAN, REFERS TO CIVIL DRAWINGS WHICH WERE NOT | | | SUBMITTED WITH THE CONSTRUCTION DOCUMENTS FOR REQUIRED | | | PARKING INFORMATION. THE FINISH FLOOR ELEVATION IS | | | SPECIFIED AS 15.0 BUT THE VERTICAL DATA IS NOT | | | SPECIFIED. PLEASE USE NAVD 88.) PROVIDE A PARKING LOT | | | PLAN THAT SHOWS THE TOTAL NUMBER OF PARKING SPACES, THE | | | TOTAL NUMBER OF REQUIRED AND PROVIDED ACCESSIBLE | | | SPACES, THE ACCESSIBLE VAN PARKING SPACES AND THE | | | LOCATIONS OF THE ACCESSIBLE PARKING SPACES. FBC | | | ACCESSIBILITY SECTIONS 208 & 502 | | | | | | 19) NOT COMPLIED. [AGAIN. THE REQUESTED INFORMATION | | | NEEDS TO BE WITH THE DOCUMENTS FOR THIS PERMIT.] SHOW | | | THAT THE PASSENGER LOADING ZONE COMPLIES WITH FBC | | | SECTIONS 209 & 503. | | | | | | 20) NOT COMPLIED. [ THIS NEEDS TO BE SHOWN ON THE | | | DRAWINGS. TYPICALLY THE STRETCHER IS DRAWN INTO THE | | | ELEVATOR ON THE PLANS WITH THE DIMENSIONS PROVIDED.] | | | SHOW COMPLIANCE WITH 3002.4 ELEVATOR CAR TO ACCOMMODATE | | | AMBULANCE STRETCHER. ANY BUILDING THAT IS MORE THAN | | | THREE STORIES HIGH OR IN WHICH THE VERTICAL DISTANCE | | | BETWEEN THE BOTTOM TERMINAL LANDING AND THE TOP | | | TERMINAL LANDING EXCEEDS 25 FEET (7620 MM), MUST BE | | | CONSTRUCTED TO CONTAIN AT LEAST ONE PASSENGER ELEVATOR | | | THAT IS OPERATIONAL FOR BUILDING OCCUPANTS AND FIRE | | | DEPARTMENT EMERGENCY ACCESS TO ALL FLOORS. THE ELEVATOR | | | CAR SHALL BE OF SUCH A SIZE AND ARRANGEMENT TO | | | ACCOMMODATE AN AMBULANCE STRETCHER 24 INCHES BY 76 | | | INCHES (610 MM BY 1950 MM) WITH NOT LESS THAN 5-INCH | | | (127 MM) RADIUS CORNERS, IN THE HORIZONTAL, OPEN | | | POSITION AND SHALL BE IDENTIFIED BY THE INTERNATIONAL | | | SYMBOL FOR EMERGENCY MEDICAL SERVICES (STAR OF LIFE). | | | THE SYMBOL SHALL BE NOT LESS THAN 3 INCHES (76 MM) IN | | | HEIGHT AND SHALL BE PLACED INSIDE ON BOTH SIDES OF THE | | | HOISTWAY DOOR FRAME. | | | | | | 21) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A | | | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE | | | CITY RE-SUBMITTAL FORM. | | | | | | NEW COMMENTS FROM PREVIOUS REVIEW: | | | | | | 22) COMPLIED. | | | | | | 23) NOT COMPLIED. [SEE THE MARKUP CLOUDS AT MISSING | | | PRESSURES ON PAGES 096-S200 AND 097-S201. ALSO SEE THE | | | MARKUPS ON PAGE 100-S204 GRIDLINES 1 AND 6 WHICH ARE | | | EXTERIOR WALL ELEVATIONS.] NEW COMMENT: SOME OF THE | | | COMPONENT AND CLADDING PRESSURES AND NEGATIVE SIGNS ARE | | | MISSING FROM THE ELEVATIONS ON THE STRUCTURAL DRAWINGS. | | | FBC 107.2.1 & 1609 | | | | | | 24) COMPLIED. | | | | | | 25) COMPLIED. | | | | | | 26 ) COMPLIED. | | | | | | 27) NOT COMPLIED. [THE SIZE OF THE ROOF HATCH IS NOT | | | SPECIFIED ON SHEETS A550 OR A011. THE RESPONSE COMMENT | | | SPECIFIES A 30" X 54" ROOF ACCESS HATCH. THESE | | | DIMENSIONS PROVIDE 11.25 SQFT AND DO NOT MEET THE | | | REQUIRED MINIMUM SIZE OF 16 SQFT.] NEW COMMENT. I DID | | | NOT SEE THAT THE SIZE OF THE ROOF HATCH IS SPECIFIED ON | | | THE DRAWINGS. THE MINIMUM SIZE IS 16 SQFT WITH THE | | | SMALLEST DIMENSION NOT LESS THAN 2 FT. PER | | | FBC1011.12.2. IF THE ROOF HATCH IS WITHIN 10 FT OF THE | | | ROOF EDGE A GUARD IS REQUIRED PER FBC1011.13 INSTALLED | | | IN ACCORDANCE WITH FBC1015. | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2020-12-22 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2020-12-22 |
Time |
10:13 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2020-12-21 |
Time |
07:23 |
Sent To |
|
|
| Notes |
| 2020-12-21 10:03:43 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW | | | FBC SIXTH EDITION (2017) & CITY OF W.P.B. CHAPTER 1 | | | AMENDMENTS | | | CITY ORDINANCES | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | NEW 4 STORY HOTEL | | | TYPE II-B CONSTRUCTION | | | R-1 OCCUPANCY TYPE | | | FLOOD ZONE AE, BFE 12.7' NAVD88 (DFE 14.7' NAVD 88 | | | INCLUDES 2' FREEBOARD) | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) COMPLIED. THE PLANS ARE NOW IN COMPLIANCE. SEE | | | THRESHOLD REVIEW FOR ADDITIONAL REQUIREMENTS. | | | | | | 2) NOT COMPLIED. (THE PERMIT CAN NOT BE ISSUED UNTIL A | | | PRE-CONSTRUCTION ELEVATION CERTIFICATE HAS BEEN | | | SUBMITTED AND APPROVED.) THIS PROJECT IS LOCATED IN A | | | SPECIAL FLOOD HAZARD AREA (AE FLOOD ZONE). SEE NFIP | | | REVIEW COMMENTS. | | | | | | 3) NOT COMPLIED. (THE PERMIT CAN NOT BE ISSUED UNTIL | | | MINOR LOT SUBDIVISION HAS BEEN APPROVED.) THE SITE PLAN | | | SHOWS A PROPERTY LINE THAT IS PART OF ANOTHER PARCEL ON | | | THE PALM BEACH COUNTY PROPERTY APPRAISER'S WEB SITE. | | | PROVIDE A COPY OF THE RECORDED PLAT FOR THIS LOT | | | DIVISION. FBC 107.2 | | | | | | 4) NOT COMPLIED. (NO DETAILED SITE PLAN WITH REQUESTED | | | INFORMATION WAS SUBMITTED. ALL ELEVATIONS ARE REQUIRED | | | TO BE IN NAVD 88.) FBC 107.2.5 SITE PLAN. THE | | | CONSTRUCTION DOCUMENTS SUBMITTED WITH THE APPLICATION | | | FOR PERMIT SHALL BE ACCOMPANIED BY A SITE PLAN SHOWING | | | TO SCALE THE SIZE AND LOCATION OF NEW CONSTRUCTION AND | | | EXISTING STRUCTURES ON THE SITE, DISTANCES FROM LOT | | | LINES, THE ESTABLISHED STREET GRADES AND THE PROPOSED | | | FINISHED GRADES AND, AS APPLICABLE, FLOOD HAZARD AREAS, | | | FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT SHALL BE | | | DRAWN IN ACCORDANCE WITH AN ACCURATE BOUNDARY LINE | | | SURVEY. PROVIDE SITE PLAN WITH ELEVATIONS OF THE | | | BUILDING, PARKING LOT, ACCESSIBLE PARKING, ACCESSIBLE | | | ROUTES, ETC. | | | | | | 5) NOT COMPLIED. (NO CIVIL PLANS WERE SUBMITTED.) SHOW | | | COMPLIANCE WITH FBC 110.9 IMPACT OF CONSTRUCTION. ALL | | | CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL BE | | | PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT THE | | | CONDITION OF ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS | | | PERMITTED TO AFFECT SAID PROPERTY PURSUANT TO A CONSENT | | | GRANTED BY THE APPLICABLE PROPERTY OWNER, UNDER TERMS | | | OR CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY | | | OWNER. THIS INCLUDES, BUT IS NOT LIMITED TO, THE | | | CONTROL OF DUST, NOISE, WATER OR DRAINAGE RUN-OFFS, | | | DEBRIS, AND THE STORAGE OF CONSTRUCTION MATERIALS. NEW | | | CONSTRUCTION ACTIVITY SHALL NOT ADVERSELY IMPACT LEGAL | | | HISTORIC SURFACE WATER DRAINAGE FLOWS SERVING ADJACENT | | | PROPERTIES, AND MAY REQUIRE SPECIAL DRAINAGE DESIGN | | | COMPLYING WITH ENGINEERING STANDARDS TO PRESERVE THE | | | POSITIVE DRAINAGE PATTERNS OF THE AFFECTED SITES. | | | ACCORDINGLY, DEVELOPERS, CONTRACTORS AND OWNERS OF ALL | | | NEW RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, | | | POOLS, PATIOS, DRIVEWAYS, DECKS OR SIMILAR ITEMS, ON | | | EXISTING PROPERTIES RESULTING IN A SIGNIFICANT DECREASE | | | OF PERMEABLE LAND AREA ON ANY PARCEL OR HAS ALTERED THE | | | DRAINAGE FLOW ON THE DEVELOPED PROPERTY SHALL, AS A | | | PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED | | | DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS | | | PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A | | | CERTIFICATION FROM A LICENSED PROFESSIONAL SHALL BE | | | SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL | | | OF THE FINAL INSPECTION. | | | | | | 6) NOT COMPLIED. (NO PLANS FOR THIS HAS BEEN | | | SUBMITTED.) SHOW COMPLIANCE WITH FBC CHAPTER 33 FOR | | | SAFEGUARDS DURING CONSTRUCTION. SUBMIT BARRIER AND MOT | | | PLANS. | | | | | | 7) COMPLIED. SIGNED AND SEALED GEOTECHNICAL | | | INVESTIGATION THAT SPECIFIES THE ALLOWABLE SOIL BEARING | | | PRESSURE WAS SUBMITTED. | | | | | | 8) COMPLIED. CORRECTED THE LABEL TO TYPICAL FOR LEVELS | | | 2-4. | | | | | | 9) COMPLIED. THE LIFE SAFETY PLANS WERE REVISED. | | | | | | 10) COMPLIED PROVIDED A LIFE SAFETY PLAN FOR THE ROOF. | | | | | | 11) PROVISO. (PRODUCT APPROVALS TO BE DEFERRED. THERE | | | IS A LIST OF PRODUCT APPROVALS ON SHEET A011.) THE CITY | | | AMENDMENTS REQUIRES THAT PRODUCT APPROVALS ARE TO BE | | | SUBMITTED FOR APPROVAL AFTER THEY HAVE BEEN REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR | | | THE PROJECT. FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT | | | APPROVALS FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC | | | 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE | | | BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER | | | OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH | | | FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS | | | AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT | | | ROOFING MATERIALS, WINDOWS (GLASS TYPES), STRUCTURAL | | | MULLIONS, STORE FRONTS, EXTERIOR DOORS, ETC. THESE | | | ITEMS CAN BE DEFERRED IF REQUESTED, HOWEVER, THE | | | DOCUMENTS MUST BE SUBMITTED AND APPROVED BY THE | | | BUILDING DEPARTMENT BEFORE THEY CAN BE INSTALLED. ONLY | | | ONE SET IS REQUIRED TO BE UPLOADED FOR ELECTRONICALLY | | | SUBMITTED DOCUMENTS. | | | FBC 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF | | | THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE | | | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE | | | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO | | | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. | | | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR | | | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED | | | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST | | | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS | | | FOR REVIEW BY THE BUILDING OFFICIAL. THE REGISTERED | | | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST | | | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS | | | FOR REVIEW BY THE BUILDING OFFICIAL. SHOP DRAWINGS AND | | | CALCULATIONS FROM DELEGATE ENGINEERS SHOULD BE INCLUDED | | | ON THE LIST. | | | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE | | | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN | | | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD | | | THEM TO THE BUILDING OFFICIAL WITH A NOTATION | | | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE | | | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO | | | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL | | | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED | | | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING | | | OFFICIAL. | | | | | | 12) NOT COMPLIED. (ELEVATIONS TO BE IN NAVD 88.) | | | PROVIDE THE FLOOR ELEVATIONS ON THE FLOOR PLAN OF THE | | | GROUND FLOOR, THE BUILDING ELEVATIONS AND BUILDING | | | SECTIONS. FBC 107.2 | | | | | | 13) PROVISO. NOTED ON THE PLANS. | | | SEPARATE PERMITS, PLANS AND FEES WILL BE REQUIRED FOR | | | THE FOLLOWING: | | | LIGHT POLES/SITE LIGHTING | | | FIRE ALARM | | | FIRE SPRINKLER | | | LOW VOLTAGE | | | ACCESS | | | LANDSCAPING | | | IRRIGATION | | | PARKING LOT | | | DUMPSTER ENCLOSURE | | | SITE WALLS | | | ALL OTHER ITEMS OTHER THAN BMEP | | | | | | 14) PROVISO. PRODUCT APPROVALS FOR THE ROOFING | | | MATERIALS TO BE APPROVED BY THE DESIGNER OF RECORD, | | | SUBMITTED AND APPROVED BY THE BUILDING DEPARTMENT | | | BEFORE THE ROOFING PERMIT IS ISSUED. A SEPARATE PERMIT | | | AND APPLICATION IS REQUIRED FOR ROOFING. | | | | | | 15) COMPLIED. HANDRAIL EXTENSIONS CORRECTED. | | | | | | 16) COMPLIED. STAIR LABELS CORRECTED. | | | | | | 17) NOT COMPLIED. (THE FLOOR PLANS ONLY SHOW A TOTAL OF | | | (5) MOBILITY ACCESSIBLE ROOMS AND (7) ARE REQUIRED. | | | SOME OF THE ACCESSIBLE ROOMS SPECIFIED IN THE ROOM | | | MATRIX ON SHEET A010, DO NOT HAVE THE ACCESSIBILITY | | | SYMBOL ON THE FLOOR PLANS.) PROVIDE A ROOM MATRIX THAT | | | SHOWS THE ROOM TYPES PER FLOOR, THE TOTAL NUMBER OF | | | ROOMS PER FLOOR, THE TOTAL NUMBER OF ROOMS (112), THE | | | NUMBER OF EACH TYPE OF MOBILITY ACCESSIBLE ROOMS PER | | | FLOOR, THE NUMBER OF ROOMS WITH COMMUNICATION FEATURES | | | PER FLOOR, THE TOTAL NUMBER OF EACH TYPE OF MOBILITY | | | ACCESSIBLE ROOMS REQUIRED (7) (2 WITH ROLL IN SHOWERS) | | | AND THE NUMBER OF EACH TYPE PROVIDED, THE TOTAL OF | | | ROOMS WITH COMMUNICATION FEATURES REQUIRED (12) AND THE | | | TOTAL PROVIDED. FBC ACCESSIBILITY SECTIONS 224.2 AND | | | 224.4 | | | | | | 18) NOT COMPLIED. (SHEET A100, THE SITE PLAN, REFERS TO | | | CIVIL DRAWINGS WHICH WERE NOT SUBMITTED WITH THE | | | CONSTRUCTION DOCUMENTS FOR REQUIRED PARKING | | | INFORMATION. THE FINISH FLOOR ELEVATION IS SPECIFIED AS | | | 15.0 BUT THE VERTICAL DATA IS NOT SPECIFIED. PLEASE USE | | | NAVD 88.) PROVIDE A PARKING LOT PLAN THAT SHOWS THE | | | TOTAL NUMBER OF PARKING SPACES, THE TOTAL NUMBER OF | | | REQUIRED AND PROVIDED ACCESSIBLE SPACES, THE ACCESSIBLE | | | VAN PARKING SPACES AND THE LOCATIONS OF THE ACCESSIBLE | | | PARKING SPACES. FBC ACCESSIBILITY SECTIONS 208 & 502 | | | | | | 19) NOT COMPLIED. SHOW THAT THE PASSENGER LOADING ZONE | | | COMPLIES WITH FBC SECTIONS 209 & 503. | | | | | | 20) NOT COMPLIED. SHOW COMPLIANCE WITH 3002.4 ELEVATOR | | | CAR TO ACCOMMODATE AMBULANCE STRETCHER. ANY BUILDING | | | THAT IS MORE THAN THREE STORIES HIGH OR IN WHICH THE | | | VERTICAL DISTANCE BETWEEN THE BOTTOM TERMINAL LANDING | | | AND THE TOP TERMINAL LANDING EXCEEDS 25 FEET (7620 MM), | | | MUST BE CONSTRUCTED TO CONTAIN AT LEAST ONE PASSENGER | | | ELEVATOR THAT IS OPERATIONAL FOR BUILDING OCCUPANTS AND | | | FIRE DEPARTMENT EMERGENCY ACCESS TO ALL FLOORS. THE | | | ELEVATOR CAR SHALL BE OF SUCH A SIZE AND ARRANGEMENT TO | | | ACCOMMODATE AN AMBULANCE STRETCHER 24 INCHES BY 76 | | | INCHES (610 MM BY 1950 MM) WITH NOT LESS THAN 5-INCH | | | (127 MM) RADIUS CORNERS, IN THE HORIZONTAL, OPEN | | | POSITION AND SHALL BE IDENTIFIED BY THE INTERNATIONAL | | | SYMBOL FOR EMERGENCY MEDICAL SERVICES (STAR OF LIFE). | | | THE SYMBOL SHALL BE NOT LESS THAN 3 INCHES (76 MM) IN | | | HEIGHT AND SHALL BE PLACED INSIDE ON BOTH SIDES OF THE | | | HOISTWAY DOOR FRAME. | | | | | | 21) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A | | | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE | | | CITY RE-SUBMITTAL FORM. | | | | | | 22) NEW COMMENT: PLEASE PROVIDE AN ITEMIZED COST | | | BREAKDOWN FOR THIS PROJECT. THIS WILL ALLOW US TO BACK | | | OUT THE ITEMS THAT REQUIRE SEPARATE PERMITS AND FEES, | | | SUCH AS FIRE SPRINKLERS. THIS WAY YOU WILL NOT BE | | | PAYING DOUBLE FOR THE SAME ITEMS. FBC 109 | | | | | | 23) NEW COMMENT: SOME OF THE COMPONENT AND CLADDING | | | PRESSURES AND NEGATIVE SIGNS ARE MISSING FROM THE | | | ELEVATIONS ON THE STRUCTURAL DRAWINGS. FBC 107.2.1 & | | | 1609 | | | | | | 24) NEW COMMENT: THE WINDLOAD TABULATION FOR THE WALL | | | COMPONENT AND CLADDING PRESSURES ON SHEET S001 DO NOT | | | SPECIFY IF THEY ARE VULT OR ASD. FBC 1609 | | | | | | 25) THERE IS A NOTE ON THE STRUCTURAL ELEVATIONS THAT | | | STATES SEE S200 AND S003 FOR WIND NOTES AND CRITERIA. | | | SHEET S003 HAS THE THRESHOLD INSPECTION PLAN, I DO NOT | | | SEE ANY WINDLOAD INFORMATION. FBC 1609 | | | | | | 26 ) NEW COMMENT. THE ROOF ZONES 1, 2 AND 3 DO NOT | | | APPEAR TO HAVE BEEN SPECIFIED ON THE STRUCTURAL | | | DRAWINGS AND THE COMPONENT AND CLADDING PRESSURES FOR | | | THESE ROOF ZONES HAVE NOT BEEN PROVIDED. FBC 1609 | | | | | | 27) NEW COMMENT. I DID NOT SEE THAT THE SIZE OF THE | | | ROOF HATCH IS SPECIFIED ON THE DRAWINGS. THE MINIMUM | | | SIZE IS 16 SQFT WITH THE SMALLEST DIMENSION NOT LESS | | | THAN 2 FT. PER FBC1011.12.2. IF THE ROOF HATCH IS | | | WITHIN 10 FT OF THE ROOF EDGE A GUARD IS REQUIRED PER | | | FBC1011.13 INSTALLED IN ACCORDANCE WITH FBC1015. | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2020-11-03 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2020-11-03 |
Time |
10:03 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2020-10-30 |
Time |
13:00 |
Sent To |
|
|
| Notes |
| 2020-11-02 08:37:11 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | NEW 4 STORY HOTEL | | | TYPE II-B CONSTRUCTION | | | R-1 OCCUPANCY TYPE | | | FLOOD ZONE AE, BFE 12.7' NAVD88 (DFE 14.7' NAVD 88 | | | INCLUDES 2' FREEBOARD) | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THIS IS A THRESHOLD BUILDING. THE THRESHOLD | | | INSPECTION STATEMENT IS REQUIRED ON THE PLANS. A | | | THRESHOLD INSPECTION PLAN IS REQUIRED TO BE ON THE | | | PLANS. SEE THE THRESHOLD REVIEW COMMENTS. | | | | | | 2) THIS PROJECT IS LOCATED IN A SPECIAL FLOOD HAZARD | | | AREA (AE FLOOD ZONE). SEE NFIP REVIEW COMMENTS. | | | | | | 3) THE SITE PLAN SHOWS A PROPERTY LINE THAT IS PART OF | | | ANOTHER PARCEL ON THE PALM BEACH COUNTY PROPERTY | | | APPRAISER'S WEB SITE. PROVIDE A COPY OF THE RECORDED | | | PLAT FOR THIS LOT DIVISION. FBC 107.2 | | | | | | 4) FBC 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS | | | SUBMITTED WITH THE APPLICATION FOR PERMIT SHALL BE | | | ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE THE SIZE | | | AND LOCATION OF NEW CONSTRUCTION AND EXISTING | | | STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE | | | ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED | | | GRADES AND, AS APPLICABLE, FLOOD HAZARD AREAS, | | | FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT SHALL BE | | | DRAWN IN ACCORDANCE WITH AN ACCURATE BOUNDARY LINE | | | SURVEY. PROVIDE SITE PLAN WITH ELEVATIONS OF THE | | | BUILDING, PARKING LOT, ACCESSIBLE PARKING, ACCESSIBLE | | | ROUTES, ETC. | | | | | | 5) SHOW COMPLIANCE WITH FBC 110.9 IMPACT OF | | | CONSTRUCTION. ALL CONSTRUCTION ACTIVITY REGULATED BY | | | THIS CODE SHALL BE PERFORMED IN A MANNER SO AS NOT TO | | | ADVERSELY IMPACT THE CONDITION OF ADJACENT PROPERTY, | | | UNLESS SUCH ACTIVITY IS PERMITTED TO AFFECT SAID | | | PROPERTY PURSUANT TO A CONSENT GRANTED BY THE | | | APPLICABLE PROPERTY OWNER, UNDER TERMS OR CONDITIONS | | | AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS | | | INCLUDES, BUT IS NOT LIMITED TO, THE CONTROL OF DUST, | | | NOISE, WATER OR DRAINAGE RUN-OFFS, DEBRIS, AND THE | | | STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION | | | ACTIVITY SHALL NOT ADVERSELY IMPACT LEGAL HISTORIC | | | SURFACE WATER DRAINAGE FLOWS SERVING ADJACENT | | | PROPERTIES, AND MAY REQUIRE SPECIAL DRAINAGE DESIGN | | | COMPLYING WITH ENGINEERING STANDARDS TO PRESERVE THE | | | POSITIVE DRAINAGE PATTERNS OF THE AFFECTED SITES. | | | ACCORDINGLY, DEVELOPERS, CONTRACTORS AND OWNERS OF ALL | | | NEW RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, | | | POOLS, PATIOS, DRIVEWAYS, DECKS OR SIMILAR ITEMS, ON | | | EXISTING PROPERTIES RESULTING IN A SIGNIFICANT DECREASE | | | OF PERMEABLE LAND AREA ON ANY PARCEL OR HAS ALTERED THE | | | DRAINAGE FLOW ON THE DEVELOPED PROPERTY SHALL, AS A | | | PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED | | | DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS | | | PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A | | | CERTIFICATION FROM A LICENSED PROFESSIONAL SHALL BE | | | SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL | | | OF THE FINAL INSPECTION. | | | | | | 6) SHOW COMPLIANCE WITH FBC CHAPTER 33 FOR SAFEGUARDS | | | DURING CONSTRUCTION. SUBMIT BARRIER AND MOT PLANS. | | | | | | 7) SUBMIT A SIGNED AND SEALED GEOTECHNICAL | | | INVESTIGATION THAT SPECIFIES THE ALLOWABLE SOIL BEARING | | | PRESSURE PER FBC SECTION 1803. | | | | | | 8) THE LIFE SAFETY PLANS ON SHEET A032 ARE LABELED | | | TYPICAL LEVEL. IT APPEARS THAT THIS IS MEANT TO BE | | | TYPICAL FOR LEVELS 2-4. TO AVOID ANY CONFUSION, PLEASE | | | CHANGE LABEL TO SHOW THE LEVELS TO WHICH IT APPLIES. | | | FBC 107.2 | | | | | | 9) THE LIFE SAFETY PLANS ARE MISSING INFORMATION. | | | PLEASE INCLUDE THE FOLLOWING ON THE LIFE SAFETY PLANS. | | | THE LIFE SAFETY PLANS NEED TO SHOW THE FOLLOWING: | | | A) NUMBER OF OCCUPANTS IN EACH AREA FBC 1004.1 | | | B) CUMULATIVE OCCUPANT LOADS FBC 1004.1.1 | | | C) EXIT SEPARATION DISTANCE FBC 1015.2.1 | | | D) COMMON PATH OF EGRESS TRAVEL DISTANCE FBC 1014.3 | | | E) EXIT ACCESS TRAVEL DISTANCE FBC 1016.3 | | | F) CLEAR WIDTH OF THE EXIT OR EXIT ACCESS DOORS FBC | | | 1008.1.1 | | | G) CAPACITY OF EGRESS DOORS, OCCUPANT LOAD SERVED AND | | | MEANS OF EGRESS FACTOR FBC1005.3.2 | | | H) DISTRIBUTION OF EGRESS CAPACITY FBC1005.5 | | | | | | 10) PROVIDE A LIFE SAFETY PLAN FOR THE ROOF. FBC 107.2 | | | | | | 11) THERE IS A LIST OF PRODUCT APPROVALS ON SHEET A011. | | | THE CITY AMENDMENTS REQUIRES THAT PRODUCT APPROVALS ARE | | | TO BE SUBMITTED FOR APPROVAL AFTER THEY HAVE BEEN | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD FOR THE PROJECT. FBC 107.3.4 - PROVIDE TWO SETS | | | OF PRODUCT APPROVALS FOR THOSE PRODUCTS WHICH ARE | | | REGULATED BY FAC 61G20-3.001 PER FLORIDA STATUTE | | | 553.842 (5) THAT HAVE BEEN REVIEWED AND APPROVED IN | | | WRITING BY THE DESIGNER OF RECORD. PROVIDE TWO COMPLETE | | | PRODUCT APPROVALS WITH FL OR NOA NUMBERS INCLUDING | | | INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES | | | FOR EACH OF THE DIFFERENT ROOFING MATERIALS, WINDOWS | | | (GLASS TYPES), STRUCTURAL MULLIONS, STORE FRONTS, | | | EXTERIOR DOORS, ETC. THESE ITEMS CAN BE DEFERRED IF | | | REQUESTED, HOWEVER, THE DOCUMENTS MUST BE SUBMITTED AND | | | APPROVED BY THE BUILDING DEPARTMENT BEFORE THEY CAN BE | | | INSTALLED. ONLY ONE SET IS REQUIRED TO BE UPLOADED FOR | | | ELECTRONICALLY SUBMITTED DOCUMENTS. | | | FBC 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF | | | THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE | | | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE | | | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO | | | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. | | | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR | | | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED | | | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST | | | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS | | | FOR REVIEW BY THE BUILDING OFFICIAL. THE REGISTERED | | | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST | | | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS | | | FOR REVIEW BY THE BUILDING OFFICIAL. SHOP DRAWINGS AND | | | CALCULATIONS FROM DELEGATE ENGINEERS SHOULD BE INCLUDED | | | ON THE LIST. | | | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE | | | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN | | | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD | | | THEM TO THE BUILDING OFFICIAL WITH A NOTATION | | | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE | | | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO | | | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL | | | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED | | | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING | | | OFFICIAL. | | | | | | 12) PROVIDE THE FLOOR ELEVATIONS ON THE BUILDING | | | ELEVATIONS AND BUILDING SECTIONS. FBC 107.2 | | | | | | 13) SEPARATE PERMITS, PLANS AND FEES WILL BE REQUIRED | | | FOR THE FOLLOWING: | | | LIGHT POLES/SITE LIGHTING | | | FIRE ALARM | | | FIRE SPRINKLER | | | LOW VOLTAGE | | | ACCESS | | | LANDSCAPING | | | IRRIGATION | | | PARKING LOT | | | DUMPSTER ENCLOSURE | | | SITE WALLS | | | ALL OTHER ITEMS OTHER THAN BMEP | | | | | | 14) A SEPARATE PERMIT AND APPLICATION IS REQUIRED FOR | | | ROOFING. | | | | | | 15) THE STAIR SECTIONS ON SHEETS A-490 AND A-491 DO NOT | | | SHOW THE HANDRAIL EXTENSIONS AT THE BOTTOM THAT ARE | | | REQUIRED BY FBC ACCESSIBILITY SECTION 505.10.3 | | | | | | 16) THE STAIR SECTIONS ON SHEET A-491 ARE LABELED AS | | | STAIR 1 AND SHOULD BE LABELED STAIR 2. FBC 107.2 | | | | | | 17) PROVIDE A ROOM MATRIX THAT SHOWS THE ROOM TYPES PER | | | FLOOR, THE TOTAL NUMBER OF ROOMS PER FLOOR, THE TOTAL | | | NUMBER OF ROOMS (112), THE NUMBER OF EACH TYPE OF | | | MOBILITY ACCESSIBLE ROOMS PER FLOOR, THE NUMBER OF | | | ROOMS WITH COMMUNICATION FEATURES PER FLOOR, THE TOTAL | | | NUMBER OF EACH TYPE OF MOBILITY ACCESSIBLE ROOMS | | | REQUIRED (7) (2 WITH ROLL IN SHOWERS) AND THE NUMBER OF | | | EACH TYPE PROVIDED, THE TOTAL OF ROOMS WITH | | | COMMUNICATION FEATURES REQUIRED (12) AND THE TOTAL | | | PROVIDED. FBC ACCESSIBILITY SECTIONS 224.2 AND 224.4 | | | | | | 18) PROVIDE A PARKING LOT PLAN THAT SHOWS THE TOTAL | | | NUMBER OF PARKING SPACES, THE TOTAL NUMBER OF REQUIRED | | | AND PROVIDED ACCESSIBLE SPACES, THE ACCESSIBLE VAN | | | PARKING SPACES AND THE LOCATIONS OF THE ACCESSIBLE | | | PARKING SPACES. FBC ACCESSIBILITY SECTIONS 208 & 502 | | | | | | 19) SHOW THAT THE PASSENGER LOADING ZONE COMPLIES WITH | | | FBC SECTIONS 209 & 503. | | | | | | 20) SHOW COMPLIANCE WITH 3002.4 ELEVATOR CAR TO | | | ACCOMMODATE AMBULANCE STRETCHER. ANY BUILDING THAT IS | | | MORE THAN THREE STORIES HIGH OR IN WHICH THE VERTICAL | | | DISTANCE BETWEEN THE BOTTOM TERMINAL LANDING AND THE | | | TOP TERMINAL LANDING EXCEEDS 25 FEET (7620 MM), MUST BE | | | CONSTRUCTED TO CONTAIN AT LEAST ONE PASSENGER ELEVATOR | | | THAT IS OPERATIONAL FOR BUILDING OCCUPANTS AND FIRE | | | DEPARTMENT EMERGENCY ACCESS TO ALL FLOORS. THE ELEVATOR | | | CAR SHALL BE OF SUCH A SIZE AND ARRANGEMENT TO | | | ACCOMMODATE AN AMBULANCE STRETCHER 24 INCHES BY 76 | | | INCHES (610 MM BY 1950 MM) WITH NOT LESS THAN 5-INCH | | | (127 MM) RADIUS CORNERS, IN THE HORIZONTAL, OPEN | | | POSITION AND SHALL BE IDENTIFIED BY THE INTERNATIONAL | | | SYMBOL FOR EMERGENCY MEDICAL SERVICES (STAR OF LIFE). | | | THE SYMBOL SHALL BE NOT LESS THAN 3 INCHES (76 MM) IN | | | HEIGHT AND SHALL BE PLACED INSIDE ON BOTH SIDES OF THE | | | HOISTWAY DOOR FRAME. | | | | | | 21) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A | | | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE | | | CITY RE-SUBMITTAL FORM. | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2021-06-21 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-06-21 |
Time |
13:26 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-06-21 |
Time |
13:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2021-03-01 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-03-01 |
Time |
10:35 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-02-26 |
Time |
15:52 |
Sent To |
|
|
| Notes |
| 2021-03-01 10:38:27 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) PLEASE SHOW LOCATION OF FIRE PUMP. | | | | | | 2) PLEASE INDICATE THE SIZE OF THE FIRE PUMP. | | | | | | 3) PANEL EV FUTURE OR PART OF THIS PROJECT? | | | | | | 4) PANEL L WHAT IS IT FOR, SUBMIT A PANEL SCHEDULE FOR | | | THE PANEL. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2020-12-21 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-12-21 |
Time |
08:34 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-12-21 |
Time |
08:34 |
Sent To |
|
|
| Notes |
| 2020-12-21 08:37:05 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | ALL COMMENTS HAVE BEEN ADDRESSED BUT I NEED SOME | | | CLEARIFICATION ON THE FIRE PUMP PANEL. A SINGLE | | | DISCONNECTING DEVICE IS ALLOWED FOR FIRE PUMP CIRCUITS | | | EM PANEL AND THEN TO THE FIRE PUMP PANEL? | | | | | | (1) NUMBER OF DISCONNECTING MEANS. | | | (A) GENERAL. A SINGLE DISCONNECTI NG MEANS AND | | | ASSOCIATED OVERCURRENT PROTECTIVE DEVICE(S) SHALL BE | | | PERMITTED TO BE INSTALLED BETWEEN THE FIRE PUMP POWER | | | SOURCE(S) AND ONE OF THE FOLLOWING: [20:9.1.2] | | | (1) A LISTED FIRE PUMP CONTROLLER (2) A LISTED FIRE | | | PUMP POWER TRANSFER SWITCH (3) A LISTED COMBINATION | | | FIRE PUMP CONTROLLER AND P OWER TRANSFER SWITCH |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2020-11-02 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-11-02 |
Time |
06:52 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-10-30 |
Time |
12:54 |
Sent To |
|
|
| Notes |
| 2020-11-02 07:22:31 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | E-301 | | | | | | 1) GFCI RECEPTACLES HAVE DESIGNATIONS OF B, C, C, D, | | | AND E WHAT DO THEY STAND FOR? | | | | | | E-302 | | | | | | 1) QQ SUITE, QQ ACCESSIBLE, QQ ACCESSIBLE 2-BAY HAVE NO | | | USB OUTLETS NOT A CODE REQUIREMENT JUST AN OBSERVATION. | | | | | | E-401 | | | | | | 1) 3000A MAIN NEEDS TO COMPLY WTH 240.87, PLEASE | | | INDICATE HOW THIS WILL BE DONE. | | | | | | 2) FAULT CURRENT RATING OF THE SERVICE AND PANELS NEEDS | | | TO BE CALCULATED 110.9, 110,10 AND LABELS APPLIED PER | | | 110.24 | | | | | | 4) PANEL EM HAS THE FIRE PUMP AND ELEVATORS INSTALLED | | | IN IT, HOW DOES THIS MEET THE REQUIREMENTS OF 695.4(B), | | | AND 695.4 (B)(3)(A) & (B) | | | | | | NOTE | | | | | | THE FOLLOWING SYSTEMS REQUIRE SEPARATE PERMITS | | | LIGHTNING PROTECTION, BDA, FIRE ALARM, SITE LIGHTING, | | | GENERATOR AND ANY LOW VOLTAGE SYSTEMS. |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
5 |
Status |
P |
Date |
2021-10-21 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
2021-10-21 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
2021-10-21 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
4 |
Status |
F |
Date |
2021-06-11 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
2021-06-11 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
2021-06-11 |
Time |
|
Sent To |
|
|
| Notes |
| 2021-06-11 17:26:03 | UNDER REVIEW - FORMAL ENG SUBMITAL E21040016. |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
3 |
Status |
F |
Date |
2021-03-05 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
2021-03-05 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
2021-03-05 |
Time |
|
Sent To |
|
|
| Notes |
| 2021-03-05 08:26:57 | SITE PLAN APPROVAL IS STILL OUTSTANDING. |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
F |
Date |
2020-12-08 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
2020-12-08 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
2020-12-08 |
Time |
|
Sent To |
|
|
| Notes |
| 2020-12-08 09:38:02 | PLEASE ADDRESS ZONING COMMENTS. |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2020-10-27 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
2020-10-27 |
Time |
|
Rev Time |
|
| Received By |
rrossano |
Date |
2020-10-27 |
Time |
|
Sent To |
|
|
| Notes |
| 2020-10-27 14:38:13 | PLEASE ADDRESS ZONING COMMENTS. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
P |
Date |
2021-10-04 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2021-10-04 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2021-10-04 |
Time |
13:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2021-06-10 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2021-06-10 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2021-06-04 |
Time |
15:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2021-02-23 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2021-02-23 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2021-02-23 |
Time |
11:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2020-12-11 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2020-12-11 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2020-12-07 |
Time |
16:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2020-10-26 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2020-10-26 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2020-10-20 |
Time |
15:11 |
Sent To |
|
|
| Notes |
| 2020-10-26 13:01:16 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) SHEET FP001 - THERE ARE INCORRECT FIRE CODE | | | REFERENCES UNDER SECTION 1. CODES AND STANDARDS | | | | | | THE FIRE SPRINKLER INSTALLATION SHALL COMPLY WITH THE | | | CURRENT EDITION OF THE FLORIDA FIRE PREVENTION CODE , | | | 6TH ED., 2015 NFPA 1 & 101 | | | | | | NFPA 13, 24 & 72 2013 EDITIONS | | | | | | PLEASE REVIEW AND CORRECT ALL FP SHEETS | | | | | | | | | | | | 2) SHEET FP001 - ALL FIRE SPRINKLER FIRE WORK SHALL BE | | | INSTALLED PER NFPA 13 UNDER SEPARATE PERMIT AND SHOP | | | DRAWINGS. | | | | | | PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWEDGEMENT. | | | | | | | | | 2A) SHEET FP002 - THERE IS NO INDICATION OF FIRE | | | SPRINKLER PROTECTION UNDER THE PORTE COCHERE. | | | | | | PLEASE REVIEW AND CORRECT. | | | | | | | | | | | | 3) SHEET FP001 - THERE IS AN INDICATION OF UNDERGROUNG | | | FIRE LINE WORK. ALL UNDERGROUND FIRE LAINE WORK, | | | INCLUDING THE FIRE LINE TAP, DDCV AND FDC SHALL BE | | | INSTALLED PER NFPA 24 UNDER SEPARATE PERMIT AND SHOP | | | DRAWINGS. | | | | | | PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWEDGEMENT. | | | | | | | | | | | | 4) THERE DOES NOT APPEAR TO BE STANDPIPES INSTALLED IN | | | EACH STAIRWELLS. STANDPIPES ARE REQUIRED UNDER THE | | | FLORIDA BUILDING CODE AND INSTALLED PER NFPA 14. | | | | | | | | | PLEASE PROVIDE AND CORRECT. | | | | | | | | | | | | 5) SHEET #121 - THERE ARE INDICATIONS OF FIRE ALARM | | | DEVICES/EQUIPMENT. ALL FIRE ALARM WORK SHALL BE | | | INSTALLED PER NFPA 72 UNDER SEPARATE PERMIT AND SHOP | | | DRAWINGS. | | | | | | PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWEDGEMENT. | | | | | | | | | | | | 6) SHEET A031 - UNDER SECTION CHAPTER 9 - FIRE | | | PROTECTION SYSTEMS, THERE IS AN INDICATION OF A | | | COMMERCIAL HOOD AND DUCT SYSTEM AND TYPE I HOOD, ANY | | | REQUIRED HOOD SYSTEM SHALL BE INSTALLED PER NFPA 96 | | | UNDER SEPARATE PERMITS, 1 FOR THE HOOD AND 1 FOR THE | | | SUPPRESSION, AND SHOP DRAWINGS. | | | | | | PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWEDGEMENT. | | | | | | | | | | | | 7) FP SHEETS - THERE DOES NOT APPEAR TO BE FIRE | | | SPRINKLERS WITHIN THE LAUNDRY CHUTE. | | | | | | PER NFPA 82 | | | | | | 6.2.6 AUTOMATIC SPRINKLERS. | | | 6.2.6.1 GRAVITY CHUTE. | | | 6.2.6.1.1 GRAVITY CHUTES SHALL BE PROTECTED INTERNALLY | | | BY AUTOMATIC | | | SPRINKLERS UNLESS THE CHUTE IS IN ACCORDANCE WITH | | | 6.2.2.5 | | | OR 6.2.2.6. | | | 6.2.6.1.2 A SPRINKLER SHALL BE INSTALLED AT OR ABOVE | | | THE TOP | | | CHUTE INTAKE OF THE CHUTE. | | | 6.2.6.1.3 AUTOMATIC SPRINKLERS INSTALLED IN GRAVITY | | | CHUTE INTAKES | | | SHALL BE RECESSED OUT OF THE CHUTE AREA THROUGH WHICH | | | THE MATERIAL TRAVELS. | | | 6.2.6.1.4 A SPRINKLER SHALL BE INSTALLED WITHIN THE | | | CHUTE AT | | | ALTERNATE FLOOR LEVELS IN CHUTES CONNECTING MORE THAN | | | TWO STORIES, | | | WITH A MANDATORY SPRINKLER LOCATED AT THE LOWEST | | | SERVICE | | | LEVEL. | | | 6.2.6.1.5 SPRINKLER SYSTEM INSTALLATION SHALL COMPLY | | | WITH | | | NFPA 13, STANDARD FOR THE INSTALLATION OF SPRINKLER | | | SYSTEMS. | | | | | | PLEASE REVIEW AND CORRECT | | | | | | | | | | | | 8) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 9) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2021-03-24 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-03-24 |
Time |
17:09 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-03-23 |
Time |
11:25 |
Sent To |
|
|
| Notes |
| 2021-03-24 17:09:23 | 03/24/21 REVIEWED FOR CODE COMPLIANCE (GAS) | | | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | | PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES | | | FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, | | | STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT | | | THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK | | | OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | | AVOID VOIDING OF THE PERMIT. | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2021-01-04 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-01-04 |
Time |
17:50 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2020-12-31 |
Time |
09:31 |
Sent To |
|
|
| Notes |
| 2021-01-04 17:50:48 | 01/04/20 2ND GAS REVIEW**DENIED** WITH COMMENTS | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | 1. PLEASE SHOW ON AN ISOMETRIC DRAWING THAT CLEARLY | | | SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 | | | FBC-FUEL GAS, SECS. 402.4.1, 402.4.2. OR 2017 FBC-R | | | SEC. G2413.4.1, G2413.4.2. | | | | | | 2. DONE | | | | | | 3. PLEASE SHOW THE TYPE OF PIPE MATERIAL BEING | | | INSTALLED ON THE ISOMETRIC AND LABEL IT NATURAL PER THE | | | WPB AMENDMENTS TO FBC SEC. 107.2.1. PLEASE NOTE THAT | | | PAGE P002 HAS THE LEFT SIDE CUT OFF, SO SQUARE ON THE | | | PAGE. | | | | | | 4. DONE | | | | | | 5. PLEASE SHOW THE ISOMETRIC THE TOTAL DISTANCE FROM | | | THE POINT OF DELIVERY (GAS METER / MP REGULATOR / LP | | | TANK) TO THE MOST REMOTE OUTLET IN THE BUILDING AND | | | SYSTEM PER THE 2017 FBC-FUEL GAS SEC. 402.4.1, 402.4.2. | | | | | | 6. DONE | | | | | | 7. PLEASE INDICATE THE DELIVERY PRESSURE (PSI) OF THE | | | SYSTEM ON THE ISOMETRIC PER THE WPB FBC 107.2.1 | | | INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | 8. PLEASE SHOW THIS INFORMATION ON PAGE ISOMETRIC | | | "DEDICATED EXHAUST LINES TERMINATING OUT THE PLAN WEST | | | SIDE OF THE BUILDING, PROVIDED BY THE MANUFACTURER." | | | | | | 9. DONE | | | | | | 10. PLEASE PLACE A NOTE ON THE ISOMETRIC DRAWINGS | | | SPECIFYING WHICH SIZING TABLE(S) FROM THE GAS CODE OR | | | OTHER STANDARD WAS USED TO DESIGN THIS GAS SYSTEM. | | | REFER TO THE 2017 FBC-FUEL GAS SECS. 401.4, 401.8, | | | 402.3, AND TABLES 402.4 (1) THRU 402.4 (37). | | | | | | 11. PLEASE SHOW AND LABEL ALL UNIONS IN FRONT OF | | | REGULATOR 1' OF EITHER SIDE AND SHOW REGULATORS PER THE | | | 2017 FBC FG SEC 410.2. | | | | | | 12. PLEASE SHOW AND LABEL THE SHUTOFF VALVE ON GAS | | | ISOMERIC PER THE 2017 FBC FG SEC. 409.4 OR 2017 FBC | | | RES. SEC. G2401.1.3. | | | | | | 13. PLEASE SHOW AND LABEL DRIP LEG ON EQUIPMENT | | | INSTALLED PER THE 2017 FBC FG 408.2. | | | | | | 14. THE CITY OF WEST PALM BEACH WILL REQUIRE THE GAS | | | SYSTEM TO BE PURGE AND ADMINISTERED BY A CITY | | | INSPECTOR. BEFORE DOING THIS PROCESS, PLEASE DESCRIBE | | | HOW THE PURGE WILL OCCUR AND WHEN SUBMITTED TO THE | | | CHIEF PLUMBING INSPECTOR IN ADVANCE. PLEASE CALL | | | 561-805-6692 FOR FURTHER CLARIFICATION. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2020-11-03 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2020-11-03 |
Time |
07:22 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2020-11-02 |
Time |
06:32 |
Sent To |
|
|
| Notes |
| 2020-11-02 06:33:42 | 1) SUBMIT A COPY OF AN ISOMETRIC DRAWING THAT CLEARLY | | | SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 | | | FBC-FUEL GAS, SECS. 402.4.1, 402.4.2. OR 2017 FBC-R | | | SEC. G2413.4.1, G2413.4.2. | | | 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE GAS | | | WATER HEATERS. | | | 3) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL | | | PIPE SIZES, TYPE OF GAS (LP OR NATURAL).WPB AMEND. TO | | | FBC SEC. 107.2.1. | | | 4) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL | | | BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS | | | SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37) | | | OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES | | | G2413.4 (1 ) THROUGH G2413.4 (21). | | | 5) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS | | | METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2017 | | | FBC-FUEL GAS SEC.402.4.1, 402.4.2, OR 2017 FBC-RES. | | | SEC. G 2413.4.1, G2413.4.2. | | | 6) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017 | | | FBC-FUEL GAS CODE SEC.304.1, 614.6 (CLOTHES DRYERS) OR | | | 2017 FBC-RES. SEC.G 2407.1 AND G2439.4 (CLOTHES | | | DRYERS). | | | 7) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM | | | ON THE PLAN PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3 | | | THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3. | | | 8) SUBMIT DETAILS SHOWING THE TYPE OF VENT, LOCATION, | | | SIZE, TERMINATION POINT, HEIGHT ABOVE THE ROOF AND | | | ANCHORING DETAILS OF THE GAS VENT(S) PER 2017 FBC-FUEL | | | GAS SECS. 502 THRU 505 OR 2017 FBC-RES. SEC.G2426 | | | THROUGH G2439. | | | 9) SUBMIT TWO COPIES OF THE MANUFACTURER'S | | | SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, | | | NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND | | | 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES | | | SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS | | | FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT | | | THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES. | | | SEC.G2408.1. | | | 10) SUBMIT A COPY OF THE APPLICABLE SIZING TABLES USED | | | TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE | | | PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM | | | THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE | | | DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL | | | GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1) | | | THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8, | | | G2413.1, G2413.2, & G2413.3. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2021-10-27 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-10-27 |
Time |
13:09 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-09-27 |
Time |
07:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2021-07-14 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-07-14 |
Time |
14:01 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-06-02 |
Time |
16:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2021-03-30 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2021-03-30 |
Time |
14:02 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2021-02-09 |
Time |
16:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2021-01-04 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-01-04 |
Time |
17:51 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2020-12-01 |
Time |
17:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2020-11-03 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2020-11-03 |
Time |
10:03 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2020-10-06 |
Time |
15:20 |
Sent To |
|
|
| Notes |
| 2020-10-20 15:21:24 | PAYMENT REJECTED BY CITY 10/6 AND 10/7, BACKDATED TO | | | DATE OF ATTEMPTED PAYMENT |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2020-10-30 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2020-10-30 |
Time |
13:00 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2020-10-30 |
Time |
13:00 |
Sent To |
|
|
| Notes |
| 2020-10-30 13:03:18 | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON | | | APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO | | | YOUR PROJECT OR EMAIL IT TO [email protected] . | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2021-06-18 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-06-18 |
Time |
15:46 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-06-18 |
Time |
15:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2021-03-01 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-03-01 |
Time |
09:31 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-03-01 |
Time |
08:56 |
Sent To |
|
|
| Notes |
| 2021-03-01 09:31:28 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-20090848 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE PROVIDE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS FOR ALL MECHANICAL SYSTEMS, NOT JUST THE | | | ROOM PTAC?S. FBC ECC403.2.1 | | | | | | 2) THE KITCHEN HOOD WILL REQUIRE A SEPARATE PERMIT AND | | | REVIEW. PLEASE ADD A NOTE EXPLAIN THIS ON THE DRAWINGS. | | | FBC 107.2.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | | UPDATED. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2020-12-16 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-12-16 |
Time |
16:17 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2020-12-16 |
Time |
14:32 |
Sent To |
|
|
| Notes |
| 2020-12-16 16:18:12 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT-20090848 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | | EDITION 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE PROVIDE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS. FBC EC C403.2.1 | | | | | | 2) SHEET M201: BREAKROOM BATHROOM EXHAUST DUCT IS | | | PENETRATING THE SAME RATED WALLS AS THE GUEST LAUNDRY | | | DRYER DUCTS ARE PENETRATING. PLEASE SHOW HOW THESE | | | RATED WALLS WILL BE PROTECTED AT THE DUCT PENETRATIONS. | | | FBC M 607 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | | UPDATED. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2020-10-30 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-10-30 |
Time |
07:26 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2020-10-29 |
Time |
16:45 |
Sent To |
|
|
| Notes |
| 2020-10-30 07:55:50 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT-20090848 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE PROVIDE EQUIPMENT SIZING CALCULATIONS. FBC EC | | | C403.2.1; FBC M 312.1 | | | | | | 2) SHEET A031 INDICATES A 2-HOUR RATED WALL FOR THE | | | STORAGE AREA WHERE AHU-1 IS LOCATED (M201). IT APPEARS | | | THAT THE AREA ABOVE THE CEILING IS BEING USED AS A | | | RETURN AIR PLENUM. PLEASE SHOW THE RETURN AIR PATH BACK | | | TO AHU-1 IN THIS AREA. FBC M 601.6 | | | | | | 3) SHEET M201: PLEASE SHOW THE PROTECTION OF THE DRYER | | | DUCT PENETRATION IN THE RATED WALL AT THE GUEST | | | LAUNDRY. FBC M 504.2 | | | | | | 4) GUEST ROOM BATH EXHAUST FANS: | | | .RATES ARE PER ROOM UNLESS OTHERWISE INDICATED. THE | | | HIGHER RATE SHALL BE PROVIDED WHERE THE EXHAUST SYSTEM | | | IS DESIGNED TO OPERATE INTERMITTENTLY. THE LOWER RATE | | | SHALL BE PERMITTED ONLY WHERE THE EXHAUST SYSTEM IS | | | DESIGNED TO OPERATE CONTINUOUSLY WHILE OCCUPIED. FBC M | | | TABLE 403.3.1.1 NOTE F | | | | | | 5) PLEASE SHOW THE PENETRATION PROTECTION AT THE | | | PENETRATION OF THE RATED WALL AT DUCT FOR THE EXHAUST | | | FAN IN THE CHUTE ROOM ON FLOORS 2, 3 AND 4. FBC M 607.5 | | | | | | 6) SHEET A440: PANTRY EQUIPMENT LEGEND, NOTE 10 IS AN | | | OVEN. PLEASE PROVIDE SPECIFICATIONS FOR THIS OVEN AND | | | EXPLAIN HOW IT WOULD MEET FBC M 507.1 | | | | | | 7) SHEET A440: PANTRY EQUIPMENT LEGEND, NOTE 3 IS A | | | DISHWASHER. PLEASE PROVIDE SPECIFICATIONS FOR THIS | | | DISHWASHER AND EXPLAIN HOW IT WOULD MEET FBC M 507.3 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | | UPDATED. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
5 |
Status |
P |
Date |
2021-10-07 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2021-10-07 |
Time |
13:44 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2021-10-07 |
Time |
13:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
4 |
Status |
F |
Date |
2021-06-29 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2021-06-29 |
Time |
15:14 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2021-06-29 |
Time |
15:14 |
Sent To |
|
|
| Notes |
| 2021-06-29 15:14:45 | THE PRE-CONSTRUCTION ELEVATION CERTIFICATE HAS ERRORS. | | | THE LATITUDE AND LONGITUDE ARE REVERSED ON THE | | | CERTIFICATE (IE. THE LONGITUDE IS IN THE SPACE FOR | | | LATITUDE AND THE LATITUDE IS IN THE SPACE FOR | | | LONGITUDE). THE NORTH AND WEST DESIGNATIONS WERE NOT | | | SPECIFIED FOR LATITUDE AND LONGITUDE. NOTE: THE | | | COORDINATES ARE REQUIRED TO BE FOR A POINT WITHIN 66 | | | FEET OF THE PROPOSED BUILDINGS MAIN ENTRANCE. |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
3 |
Status |
F |
Date |
2021-03-08 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2021-03-08 |
Time |
09:55 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2021-03-08 |
Time |
09:55 |
Sent To |
|
|
| Notes |
| 2021-03-08 09:56:16 | THE REQUIRED PRE-CONSTRUCTION ELEVATION CERTIFICATE | | | BASED ON THE CONSTRUCTION DRAWINGS HAS NOT BEEN | | | SUBMITTED FOR REVIEW. | | | | | | AS OF OCTOBER 5TH, 2017 THE CITY HAS ADOPTED NEW FLOOD | | | INSURANCE RATE MAPS WHICH USE NAVD 88 AS THE VERTICAL | | | DATUM. THE CITY ALSO ADOPTED A 2' FREEBOARD WHICH | | | REQUIRES THE FINISH FLOOR AND EQUIPMENT TO BE A MINIMUM | | | OF TWO FEET ABOVE THE BFE. | | | ACCORDING TO THE FLOOD INSURANCE RATE MAP WHICH WAS | | | ADOPTED ON OCTOBER 5, 2017 AND IS APPLICABLE TO THIS | | | PROJECT, THE STRUCTURE IS IN AN AE FLOOD ZONE WHICH IS | | | A SPECIAL FLOOD HAZARD AREA. THE BASE FLOOD ELEVATION | | | FOR THE PROPERTY IS 12.7' NAVD 88. THE CITY OF WEST | | | PALM BEACH HAS ADOPTED A FLOOD ORDINANCE THAT REQUIRES | | | A TWO (2) FOOT FREE BOARD. THIS MEANS THAT THE LOWEST | | | FLOOR AND ALL EQUIPMENT SERVICING THE BUILDING IS | | | REQUIRED TO BE AT OR ABOVE 14.7' NAVD 88. SHOW | | | COMPLIANCE WITH THESE REQUIREMENTS ON THE PLANS. | | | SPECIFY ALL ELEVATIONS IN NAVD 88. | | | THREE ELEVATION CERTIFICATES ARE REQUIRED TO BE | | | SUBMITTED. 1) A PRE-CONSTRUCTION ELEVATION CERTIFICATE | | | BASED ON THE CONSTRUCTION PLANS IS REQUIRED BEFORE THE | | | PERMIT IS ISSUED. 2) A BUILDING UNDER CONSTRUCTION | | | ELEVATION CERTIFICATE WHEN FIRST FLOOR SLABS ARE | | | POURED. 3) A FINISHED CONSTRUCTION ELEVATION WHEN THE | | | JOB IS COMPLETE INCLUDING LANDSCAPING. THE FINAL | | | ELEVATION CERTIFICATE IS REQUIRED TO BE SUBMITTED AND | | | APPROVED BEFORE THE C.O. WILL BE ISSUE. | | | |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
2 |
Status |
F |
Date |
2020-12-22 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2020-12-22 |
Time |
10:16 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2020-12-22 |
Time |
10:15 |
Sent To |
|
|
| Notes |
| 2020-12-22 10:16:31 | THE REQUIRED PRE-CONSTRUCTION ELEVATION CERTIFICATE | | | BASED ON THE CONSTRUCTION DRAWINGS HAS NOT BEEN | | | SUBMITTED FOR REVIEW. | | | | | | AS OF OCTOBER 5TH, 2017 THE CITY HAS ADOPTED NEW FLOOD | | | INSURANCE RATE MAPS WHICH USE NAVD 88 AS THE VERTICAL | | | DATUM. THE CITY ALSO ADOPTED A 2' FREEBOARD WHICH | | | REQUIRES THE FINISH FLOOR AND EQUIPMENT TO BE A MINIMUM | | | OF TWO FEET ABOVE THE BFE. | | | ACCORDING TO THE FLOOD INSURANCE RATE MAP WHICH WAS | | | ADOPTED ON OCTOBER 5, 2017 AND IS APPLICABLE TO THIS | | | PROJECT, THE STRUCTURE IS IN AN AE FLOOD ZONE WHICH IS | | | A SPECIAL FLOOD HAZARD AREA. THE BASE FLOOD ELEVATION | | | FOR THE PROPERTY IS 12.7' NAVD 88. THE CITY OF WEST | | | PALM BEACH HAS ADOPTED A FLOOD ORDINANCE THAT REQUIRES | | | A TWO (2) FOOT FREE BOARD. THIS MEANS THAT THE LOWEST | | | FLOOR AND ALL EQUIPMENT SERVICING THE BUILDING IS | | | REQUIRED TO BE AT OR ABOVE 14.7' NAVD 88. SHOW | | | COMPLIANCE WITH THESE REQUIREMENTS ON THE PLANS. | | | SPECIFY ALL ELEVATIONS IN NAVD 88. | | | THREE ELEVATION CERTIFICATES ARE REQUIRED TO BE | | | SUBMITTED. 1) A PRE-CONSTRUCTION ELEVATION CERTIFICATE | | | BASED ON THE CONSTRUCTION PLANS IS REQUIRED BEFORE THE | | | PERMIT IS ISSUED. 2) A BUILDING UNDER CONSTRUCTION | | | ELEVATION CERTIFICATE WHEN FIRST FLOOR SLABS ARE | | | POURED. 3) A FINISHED CONSTRUCTION ELEVATION WHEN THE | | | JOB IS COMPLETE INCLUDING LANDSCAPING. THE FINAL | | | ELEVATION CERTIFICATE IS REQUIRED TO BE SUBMITTED AND | | | APPROVED BEFORE THE C.O. WILL BE ISSUE. | | | |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
1 |
Status |
F |
Date |
2020-11-02 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2020-11-02 |
Time |
08:08 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2020-11-02 |
Time |
08:08 |
Sent To |
|
|
| Notes |
| 2020-11-02 08:08:22 | AS OF OCTOBER 5TH, 2017 THE CITY HAS ADOPTED NEW FLOOD | | | INSURANCE RATE MAPS WHICH USE NAVD 88 AS THE VERTICAL | | | DATUM. THE CITY ALSO ADOPTED A 2' FREEBOARD WHICH | | | REQUIRES THE FINISH FLOOR AND EQUIPMENT TO BE A MINIMUM | | | OF TWO FEET ABOVE THE BFE. | | | ACCORDING TO THE FLOOD INSURANCE RATE MAP WHICH WAS | | | ADOPTED ON OCTOBER 5, 2017 AND IS APPLICABLE TO THIS | | | PROJECT, THE STRUCTURE IS IN AN AE FLOOD ZONE WHICH IS | | | A SPECIAL FLOOD HAZARD AREA. THE BASE FLOOD ELEVATION | | | FOR THE PROPERTY IS 12.7' NAVD 88. THE CITY OF WEST | | | PALM BEACH HAS ADOPTED A FLOOD ORDINANCE THAT REQUIRES | | | A TWO (2) FOOT FREE BOARD. THIS MEANS THAT THE LOWEST | | | FLOOR AND ALL EQUIPMENT SERVICING THE BUILDING IS | | | REQUIRED TO BE AT OR ABOVE 14.7' NAVD 88. SHOW | | | COMPLIANCE WITH THESE REQUIREMENTS ON THE PLANS. | | | SPECIFY ALL ELEVATIONS IN NAVD 88. | | | THREE ELEVATION CERTIFICATES ARE REQUIRED TO BE | | | SUBMITTED. 1) A PRE-CONSTRUCTION ELEVATION CERTIFICATE | | | BASED ON THE CONSTRUCTION PLANS IS REQUIRED BEFORE THE | | | PERMIT IS ISSUED. 2) A BUILDING UNDER CONSTRUCTION | | | ELEVATION CERTIFICATE WHEN FIRST FLOOR SLABS ARE | | | POURED. 3) A FINISHED CONSTRUCTION ELEVATION WHEN THE | | | JOB IS COMPLETE INCLUDING LANDSCAPING. THE FINAL | | | ELEVATION CERTIFICATE IS REQUIRED TO BE SUBMITTED AND | | | APPROVED BEFORE THE C.O. WILL BE ISSUE. | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2021-10-27 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-10-27 |
Time |
13:06 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-10-27 |
Time |
13:05 |
Sent To |
|
|
| Notes |
| 2021-10-27 13:08:08 | 10/27/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING) | | | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | | PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES | | | FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, | | | STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT | | | THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK | | | OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | | AVOID VOIDING OF THE PERMIT. | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2021-07-14 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-07-14 |
Time |
13:23 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-07-14 |
Time |
11:45 |
Sent To |
|
|
| Notes |
| 2021-07-14 13:24:08 | 07/14/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING) | | | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | | PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES | | | FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, | | | STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT | | | THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK | | | OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | | AVOID VOIDING OF THE PERMIT. | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2021-03-24 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-03-24 |
Time |
17:09 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-03-23 |
Time |
11:26 |
Sent To |
|
|
| Notes |
| 2021-03-24 16:42:47 | 03/24/21 3RD PLUMBING REVIEW**DENIED** WITH COMMENTS | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | 1. PERMIT Z20010014, REFER TO EMAIL SENT TO ARCHITECT | | | FROM MRS. S, HILL. | | | | | | 2. DONE. | | | | | | 3. DONE. | | | | | | 4. DONE. | | | | | | 5. DONE. | | | | | | 6. DONE. | | | | | | 7. DONE. | | | | | | 8. DONE. | | | | | | 9. DONE. | | | | | | 10. DONE. | | | | | | 11. DONE. | | | | | | 12. DONE. | | | | | | 13. DONE. | | | | | | 14. DONE. | | | | | | 15. DONE. | | | | | | A. DONE. | | | | | | B. DONE. | | | | | | C. DONE. | | | | | | D. DONE. | | | | | | 16. DONE | | | | | | 17. DONE | | | | | | 18. ON SHEET A422, | | | A. DONE. | | | | | | B. ON DETAIL 13 AND 15, THE GRAB BARS SHALL BE MEASURED | | | TO THE TOP OF THE GRIPPING SURFACE PER THE 2017 FBC ACC | | | SEC. 609.4. ON DETAIL 13 AND 18, PLEASE SHOW THE TOILET | | | PAPER DISPENSERS 7? INCHES MINIMUM AND 9? INCHES | | | MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO THE | | | CENTERLINE OF DISPENSER PER THE 2017 FBC ACC SEC. | | | 604.7. | | | | | | C. DONE. | | | | | | 19. DONE. | | | | | | NOTE, PLEASE CORRECT ALL ACCESSIBILITIES PAGES TO | | | COINCIDE WITH EACH OTHER, TOO MANY TO ITEMIZE. THANK | | | YOU. | | | | | | 20. DONE. | | | | | | 21. DONE. | | | | | | 22. DONE ALL. | | | | | | A. DONE. | | | | | | B. DONE. | | | | | | C. DONE. | | | | | | D. DONE. | | | | | | E. DONE. | | | | | | 23. DONE. | | | | | | 24. DONE. | | | | | | 25. DONE. | | | | | | 26. DONE. | | | | | | 27. DONE. | | | | | | 28. ON SHEET P201, | | | | | | A. ALL TAGS ARE NOTED. PLEASE REMOVE CLOUDS FOR CLARITY | | | PER THE WPB FBC 107.2.1 INFORMATION ON CONSTRUCTION | | | DOCUMENTS. | | | | | | B. DONE. | | | | | | C. DONE. | | | | | | D. DONE. | | | | | | E. THE ELEVATORS MUST BE ON AN INDIRECT WASTE NOT TO | | | THE SANITARY, SO PLEASE PROVIDE A DETAIL THAT SHOWS THE | | | INDIRECT CONNECTION PER THE 2017 FBC SEC. P 1113. | | | | | | F. THE LINE IN THE STORAGE ROOM MUST HAVE A TRAP PRIMER | | | AND A FUNNEL FOR THE INDIRECT WASTE FROM THE PUMP, AND | | | IT NEEDS TO BE LOCATED AT THE STORAGE ROOM AND SHOW ON | | | P801 AND SHOW ON P201 PER THE WPB FBC 107.2.1 | | | INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | 29. ON SHEET P805; | | | | | | A. PLEASE PROVIDE THE GPM AND ROOF AREA IN FEET OF | | | COVERED AREA FOR EACH RAIN LEADER STORMWATER RISER | | | DIAGRAM FOR THE 2017 FBC SEC CALCULATIONS. P1106. | | | | | | B. PLEASE SHOW THE SLOPE OF ALL HORIZONTAL PIPES PER | | | THE WPB FBC 107.2.1 INFORMATION ON CONSTRUCTION | | | DOCUMENTS. SHOW THE HORIZONTAL PIPE SLOPE ON THE PLAN. | | | | | | 30. DONE. | | | | | | 31. DONE. | | | | | | PLEASE NOTE THAT A SHEET FOR THE CIVIL DRAWING IS | | | REQUIRED ON THIS SET OF PLANS SUBMITTED IN COMMENT ONE. | | | | | | 32. DONE. | | | | | | 33. DONE. | | | | | | 34. DONE. | | | | | | 35. DONE. | | | | | | 36. DONE. | | | | | | 37. DONE. | | | | | | 38. DONE. | | | | | | 39. DONE. | | | | | | 40. DONE. | | | | | | 41. ON SHEET P801, | | | | | | A. DONE, PLEASE PROVIDE THIS VERBIAGE ON THIS PAGE FOR | | | YOUR RESPONSE | | | | | | B. DONE, PLEASE REMOVE ALL CLOUDS ON THIS PAGE AND ALL | | | OTHER PAGES ON THE PREVIOUS REVIEW THAT HAVE BEEN | | | ADDRESSED FOR CLARITY PER THE WPB FBC 107.2.1 | | | INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | C. DONE. | | | | | | D. DONE. | | | | | | 42. ON SHEETS P802, | | | | | | A. DONE. | | | | | | B. DONE. | | | | | | C. DONE. | | | | | | D. NOT TO CLEAR ON THIS TASK P201 WE COULD NOT FIND THE | | | RESPONSE MADE, PLEASE CLARIFY PER THE WPB FBC 107.2.1 | | | INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | E. CONTINUATION POINTS ON P801 AND P502 ARE NOT CLEAR | | | AND POINTING TO THE WRONG PIPES IN SOME CASES. PLEASE | | | CORRECT TO REFECTION CONNECTION POINTS PER THE WPB FBC | | | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | 43. DONE | | | | | | 44. PLEASE REMOVE THE CLOUDS ON THE PLANS AS THESE ARE | | | CONFUSING IN THE FIELD. THIS IS FOR FIELD CLARITY PER | | | WPB FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | SUGGESTION TO PUT 801E AND 802W TO REFER RISER BETTER. | | | | | | 45. DONE. | | | | | | 46. DONE. | | | | | | 47. DONE. | | | | | | 48. DONE. | | | | | | 49. DONE. | | | | | | 50. DONE. | | | | | | 51. DONE AS A NOTE. | | | | | | 52. ON P601, ON THE INDIRECT CONNECTION FOR THE SUMP | | | DETAIL, THREE IS SAID TO SANITARY, AND NO DIRECT DETAIL | | | OR REFERENCE IS NOTED. PLEASE CORRECT PER THE WPB FBC | | | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | 53. DONE. | | | | | | 54. THE CIVIL PLANS ARE NOT PART OF THIS SUBMITTED SET | | | PLANS AND ARE NOT AN ELECTRIC VERSION AS THEY ARE A | | | PAPER PLAN. THOSE PLANS ARE FOR REVIEW AND ARE | | | SUBMITTED FOR A DIFFERENT DEPARTMENT, AND WE WOULD NEED | | | CIVIL SUBMITTED WITH THESE SETS. THE CHIEF PLAN | | | EXAMINER WILL BE SENT OUT AN EMAIL CLARIFYING THIS | | | REQUEST TO THE ARCHITECTURAL FIRM ON FILE. | | | THE INFORMATION FOR THE GREASER INTERCEPTOR IS A ZONING | | | REVIEW, AND AS REQUESTED IN THE PREVIOUS COMMENT, A | | | CIVIL PLAN WAS ASKED FOR A REVIEW. CONTACT THE CITY'S | | | ENGINEERING DEPT, AT 561-494-1040 FOR FURTHER | | | INFORMATION ON STANDARD DRAWING GC-7. | | | | | | 55. DONE. | | | | | | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2021-01-04 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-01-04 |
Time |
12:11 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2020-12-31 |
Time |
09:31 |
Sent To |
|
|
| Notes |
| 2021-01-04 15:39:58 | 01/04/20 2ND PLUMBING REVIEW**DENIED** WITH COMMENTS | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | 1. SECOND REQUEST, PLEASE SUBMIT A COMPLETE SET OF | | | CIVIL DRAWINGS SHOWING THE WATER, SEWER, STORM | | | DRAINAGE, AND GAS PIPING SYSTEMS. THE RESPONSE TO THIS | | | REFERRING TO A ZONING PERMIT IS NOT ACCEPTABLE. | | | REFERENCES TO THIS REVIEW ARE IMPERATIVE PER THE WPB | | | AMENDMENTS TO FBC SEC. 107.2.1 AND 107.3.5.1.3. | | | | | | 2. DONE | | | | | | 3. DONE | | | | | | 4. DONE | | | | | | 5. DONE | | | | | | 6. DONE | | | | | | 7. ON SHEET A400 - BATHTUB DETAIL -THE EDGE OF THE GRAB | | | BARS AT THE TUB'S FOOT, THE DIMENSION HAD A CLOUD OVER | | | IT AND HARD TO READ. THE GRAB BAR ON THE SIDE OF THE | | | 1'-0 IS ON THE SAME LINE OF THE MEASUREMENT IT MAKES IT | | | HARD TO READ. PLEASE CORRECT PER THE WPB AMENDMENTS TO | | | THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION | | | DOCUMENTS. | | | | | | 8. DONE | | | | | | 9. DONE | | | | | | 10. DONE | | | | | | 11. DONE | | | | | | 12. DONE | | | | | | 13. DONE | | | | | | 14. DONE | | | | | | 15. THE SECOND REQUEST, | | | | | | A. FOR SHEET A412, A414, A417, A422, A423 - IN THE | | | DETAILS PERTAINING TO THE FOLLOWING SHOW THE DIMENSIONS | | | REQUIRED FOR CLEAR FLOOR SPACES FOR THE HANDICAP | | | ACCESSIBLE FIXTURES ON THE PLANS. COMPLY WITH | | | FBC-ACCESSIBILITY CODE SECS. 604.3, 606.2. SHOW THE | | | DIMENSION CLEAR FLOOR SPACE ADJACENT TO THE TUB OR | | | SHOWER, LAV, AND WATER CLOSET. | | | | | | B. ON SHEET A410, A411, AND A416, DETAILS 13 SHOWS A | | | VERTICAL GRAB BAR ON THE SHOWER AND NOT PERMITTED PER | | | THE 2017 FBC ACC SEC. 609.4. | | | | | | C. ON SHEET A413 DETAIL 15, SHOWS A VERTICAL GRAB BAR | | | ON THE SHOWER AND NOT PERMITTED PER THE 2017 FBC ACC | | | SEC. 609.4. | | | | | | D. ON SHEET A420 AND A421, DETAILS 13, 15, AND 16 SHOW | | | A VERTICAL GRAB BAR ON THE TUB AND NOT PERMITTED PER | | | THE 2017 FBC ACC SEC. 609.4. | | | | | | 16. DIMENSIONING NOT DONE | | | | | | 17. DIMENSIONING NOT DONE | | | | | | 18. ON SHEET A422, | | | | | | A. DIMENSIONING NOT DONE. | | | | | | B. ON DETAIL 15, GARB BARS FOR THE TUB SHOULD BE FROM | | | THE TOP OF THE TUB TO THE FIRST GRAB BAR (8'-10"), AND | | | THE BAK GRAB BAR IS 33" T0 36" MAX PER THE 2017 FBC | | | SEC. ACC 607.4.2. | | | | | | C. ON DETAIL 16 LAV SHALL BE 34" TO TOP PLEASE SHOW PER | | | THE 2017 FBC ACC SEC. 606.3. | | | | | | 19. DIMENSIONING NOT DONE | | | | | | NOTE, PLEASE CORRECT ALL ACCESSIBILITIES PAGES TO | | | COINCIDE WITH EACH OTHER, TOO MANY TO ITEMIZE. THANK | | | YOU. | | | | | | 20. DONE | | | | | | 21. DONE | | | | | | 22. SECOND REQUEST, SHEET A495; | | | | | | A. DETAIL 5; IN THE LAUNDRY ROOM, THE WASHER AND DRYER | | | CLEAR FLOOR SPACE IS MISSING, AND THE DIMENSIONS ARE | | | REQUIRED PER THE 2017 FBC-ACCESS. SECS. 305 SIZE. | | | | | | B. DETAIL 5; IN THE WOMEN'S AND MEN'S RESTROOMS ARE | | | MISSING CLEAR FLOOR SPACE FOR THE WATER CLOSET, AND LAV | | | AND ALL DIMENSIONS ARE REQUIRED PER THE 2017 | | | FBC-ACCESS. SECS. 305 SIZE. | | | | | | C. DETAIL 5; IN THE DRINKING FOUNTAIN IS MISSING CLEAR | | | FLOOR SPACE, AND THE DIMENSIONS ARE REQUIRED PER THE | | | 2017 FBC-ACCESS. SECS. 305 SIZE. | | | | | | D. DETAIL 2; IN THE QQ ACCESS BATHROOM, THERE IS NO | | | CLEAR FLOOR SPACE FOR THE WATER CLOSET, AND ALL | | | DIMENSIONS ARE REQUIRED FOR TUB LAV AND TURNING RADIUS | | | PER THE 2017 FBC-ACCESS. SECS. 305 SIZE. | | | | | | E. DETAILS 2, 3, AND 4 SHOW ICE BIN. PLEASE SHOW CLEAR | | | FLOOR SPACE AND DIMENSIONS PER THE 2017 FBC-ACCESS. | | | SECS. 305 SIZE. PLEASE PROVIDE DETAILS OF THE BIN THAT | | | COMPLIES WITH REACHABILITY OFF THE DOOR PER THE 2017 | | | FBC ACC SEC. 308. | | | | | | 23. COULD NOT FIND A FIRE STOP FROM THE ARCHITECT, SO | | | PLEASE PROVIDE ALL DETAILS OF ALL THE COMPLETE ASSEMBLY | | | ON UL 449 AND UL 605 SYSTEMS PER THE WPB FBC 107.2.1 | | | INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | 24. DONE | | | | | | 25. DONE | | | | | | 26. WHICH PAGE OF NOTES, 7. | | | | | | A LINT INTERCEPTOR IS REQUIRED ON THE WASHING MACHINES | | | IN THE GUEST AND STAFF LAUNDRY FACILITIES PER THE 2017 | | | FBC-PLUMBING SEC. P1003..6. | | | | | | 27. DONE | | | | | | 28. ON SHEET P201, | | | | | | A. PLEASE PLACE TAGS ON ALL THE RISERS (SANITARY UP) TO | | | COINCIDE WITH RISERS ON ISOMETRIC DRAWING IN OTHER | | | PAGES FOR THE CONTINUATION PER THE WPB FBC 107.2.1 | | | INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | B. ON-GRID E/8, THE THREE-INCH PARTIAL PIPES NEED TO BE | | | LABELED TO WHERE THE CONTINUATION WILL BE. THE LAST | | | COMMENT RESPONSE SAYS, ?PIPE INDICATES THE LOCATION OF | | | THE DOWNSPOUT FROM PORTE-COCHERE ROOF GUTTER. PIPE WILL | | | CONNECT TO STORM WATER PER CIVIL PLANS. SEE CIVIL PLANS | | | FOR ADDITIONAL INFORMATION? PLEASE NOTE IT ON THE | | | SECTION OF PIPE PER THE WPB FBC 107.2.1 INFORMATION ON | | | CONSTRUCTION DOCUMENTS. | | | | | | C. THERE IS NO SANITARY CONNECTION FOR THIS BATHROOM | | | GROUP IN GRID 10-11 AND C-D FOR UNIT 114. PLEASE | | | CORRECT FOR ALL PAGES PER THE WPB FBC 107.2.1 | | | INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | D. THERE IS 4" SANITARY UP IN THE MIDDLE OF THE LOBBY | | | GREAT ROOM THAT IS NOT IN A WALL AND THE CENTER OF THE | | | ROOM. PLEASE MOVE TO A WALL PER THE WPB FBC 107.2.1 | | | INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | E. THE ELEVATORS HAVE INDIRECT WASTE. PLEASE PROVIDE A | | | DETAIL PER THE 2017 FBC SEC. P 1113. | | | | | | F. PLEASE MOVE THE ELEVATOR INDIRECT WASTE PIPE TO THE | | | STORAGE ROOM, SIZE, AND SHOW ON P801 PER THE WPB FBC | | | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | 29. ON SHEET P805; | | | | | | A. PLEASE PROVIDE THE GPM AND ROOF AREA IN FEET OF | | | COVERED AREA FOR EACH RAIN LEADER STORM WATER RISER | | | DIAGRAM FOR THE 2017 FBC SEC CALCULATIONS. P1106. | | | | | | B. PLEASE SHOW THE SLOPE OF ALL HORIZONTAL PIPE PER THE | | | WPB FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | SHOW THE HORIZONTAL PIPE SLOPE ON THE PLANS AND THE | | | PIPE SIZE OF EACH SECTION OF PIPE. THE STORM DRAINAGE | | | SYSTEM SHALL BE SIZED IN ACCORDANCE WITH FBC-PLUMBING | | | SEC.1106. THE PARAPET WALL SHALL BE INCLUDED IN THE | | | STORM DRAINAGE SYSTEM'S SIZING IN ACCORDANCE WITH | | | SEC.1106.4. THE FLOW RATE THROUGH THE ROOF DRAIN SHALL | | | BE CALCULATED IN ACCORDANCE WITH SEC.1105. | | | | | | 30. DONE | | | | | | 31. ON SHEET P201, P202, P203, P204, P301, P302, P303, | | | AND P304, GRID 5-7, 15, 19 WHERE CHANGE AND NOT IN | | | ORDER, ALSO D WAS MOVED UP TO FOLLOW A-8. PLEASE | | | CORRECT FOR ALL PAGES PER THE WPB FBC 107.2.1 | | | INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | PLEASE NOTE THAT A SHEET FOR THE CIVIL DRAWING IS | | | REQUIRED ON THIS SET OF PLANS SUBMITTED IN COMMENT ONE. | | | | | | 32. DONE | | | | | | 33. DONE | | | | | | 34.DONE | | | | | | 35. DONE | | | | | | 36. DONE | | | | | | 37. THE SECOND REQUEST, PLEASE PLACE RISER TAGS ON THE | | | WATER RISER AS ON P201 FOR THE EARLIER COMMENT; ALL | | | RISERS ON P801, P802, P803, AND P804 SHALL MATCH THE | | | FLAT CROSS-REFERENCE AND CONTINUATION. PER THE WPB | | | AMENDMENTS TO FBC SEC. 107.2.1. CONSTRUCTION DOCUMENTS | | | SHALL BE OF SUFFICIENT CLARITY TO INDICATE THE | | | LOCATION, NATURE, AND EXTENT OF THE WORK PROPOSED AND | | | SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS | | | OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES, AND | | | REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL. | | | SUCH DRAWINGS AND SPECIFICATIONS SHALL CONTAIN | | | INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO | | | THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO | | | CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION | | | SHALL BE SPECIFIC, AND THE TECHNICAL CODES SHALL NOT BE | | | CITED AS A WHOLE OR IN PART, NOR SHALL THE TERM "LEGAL" | | | OR IT IS EQUIVALENT BE USED AS A SUBSTITUTE FOR | | | SPECIFIC INFORMATION. | | | | | | 38.DONE | | | | | | 39. DONE | | | | | | 40. DONE | | | | | | 41. ON SHEET P801, | | | | | | A. PLEASE SHOW P-TRAPS ON LAVATORIES, TUBS, AND SHOWERS | | | ON ALL RISERS PER THE WPB FBC 107.2.1 INFORMATION ON | | | CONSTRUCTION DOCUMENTS. | | | | | | B. PLEASE SHOW THE CONTINUATION POINTS OF ALL PARTIAL | | | PIPING SECTIONS SHOWN ON BOTH RISER DIAGRAMS PER THE | | | WPB FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | C. THERE ARE MANY FITTING ON THE ISOMETRIC SHOWN IN THE | | | WITH NO FLOW DIRECTION. PLEASE NOTE THAT SANITARY | | | FITTINGS ON ALL ISOMETRIC DRAWINGS SHALL BE INSTALLED | | | TO GUIDE SEWAGE AND WASTE IN THE DIRECTION OF FLOW PER | | | THE 2017 FBC SECTION 706.3 INSTALLATION OF FITTINGS. | | | | | | D. THERE ARE CROSS TEE FITTINGS ON THE BRANCHES TO THE | | | UNIT, AND ALL CONNECTIONS AND CHANGES IN DIRECTION OF | | | THE SANITARY DRAINAGE SYSTEM SHALL BE MADE WITH | | | APPROVED DRAINAGE FITTINGS PER THE 2017 FBC SEC. P | | | 706.1 1 CONNECTIONS AND CHANGES IN DIRECTION. | | | | | | 42. ON SHEETS P802, | | | A. SECOND REQUEST, PLEASE SIZE ALL SECTIONS OF WASTE | | | AND SENT THE SYSTEM ON ALL THE SANITARY RISERS PER THE | | | 2017 FBC TABLE 710.1. (1) AND WPB FBC 107.2.1 | | | INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | B. UNIT 114 IS NOT CONNECTED TO THE 6? LINE AS NOTED ON | | | P201 AS WELL; PLEASE RE-SIZE IF NEEDED AND CORRECT PER | | | THE WPB AMENDMENTS TO FBC SEC. 107.2.1. | | | | | | C. FLOOR DRAIN IN LAUNDRY ROOM NOT CONNECTED TO ITS | | | FEED AND NEED TO SHOW P-TRAP PER THE WPB FBC 107.2.1 | | | INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | D. THE TAGS THAT REFER TO 801 AND 801 NEED TO BE SHOWN | | | ON P 201 TO REFERENCING EACH OTHER PER THE WPB FBC | | | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | E. PLEASE LABEL AND PIPE THAT IS BRANCHING OFF THE MAIN | | | TRUNK LINE TO ITS CONTINUATION POINT PER THE WPB FBC | | | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | 43. DONE | | | | | | 44. ON SHEET P802, THE SECOND REQUEST, THERE ARE | | | SECTIONS OF PIPE MISSING ON THE SANITARY RISER DIAGRAM. | | | PLEASE REFER TO COMMENT 28 FOR SECTION MISS, AND PLEASE | | | REVISE THE DRAWING PER THE WPB FBC 107.2.1 INFORMATION | | | ON CONSTRUCTION DOCUMENTS. | | | | | | 45. ON SHEET P803 & P804 - HOSE BIBBS SHALL BE | | | SEPARATELY VALVES PER FBC-PLUMBING SEC.606.2 (2) THERE | | | IS A NOTE ON 803, BUT 804 HAS NO NOTE, PLEASE SHOW | | | VALVE ON ISOMETRIC AND TO WHICH PAGE OF THE DETAIL IS | | | THE HB-1 LOCATED PER THE WPB FBC 107.2.1 INFORMATION ON | | | CONSTRUCTION DOCUMENTS. | | | | | | 46. DONE | | | | | | 47. DONE | | | | | | 48. THE SERVICE SINKS HAVE BEEN MOVED AND NOTED, BUT | | | THE SERVICE SINK (MOP SINK) SURROUNDING WALLS SHALL BE | | | NON-ABSORBENT SURFACE IN ACCORDANCE WITH THE 2017 FBC | | | BUILDING SEC. 1210.2.2 AND 2017 FBC SEC. P 310.3. | | | PLEASE MAKE A NOTE ON THIS SHEET. | | | | | | 49. ON SHEET P803 & P804 - DOWN FEED RISERS SHALL BE | | | EQUIPPED WITH FULLY OPEN SHUTOFF VALVES PER | | | FBC-PLUMBING SEC.606.1 (5). THE RESPONSE REFERS TO AN | | | AIR VENT THAT WAS NOT FOUND ON P601; PLEASE ADD VALVES | | | TO ISOMETRIC OR ANNOTATE FOR FIELD CLARITY PER THE WPB | | | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | 50. DONE | | | | | | 51. DONE AS A NOTE | | | | | | 52. DONE BUT REQUIRES DETAIL AS REQUESTED IN A PREVIOUS | | | COMMENT. | | | | | | 53. DONE | | | | | | 54. THE GREASER INTERCEPTOR REQUIRES A ZONING REVIEW, | | | AND AS REQUESTED IN THE PREVIOUS COMMENT, A CIVIL PLAN | | | WAS ASKED FOR A REVIEW. CONTACT THE CITY'S ENGINEERING | | | DEPT, AT 561-494-1040 FOR FURTHER INFORMATION ON | | | STANDARD DRAWING GC-7. | | | | | | 55. DONE | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2020-11-02 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2020-11-02 |
Time |
13:08 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2020-10-27 |
Time |
03:58 |
Sent To |
|
|
| Notes |
| 2020-11-01 07:33:54 | 1) SUBMIT A COMPLETE SET OF CIVIL DRAWINGS SHOWING THE | | | WATER, SEWER, STORM DRAINAGE AND GAS PIPING SYSTEMS. | | | WPB AMEND. TO FBC SEC. 107.2.1, 107.3.5.1.3. | | | 2) SHT. A030 - CHAPTER 11 - ACCESSIBILITY NOTES - THERE | | | IS A NOTE ON THE BOTTOM LEFT COLUMN THAT REFERS TO | | | FLORIDA ACCESSIBILITY CODE SECTION 213.2 , EXCEPTION | | | #2. THIS EXCEPTION REFERS TO HISTORIC BUILDINGS AND HAS | | | NOTHING TO DO WITH THIS PROJECT. DELETE THIS FROM THE | | | PLAN.THE NOTE ALSO REFERS TO SECTION 1107. SECTION 1107 | | | IN THE FBC-BUILDING IS NOTED AS "RESERVED" SO THIS IS | | | ALSO NOT APPLICABLE.REMOVE THIS NOTE FROM THE PLAN. | | | 3) SHT. A400 - THE GRAB BARS SHALL BE MEASURED TO THE | | | TOP OF THE GRIPPING SURFACE, NOT TO THE CENTERLINE. | | | FBC-ACCESS. SEC. 609.4. | | | 4) THE PLANS SHOW THE INSTALLATION OF VERTICAL GRAB | | | BARS ON SHT. A400 AND IN NUMEROUS OTHER DETAILS AND | | | ELEVATIONS THROUGHOUT THE PLANS. SECTION 609.4 OF THE | | | FBC-ACCESS. REQUIRES GRAB BARS TO BE INSTALLED IN THE | | | HORIZONTAL POSITION. THERE IS NO EXCEPTION IN THE | | | ACCESSIBILITY CODE ALLOWING FOR THE INSTALLATION OF | | | GRAB BARS IN THE VERTICAL POSITION. DELETE THIS DETAIL | | | FROM THE PLANS. REFER TO SHTS. A410 - A415 AMONG | | | OTHERS. | | | 5) SHT. A400 - BATHTUB DETAIL - SHOWS CONTROLS NEXT TO | | | THE TUB SPOUT AND ALSO A SET OF SHOWER CONTROLS. | | | CLARIFY. THE CONTROLS SHALL BE LOCATED PER FBC-ACCESS. | | | SEC. 607..5. | | | 6) SHT. A400 - BATHTUB DETAIL -THE REMOVABLE TUB SEAT | | | SHALL COMPLY WITH FBC-ACCESS. SEC.610.2 AND FIGURE | | | 610.2. SHOW COMPLIANCE ON THE PLAN. | | | 7) SHT. A400 - BATHTUB DETAIL -THE EDGE OF THE GRAB | | | BARS AT THE HEAD AND FOOT OF THE TUB SHALL BE LOCATED | | | AT THE FRONT EDGE OF THE TUB BUT THE DETAIL SHOWS THE | | | GRAB BARS SET BACK 4 INCHES FROM THE EDGE OF THE TUB. | | | COMPLY WITH FBC-ACCESS. SEC. 607.4.2.2 & 607.4.2.3. | | | 8) SHT.A400 - HOUSEKEEPING/EVS CLOSET DETAIL - CLARIFY | | | THE TYPE OF WALL SURFACE TO BE INSTALLED AROUND THE | | | SERVICE SINKS. SECTION 1210.2.2. OF THE FBC-BUILDING | | | REQUIRES WALLS AND PARTITIONS WITHIN 2 FEET OF SERVICE | | | SINKS TO HAVE A SMOOTH, HARD, NONABSORBENT SURFACE, TO | | | A HEIGHT OF NOT LESS THAN 4 FEET ABOVE THE FLOOR AND | | | THE MATERIALS USED IN SUCH WALLS SHALL BE OF A TYPE | | | THAT IS NOT ADVERSELY AFFECTED BY MOISTURE. EPOXY PAINT | | | DOES MEET THE REQUIREMENTS OF THIS SECTION. | | | 9) SHT. A400 - TOILET/WATER CLOSETS DETAIL - SHOW THE | | | MINIMUM HEIGHT OF THE TOILET PAPER DISPENSER. COMPLY | | | WITH FBC-ACCCESS. SEC.604.7. | | | 10) SHOW THE REQUIRED CLEAR FLOOR SPACE FOR THE | | | DRINKING FOUNTAINS AS REQUIRED BY FBC-ACCESS. SECS.305 | | | & 602.2. | | | 11) SHT. A400 - DRIINKING FOUNTAIN DETAIL - SHOW THE | | | REQUIRED CLEARANCE UNDER THE DRINKING FOUNTAIN. THE | | | CLEARANCE SHALL BE FROM THE FINISH FLOOR TO THE BOTTOM | | | OF THE UNIT, NOT TO THE BOTTOM OFF THE BASIN. COMPLY | | | WITH FBC-ACCESS. FOR KNEE AND TOE CLEARANCE. | | | 12) SHT. A400 - ACCESSIBLE TRANSFER SHOWER DETAIL - | | | SHOW THE HEIGHT OF THE SHOWER CONTROLS ON THE PLAN TO | | | THE CENTERLINE OF THE HANDLE. COMPLY WITH FBC-ACCESS. | | | SEC. 608.5.1 & FIGURE 608.5.1. | | | 13) SHT. A400 - SUBMIT DETAILS ON THE TRANSFER SHOWER | | | SEAT.THE SEAT SHALL COMPLY WITH FBC-ACCESS. SECS. | | | 610.3, 610.3.2. | | | 14) SHT. A400 - ROLL IN SHOWER DETAIL - SUBMIT DETAILS | | | ON THE ROLL IN SHOWER SEAT. THE SEAT SHALL COMPLY WITH | | | FBC-ACCESS. SEC.610.3, 610.3.1. | | | 15) SHT. A412 - DETAIL #1 - SHOW THE DIMENSIONS OF THE | | | REQUIRED CLEAR FLOOR SPACES FOR THE HANDICAP ACCESSIBLE | | | FIXTURES ON THE PLANS. COMPLY WITH FBC-ACCESSIBILITY | | | CODE SECS.604.3, 606.2. SHOW THE CLEAR FLOOR SPACE | | | ADJACENT TO THE SHOWER. | | | 16) SHT. A414 - SHOW THE DIMENSIONS OF THE REQUIRED | | | CLEAR FLOOR SPACES FOR THE HANDICAP ACCESSIBLE FIXTURES | | | ON THE PLANS. COMPLY WITH FBC-ACCESSIBILITY CODE | | | SECS.604.3, 606.2. SHOW THE CLEAR FLOOR SPACE ADJACENT | | | TO THE SHOWER. THE CLEAR FLOOR SPACE FOR THE LAVATORY | | | SHALL BE POSITIONED FOR A FORWARD APPROACH PER SEC. | | | 606.2. | | | 17) SHT. A417 - SHOW THE DIMENSIONS OF THE REQUIRED | | | CLEAR FLOOR SPACES FOR THE HANDICAP ACCESSIBLE FIXTURES | | | ON THE PLANS. COMPLY WITH FBC-ACCESSIBILITY CODE | | | SECS.604.3, 606.2. SHOW THE CLEAR FLOOR SPACE ADJACENT | | | TO THE TUB. THE CLEAR FLOOR SPACE FOR THE LAVATORY | | | SHALL BE POSITIONED FOR A FORWARD APPROACH PER SEC. | | | 606.2. | | | 18) SHT. A422 - SHOW THE DIMENSIONS OF THE REQUIRED | | | CLEAR FLOOR SPACES FOR THE HANDICAP ACCESSIBLE FIXTURES | | | ON THE PLANS. COMPLY WITH FBC-ACCESSIBILITY CODE | | | SECS.604.3, 606.2. SHOW THE CLEAR FLOOR SPACE ADJACENT | | | TO THE TUB. | | | 19) SHT. A423 - SHOW THE DIMENSIONS OF THE REQUIRED | | | CLEAR FLOOR SPACES FOR THE HANDICAP ACCESSIBLE FIXTURES | | | ON THE PLANS. COMPLY WITH FBC-ACCESSIBILITY CODE | | | SECS.604.3, 606.2. SHOW THE CLEAR FLOOR SPACE ADJACENT | | | TO THE TUB. THE CLEAR FLOOR SPACE FOR THE LAVATORY | | | SHALL BE POSITIONED FOR A FORWARD APPROACH PER SEC. | | | 606.2. | | | 20) SUBMIT MANUFACTURER'S SSPECIFICATIONS FOR THE | | | DRINKING FOUNTAIN/BOTTLE FILLER IN THE FITNESS ROOM. | | | 21) SHT. A450 - DETAIL #8 SHOWS THE LAVATORY WITH 2 | | | FEET OF CLEARANCE BELOW THE LAVATORY. A MINIMUM | | | CLEARANCE OF 27 INCHES FROM THE FINISH FLOOR TO THE | | | BOTTOM OF THE CABINET/APRONIS REQUIRED PER FBC-ACCESS. | | | SEC. 306 FOR KNEE AND TOE CLEARANCE. | | | 22) SHT. A450 - LAUNDRY DETAIL - THE WASHER AND DRYER | | | SHALL COMPLY WITH FBC-ACCESS. SECS. 309, 611.2, 611.3, | | | 611.4. SHOW COMPLIANCE ON THE PLANS. | | | 23) SUBMIT LISTED FIRESTOPPING DETAILS FOR NONMETALLIC | | | PIPING THROUGH RATED WALLS AND FLOORS. THE DETAIL ON | | | SHT. A805 APPEARS TO BE ONLY FOR DRAIN CONNECTIONS TO | | | WATER CLOSETS AND THE DETAIL ON SHT. A806 FOR RATED | | | WALL ASSEMBLIES IS FOR NONMETALLIC PIPE WITH A DIAMETER | | | OF 2 INCHES OR LESS. ALSO, THE DETAILS ON SHT. P601 ARE | | | VAGUE AND UNACCEPTABLE. SUBMIT THE COMPLETE UL ASSEMBLY | | | DETAILS FOR THE UL 449 & UL 605 SYSTEMS. WPB AMEND. TO | | | FBC SEC. 107.2.1. | | | 24) SHT. P001 - INDICATE ON THE PLAN WHAT STANDARD WAS | | | USED IN THE SIZING OF THE GREASE INTERCEPTOR. THE | | | INTERCEPTOR SHALL BE SIZED IN THE ACCORDANCE WITH ONE | | | OF THE STANDARDS LISTED IN FBC-PLUMBING SEC.1003.3.4. | | | OR RULE 64E-6 OF THE FL. ADMIN. CODE. THE EQUATION ON | | | THE PLANS APPEARS TO BE INCOMPLETE. | | | 25) TEMPERED WATER IS REQUIRED TO THE LAVATORIES | | | LOCATED IN PUBLIC TOILET FACILITIES. TEMPERED WATER | | | SHALL BE DELIVERED THROUGH AN APPROVED | | | WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE | | | 1070 OR CSA B 125.3 PER FBC-PLUMBING SEC.416.5. | | | 26) A LINT INTERCEPTOR IS REQUIRED ON THE WASHING | | | MACHINES IN THE GUEST AND STAFF LAUNDRY FACILITIES PER | | | FBC-PLUMBING SEC.1003..6. | | | 27) A FLOOR DRAIN IS REQUIRED IN THE ROOM CONTAINING | | | THE AUTOMATIC CLOTHES WASHERS PER FBC-PLUMBING | | | SEC.412.4. THE DRAIN SHALL HAVE AN OUTLET OF NOT LESS | | | THAN 3 INCHES. | | | 28) SHT. P201 - PLACE RISER TAGS ON THE RISERS. WPB | | | AMEND. TO FBC SEC. 107.2.1. | | | 29) SUBMIT A COMPLETE STORM WATER RISER DIAGRAM. SHOW | | | THE SLOPE OF THE HORIZONTAL PIPE ON THE PLANS AND THE | | | PIPE SIZE OF EACH SECTION OF PIPE. THE STORM DRAINAGE | | | SYSTEM SHALL BE SIZED IN ACCORDANCE WITH FBC-PLUMBING | | | SEC.1106. THE PARAPET WALL SHALL BE INLUDED IN THE | | | SIZING OF THE STORM DRAINAGE SYSTEM IN ACCORDANCE WWITH | | | SEC.1106.4. THE FLOW RATE THROUGH THE ROOF DRAIN SHALL | | | BE CALCULATED IN ACCORDANCE WITH SEC.1105. | | | 30) SHT. P201 - THE PLAN NOTES "6 INCH STORM TO CLEAR | | | WATER WASTE" WITH ARROWS POINTING TO AN AREA BUT THERE | | | IS NO PIPING SHOWN. CLARIFY. REFER TO GRID LINES D/4-5. | | | CLARIFY. | | | 31) SHT. P201 - THERE IS A PARTIAL SECTION OF 3 INCH | | | PIPE SHOWN AT GRID LINE E/8. SHOW CONTINUATION POINT | | | AND TERMINATION POINT. | | | 32) THE RAIN WATER LEADERS AND THE OVERFLOW DRAINS | | | SHALL DISCHARGE A MINIMUM OF ONE FOOT FROM THE | | | STRUCTURE SIDEWALL. FBC-BUILDING SEC.1503.7. | | | 33) SHT. P201 SHOWS A 4 INCH SANITARY LINE AT GRID | | | LINES A.8/18.2-19 AND THE SAME LINE IS SHOWN AS 3 INCH | | | ON SHT. P801. CLARIFY. | | | 34) SHT. P201 - THE FLOOR DRAINS IN THE MEN'S AND | | | WOMEN'S TOILET ROOMS ON THE FIRST FLOOR APPEAR TO | | | EXCEED THE DISTANCE FROM A VENT PER FBC-PLUMBING TABLE | | | 9091. | | | 35) SHT. P203 - GENERAL NOTE #3 - SLOPE OF HORIZONTAL | | | DRAINAGE PIPE SHALL COMPLY WITH FBC-PLUMBING SEC. 704.1 | | | & TABLE 704.1. REVISE THE NOTE. | | | 36) HOT WATER PIPING SHALL BE INSULATED PER FBC-ENERGY | | | SEC. C404.4 & TABLE C403.2.10.INDICATE THE INSULATION | | | THICKNESS FOR THE DIFFERENT PIPE SIZES ON THE PLANS. | | | 37) PLACE RISER TAGS ON THE WATER RISER. WPB AMEND. TO | | | FBC SEC. 107.2.1. | | | 38) SHT. P301 - LABEL THE 1 1/2 INCH DHR LINE FOR THE | | | UNISEX TOILET ROOM ON THE PLANS. | | | 39) SHT. P301 - THERE IS A SECTION OF SANITARY PIPE | | | OVERLAYED IN THE GREAT ROOM AREA THAT DOES NOT | | | BELONG.REVISE THE DRAWING . | | | 40) SHT. P301 SHOWS A 4 INCH DWHR UP AND SHT. P804 | | | SHOWS THIS LINE AS 4 INCH DCW UP. CLARIFY. | | | 41) SHT. P801 - THERE ARE SECTIONS OF PIPE MISSING ON | | | THE KITCHEN SINKS (KS-1) AND ALSO ON US-1 AND OTHER | | | AREAS, TRAPS NOT SHOWN ON LAVATORIES OR SHOWERS. SHOW | | | THE CONTINUATION POINTS OF ALL PARTIAL SECTIONS OF | | | PIPING SHOWN ON BOTH RISER DIAGRAMS. WPB AMEND. TO FBC | | | SEC. 107.2.1. | | | 42) SHT. P801 & P802 - SIZE ALL SECTIONS OF THE WASTE | | | AND VENT SYSTEM ON ALL THE SANITARY RISERS AND SHOW THE | | | DRAINAGE FIXTURE LOAD ON THE RISERS AND THE TOTAL | | | DRAINAGE FIXTURE LOAD ON THE MAIN LINE. COMPLY WITH | | | FBC-PLUMBING TABLE 710.1 (1) & TABLE 710..1 (2) . WPB | | | AMEND. TO FBC SEC. 107.2.1. | | | 43) SHT. P801 & P201 - THE FLOOR DRAINS IN THE STAFF | | | AND GUEST LAUNDRIES AND ALSO IN THE PANTRY APPEAR TO | | | EXCED THE DISTANCE FROM A VENT. COMPLY WITH | | | FBC-PLUMBING TABLE 909.1. | | | 44) SHT. P802 - THERE ARE SECTIONS OF PIPE MISSING ON | | | THE SANITARY RISER DIAGRAM. REVISE THE DRAWING.WPB | | | AMEND. TO FBC SEC. 107.2.1. | | | 45) SHTS. P803 & P804 - HOSE BIBBS SHALL BE SEPARATELY | | | VALVED PER FBC-PLUMBING SEC.606.2 (2). | | | 46) SHT. P803 - SHOW THE 1/2 INCH DHR LINE BY STORAGE | | | ROOM EQ1.11 ON THE WATER RISER. | | | 47) SHT. P804 - IDENTIFY THE WASHING MACHINE IN THE | | | STAFF LAUNDRY ON THE WATER RISER.(EQUIPMENT ROOM EQ | | | 1.2). | | | 48) THE PLUMBING SHEETS SHOW SERVICE SINKS ON LEVELS 2, | | | 3 & 4 BUT THEY ARE NOT SHOWN ON THE ARCHITECTURAL | | | PLANS. CLARIFY. | | | 49) SHTS. P803 & P804 - DOWNFEED RISERS SHALL BE | | | EQUIPPED WITH FULLL OPEN SHUTOFF VALVES PER | | | FBC-PLUMBING SEC.606.1 (5). | | | 50) SHT. P803 - IDENTIFY THE WASHING MACHINE IN THE | | | GUEST LAUNDRY ON THE WATER RISER. | | | 51) SHUTOFF VALVES ARE REQUIRED AT THE BASE OF RISERS 3 | | | INCH DHW & 4 INCH DCW | | | 52) THE FLOOR DRAIN IN THE ELEVATOR SHAFT SHALL BE | | | INDIRECTLY CONNETED TO THE PLUMBING SYSTEM PER | | | FBC-PLUMBING SEC. 3301.6. | | | 53) INDICATE ON THE PLAN IF THE ELEVATOR IS HYDRAULIC | | | OR TRACTION TYPE. IF HYYDRAULIC, THE INSTALLATION OF | | | THE FLOOR DRAIN IN THE PIT SHALL OMPLY WITH | | | FBC-PLUMBING SEC.1003.4. | | | 54) SUBMIT A DETAIL OF THE GREASE INTERCEPTOR. THE | | | GREASE INTERCEPTOR SHALL COMPLY WITH THE FL. ADMIN.CODE | | | RULE 64E-6 AND THE CITY OF WEST PALM BEACH STANDARD | | | DETAIL GS-7. CONTACT THE CITY'S ENGINEERING DEPT. AT | | | 561-494-1040 FOR FURTHER INFORMATION ON TANDARDD | | | DRAWING GC-7. | | | 55) SWAY BRACING SHALL BE PROVIDED AT CHANGES IN | | | DIRECTION GREATER THAN 45 DEGREES FOR DRAINAGE PIPE | | | SIZES 4 INCHES AND LARGER PER FBC-PLUMBING SEC.308.6. | | | SUBMIT DETAIL. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
P-GREASE |
GREASE INTERCEPTOR/TRAP REVIEW |
| Rev No |
3 |
Status |
N |
Date |
2021-10-27 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-10-27 |
Time |
13:06 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-10-27 |
Time |
13:06 |
Sent To |
|
|
| Notes |
| 2021-10-27 13:08:44 | GREASE INTERCEPT IS NOT A TURNAROUND. THE CALCULATIONS | | | UNDER THE PRIMARY PERMIT AND WE NEED TO FACILITATE THE | | | PLUMBING REVIEW ON THE INTERCEPT PERMIT. | | | | | | A SEPARATE PERMIT AND REVIEW FROM PLUMBING AND | | | ENGINEERING FOR THE GREASE INTERCEPTOR IS REQUIRED BY A | | | LICENSED CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB | | | AMENDMENTS TO THE FBC SEC. 105.1. |
|
|
| Review Stop |
P-GREASE |
GREASE INTERCEPTOR/TRAP REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2021-07-14 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-07-14 |
Time |
14:00 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-07-14 |
Time |
11:45 |
Sent To |
|
|
| Notes |
| 2021-07-14 14:00:26 | 07/14/21 3RD PLUMBING REVIEW**DENIED** WITH COMMENTS | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | 1. PLEASE SUBMIT A COMPLETE SET OF CIVIL DRAWING | | | SHOWING THE LOCATION OF THE GREASE INTERCEPTOR PER THE | | | WPB AMENDMENTS TO FBC SEC. 107.2.1, 107.3.5.1.3. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | |
|
|
| Review Stop |
P-GREASE |
GREASE INTERCEPTOR/TRAP REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2021-01-04 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-01-04 |
Time |
16:01 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-01-04 |
Time |
15:43 |
Sent To |
|
|
| Notes |
| 2021-01-04 16:02:39 | 01/04/20 2ND PLUMBING REVIEW**DENIED** WITH COMMENTS | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | 1. PLEASE SUBMIT A COMPLETE SET OF CIVIL DRAWING | | | SHOWING THE LOCATION OF THE GREASE INTERCEPTOR PER THE | | | WPB AMENDMENTS TO FBC SEC. 107.2.1, 107.3.5.1.3. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
N |
Date |
2020-12-21 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2020-12-21 |
Time |
13:55 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2020-12-21 |
Time |
07:24 |
Sent To |
|
|
| Notes |
| 2020-12-21 13:55:24 | ROOFING PRODUCT APPROVALS ARE DEFERRED AND ARE TO BE | | | SUBMITTED FOR APPROVAL PRIOR TO RECEIVING THE ROOFING | | | SUB-PERMIT. | | | NO PRODUCT APPROVALS WERE SUBMITTED FOR THE ROOFING | | | MATERIALS: | | | SEE SHEET A011 | | | 1) TPO ROOFING MATERIAL FOR THE MAIN BUILDING. NOA NO. | | | 18-0501.03 | | | 2) STANDING SEAM METAL ROOF FOR THE PORTE COCHERE. NOA | | | NO. 17-1002.12 | | | 3) ROOF COPING: NOA NO. 19-0430.02 |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2020-11-02 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2020-11-02 |
Time |
07:36 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2020-11-02 |
Time |
07:36 |
Sent To |
|
|
| Notes |
| 2020-11-02 07:42:31 | NO PRODUCT APPROVALS WERE SUBMITTED FOR THE TPO ROOFING | | | MATERIAL FOR THE MAIN BUILDING OR THE STANDING SEAM | | | METAL ROOF FOR THE PORTE COCHERE. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
5 |
Status |
P |
Date |
2021-10-12 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2021-10-12 |
Time |
17:28 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2021-10-12 |
Time |
17:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
F |
Date |
2021-06-29 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2021-06-29 |
Time |
15:47 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2021-06-29 |
Time |
15:47 |
Sent To |
|
|
| Notes |
| 2021-06-29 15:47:26 | SOME OF THE ENGINEER'S SIGNATURES ARE INVALID AND HAVE | | | BEEN REVOKED. SEE SEVERAL STRUCTURAL SHEETS, SOME OF | | | THE ARCHITECTURAL SHEETS INCLUDING A100 AND THE | | | STRUCTURAL CALCULATION PACKAGE IN THE SUPPORTING | | | DOCUMENTS. ELECTRONICALLY SUBMITTED DRAWINGS ARE | | | REQUIRED TO HAVE THE ARCHITECT OR ENGINEER'S DIGITAL | | | SIGNATURE ON THEM. YOU ALSO HAVE THE OPTION TO SUBMIT | | | THE SIGNED AND SEALED PAPER VERSION OF DRAWINGS. AFTER | | | THE ELECTRONIC PLANS HAVE BEEN APPROVED, YOU CAN SUBMIT | | | THE CORRESPONDING PAPER DRAWINGS AT THE BUILDING | | | DEPARTMENT TO BE VERIFIED. THE ARCHITECT OR ENGINEER'S | | | ORIGINAL HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO | | | BE ON THE DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF | | | THE SIGNATURE ARE ACCEPTABLE. FS 481 & 61G1 OR FS 471 & | | | 61G15 |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2021-03-01 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-03-01 |
Time |
09:49 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-03-01 |
Time |
09:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2020-12-16 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-12-16 |
Time |
17:07 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2020-12-16 |
Time |
17:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2020-10-30 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-10-30 |
Time |
08:51 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2020-10-30 |
Time |
08:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
5 |
Status |
F |
Date |
2021-10-07 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2021-10-07 |
Time |
17:06 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2021-10-07 |
Time |
17:06 |
Sent To |
|
|
| Notes |
| 2021-10-07 17:12:06 | THE THRESHOLD DOCUMENTS ARE INCOMPLETE. THE OWNER'S AND | | | CONTRACTOR'S NOTARIZED SIGNATURES ARE MISSING FROM | | | THEIR SECTION OF THE THRESHOLD DOCUMENTS. |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
4 |
Status |
F |
Date |
2021-06-29 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2021-06-29 |
Time |
15:16 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2021-06-29 |
Time |
15:16 |
Sent To |
|
|
| Notes |
| 2021-06-29 15:19:28 | THE REQUIRED THRESHOLD NOTARIZED FORMS AND | | | DOCUMENTATION HAS NOT BEEN SUBMITTED. THE FORMS IN THE | | | THRESHOLD BOOKLET THAT WAS SUBMITTED HAVE NOT BEEN | | | COMPLETED. | | | | | | THRESHOLD BUILDING / FL S. S. 553.71(7) "THRESHOLD | | | BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN | | | (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN | | | ASSEMBLY OCCUPANCY CLASSIFICATION AS DEFINED IN THE | | | FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN | | | AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 | | | PERSONS. | | | | | | A) FBC (CITY AMENDMENTS)110.8.1 THRESHOLD INSPECTION | | | PLAN. THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL | | | INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A | | | THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION | | | PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL | | | INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING | | | AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR | | | THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE | | | OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE | | | SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT | | | THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE | | | WITH THE PERMITTED DOCUMENTS. | | | | | | B) THRESHOLD INSPECTOR: WPB AMENDMENT 110.8.1 W.P.B. | | | CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD | | | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY 553.79(5) | | | FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY | | | THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED | | | TO BE FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED | | | AND RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED | | | BEFORE PERMIT ISSUANCE WILL TAKE PLACE. | | | | | | C) THRESHOLD BLDG. REQUIRED STATEMENT: W.P.B. AMENDMENT | | | 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED | | | TO BE SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF | | | RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE | | | ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND | | | SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM | | | BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS | | | AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH | | | THIS SECTION AND CHAPTER 633 FLORIDA STATUTES. | | | | | | D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME OF | | | INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME | | | MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED | | | HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL | | | REVIEW THE RESUME. AFTER THE RESUME IS REVIEWED, AN | | | INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES | | | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST | | | MEETING THE ABOVE CRITERIA. | | | | | | E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY | | | FOR THIS TYPE OF CONSTRUCTION. | | | | | | F) NOTE: FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, | | | PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING | | | ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE | | | APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR | | | PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN | | | COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR | | | THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE | | | IN BLACK & WHITE. | | | | | | G) 110.8.4.3 ALL SHORING AND RESHORING PROCEDURES, | | | PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT | | | AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING | | | INSTALLATION SHALL BE SUPERVISED, INSPECTED AND | | | CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING | | | DOCUMENTS BY THE CONTRACTOR. | | | | | | H) PLEASE CALL THE CITY OF WEST PALM BEACH'S AUTOMATED | | | TELEPHONE INSPECTIONS LINE (561) 805-6700 FOR ALL | | | BUILDING INSPECTIONS FOR AUDITING OF JOBSITE | | | INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6 | | | MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. | | | | | | I) 110.8 THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR | | | THRESHOLD INSPECTORS #25. ASSURE THAT THE DESIGNER HAS | | | REQUIRED ON THE PLANS OR SPECIFICATIONS ONE MATERIAL, | | | APPROVED FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND | | | CEILINGS. | | | | | | J) PLEASE CONTACT ME WITH AN EMAIL ADDRESS AND I WILL | | | BE HAPPY TO SEND YOU A COPY OF THE CURRENT (OCTOBER | | | 2018) GUIDELINES AND POLICIES FOR PROJECTS CONCERNING | | | THRESHOLD/SPECIAL INSPECTORS AND RESIDENT INSPECTORS. | | | | | | | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
3 |
Status |
F |
Date |
2021-03-08 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2021-03-08 |
Time |
10:01 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2021-03-08 |
Time |
10:01 |
Sent To |
|
|
| Notes |
| 2021-03-08 10:08:36 | NOT ALL OF THE REQUIRED THRESHOLD NOTARIZED FORMS AND | | | INFORMATION WAS SUBMITTED. PLEASE CONTACT ME AT | | | [email protected] WITH AN EMAIL ADDRESS AND I WILL SEND | | | YOU THE CURRENT (OCTOBER 2018) GUIDELINES AND POLICIES | | | FOR PROJECTS CONCERNING THRESHOLD/SPECIAL INSPECTORS | | | AND RESIDENT INSPECTORS WITH ALL OF THE REQUIRED FORMS | | | TO BE FILLED OUT, NOTARIZED AND SUBMITTED. | | | | | | | | | THRESHOLD BUILDING / FL S. S. 553.71(7) "THRESHOLD | | | BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN | | | (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN | | | ASSEMBLY OCCUPANCY CLASSIFICATION AS DEFINED IN THE | | | FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN | | | AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 | | | PERSONS. | | | | | | A) FBC (CITY AMENDMENTS)110.8.1 THRESHOLD INSPECTION | | | PLAN. THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL | | | INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A | | | THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION | | | PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL | | | INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING | | | AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR | | | THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE | | | OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE | | | SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT | | | THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE | | | WITH THE PERMITTED DOCUMENTS. | | | | | | B) THRESHOLD INSPECTOR: WPB AMENDMENT 110.8.1 W.P.B. | | | CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD | | | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY 553.79(5) | | | FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY | | | THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED | | | TO BE FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED | | | AND RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED | | | BEFORE PERMIT ISSUANCE WILL TAKE PLACE. | | | | | | C) THRESHOLD BLDG. REQUIRED STATEMENT: W.P.B. AMENDMENT | | | 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED | | | TO BE SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF | | | RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE | | | ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND | | | SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM | | | BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS | | | AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH | | | THIS SECTION AND CHAPTER 633 FLORIDA STATUTES. | | | | | | D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME OF | | | INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME | | | MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED | | | HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL | | | REVIEW THE RESUME. AFTER THE RESUME IS REVIEWED, AN | | | INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES | | | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST | | | MEETING THE ABOVE CRITERIA. | | | | | | E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY | | | FOR THIS TYPE OF CONSTRUCTION. | | | | | | F) NOTE: FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, | | | PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING | | | ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE | | | APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR | | | PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN | | | COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR | | | THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE | | | IN BLACK & WHITE. | | | | | | G) 110.8.4.3 ALL SHORING AND RESHORING PROCEDURES, | | | PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT | | | AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING | | | INSTALLATION SHALL BE SUPERVISED, INSPECTED AND | | | CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING | | | DOCUMENTS BY THE CONTRACTOR. | | | | | | H) PLEASE CALL THE CITY OF WEST PALM BEACH'S AUTOMATED | | | TELEPHONE INSPECTIONS LINE (561) 805-6700 FOR ALL | | | BUILDING INSPECTIONS FOR AUDITING OF JOBSITE | | | INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6 | | | MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. | | | | | | I) 110.8 THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR | | | THRESHOLD INSPECTORS #25. ASSURE THAT THE DESIGNER HAS | | | REQUIRED ON THE PLANS OR SPECIFICATIONS ONE MATERIAL, | | | APPROVED FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND | | | CEILINGS. | | | | | | J) PLEASE CONTACT ME WITH AN EMAIL ADDRESS AND I WILL | | | BE HAPPY TO SEND YOU A COPY OF THE CURRENT (OCTOBER | | | 2018) GUIDELINES AND POLICIES FOR PROJECTS CONCERNING | | | THRESHOLD/SPECIAL INSPECTORS AND RESIDENT INSPECTORS. | | | | | | | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
2 |
Status |
F |
Date |
2020-12-21 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2020-12-21 |
Time |
14:03 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2020-12-21 |
Time |
14:03 |
Sent To |
|
|
| Notes |
| 2020-12-21 14:04:32 | THE REQUIRED THRESHOLD DOCUMENTS HAVE NOT BEEN | | | SUBMITTED. SEE PREVIOUS REVIEW COMMENTS. |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
1 |
Status |
F |
Date |
2020-11-02 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2020-11-02 |
Time |
07:42 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2020-11-02 |
Time |
07:42 |
Sent To |
|
|
| Notes |
| 2020-11-02 08:10:30 | THRESHOLD BUILDING / FL S. S. 553.71(7) "THRESHOLD | | | BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN | | | (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN | | | ASSEMBLY OCCUPANCY CLASSIFICATION AS DEFINED IN THE | | | FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN | | | AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 | | | PERSONS. | | | | | | A) FBC (CITY AMENDMENTS)110.8.1 THRESHOLD INSPECTION | | | PLAN. THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL | | | INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A | | | THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION | | | PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL | | | INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING | | | AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR | | | THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE | | | OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE | | | SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT | | | THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE | | | WITH THE PERMITTED DOCUMENTS. | | | | | | B) THRESHOLD INSPECTOR: WPB AMENDMENT 110.8.1 W.P.B. | | | CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD | | | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY 553.79(5) | | | FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY | | | THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED | | | TO BE FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED | | | AND RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED | | | BEFORE PERMIT ISSUANCE WILL TAKE PLACE. | | | | | | C) THRESHOLD BLDG. REQUIRED STATEMENT: W.P.B. AMENDMENT | | | 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED | | | TO BE SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF | | | RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE | | | ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND | | | SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM | | | BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS | | | AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH | | | THIS SECTION AND CHAPTER 633 FLORIDA STATUTES. | | | | | | D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME OF | | | INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME | | | MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED | | | HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL | | | REVIEW THE RESUME. AFTER THE RESUME IS REVIEWED, AN | | | INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES | | | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST | | | MEETING THE ABOVE CRITERIA. | | | | | | E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY | | | FOR THIS TYPE OF CONSTRUCTION. | | | | | | F) NOTE: FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, | | | PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING | | | ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE | | | APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR | | | PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN | | | COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR | | | THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE | | | IN BLACK & WHITE. | | | | | | G) 110.8.4.3 ALL SHORING AND RESHORING PROCEDURES, | | | PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT | | | AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING | | | INSTALLATION SHALL BE SUPERVISED, INSPECTED AND | | | CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING | | | DOCUMENTS BY THE CONTRACTOR. | | | | | | H) PLEASE CALL THE CITY OF WEST PALM BEACH'S AUTOMATED | | | TELEPHONE INSPECTIONS LINE (561) 805-6700 FOR ALL | | | BUILDING INSPECTIONS FOR AUDITING OF JOBSITE | | | INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6 | | | MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. | | | | | | I) 110.8 THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR | | | THRESHOLD INSPECTORS #25. ASSURE THAT THE DESIGNER HAS | | | REQUIRED ON THE PLANS OR SPECIFICATIONS ONE MATERIAL, | | | APPROVED FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND | | | CEILINGS. | | | | | | J) PLEASE CONTACT ME WITH AN EMAIL ADDRESS AND I WILL | | | BE HAPPY TO SEND YOU A COPY OF THE CURRENT (OCTOBER | | | 2018) GUIDELINES AND POLICIES FOR PROJECTS CONCERNING | | | THRESHOLD/SPECIAL INSPECTORS AND RESIDENT INSPECTORS. | | | | | | | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
5 |
Status |
P |
Date |
2021-10-12 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2021-10-12 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2021-10-12 |
Time |
|
Sent To |
|
|
| Notes |
| 2021-10-12 08:45:25 | ZONING APPROVED WITH THE FOLLOWING PROVISOS: | | | | | | 1.) SEPARATE PERMITS REQUIRED FOR: SIGNAGE, | | | LANDSCAPING, SITE LIGHTING, FENCING, DUMPSTER | | | ENCLOSURE, PARKING AREA PAVING AND STRIPING. | | | | | | 2.) ANY CHANGE TO THE APPROVED PLANS SHALL REQUIRED A | | | PLANNED DEVELOPMENT (PD) AMENDMENT SUBMISSION BY THE | | | APPLICANT AND APPROVED BY THE DEVELOPMENT SERVICES | | | DEPARTMENT - PLANNING DIVISION. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2021-06-21 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2021-06-21 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2021-06-21 |
Time |
|
Sent To |
|
|
| Notes |
| 2021-06-21 12:06:48 | ZONING APPROVED WITH THE FOLLOWING PROVISOS: | | | | | | 1.) SEPARATE PERMITS REQUIRED FOR: SIGNAGE, | | | LANDSCAPING, SITE LIGHTING, FENCING, DUMPSTER | | | ENCLOSURES, PARKING AREA PAVING/STRIPING. | | | | | | 2.) ANY CHANGES TO THE APPROVED PLANS SHALL REQUIRE A | | | PD AMENDMENT SUBMISSION BY THE APPLICANT AND APPROVAL | | | BY THE DEVELOPMENT SERVICES DEPARTMENT - PLANNING | | | DIVISION. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2021-03-30 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2021-03-30 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2021-03-30 |
Time |
|
Sent To |
|
|
| Notes |
| 2021-03-30 10:30:44 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | 1.) THE SURVEY AND APPROVED PLAT DOCUMENTS ARE MISSING | | | FROM THE PERMIT SUBMITTAL. THESE ARE CRITICAL | | | COMPONENTS OF THE BUILDING PERMIT SET. PLEASE PROVIDE. | | | | | | | | | NOTES: | | | | | | * ANY CHANGES WHICH DEVIATE FROM THE PLANS APPROVED BY | | | THE CITY COMMISSION WILL REQUIRE AN AMENDMENT TO THE | | | OCPD (OFFICE COMMERCIAL PLANNED DEVELOPMENT). THE | | | AMENDMENT WILL REQUIRE REVIEW AND APPROVAL BY THE | | | PLANNING DIVISION PRIOR TO THE APPROVAL OF SUCH CHANGES | | | FOR BUILDING PERMIT. | | | | | | * SEPARATE PERMIT REQUIRED FOR LANDSCAPING. | | | | | | * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS. | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | | QUESTIONS. | | | | | | * ZONE: HOLIDAY INN EXPRESS OCPD (REFERENCE: RESOLUTION | | | NOS. 338-20 AND 339-20) | | | | | | * LEFT VOICE MESSAGE FOR COREY RUNTE OF CERTIFIED | | | GENERAL CONTRACTORS ON 3/30/21 REQUESTING SURVEY AND | | | PLAT DOCUMENTS AS PART OF THE BUILDING PERMIT SET/FILE. | | | ALSO INFORMED THAT ANY CHANGES WILL REQUIRE PD | | | AMENDMENT. FOLLOW-EMAIL PROVIDED. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2020-12-07 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2020-12-07 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2020-12-07 |
Time |
|
Sent To |
|
|
| Notes |
| 2020-12-07 13:30:08 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | 1.) PROJECT REQUIRES APPROVAL FROM THE CITY COMMISSION. | | | PROJECT IS CURRENTLY IN REVIEW AND PENDING APPROVAL | | | (REFERENCE: PB CASE NO. 1846). [10/20 REPEAT COMMENT: | | | APPLICATION PB NO. 1846 IS STILL PENDING; SCHEDULED FOR | | | FIRST READING ON 12/14/20] | | | | | | | | | NOTES: | | | | | | * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS. | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | | QUESTIONS. | | | | | | * ZONE: PROPOSED REZONING TO OCPDD (HOLIDAY INN | | | EXPRESS). | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2020-10-20 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2020-10-20 |
Time |
|
Rev Time |
|
| Received By |
llouie |
Date |
2020-10-20 |
Time |
|
Sent To |
|
|
| Notes |
| 2020-10-20 18:10:39 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | 1.) PROJECT REQUIRES APPROVAL FROM THE CITY COMMISSION. | | | PROJECT IS CURRENTLY IN REVIEW AND PENDING APPROVAL | | | (REFERENCE: PB CASE NO. 1846). | | | | | | | | | NOTES: | | | | | | * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS. | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | | QUESTIONS. | | | | | | * ZONE: PROPOSED REZONING TO OCPDD (HOLIDAY INN | | | EXPRESS). | | | |
|
|
|