Plan Review Details - Permit 20090848
Plan Review Stops For Permit 20090848
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2021-01-19 Cont ID  
Sent By cpuell Date 2021-01-19 Time 10:45 Rev Time 0.00
Received By cpuell Date 2021-01-19 Time 10:45 Sent To  
Notes
2021-01-19 10:46:40NEW HOTEL WILL HAVE ADDRESS OF 1221 BELVEDERE RD

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2020-10-16 Cont ID  
Sent By cpuell Date 2020-10-16 Time 15:13 Rev Time 0.00
Received By cpuell Date 2020-10-16 Time 15:13 Sent To  
Notes
2020-10-16 15:15:29PLEASE EMAIL [email protected] A SITE PLAN AND FIRST FLOOR
 PLAN CLEARLY MARKING THE MAIN ENTRANCE TO THE PROPERTY.

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 4 Status P Date 2021-05-26 Cont ID  
Sent By dbattles Date 2021-05-26 Time 10:53 Rev Time 0.00
Received By dbattles Date 2021-05-26 Time 10:53 Sent To  
Notes
2021-05-26 10:54:25AIPP SATIFIED PER E-MAIL ON 5/26/21 FORM S.W.
 PLEASE RELEASE THE CO HOLD ON PERMIT #20090848 AD1 PB2
 AIRPORT HOTELS 1301 BELVEDERE ROAD, THEY HAVE SATISFIED
 THE PUBLIC ART REQUIREMENT.

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 3 Status F Date 2021-03-30 Cont ID  
Sent By scwelter Date 2021-03-30 Time 15:18 Rev Time 0.00
Received By scwelter Date   Time   Sent To  
Notes
***NONE***

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 2 Status F Date 2021-03-05 Cont ID  
Sent By rmcdouga Date 2021-03-05 Time 11:21 Rev Time 0.00
Received By rmcdouga Date 2021-03-05 Time 11:21 Sent To  
Notes
2021-03-05 11:27:18A HOLD HAS BEEN PLACED ON THE C.O. HOWEVER, BEFORE THE
 PERMIT IS ISSUED YOU ARE REQUIRED TO CONTACT SYBILLIE
 WELTER AND FILE AN APPLICATION FOR ART IN PUBLIC
 PLACES. HER PHONE NUMBER IS 561-822-1521 AND HER EMAIL
 IS [email protected].

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status F Date 2020-11-02 Cont ID  
Sent By rmcdouga Date 2020-11-02 Time 07:35 Rev Time 0.00
Received By rmcdouga Date 2020-11-02 Time 07:35 Sent To  
Notes
2020-11-02 07:36:08THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES
 ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR
 NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT
 APPLICATION WAS SUBMITTED AFTER 6/29/14, AND THE TOTAL
 PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $750,000 WILL NEED TO COMPLY WITH THIS ORDINANCE.
 PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND
 CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V,
 ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION
 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL
 PROJECT CONSTRUCTION COST.
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
 FOR INFORMATION PLEASE CONTACT: MS. SYBILLE WELTER, ART
 IN PUBLIC PLACES COORDINATOR AT 822-1521 OR E-MAIL:
 [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2021-10-12 Cont ID  
Sent By rmcdouga Date 2021-10-12 Time 17:00 Rev Time 0.00
Received By rmcdouga Date 2021-10-07 Time 09:44 Sent To  
Notes
2021-10-12 15:55:09PLAN
 REVIEW COMMENTS
  
 5TH REVIEW
 FBC SIXTH EDITION (2017) & CITY OF W.P.B. CHAPTER 1
 AMENDMENTS
 CITY ORDINANCES
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
 NEW 4 STORY HOTEL
 TYPE II-B CONSTRUCTION
 R-1 OCCUPANCY TYPE
 FLOOD ZONE AE, BFE 12.7' NAVD88 (DFE 14.7' NAVD 88
 INCLUDES 2' FREEBOARD)
  
 1) COMPLIED.
  
 2) COMPLIED.
  
 3) PARTIALLY COMPLIED. THE BUILDING OFFICIAL, ROBERT
 BROWN, HAS CONDITIONALLY AGREED TO ACCEPT THE OPTION TO
 ENCLOSE THE WINDOW OPENINGS THAT EXCEED THE AMOUNT OF
 ALLOWABLE OPENINGS BASED ON THE FIRE SEPARATION
 DISTANCE TO THE RE-PLATTED PROPERTY LINE IN THE
 EXISTING HOTEL. THE CONDITIONS ARE THAT A HOLD WILL BE
 PLACED ON THE PROPOSED HOTEL'S C.O. UNTIL THE ALLOWABLE
 OPENINGS ISSUE IS RESOLVED AND THE PROPOSED WORK TO
 ENCLOSE THE WINDOW OPENINGS IS REQUIRED TO BE SHOWN ON
 THE REMODEL PLANS FOR THE EXISTING HOTEL LOCATED AT
 1301 BELVEDERE RD. UNDER PERMIT #20120964.
  
 4) NOT COMPLIED. [BARRIER AND MOT PLANS STILL HAVE NOT
 BEEN SUBMITTED.](NO PLANS FOR THIS HAVE BEEN
 SUBMITTED.) SHOW COMPLIANCE WITH FBC CHAPTER 33 FOR
 SAFEGUARDS DURING CONSTRUCTION. SUBMIT BARRIER AND MOT
 PLANS.
  
 5) PROVISO. PRODUCT APPROVALS TO BE DEFERRED. THERE IS
 A LIST OF PRODUCT APPROVALS TO BE DEFERRED ON SHEET
 A011. DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 6) PROVISO. NOTED ON THE PLANS.
 SEPARATE PERMITS, PLANS AND FEES WILL BE REQUIRED FOR
 THE FOLLOWING:
 LIGHT POLES/SITE LIGHTING
 FIRE ALARM
 FIRE SPRINKLER
 LOW VOLTAGE
 ACCESS
 LANDSCAPING
 IRRIGATION
 PARKING LOT
 DUMPSTER ENCLOSURE
 SITE WALLS
 ALL OTHER ITEMS OTHER THAN BMEP
  
 7) NOTE: A SEPARATE SUB-PERMIT IS REQUIRED FOR ROOFING.
  
 8) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
  
 9) COMPLIED.
  
 10) NEW COMMENT. THE PRODUCT APPROVAL THAT WAS
 SUBMITTED FOR THE ROOF HATCH, NOA NO. 18-0110.05, HAS
 NOT BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. FBC 107. FBC 107.3.4 - PROVIDE TWO
 SETS OF PRODUCT APPROVALS FOR THOSE PRODUCTS WHICH ARE
 REGULATED BY FAC 61G20-3.001 PER FLORIDA STATUTE
 553.842 (5) THAT HAVE BEEN REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD. PROVIDE TWO COMPLETE
 PRODUCT APPROVALS WITH FL OR NOA NUMBERS INCLUDING
 INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES
 FOR EACH OF THE DIFFERENT ROOFING MATERIALS, WINDOW
 (GLASS TYPES), STRUCTURAL MULLIONS AND EXTERIOR DOOR
 TYPES. THESE ITEMS CAN BE DEFERRED IF REQUESTED,
 HOWEVER, THE DOCUMENTS MUST BE SUBMITTED AND APPROVED
 BY THE BUILDING DEPARTMENT BEFORE THEY CAN BE
 INSTALLED. ONLY ONE SET IS REQUIRED TO BE UPLOADED FOR
 ELECTRONICALLY SUBMITTED DOCUMENTS.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2021-06-29 Cont ID  
Sent By rmcdouga Date 2021-06-29 Time 15:15 Rev Time 0.00
Received By rmcdouga Date 2021-06-28 Time 14:02 Sent To  
Notes
2021-06-29 14:20:21PLAN
 REVIEW COMMENTS
  
 4TH REVIEW
 FBC SIXTH EDITION (2017) & CITY OF W.P.B. CHAPTER 1
 AMENDMENTS
 CITY ORDINANCES
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
 NEW 4 STORY HOTEL
 TYPE II-B CONSTRUCTION
 R-1 OCCUPANCY TYPE
 FLOOD ZONE AE, BFE 12.7' NAVD88 (DFE 14.7' NAVD 88
 INCLUDES 2' FREEBOARD)
  
 NOTE: THE NUMBERING IS OFF ON THE RESPONSES STARTING AT
 NUMBER 17. THE RESPONSE FOR #17 IS ACTUALLY FOR COMMENT
 # 18 AND SO ON.
  
 1) THE PRE-CONSTRUCTION ELEVATION CERTIFICATE HAS
 ERRORS. THE LATITUDE AND LONGITUDE ARE REVERSED ON THE
 CERTIFICATE (IE. THE LONGITUDE IS IN THE SPACE FOR
 LATITUDE AND THE LATITUDE IS IN THE SPACE FOR
 LONGITUDE). THE NORTH AND WEST DESIGNATIONS WERE NOT
 SPECIFIED FOR LONGITUDE AND LATITUDE. NOTE: THE
 COORDINATES ARE REQUIRED TO BE WITHIN 66 FEET OF THE
 MAIN BUILDING ENTRANCE. [PREVIOUS COMMENT #2. THE NOT
 COMPLIED.] [PRECONSTRUCTION ELEVATION CERTIFICATE WAS
 NOT SUBMITTED.] (THE PERMIT CAN NOT BE ISSUED UNTIL A
 PRE-CONSTRUCTION ELEVATION CERTIFICATE HAS BEEN
 SUBMITTED AND APPROVED.) THIS PROJECT IS LOCATED IN A
 SPECIAL FLOOD HAZARD AREA (AE FLOOD ZONE). SEE NFIP
 REVIEW COMMENTS.
  
 2) ENGINEERING APPROVAL IS REQUIRED. [PREVIOUS COMMENT
 #3. NOT COMPLIED.] [SEE ENGINEERING COMMENT THAT STATES
 SITE PLAN HAS NOT BEEN APPROVED](THE PERMIT CAN NOT BE
 ISSUED UNTIL MINOR LOT SUBDIVISION HAS BEEN APPROVED.)
 THE SITE PLAN SHOWS A PROPERTY LINE THAT IS PART OF
 ANOTHER PARCEL ON THE PALM BEACH COUNTY PROPERTY
 APPRAISER'S WEB SITE. PROVIDE A COPY OF THE RECORDED
 PLAT FOR THIS LOT DIVISION. FBC 107.2
  
 3) SITE PLANS WERE SUBMITTED FOR REFERENCE. A REVIEW OF
 THESE DOCUMENTS, PREVIOUS COMMENT #4, HAS RESULTED IN
 THE FOLLOWING ADDITIONAL COMMENTS.
 A) SHOW HOW THE EXISTING HOTEL WILL COMPLY WITH FBC
 705.8 MAXIMUM AREA OF EXTERIOR WALL OPENINGS BASED ON
 FIRE SEPARATION DISTANCE TO THE PROPOSED PARCEL LINE
 BETWEEN THE TWO BUILDINGS.
 B) THE PLANS SPECIFY (5) ACCESSIBLE PARKING SPACES. FBC
 ACCESSIBILITY 208.2 REQUIRES (9) ACCESSIBILE SPACES FOR
 PARKING FACILITIES WITH 401 - 500 SPACES AND (8)
 ACCESSIBILE SPACES FOR PARKING FACILITIES WITH 301 -
 400 SPACES. THE ACTUAL NUMBER WILL DEPEND ON THE TOTAL
 NUMBER OF SPACES IF THE WAVIER THAT YOU HAVE REQUESTED
 IS GRANTED OR NOT. FBC ACCESSIBILITY 208.2.4 REQUIRES
 (2) OF THE ACCESSIBILE SPACES TO BE VAN PARKING SPACES.
 (ONE FOR EVERY SIX OR FRACTION OF SIX ACCESSIBLE
 SPACES.)
  
 4) PREVIOUS COMMENT #6. NOT COMPLIED. [BARRIER AND MOT
 PLANS STILL HAVE NOT BEEN SUBMITTED.](NO PLANS FOR THIS
 HAS BEEN SUBMITTED.) SHOW COMPLIANCE WITH FBC CHAPTER
 33 FOR SAFEGUARDS DURING CONSTRUCTION. SUBMIT BARRIER
 AND MOT PLANS.
  
 5) PROVISO. PRODUCT APPROVALS TO BE DEFERRED. THERE IS
 A LIST OF PRODUCT APPROVALS TO BE DEFERRED ON SHEET
 A011. DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 6) PROVISO. NOTED ON THE PLANS.
 SEPARATE PERMITS, PLANS AND FEES WILL BE REQUIRED FOR
 THE FOLLOWING:
 LIGHT POLES/SITE LIGHTING
 FIRE ALARM
 FIRE SPRINKLER
 LOW VOLTAGE
 ACCESS
 LANDSCAPING
 IRRIGATION
 PARKING LOT
 DUMPSTER ENCLOSURE
 SITE WALLS
 ALL OTHER ITEMS OTHER THAN BMEP
  
 7) NOTE: A SEPARATE SUB-PERMIT IS REQUIRED FOR ROOFING.
  
 8) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
  
 9) [PREVIOUS COMMENT #23.] NOT COMPLIED. [SEE THE
 MARKUP CLOUDS AT MISSING PRESSURES ON PAGES 096-S200
 AND 097-S201. ALSO SEE THE MARKUPS ON PAGE 100-S204
 GRIDLINES 1 AND 6 WHICH ARE EXTERIOR WALL ELEVATIONS.]
 NEW COMMENT: SOME OF THE COMPONENT AND CLADDING
 PRESSURES AND NEGATIVE SIGNS ARE MISSING FROM THE
 ELEVATIONS ON THE STRUCTURAL DRAWINGS. FBC 107.2.1 &
 1609
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-03-08 Cont ID  
Sent By rmcdouga Date 2021-03-08 Time 09:55 Rev Time 0.00
Received By rmcdouga Date 2021-03-05 Time 08:50 Sent To  
Notes
2021-03-05 11:27:49PLAN
 REVIEW COMMENTS
  
 3RD REVIEW
 FBC SIXTH EDITION (2017) & CITY OF W.P.B. CHAPTER 1
 AMENDMENTS
 CITY ORDINANCES
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
 NEW 4 STORY HOTEL
 TYPE II-B CONSTRUCTION
 R-1 OCCUPANCY TYPE
 FLOOD ZONE AE, BFE 12.7' NAVD88 (DFE 14.7' NAVD 88
 INCLUDES 2' FREEBOARD)
  
 NOTE: THE NUMBERING IS OFF ON THE RESPONSES STARTING AT
 NUMBER 17. THE RESPONSE FOR #17 IS ACTUALLY FOR COMMENT
 # 18 AND SO ON.
  
 1) COMPLIED.
  
 2) NOT COMPLIED. [PRECONSTRUCTION ELEVATION CERTIFICATE
 WAS NOT SUBMITTED.] (THE PERMIT CAN NOT BE ISSUED UNTIL
 A PRE-CONSTRUCTION ELEVATION CERTIFICATE HAS BEEN
 SUBMITTED AND APPROVED.) THIS PROJECT IS LOCATED IN A
 SPECIAL FLOOD HAZARD AREA (AE FLOOD ZONE). SEE NFIP
 REVIEW COMMENTS.
  
 3) NOT COMPLIED. [SEE ENGINEERING COMMENT THAT STATES
 SITE PLAN HAS NOT BEEN APPROVED](THE PERMIT CAN NOT BE
 ISSUED UNTIL MINOR LOT SUBDIVISION HAS BEEN APPROVED.)
 THE SITE PLAN SHOWS A PROPERTY LINE THAT IS PART OF
 ANOTHER PARCEL ON THE PALM BEACH COUNTY PROPERTY
 APPRAISER'S WEB SITE. PROVIDE A COPY OF THE RECORDED
 PLAT FOR THIS LOT DIVISION. FBC 107.2
  
 4) NOT COMPLIED. [THE REQUESTED DETAILED SITE PLAN
 NEEDS TO BE SUBMITTED WITH THE DOCUMENTS FOR THIS
 PERMIT.] (NO DETAILED SITE PLAN WITH REQUESTED
 INFORMATION WAS SUBMITTED. ALL ELEVATIONS ARE REQUIRED
 TO BE IN NAVD 88.) FBC 107.2.5 SITE PLAN. THE
 CONSTRUCTION DOCUMENTS SUBMITTED WITH THE APPLICATION
 FOR PERMIT SHALL BE ACCOMPANIED BY A SITE PLAN SHOWING
 TO SCALE THE SIZE AND LOCATION OF NEW CONSTRUCTION AND
 EXISTING STRUCTURES ON THE SITE, DISTANCES FROM LOT
 LINES, THE ESTABLISHED STREET GRADES AND THE PROPOSED
 FINISHED GRADES AND, AS APPLICABLE, FLOOD HAZARD AREAS,
 FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT SHALL BE
 DRAWN IN ACCORDANCE WITH AN ACCURATE BOUNDARY LINE
 SURVEY. PROVIDE SITE PLAN WITH ELEVATIONS OF THE
 BUILDING, PARKING LOT, ACCESSIBLE PARKING, ACCESSIBLE
 ROUTES, ETC.
  
 5) NOT COMPLIED. [ENGINEERING HAS NOT APPROVED THE SITE
 PLAN.] (NO CIVIL PLANS WERE SUBMITTED.) SHOW COMPLIANCE
 WITH FBC 110.9 IMPACT OF CONSTRUCTION. ALL CONSTRUCTION
 ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A
 MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF
 ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO
 AFFECT SAID PROPERTY PURSUANT TO A CONSENT GRANTED BY
 THE APPLICABLE PROPERTY OWNER, UNDER TERMS OR
 CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY OWNER.
 THIS INCLUDES, BUT IS NOT LIMITED TO, THE CONTROL OF
 DUST, NOISE, WATER OR DRAINAGE RUN-OFFS, DEBRIS, AND
 THE STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT LEGAL HISTORIC
 SURFACE WATER DRAINAGE FLOWS SERVING ADJACENT
 PROPERTIES, AND MAY REQUIRE SPECIAL DRAINAGE DESIGN
 COMPLYING WITH ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE DRAINAGE PATTERNS OF THE AFFECTED SITES.
 ACCORDINGLY, DEVELOPERS, CONTRACTORS AND OWNERS OF ALL
 NEW RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS,
 POOLS, PATIOS, DRIVEWAYS, DECKS OR SIMILAR ITEMS, ON
 EXISTING PROPERTIES RESULTING IN A SIGNIFICANT DECREASE
 OF PERMEABLE LAND AREA ON ANY PARCEL OR HAS ALTERED THE
 DRAINAGE FLOW ON THE DEVELOPED PROPERTY SHALL, AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED PROFESSIONAL SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 6) NOT COMPLIED. [BARRIER AND MOT PLANS STILL HAVE NOT
 BEEN SUBMITTED.](NO PLANS FOR THIS HAS BEEN SUBMITTED.)
 SHOW COMPLIANCE WITH FBC CHAPTER 33 FOR SAFEGUARDS
 DURING CONSTRUCTION. SUBMIT BARRIER AND MOT PLANS.
  
 7) COMPLIED.
  
 8) COMPLIED.
  
 9) COMPLIED.
  
 10) COMPLIED.
  
 11) NOT COMPLIED. [THE REQUEST TO DEFER PRODUCT
 APPROVALS IS NOT CLEAR. THE REQUEST FOR THE PRODUCT
 APPROVALS AND OTHER ITEMS TO BE DEFERRED IS REQUIRED TO
 BE ON THE PLANS WITH THE ITEMS LISTED OR THEY WILL NEED
 TO BE SUBMITTED AND APPROVED BEFORE THE PERMIT IS
 ISSUED.] (PRODUCT APPROVALS TO BE DEFERRED. THERE IS A
 LIST OF PRODUCT APPROVALS ON SHEET A011.) THE CITY
 AMENDMENTS REQUIRES THAT PRODUCT APPROVALS ARE TO BE
 SUBMITTED FOR APPROVAL AFTER THEY HAVE BEEN REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR
 THE PROJECT. FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT
 APPROVALS FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT
 ROOFING MATERIALS, WINDOWS (GLASS TYPES), STRUCTURAL
 MULLIONS, STORE FRONTS, EXTERIOR DOORS, ETC. THESE
 ITEMS CAN BE DEFERRED IF REQUESTED, HOWEVER, THE
 DOCUMENTS MUST BE SUBMITTED AND APPROVED BY THE
 BUILDING DEPARTMENT BEFORE THEY CAN BE INSTALLED. ONLY
 ONE SET IS REQUIRED TO BE UPLOADED FOR ELECTRONICALLY
 SUBMITTED DOCUMENTS.
 FBC 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL. SHOP DRAWINGS AND
 CALCULATIONS FROM DELEGATE ENGINEERS SHOULD BE INCLUDED
 ON THE LIST.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 12) NOT COMPLIED. [THIS IS REQUIRED TO BE ON DOCUMENTS
 FOR THIS PERMIT.] (ELEVATIONS TO BE IN NAVD 88.)
 PROVIDE THE FLOOR ELEVATIONS ON THE FLOOR PLAN OF THE
 GROUND FLOOR, THE BUILDING ELEVATIONS AND BUILDING
 SECTIONS. FBC 107.2
  
 13) PROVISO. NOTED ON THE PLANS.
 SEPARATE PERMITS, PLANS AND FEES WILL BE REQUIRED FOR
 THE FOLLOWING:
 LIGHT POLES/SITE LIGHTING
 FIRE ALARM
 FIRE SPRINKLER
 LOW VOLTAGE
 ACCESS
 LANDSCAPING
 IRRIGATION
 PARKING LOT
 DUMPSTER ENCLOSURE
 SITE WALLS
 ALL OTHER ITEMS OTHER THAN BMEP
  
 14) PROVISO. PRODUCT APPROVALS FOR THE ROOFING
 MATERIALS TO BE APPROVED BY THE DESIGNER OF RECORD,
 SUBMITTED AND APPROVED BY THE BUILDING DEPARTMENT
 BEFORE THE ROOFING PERMIT IS ISSUED. A SEPARATE SUB-
 PERMIT AND APPLICATION IS REQUIRED FOR ROOFING.
  
 15) COMPLIED.
  
 16) COMPLIED.
  
 17) COMPLIED.
  
 18) NOT COMPLIED. [NONE OF THE REQUESTED INFORMATION
 HAS BEEN PROVIDED FOR THIS PERMIT.] (SHEET A100, THE
 SITE PLAN, REFERS TO CIVIL DRAWINGS WHICH WERE NOT
 SUBMITTED WITH THE CONSTRUCTION DOCUMENTS FOR REQUIRED
 PARKING INFORMATION. THE FINISH FLOOR ELEVATION IS
 SPECIFIED AS 15.0 BUT THE VERTICAL DATA IS NOT
 SPECIFIED. PLEASE USE NAVD 88.) PROVIDE A PARKING LOT
 PLAN THAT SHOWS THE TOTAL NUMBER OF PARKING SPACES, THE
 TOTAL NUMBER OF REQUIRED AND PROVIDED ACCESSIBLE
 SPACES, THE ACCESSIBLE VAN PARKING SPACES AND THE
 LOCATIONS OF THE ACCESSIBLE PARKING SPACES. FBC
 ACCESSIBILITY SECTIONS 208 & 502
  
 19) NOT COMPLIED. [AGAIN. THE REQUESTED INFORMATION
 NEEDS TO BE WITH THE DOCUMENTS FOR THIS PERMIT.] SHOW
 THAT THE PASSENGER LOADING ZONE COMPLIES WITH FBC
 SECTIONS 209 & 503.
  
 20) NOT COMPLIED. [ THIS NEEDS TO BE SHOWN ON THE
 DRAWINGS. TYPICALLY THE STRETCHER IS DRAWN INTO THE
 ELEVATOR ON THE PLANS WITH THE DIMENSIONS PROVIDED.]
 SHOW COMPLIANCE WITH 3002.4 ELEVATOR CAR TO ACCOMMODATE
 AMBULANCE STRETCHER. ANY BUILDING THAT IS MORE THAN
 THREE STORIES HIGH OR IN WHICH THE VERTICAL DISTANCE
 BETWEEN THE BOTTOM TERMINAL LANDING AND THE TOP
 TERMINAL LANDING EXCEEDS 25 FEET (7620 MM), MUST BE
 CONSTRUCTED TO CONTAIN AT LEAST ONE PASSENGER ELEVATOR
 THAT IS OPERATIONAL FOR BUILDING OCCUPANTS AND FIRE
 DEPARTMENT EMERGENCY ACCESS TO ALL FLOORS. THE ELEVATOR
 CAR SHALL BE OF SUCH A SIZE AND ARRANGEMENT TO
 ACCOMMODATE AN AMBULANCE STRETCHER 24 INCHES BY 76
 INCHES (610 MM BY 1950 MM) WITH NOT LESS THAN 5-INCH
 (127 MM) RADIUS CORNERS, IN THE HORIZONTAL, OPEN
 POSITION AND SHALL BE IDENTIFIED BY THE INTERNATIONAL
 SYMBOL FOR EMERGENCY MEDICAL SERVICES (STAR OF LIFE).
 THE SYMBOL SHALL BE NOT LESS THAN 3 INCHES (76 MM) IN
 HEIGHT AND SHALL BE PLACED INSIDE ON BOTH SIDES OF THE
 HOISTWAY DOOR FRAME.
  
 21) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
  
 NEW COMMENTS FROM PREVIOUS REVIEW:
  
 22) COMPLIED.
  
 23) NOT COMPLIED. [SEE THE MARKUP CLOUDS AT MISSING
 PRESSURES ON PAGES 096-S200 AND 097-S201. ALSO SEE THE
 MARKUPS ON PAGE 100-S204 GRIDLINES 1 AND 6 WHICH ARE
 EXTERIOR WALL ELEVATIONS.] NEW COMMENT: SOME OF THE
 COMPONENT AND CLADDING PRESSURES AND NEGATIVE SIGNS ARE
 MISSING FROM THE ELEVATIONS ON THE STRUCTURAL DRAWINGS.
 FBC 107.2.1 & 1609
  
 24) COMPLIED.
  
 25) COMPLIED.
  
 26 ) COMPLIED.
  
 27) NOT COMPLIED. [THE SIZE OF THE ROOF HATCH IS NOT
 SPECIFIED ON SHEETS A550 OR A011. THE RESPONSE COMMENT
 SPECIFIES A 30" X 54" ROOF ACCESS HATCH. THESE
 DIMENSIONS PROVIDE 11.25 SQFT AND DO NOT MEET THE
 REQUIRED MINIMUM SIZE OF 16 SQFT.] NEW COMMENT. I DID
 NOT SEE THAT THE SIZE OF THE ROOF HATCH IS SPECIFIED ON
 THE DRAWINGS. THE MINIMUM SIZE IS 16 SQFT WITH THE
 SMALLEST DIMENSION NOT LESS THAN 2 FT. PER
 FBC1011.12.2. IF THE ROOF HATCH IS WITHIN 10 FT OF THE
 ROOF EDGE A GUARD IS REQUIRED PER FBC1011.13 INSTALLED
 IN ACCORDANCE WITH FBC1015.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-12-22 Cont ID  
Sent By rmcdouga Date 2020-12-22 Time 10:13 Rev Time 0.00
Received By rmcdouga Date 2020-12-21 Time 07:23 Sent To  
Notes
2020-12-21 10:03:43PLAN
 REVIEW COMMENTS
  
 2ND REVIEW
 FBC SIXTH EDITION (2017) & CITY OF W.P.B. CHAPTER 1
 AMENDMENTS
 CITY ORDINANCES
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
 NEW 4 STORY HOTEL
 TYPE II-B CONSTRUCTION
 R-1 OCCUPANCY TYPE
 FLOOD ZONE AE, BFE 12.7' NAVD88 (DFE 14.7' NAVD 88
 INCLUDES 2' FREEBOARD)
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) COMPLIED. THE PLANS ARE NOW IN COMPLIANCE. SEE
 THRESHOLD REVIEW FOR ADDITIONAL REQUIREMENTS.
  
 2) NOT COMPLIED. (THE PERMIT CAN NOT BE ISSUED UNTIL A
 PRE-CONSTRUCTION ELEVATION CERTIFICATE HAS BEEN
 SUBMITTED AND APPROVED.) THIS PROJECT IS LOCATED IN A
 SPECIAL FLOOD HAZARD AREA (AE FLOOD ZONE). SEE NFIP
 REVIEW COMMENTS.
  
 3) NOT COMPLIED. (THE PERMIT CAN NOT BE ISSUED UNTIL
 MINOR LOT SUBDIVISION HAS BEEN APPROVED.) THE SITE PLAN
 SHOWS A PROPERTY LINE THAT IS PART OF ANOTHER PARCEL ON
 THE PALM BEACH COUNTY PROPERTY APPRAISER'S WEB SITE.
 PROVIDE A COPY OF THE RECORDED PLAT FOR THIS LOT
 DIVISION. FBC 107.2
  
 4) NOT COMPLIED. (NO DETAILED SITE PLAN WITH REQUESTED
 INFORMATION WAS SUBMITTED. ALL ELEVATIONS ARE REQUIRED
 TO BE IN NAVD 88.) FBC 107.2.5 SITE PLAN. THE
 CONSTRUCTION DOCUMENTS SUBMITTED WITH THE APPLICATION
 FOR PERMIT SHALL BE ACCOMPANIED BY A SITE PLAN SHOWING
 TO SCALE THE SIZE AND LOCATION OF NEW CONSTRUCTION AND
 EXISTING STRUCTURES ON THE SITE, DISTANCES FROM LOT
 LINES, THE ESTABLISHED STREET GRADES AND THE PROPOSED
 FINISHED GRADES AND, AS APPLICABLE, FLOOD HAZARD AREAS,
 FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT SHALL BE
 DRAWN IN ACCORDANCE WITH AN ACCURATE BOUNDARY LINE
 SURVEY. PROVIDE SITE PLAN WITH ELEVATIONS OF THE
 BUILDING, PARKING LOT, ACCESSIBLE PARKING, ACCESSIBLE
 ROUTES, ETC.
  
 5) NOT COMPLIED. (NO CIVIL PLANS WERE SUBMITTED.) SHOW
 COMPLIANCE WITH FBC 110.9 IMPACT OF CONSTRUCTION. ALL
 CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL BE
 PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS
 PERMITTED TO AFFECT SAID PROPERTY PURSUANT TO A CONSENT
 GRANTED BY THE APPLICABLE PROPERTY OWNER, UNDER TERMS
 OR CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY
 OWNER. THIS INCLUDES, BUT IS NOT LIMITED TO, THE
 CONTROL OF DUST, NOISE, WATER OR DRAINAGE RUN-OFFS,
 DEBRIS, AND THE STORAGE OF CONSTRUCTION MATERIALS. NEW
 CONSTRUCTION ACTIVITY SHALL NOT ADVERSELY IMPACT LEGAL
 HISTORIC SURFACE WATER DRAINAGE FLOWS SERVING ADJACENT
 PROPERTIES, AND MAY REQUIRE SPECIAL DRAINAGE DESIGN
 COMPLYING WITH ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE DRAINAGE PATTERNS OF THE AFFECTED SITES.
 ACCORDINGLY, DEVELOPERS, CONTRACTORS AND OWNERS OF ALL
 NEW RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS,
 POOLS, PATIOS, DRIVEWAYS, DECKS OR SIMILAR ITEMS, ON
 EXISTING PROPERTIES RESULTING IN A SIGNIFICANT DECREASE
 OF PERMEABLE LAND AREA ON ANY PARCEL OR HAS ALTERED THE
 DRAINAGE FLOW ON THE DEVELOPED PROPERTY SHALL, AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED PROFESSIONAL SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 6) NOT COMPLIED. (NO PLANS FOR THIS HAS BEEN
 SUBMITTED.) SHOW COMPLIANCE WITH FBC CHAPTER 33 FOR
 SAFEGUARDS DURING CONSTRUCTION. SUBMIT BARRIER AND MOT
 PLANS.
  
 7) COMPLIED. SIGNED AND SEALED GEOTECHNICAL
 INVESTIGATION THAT SPECIFIES THE ALLOWABLE SOIL BEARING
 PRESSURE WAS SUBMITTED.
  
 8) COMPLIED. CORRECTED THE LABEL TO TYPICAL FOR LEVELS
 2-4.
  
 9) COMPLIED. THE LIFE SAFETY PLANS WERE REVISED.
  
 10) COMPLIED PROVIDED A LIFE SAFETY PLAN FOR THE ROOF.
  
 11) PROVISO. (PRODUCT APPROVALS TO BE DEFERRED. THERE
 IS A LIST OF PRODUCT APPROVALS ON SHEET A011.) THE CITY
 AMENDMENTS REQUIRES THAT PRODUCT APPROVALS ARE TO BE
 SUBMITTED FOR APPROVAL AFTER THEY HAVE BEEN REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR
 THE PROJECT. FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT
 APPROVALS FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT
 ROOFING MATERIALS, WINDOWS (GLASS TYPES), STRUCTURAL
 MULLIONS, STORE FRONTS, EXTERIOR DOORS, ETC. THESE
 ITEMS CAN BE DEFERRED IF REQUESTED, HOWEVER, THE
 DOCUMENTS MUST BE SUBMITTED AND APPROVED BY THE
 BUILDING DEPARTMENT BEFORE THEY CAN BE INSTALLED. ONLY
 ONE SET IS REQUIRED TO BE UPLOADED FOR ELECTRONICALLY
 SUBMITTED DOCUMENTS.
 FBC 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL. SHOP DRAWINGS AND
 CALCULATIONS FROM DELEGATE ENGINEERS SHOULD BE INCLUDED
 ON THE LIST.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 12) NOT COMPLIED. (ELEVATIONS TO BE IN NAVD 88.)
 PROVIDE THE FLOOR ELEVATIONS ON THE FLOOR PLAN OF THE
 GROUND FLOOR, THE BUILDING ELEVATIONS AND BUILDING
 SECTIONS. FBC 107.2
  
 13) PROVISO. NOTED ON THE PLANS.
 SEPARATE PERMITS, PLANS AND FEES WILL BE REQUIRED FOR
 THE FOLLOWING:
 LIGHT POLES/SITE LIGHTING
 FIRE ALARM
 FIRE SPRINKLER
 LOW VOLTAGE
 ACCESS
 LANDSCAPING
 IRRIGATION
 PARKING LOT
 DUMPSTER ENCLOSURE
 SITE WALLS
 ALL OTHER ITEMS OTHER THAN BMEP
  
 14) PROVISO. PRODUCT APPROVALS FOR THE ROOFING
 MATERIALS TO BE APPROVED BY THE DESIGNER OF RECORD,
 SUBMITTED AND APPROVED BY THE BUILDING DEPARTMENT
 BEFORE THE ROOFING PERMIT IS ISSUED. A SEPARATE PERMIT
 AND APPLICATION IS REQUIRED FOR ROOFING.
  
 15) COMPLIED. HANDRAIL EXTENSIONS CORRECTED.
  
 16) COMPLIED. STAIR LABELS CORRECTED.
  
 17) NOT COMPLIED. (THE FLOOR PLANS ONLY SHOW A TOTAL OF
 (5) MOBILITY ACCESSIBLE ROOMS AND (7) ARE REQUIRED.
 SOME OF THE ACCESSIBLE ROOMS SPECIFIED IN THE ROOM
 MATRIX ON SHEET A010, DO NOT HAVE THE ACCESSIBILITY
 SYMBOL ON THE FLOOR PLANS.) PROVIDE A ROOM MATRIX THAT
 SHOWS THE ROOM TYPES PER FLOOR, THE TOTAL NUMBER OF
 ROOMS PER FLOOR, THE TOTAL NUMBER OF ROOMS (112), THE
 NUMBER OF EACH TYPE OF MOBILITY ACCESSIBLE ROOMS PER
 FLOOR, THE NUMBER OF ROOMS WITH COMMUNICATION FEATURES
 PER FLOOR, THE TOTAL NUMBER OF EACH TYPE OF MOBILITY
 ACCESSIBLE ROOMS REQUIRED (7) (2 WITH ROLL IN SHOWERS)
 AND THE NUMBER OF EACH TYPE PROVIDED, THE TOTAL OF
 ROOMS WITH COMMUNICATION FEATURES REQUIRED (12) AND THE
 TOTAL PROVIDED. FBC ACCESSIBILITY SECTIONS 224.2 AND
 224.4
  
 18) NOT COMPLIED. (SHEET A100, THE SITE PLAN, REFERS TO
 CIVIL DRAWINGS WHICH WERE NOT SUBMITTED WITH THE
 CONSTRUCTION DOCUMENTS FOR REQUIRED PARKING
 INFORMATION. THE FINISH FLOOR ELEVATION IS SPECIFIED AS
 15.0 BUT THE VERTICAL DATA IS NOT SPECIFIED. PLEASE USE
 NAVD 88.) PROVIDE A PARKING LOT PLAN THAT SHOWS THE
 TOTAL NUMBER OF PARKING SPACES, THE TOTAL NUMBER OF
 REQUIRED AND PROVIDED ACCESSIBLE SPACES, THE ACCESSIBLE
 VAN PARKING SPACES AND THE LOCATIONS OF THE ACCESSIBLE
 PARKING SPACES. FBC ACCESSIBILITY SECTIONS 208 & 502
  
 19) NOT COMPLIED. SHOW THAT THE PASSENGER LOADING ZONE
 COMPLIES WITH FBC SECTIONS 209 & 503.
  
 20) NOT COMPLIED. SHOW COMPLIANCE WITH 3002.4 ELEVATOR
 CAR TO ACCOMMODATE AMBULANCE STRETCHER. ANY BUILDING
 THAT IS MORE THAN THREE STORIES HIGH OR IN WHICH THE
 VERTICAL DISTANCE BETWEEN THE BOTTOM TERMINAL LANDING
 AND THE TOP TERMINAL LANDING EXCEEDS 25 FEET (7620 MM),
 MUST BE CONSTRUCTED TO CONTAIN AT LEAST ONE PASSENGER
 ELEVATOR THAT IS OPERATIONAL FOR BUILDING OCCUPANTS AND
 FIRE DEPARTMENT EMERGENCY ACCESS TO ALL FLOORS. THE
 ELEVATOR CAR SHALL BE OF SUCH A SIZE AND ARRANGEMENT TO
 ACCOMMODATE AN AMBULANCE STRETCHER 24 INCHES BY 76
 INCHES (610 MM BY 1950 MM) WITH NOT LESS THAN 5-INCH
 (127 MM) RADIUS CORNERS, IN THE HORIZONTAL, OPEN
 POSITION AND SHALL BE IDENTIFIED BY THE INTERNATIONAL
 SYMBOL FOR EMERGENCY MEDICAL SERVICES (STAR OF LIFE).
 THE SYMBOL SHALL BE NOT LESS THAN 3 INCHES (76 MM) IN
 HEIGHT AND SHALL BE PLACED INSIDE ON BOTH SIDES OF THE
 HOISTWAY DOOR FRAME.
  
 21) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
  
 22) NEW COMMENT: PLEASE PROVIDE AN ITEMIZED COST
 BREAKDOWN FOR THIS PROJECT. THIS WILL ALLOW US TO BACK
 OUT THE ITEMS THAT REQUIRE SEPARATE PERMITS AND FEES,
 SUCH AS FIRE SPRINKLERS. THIS WAY YOU WILL NOT BE
 PAYING DOUBLE FOR THE SAME ITEMS. FBC 109
  
 23) NEW COMMENT: SOME OF THE COMPONENT AND CLADDING
 PRESSURES AND NEGATIVE SIGNS ARE MISSING FROM THE
 ELEVATIONS ON THE STRUCTURAL DRAWINGS. FBC 107.2.1 &
 1609
  
 24) NEW COMMENT: THE WINDLOAD TABULATION FOR THE WALL
 COMPONENT AND CLADDING PRESSURES ON SHEET S001 DO NOT
 SPECIFY IF THEY ARE VULT OR ASD. FBC 1609
  
 25) THERE IS A NOTE ON THE STRUCTURAL ELEVATIONS THAT
 STATES SEE S200 AND S003 FOR WIND NOTES AND CRITERIA.
 SHEET S003 HAS THE THRESHOLD INSPECTION PLAN, I DO NOT
 SEE ANY WINDLOAD INFORMATION. FBC 1609
  
 26 ) NEW COMMENT. THE ROOF ZONES 1, 2 AND 3 DO NOT
 APPEAR TO HAVE BEEN SPECIFIED ON THE STRUCTURAL
 DRAWINGS AND THE COMPONENT AND CLADDING PRESSURES FOR
 THESE ROOF ZONES HAVE NOT BEEN PROVIDED. FBC 1609
  
 27) NEW COMMENT. I DID NOT SEE THAT THE SIZE OF THE
 ROOF HATCH IS SPECIFIED ON THE DRAWINGS. THE MINIMUM
 SIZE IS 16 SQFT WITH THE SMALLEST DIMENSION NOT LESS
 THAN 2 FT. PER FBC1011.12.2. IF THE ROOF HATCH IS
 WITHIN 10 FT OF THE ROOF EDGE A GUARD IS REQUIRED PER
 FBC1011.13 INSTALLED IN ACCORDANCE WITH FBC1015.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-11-03 Cont ID  
Sent By rmcdouga Date 2020-11-03 Time 10:03 Rev Time 0.00
Received By rmcdouga Date 2020-10-30 Time 13:00 Sent To  
Notes
2020-11-02 08:37:11PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
 NEW 4 STORY HOTEL
 TYPE II-B CONSTRUCTION
 R-1 OCCUPANCY TYPE
 FLOOD ZONE AE, BFE 12.7' NAVD88 (DFE 14.7' NAVD 88
 INCLUDES 2' FREEBOARD)
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THIS IS A THRESHOLD BUILDING. THE THRESHOLD
 INSPECTION STATEMENT IS REQUIRED ON THE PLANS. A
 THRESHOLD INSPECTION PLAN IS REQUIRED TO BE ON THE
 PLANS. SEE THE THRESHOLD REVIEW COMMENTS.
  
 2) THIS PROJECT IS LOCATED IN A SPECIAL FLOOD HAZARD
 AREA (AE FLOOD ZONE). SEE NFIP REVIEW COMMENTS.
  
 3) THE SITE PLAN SHOWS A PROPERTY LINE THAT IS PART OF
 ANOTHER PARCEL ON THE PALM BEACH COUNTY PROPERTY
 APPRAISER'S WEB SITE. PROVIDE A COPY OF THE RECORDED
 PLAT FOR THIS LOT DIVISION. FBC 107.2
  
 4) FBC 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS
 SUBMITTED WITH THE APPLICATION FOR PERMIT SHALL BE
 ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE THE SIZE
 AND LOCATION OF NEW CONSTRUCTION AND EXISTING
 STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE
 ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED
 GRADES AND, AS APPLICABLE, FLOOD HAZARD AREAS,
 FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT SHALL BE
 DRAWN IN ACCORDANCE WITH AN ACCURATE BOUNDARY LINE
 SURVEY. PROVIDE SITE PLAN WITH ELEVATIONS OF THE
 BUILDING, PARKING LOT, ACCESSIBLE PARKING, ACCESSIBLE
 ROUTES, ETC.
  
 5) SHOW COMPLIANCE WITH FBC 110.9 IMPACT OF
 CONSTRUCTION. ALL CONSTRUCTION ACTIVITY REGULATED BY
 THIS CODE SHALL BE PERFORMED IN A MANNER SO AS NOT TO
 ADVERSELY IMPACT THE CONDITION OF ADJACENT PROPERTY,
 UNLESS SUCH ACTIVITY IS PERMITTED TO AFFECT SAID
 PROPERTY PURSUANT TO A CONSENT GRANTED BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS OR CONDITIONS
 AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS
 INCLUDES, BUT IS NOT LIMITED TO, THE CONTROL OF DUST,
 NOISE, WATER OR DRAINAGE RUN-OFFS, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT LEGAL HISTORIC
 SURFACE WATER DRAINAGE FLOWS SERVING ADJACENT
 PROPERTIES, AND MAY REQUIRE SPECIAL DRAINAGE DESIGN
 COMPLYING WITH ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE DRAINAGE PATTERNS OF THE AFFECTED SITES.
 ACCORDINGLY, DEVELOPERS, CONTRACTORS AND OWNERS OF ALL
 NEW RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS,
 POOLS, PATIOS, DRIVEWAYS, DECKS OR SIMILAR ITEMS, ON
 EXISTING PROPERTIES RESULTING IN A SIGNIFICANT DECREASE
 OF PERMEABLE LAND AREA ON ANY PARCEL OR HAS ALTERED THE
 DRAINAGE FLOW ON THE DEVELOPED PROPERTY SHALL, AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED PROFESSIONAL SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 6) SHOW COMPLIANCE WITH FBC CHAPTER 33 FOR SAFEGUARDS
 DURING CONSTRUCTION. SUBMIT BARRIER AND MOT PLANS.
  
 7) SUBMIT A SIGNED AND SEALED GEOTECHNICAL
 INVESTIGATION THAT SPECIFIES THE ALLOWABLE SOIL BEARING
 PRESSURE PER FBC SECTION 1803.
  
 8) THE LIFE SAFETY PLANS ON SHEET A032 ARE LABELED
 TYPICAL LEVEL. IT APPEARS THAT THIS IS MEANT TO BE
 TYPICAL FOR LEVELS 2-4. TO AVOID ANY CONFUSION, PLEASE
 CHANGE LABEL TO SHOW THE LEVELS TO WHICH IT APPLIES.
 FBC 107.2
  
 9) THE LIFE SAFETY PLANS ARE MISSING INFORMATION.
 PLEASE INCLUDE THE FOLLOWING ON THE LIFE SAFETY PLANS.
 THE LIFE SAFETY PLANS NEED TO SHOW THE FOLLOWING:
 A) NUMBER OF OCCUPANTS IN EACH AREA FBC 1004.1
 B) CUMULATIVE OCCUPANT LOADS FBC 1004.1.1
 C) EXIT SEPARATION DISTANCE FBC 1015.2.1
 D) COMMON PATH OF EGRESS TRAVEL DISTANCE FBC 1014.3
 E) EXIT ACCESS TRAVEL DISTANCE FBC 1016.3
 F) CLEAR WIDTH OF THE EXIT OR EXIT ACCESS DOORS FBC
 1008.1.1
 G) CAPACITY OF EGRESS DOORS, OCCUPANT LOAD SERVED AND
 MEANS OF EGRESS FACTOR FBC1005.3.2
 H) DISTRIBUTION OF EGRESS CAPACITY FBC1005.5
  
 10) PROVIDE A LIFE SAFETY PLAN FOR THE ROOF. FBC 107.2
  
 11) THERE IS A LIST OF PRODUCT APPROVALS ON SHEET A011.
 THE CITY AMENDMENTS REQUIRES THAT PRODUCT APPROVALS ARE
 TO BE SUBMITTED FOR APPROVAL AFTER THEY HAVE BEEN
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD FOR THE PROJECT. FBC 107.3.4 - PROVIDE TWO SETS
 OF PRODUCT APPROVALS FOR THOSE PRODUCTS WHICH ARE
 REGULATED BY FAC 61G20-3.001 PER FLORIDA STATUTE
 553.842 (5) THAT HAVE BEEN REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD. PROVIDE TWO COMPLETE
 PRODUCT APPROVALS WITH FL OR NOA NUMBERS INCLUDING
 INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES
 FOR EACH OF THE DIFFERENT ROOFING MATERIALS, WINDOWS
 (GLASS TYPES), STRUCTURAL MULLIONS, STORE FRONTS,
 EXTERIOR DOORS, ETC. THESE ITEMS CAN BE DEFERRED IF
 REQUESTED, HOWEVER, THE DOCUMENTS MUST BE SUBMITTED AND
 APPROVED BY THE BUILDING DEPARTMENT BEFORE THEY CAN BE
 INSTALLED. ONLY ONE SET IS REQUIRED TO BE UPLOADED FOR
 ELECTRONICALLY SUBMITTED DOCUMENTS.
 FBC 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL. SHOP DRAWINGS AND
 CALCULATIONS FROM DELEGATE ENGINEERS SHOULD BE INCLUDED
 ON THE LIST.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 12) PROVIDE THE FLOOR ELEVATIONS ON THE BUILDING
 ELEVATIONS AND BUILDING SECTIONS. FBC 107.2
  
 13) SEPARATE PERMITS, PLANS AND FEES WILL BE REQUIRED
 FOR THE FOLLOWING:
 LIGHT POLES/SITE LIGHTING
 FIRE ALARM
 FIRE SPRINKLER
 LOW VOLTAGE
 ACCESS
 LANDSCAPING
 IRRIGATION
 PARKING LOT
 DUMPSTER ENCLOSURE
 SITE WALLS
 ALL OTHER ITEMS OTHER THAN BMEP
  
 14) A SEPARATE PERMIT AND APPLICATION IS REQUIRED FOR
 ROOFING.
  
 15) THE STAIR SECTIONS ON SHEETS A-490 AND A-491 DO NOT
 SHOW THE HANDRAIL EXTENSIONS AT THE BOTTOM THAT ARE
 REQUIRED BY FBC ACCESSIBILITY SECTION 505.10.3
  
 16) THE STAIR SECTIONS ON SHEET A-491 ARE LABELED AS
 STAIR 1 AND SHOULD BE LABELED STAIR 2. FBC 107.2
  
 17) PROVIDE A ROOM MATRIX THAT SHOWS THE ROOM TYPES PER
 FLOOR, THE TOTAL NUMBER OF ROOMS PER FLOOR, THE TOTAL
 NUMBER OF ROOMS (112), THE NUMBER OF EACH TYPE OF
 MOBILITY ACCESSIBLE ROOMS PER FLOOR, THE NUMBER OF
 ROOMS WITH COMMUNICATION FEATURES PER FLOOR, THE TOTAL
 NUMBER OF EACH TYPE OF MOBILITY ACCESSIBLE ROOMS
 REQUIRED (7) (2 WITH ROLL IN SHOWERS) AND THE NUMBER OF
 EACH TYPE PROVIDED, THE TOTAL OF ROOMS WITH
 COMMUNICATION FEATURES REQUIRED (12) AND THE TOTAL
 PROVIDED. FBC ACCESSIBILITY SECTIONS 224.2 AND 224.4
  
 18) PROVIDE A PARKING LOT PLAN THAT SHOWS THE TOTAL
 NUMBER OF PARKING SPACES, THE TOTAL NUMBER OF REQUIRED
 AND PROVIDED ACCESSIBLE SPACES, THE ACCESSIBLE VAN
 PARKING SPACES AND THE LOCATIONS OF THE ACCESSIBLE
 PARKING SPACES. FBC ACCESSIBILITY SECTIONS 208 & 502
  
 19) SHOW THAT THE PASSENGER LOADING ZONE COMPLIES WITH
 FBC SECTIONS 209 & 503.
  
 20) SHOW COMPLIANCE WITH 3002.4 ELEVATOR CAR TO
 ACCOMMODATE AMBULANCE STRETCHER. ANY BUILDING THAT IS
 MORE THAN THREE STORIES HIGH OR IN WHICH THE VERTICAL
 DISTANCE BETWEEN THE BOTTOM TERMINAL LANDING AND THE
 TOP TERMINAL LANDING EXCEEDS 25 FEET (7620 MM), MUST BE
 CONSTRUCTED TO CONTAIN AT LEAST ONE PASSENGER ELEVATOR
 THAT IS OPERATIONAL FOR BUILDING OCCUPANTS AND FIRE
 DEPARTMENT EMERGENCY ACCESS TO ALL FLOORS. THE ELEVATOR
 CAR SHALL BE OF SUCH A SIZE AND ARRANGEMENT TO
 ACCOMMODATE AN AMBULANCE STRETCHER 24 INCHES BY 76
 INCHES (610 MM BY 1950 MM) WITH NOT LESS THAN 5-INCH
 (127 MM) RADIUS CORNERS, IN THE HORIZONTAL, OPEN
 POSITION AND SHALL BE IDENTIFIED BY THE INTERNATIONAL
 SYMBOL FOR EMERGENCY MEDICAL SERVICES (STAR OF LIFE).
 THE SYMBOL SHALL BE NOT LESS THAN 3 INCHES (76 MM) IN
 HEIGHT AND SHALL BE PLACED INSIDE ON BOTH SIDES OF THE
 HOISTWAY DOOR FRAME.
  
 21) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2021-06-21 Cont ID  
Sent By jleahy Date 2021-06-21 Time 13:26 Rev Time 0.00
Received By jleahy Date 2021-06-21 Time 13:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2021-03-01 Cont ID  
Sent By jleahy Date 2021-03-01 Time 10:35 Rev Time 0.00
Received By jleahy Date 2021-02-26 Time 15:52 Sent To  
Notes
2021-03-01 10:38:27ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) PLEASE SHOW LOCATION OF FIRE PUMP.
  
 2) PLEASE INDICATE THE SIZE OF THE FIRE PUMP.
  
 3) PANEL EV FUTURE OR PART OF THIS PROJECT?
  
 4) PANEL L WHAT IS IT FOR, SUBMIT A PANEL SCHEDULE FOR
 THE PANEL.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-12-21 Cont ID  
Sent By jleahy Date 2020-12-21 Time 08:34 Rev Time 0.00
Received By jleahy Date 2020-12-21 Time 08:34 Sent To  
Notes
2020-12-21 08:37:05ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 ALL COMMENTS HAVE BEEN ADDRESSED BUT I NEED SOME
 CLEARIFICATION ON THE FIRE PUMP PANEL. A SINGLE
 DISCONNECTING DEVICE IS ALLOWED FOR FIRE PUMP CIRCUITS
 EM PANEL AND THEN TO THE FIRE PUMP PANEL?
  
 (1) NUMBER OF DISCONNECTING MEANS.
 (A) GENERAL. A SINGLE DISCONNECTI NG MEANS AND
 ASSOCIATED OVERCURRENT PROTECTIVE DEVICE(S) SHALL BE
 PERMITTED TO BE INSTALLED BETWEEN THE FIRE PUMP POWER
 SOURCE(S) AND ONE OF THE FOLLOWING: [20:9.1.2]
 (1) A LISTED FIRE PUMP CONTROLLER (2) A LISTED FIRE
 PUMP POWER TRANSFER SWITCH (3) A LISTED COMBINATION
 FIRE PUMP CONTROLLER AND P OWER TRANSFER SWITCH

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-11-02 Cont ID  
Sent By jleahy Date 2020-11-02 Time 06:52 Rev Time 0.00
Received By jleahy Date 2020-10-30 Time 12:54 Sent To  
Notes
2020-11-02 07:22:31ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 E-301
  
 1) GFCI RECEPTACLES HAVE DESIGNATIONS OF B, C, C, D,
 AND E WHAT DO THEY STAND FOR?
  
 E-302
  
 1) QQ SUITE, QQ ACCESSIBLE, QQ ACCESSIBLE 2-BAY HAVE NO
 USB OUTLETS NOT A CODE REQUIREMENT JUST AN OBSERVATION.
  
 E-401
  
 1) 3000A MAIN NEEDS TO COMPLY WTH 240.87, PLEASE
 INDICATE HOW THIS WILL BE DONE.
  
 2) FAULT CURRENT RATING OF THE SERVICE AND PANELS NEEDS
 TO BE CALCULATED 110.9, 110,10 AND LABELS APPLIED PER
 110.24
  
 4) PANEL EM HAS THE FIRE PUMP AND ELEVATORS INSTALLED
 IN IT, HOW DOES THIS MEET THE REQUIREMENTS OF 695.4(B),
 AND 695.4 (B)(3)(A) & (B)
  
 NOTE
  
 THE FOLLOWING SYSTEMS REQUIRE SEPARATE PERMITS
 LIGHTNING PROTECTION, BDA, FIRE ALARM, SITE LIGHTING,
 GENERATOR AND ANY LOW VOLTAGE SYSTEMS.

Review Stop ENG ENGINEERING CSD
Rev No 5 Status P Date 2021-10-21 Cont ID  
Sent By rrossano Date 2021-10-21 Time   Rev Time 0.00
Received By rrossano Date 2021-10-21 Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 4 Status F Date 2021-06-11 Cont ID  
Sent By rrossano Date 2021-06-11 Time   Rev Time 0.00
Received By rrossano Date 2021-06-11 Time   Sent To  
Notes
2021-06-11 17:26:03UNDER REVIEW - FORMAL ENG SUBMITAL E21040016.

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2021-03-05 Cont ID  
Sent By rrossano Date 2021-03-05 Time   Rev Time 0.00
Received By rrossano Date 2021-03-05 Time   Sent To  
Notes
2021-03-05 08:26:57SITE PLAN APPROVAL IS STILL OUTSTANDING.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2020-12-08 Cont ID  
Sent By rrossano Date 2020-12-08 Time   Rev Time 0.00
Received By rrossano Date 2020-12-08 Time   Sent To  
Notes
2020-12-08 09:38:02PLEASE ADDRESS ZONING COMMENTS.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2020-10-27 Cont ID  
Sent By rrossano Date 2020-10-27 Time   Rev Time  
Received By rrossano Date 2020-10-27 Time   Sent To  
Notes
2020-10-27 14:38:13PLEASE ADDRESS ZONING COMMENTS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2021-10-04 Cont ID  
Sent By pleduc Date 2021-10-04 Time   Rev Time 0.00
Received By pleduc Date 2021-10-04 Time 13:50 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2021-06-10 Cont ID  
Sent By pleduc Date 2021-06-10 Time   Rev Time 0.00
Received By pleduc Date 2021-06-04 Time 15:22 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2021-02-23 Cont ID  
Sent By pleduc Date 2021-02-23 Time   Rev Time 0.00
Received By pleduc Date 2021-02-23 Time 11:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-12-11 Cont ID  
Sent By pleduc Date 2020-12-11 Time   Rev Time 0.00
Received By pleduc Date 2020-12-07 Time 16:17 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-10-26 Cont ID  
Sent By pleduc Date 2020-10-26 Time   Rev Time 0.00
Received By pleduc Date 2020-10-20 Time 15:11 Sent To  
Notes
2020-10-26 13:01:16THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET FP001 - THERE ARE INCORRECT FIRE CODE
 REFERENCES UNDER SECTION 1. CODES AND STANDARDS
  
 THE FIRE SPRINKLER INSTALLATION SHALL COMPLY WITH THE
 CURRENT EDITION OF THE FLORIDA FIRE PREVENTION CODE ,
 6TH ED., 2015 NFPA 1 & 101
  
 NFPA 13, 24 & 72 2013 EDITIONS
  
 PLEASE REVIEW AND CORRECT ALL FP SHEETS
  
  
  
 2) SHEET FP001 - ALL FIRE SPRINKLER FIRE WORK SHALL BE
 INSTALLED PER NFPA 13 UNDER SEPARATE PERMIT AND SHOP
 DRAWINGS.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWEDGEMENT.
  
  
 2A) SHEET FP002 - THERE IS NO INDICATION OF FIRE
 SPRINKLER PROTECTION UNDER THE PORTE COCHERE.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 3) SHEET FP001 - THERE IS AN INDICATION OF UNDERGROUNG
 FIRE LINE WORK. ALL UNDERGROUND FIRE LAINE WORK,
 INCLUDING THE FIRE LINE TAP, DDCV AND FDC SHALL BE
 INSTALLED PER NFPA 24 UNDER SEPARATE PERMIT AND SHOP
 DRAWINGS.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWEDGEMENT.
  
  
  
 4) THERE DOES NOT APPEAR TO BE STANDPIPES INSTALLED IN
 EACH STAIRWELLS. STANDPIPES ARE REQUIRED UNDER THE
 FLORIDA BUILDING CODE AND INSTALLED PER NFPA 14.
  
  
 PLEASE PROVIDE AND CORRECT.
  
  
  
 5) SHEET #121 - THERE ARE INDICATIONS OF FIRE ALARM
 DEVICES/EQUIPMENT. ALL FIRE ALARM WORK SHALL BE
 INSTALLED PER NFPA 72 UNDER SEPARATE PERMIT AND SHOP
 DRAWINGS.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWEDGEMENT.
  
  
  
 6) SHEET A031 - UNDER SECTION CHAPTER 9 - FIRE
 PROTECTION SYSTEMS, THERE IS AN INDICATION OF A
 COMMERCIAL HOOD AND DUCT SYSTEM AND TYPE I HOOD, ANY
 REQUIRED HOOD SYSTEM SHALL BE INSTALLED PER NFPA 96
 UNDER SEPARATE PERMITS, 1 FOR THE HOOD AND 1 FOR THE
 SUPPRESSION, AND SHOP DRAWINGS.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWEDGEMENT.
  
  
  
 7) FP SHEETS - THERE DOES NOT APPEAR TO BE FIRE
 SPRINKLERS WITHIN THE LAUNDRY CHUTE.
  
 PER NFPA 82
  
 6.2.6 AUTOMATIC SPRINKLERS.
 6.2.6.1 GRAVITY CHUTE.
 6.2.6.1.1 GRAVITY CHUTES SHALL BE PROTECTED INTERNALLY
 BY AUTOMATIC
 SPRINKLERS UNLESS THE CHUTE IS IN ACCORDANCE WITH
 6.2.2.5
 OR 6.2.2.6.
 6.2.6.1.2 A SPRINKLER SHALL BE INSTALLED AT OR ABOVE
 THE TOP
 CHUTE INTAKE OF THE CHUTE.
 6.2.6.1.3 AUTOMATIC SPRINKLERS INSTALLED IN GRAVITY
 CHUTE INTAKES
 SHALL BE RECESSED OUT OF THE CHUTE AREA THROUGH WHICH
 THE MATERIAL TRAVELS.
 6.2.6.1.4 A SPRINKLER SHALL BE INSTALLED WITHIN THE
 CHUTE AT
 ALTERNATE FLOOR LEVELS IN CHUTES CONNECTING MORE THAN
 TWO STORIES,
 WITH A MANDATORY SPRINKLER LOCATED AT THE LOWEST
 SERVICE
 LEVEL.
 6.2.6.1.5 SPRINKLER SYSTEM INSTALLATION SHALL COMPLY
 WITH
 NFPA 13, STANDARD FOR THE INSTALLATION OF SPRINKLER
 SYSTEMS.
  
 PLEASE REVIEW AND CORRECT
  
  
  
 8) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 9) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2021-03-24 Cont ID  
Sent By lcrespo Date 2021-03-24 Time 17:09 Rev Time 0.00
Received By lcrespo Date 2021-03-23 Time 11:25 Sent To  
Notes
2021-03-24 17:09:2303/24/21 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2021-01-04 Cont ID  
Sent By lcrespo Date 2021-01-04 Time 17:50 Rev Time 0.00
Received By lcrespo Date 2020-12-31 Time 09:31 Sent To  
Notes
2021-01-04 17:50:4801/04/20 2ND GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE SHOW ON AN ISOMETRIC DRAWING THAT CLEARLY
 SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017
 FBC-FUEL GAS, SECS. 402.4.1, 402.4.2. OR 2017 FBC-R
 SEC. G2413.4.1, G2413.4.2.
  
 2. DONE
  
 3. PLEASE SHOW THE TYPE OF PIPE MATERIAL BEING
 INSTALLED ON THE ISOMETRIC AND LABEL IT NATURAL PER THE
 WPB AMENDMENTS TO FBC SEC. 107.2.1. PLEASE NOTE THAT
 PAGE P002 HAS THE LEFT SIDE CUT OFF, SO SQUARE ON THE
 PAGE.
  
 4. DONE
  
 5. PLEASE SHOW THE ISOMETRIC THE TOTAL DISTANCE FROM
 THE POINT OF DELIVERY (GAS METER / MP REGULATOR / LP
 TANK) TO THE MOST REMOTE OUTLET IN THE BUILDING AND
 SYSTEM PER THE 2017 FBC-FUEL GAS SEC. 402.4.1, 402.4.2.
  
 6. DONE
  
 7. PLEASE INDICATE THE DELIVERY PRESSURE (PSI) OF THE
 SYSTEM ON THE ISOMETRIC PER THE WPB FBC 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 8. PLEASE SHOW THIS INFORMATION ON PAGE ISOMETRIC
 "DEDICATED EXHAUST LINES TERMINATING OUT THE PLAN WEST
 SIDE OF THE BUILDING, PROVIDED BY THE MANUFACTURER."
  
 9. DONE
  
 10. PLEASE PLACE A NOTE ON THE ISOMETRIC DRAWINGS
 SPECIFYING WHICH SIZING TABLE(S) FROM THE GAS CODE OR
 OTHER STANDARD WAS USED TO DESIGN THIS GAS SYSTEM.
 REFER TO THE 2017 FBC-FUEL GAS SECS. 401.4, 401.8,
 402.3, AND TABLES 402.4 (1) THRU 402.4 (37).
  
 11. PLEASE SHOW AND LABEL ALL UNIONS IN FRONT OF
 REGULATOR 1' OF EITHER SIDE AND SHOW REGULATORS PER THE
 2017 FBC FG SEC 410.2.
  
 12. PLEASE SHOW AND LABEL THE SHUTOFF VALVE ON GAS
 ISOMERIC PER THE 2017 FBC FG SEC. 409.4 OR 2017 FBC
 RES. SEC. G2401.1.3.
  
 13. PLEASE SHOW AND LABEL DRIP LEG ON EQUIPMENT
 INSTALLED PER THE 2017 FBC FG 408.2.
  
 14. THE CITY OF WEST PALM BEACH WILL REQUIRE THE GAS
 SYSTEM TO BE PURGE AND ADMINISTERED BY A CITY
 INSPECTOR. BEFORE DOING THIS PROCESS, PLEASE DESCRIBE
 HOW THE PURGE WILL OCCUR AND WHEN SUBMITTED TO THE
 CHIEF PLUMBING INSPECTOR IN ADVANCE. PLEASE CALL
 561-805-6692 FOR FURTHER CLARIFICATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-11-03 Cont ID  
Sent By tklarge Date 2020-11-03 Time 07:22 Rev Time 0.00
Received By tklarge Date 2020-11-02 Time 06:32 Sent To  
Notes
2020-11-02 06:33:421) SUBMIT A COPY OF AN ISOMETRIC DRAWING THAT CLEARLY
 SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017
 FBC-FUEL GAS, SECS. 402.4.1, 402.4.2. OR 2017 FBC-R
 SEC. G2413.4.1, G2413.4.2.
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE GAS
 WATER HEATERS.
 3) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, TYPE OF GAS (LP OR NATURAL).WPB AMEND. TO
 FBC SEC. 107.2.1.
 4) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS
 SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37)
 OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES
 G2413.4 (1 ) THROUGH G2413.4 (21).
 5) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2017
 FBC-FUEL GAS SEC.402.4.1, 402.4.2, OR 2017 FBC-RES.
 SEC. G 2413.4.1, G2413.4.2.
 6) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017
 FBC-FUEL GAS CODE SEC.304.1, 614.6 (CLOTHES DRYERS) OR
 2017 FBC-RES. SEC.G 2407.1 AND G2439.4 (CLOTHES
 DRYERS).
 7) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3
 THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3.
 8) SUBMIT DETAILS SHOWING THE TYPE OF VENT, LOCATION,
 SIZE, TERMINATION POINT, HEIGHT ABOVE THE ROOF AND
 ANCHORING DETAILS OF THE GAS VENT(S) PER 2017 FBC-FUEL
 GAS SECS. 502 THRU 505 OR 2017 FBC-RES. SEC.G2426
 THROUGH G2439.
 9) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND
 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES
 SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS
 FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT
 THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES.
 SEC.G2408.1.
 10) SUBMIT A COPY OF THE APPLICABLE SIZING TABLES USED
 TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL
 GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1)
 THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8,
 G2413.1, G2413.2, & G2413.3.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2021-10-27 Cont ID  
Sent By lcrespo Date 2021-10-27 Time 13:09 Rev Time 0.00
Received By lcrespo Date 2021-09-27 Time 07:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-07-14 Cont ID  
Sent By lcrespo Date 2021-07-14 Time 14:01 Rev Time 0.00
Received By lcrespo Date 2021-06-02 Time 16:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-03-30 Cont ID  
Sent By shill Date 2021-03-30 Time 14:02 Rev Time 0.00
Received By shill Date 2021-02-09 Time 16:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-01-04 Cont ID  
Sent By lcrespo Date 2021-01-04 Time 17:51 Rev Time 0.00
Received By lcrespo Date 2020-12-01 Time 17:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-11-03 Cont ID  
Sent By rmcdouga Date 2020-11-03 Time 10:03 Rev Time 0.00
Received By rmcdouga Date 2020-10-06 Time 15:20 Sent To  
Notes
2020-10-20 15:21:24PAYMENT REJECTED BY CITY 10/6 AND 10/7, BACKDATED TO
 DATE OF ATTEMPTED PAYMENT

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-10-30 Cont ID  
Sent By rmcdouga Date 2020-10-30 Time 13:00 Rev Time 0.00
Received By rmcdouga Date 2020-10-30 Time 13:00 Sent To  
Notes
2020-10-30 13:03:18PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
  
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2021-06-18 Cont ID  
Sent By medwards Date 2021-06-18 Time 15:46 Rev Time 0.00
Received By medwards Date 2021-06-18 Time 15:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2021-03-01 Cont ID  
Sent By medwards Date 2021-03-01 Time 09:31 Rev Time 0.00
Received By medwards Date 2021-03-01 Time 08:56 Sent To  
Notes
2021-03-01 09:31:281ST REVIEW FBC-2020 MECHANICAL
 PERMIT-20090848
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS FOR ALL MECHANICAL SYSTEMS, NOT JUST THE
 ROOM PTAC?S. FBC ECC403.2.1
  
 2) THE KITCHEN HOOD WILL REQUIRE A SEPARATE PERMIT AND
 REVIEW. PLEASE ADD A NOTE EXPLAIN THIS ON THE DRAWINGS.
 FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2020-12-16 Cont ID  
Sent By medwards Date 2020-12-16 Time 16:17 Rev Time 0.00
Received By medwards Date 2020-12-16 Time 14:32 Sent To  
Notes
2020-12-16 16:18:121ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20090848
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FBC EC C403.2.1
  
 2) SHEET M201: BREAKROOM BATHROOM EXHAUST DUCT IS
 PENETRATING THE SAME RATED WALLS AS THE GUEST LAUNDRY
 DRYER DUCTS ARE PENETRATING. PLEASE SHOW HOW THESE
 RATED WALLS WILL BE PROTECTED AT THE DUCT PENETRATIONS.
 FBC M 607
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-10-30 Cont ID  
Sent By medwards Date 2020-10-30 Time 07:26 Rev Time 0.00
Received By medwards Date 2020-10-29 Time 16:45 Sent To  
Notes
2020-10-30 07:55:501ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20090848
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE EQUIPMENT SIZING CALCULATIONS. FBC EC
 C403.2.1; FBC M 312.1
  
 2) SHEET A031 INDICATES A 2-HOUR RATED WALL FOR THE
 STORAGE AREA WHERE AHU-1 IS LOCATED (M201). IT APPEARS
 THAT THE AREA ABOVE THE CEILING IS BEING USED AS A
 RETURN AIR PLENUM. PLEASE SHOW THE RETURN AIR PATH BACK
 TO AHU-1 IN THIS AREA. FBC M 601.6
  
 3) SHEET M201: PLEASE SHOW THE PROTECTION OF THE DRYER
 DUCT PENETRATION IN THE RATED WALL AT THE GUEST
 LAUNDRY. FBC M 504.2
  
 4) GUEST ROOM BATH EXHAUST FANS:
 .RATES ARE PER ROOM UNLESS OTHERWISE INDICATED. THE
 HIGHER RATE SHALL BE PROVIDED WHERE THE EXHAUST SYSTEM
 IS DESIGNED TO OPERATE INTERMITTENTLY. THE LOWER RATE
 SHALL BE PERMITTED ONLY WHERE THE EXHAUST SYSTEM IS
 DESIGNED TO OPERATE CONTINUOUSLY WHILE OCCUPIED. FBC M
 TABLE 403.3.1.1 NOTE F
  
 5) PLEASE SHOW THE PENETRATION PROTECTION AT THE
 PENETRATION OF THE RATED WALL AT DUCT FOR THE EXHAUST
 FAN IN THE CHUTE ROOM ON FLOORS 2, 3 AND 4. FBC M 607.5
  
 6) SHEET A440: PANTRY EQUIPMENT LEGEND, NOTE 10 IS AN
 OVEN. PLEASE PROVIDE SPECIFICATIONS FOR THIS OVEN AND
 EXPLAIN HOW IT WOULD MEET FBC M 507.1
  
 7) SHEET A440: PANTRY EQUIPMENT LEGEND, NOTE 3 IS A
 DISHWASHER. PLEASE PROVIDE SPECIFICATIONS FOR THIS
 DISHWASHER AND EXPLAIN HOW IT WOULD MEET FBC M 507.3
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 5 Status P Date 2021-10-07 Cont ID  
Sent By rmcdouga Date 2021-10-07 Time 13:44 Rev Time 0.00
Received By rmcdouga Date 2021-10-07 Time 13:44 Sent To  
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 4 Status F Date 2021-06-29 Cont ID  
Sent By rmcdouga Date 2021-06-29 Time 15:14 Rev Time 0.00
Received By rmcdouga Date 2021-06-29 Time 15:14 Sent To  
Notes
2021-06-29 15:14:45THE PRE-CONSTRUCTION ELEVATION CERTIFICATE HAS ERRORS.
 THE LATITUDE AND LONGITUDE ARE REVERSED ON THE
 CERTIFICATE (IE. THE LONGITUDE IS IN THE SPACE FOR
 LATITUDE AND THE LATITUDE IS IN THE SPACE FOR
 LONGITUDE). THE NORTH AND WEST DESIGNATIONS WERE NOT
 SPECIFIED FOR LATITUDE AND LONGITUDE. NOTE: THE
 COORDINATES ARE REQUIRED TO BE FOR A POINT WITHIN 66
 FEET OF THE PROPOSED BUILDINGS MAIN ENTRANCE.

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 3 Status F Date 2021-03-08 Cont ID  
Sent By rmcdouga Date 2021-03-08 Time 09:55 Rev Time 0.00
Received By rmcdouga Date 2021-03-08 Time 09:55 Sent To  
Notes
2021-03-08 09:56:16THE REQUIRED PRE-CONSTRUCTION ELEVATION CERTIFICATE
 BASED ON THE CONSTRUCTION DRAWINGS HAS NOT BEEN
 SUBMITTED FOR REVIEW.
  
 AS OF OCTOBER 5TH, 2017 THE CITY HAS ADOPTED NEW FLOOD
 INSURANCE RATE MAPS WHICH USE NAVD 88 AS THE VERTICAL
 DATUM. THE CITY ALSO ADOPTED A 2' FREEBOARD WHICH
 REQUIRES THE FINISH FLOOR AND EQUIPMENT TO BE A MINIMUM
 OF TWO FEET ABOVE THE BFE.
 ACCORDING TO THE FLOOD INSURANCE RATE MAP WHICH WAS
 ADOPTED ON OCTOBER 5, 2017 AND IS APPLICABLE TO THIS
 PROJECT, THE STRUCTURE IS IN AN AE FLOOD ZONE WHICH IS
 A SPECIAL FLOOD HAZARD AREA. THE BASE FLOOD ELEVATION
 FOR THE PROPERTY IS 12.7' NAVD 88. THE CITY OF WEST
 PALM BEACH HAS ADOPTED A FLOOD ORDINANCE THAT REQUIRES
 A TWO (2) FOOT FREE BOARD. THIS MEANS THAT THE LOWEST
 FLOOR AND ALL EQUIPMENT SERVICING THE BUILDING IS
 REQUIRED TO BE AT OR ABOVE 14.7' NAVD 88. SHOW
 COMPLIANCE WITH THESE REQUIREMENTS ON THE PLANS.
 SPECIFY ALL ELEVATIONS IN NAVD 88.
 THREE ELEVATION CERTIFICATES ARE REQUIRED TO BE
 SUBMITTED. 1) A PRE-CONSTRUCTION ELEVATION CERTIFICATE
 BASED ON THE CONSTRUCTION PLANS IS REQUIRED BEFORE THE
 PERMIT IS ISSUED. 2) A BUILDING UNDER CONSTRUCTION
 ELEVATION CERTIFICATE WHEN FIRST FLOOR SLABS ARE
 POURED. 3) A FINISHED CONSTRUCTION ELEVATION WHEN THE
 JOB IS COMPLETE INCLUDING LANDSCAPING. THE FINAL
 ELEVATION CERTIFICATE IS REQUIRED TO BE SUBMITTED AND
 APPROVED BEFORE THE C.O. WILL BE ISSUE.
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status F Date 2020-12-22 Cont ID  
Sent By rmcdouga Date 2020-12-22 Time 10:16 Rev Time 0.00
Received By rmcdouga Date 2020-12-22 Time 10:15 Sent To  
Notes
2020-12-22 10:16:31THE REQUIRED PRE-CONSTRUCTION ELEVATION CERTIFICATE
 BASED ON THE CONSTRUCTION DRAWINGS HAS NOT BEEN
 SUBMITTED FOR REVIEW.
  
 AS OF OCTOBER 5TH, 2017 THE CITY HAS ADOPTED NEW FLOOD
 INSURANCE RATE MAPS WHICH USE NAVD 88 AS THE VERTICAL
 DATUM. THE CITY ALSO ADOPTED A 2' FREEBOARD WHICH
 REQUIRES THE FINISH FLOOR AND EQUIPMENT TO BE A MINIMUM
 OF TWO FEET ABOVE THE BFE.
 ACCORDING TO THE FLOOD INSURANCE RATE MAP WHICH WAS
 ADOPTED ON OCTOBER 5, 2017 AND IS APPLICABLE TO THIS
 PROJECT, THE STRUCTURE IS IN AN AE FLOOD ZONE WHICH IS
 A SPECIAL FLOOD HAZARD AREA. THE BASE FLOOD ELEVATION
 FOR THE PROPERTY IS 12.7' NAVD 88. THE CITY OF WEST
 PALM BEACH HAS ADOPTED A FLOOD ORDINANCE THAT REQUIRES
 A TWO (2) FOOT FREE BOARD. THIS MEANS THAT THE LOWEST
 FLOOR AND ALL EQUIPMENT SERVICING THE BUILDING IS
 REQUIRED TO BE AT OR ABOVE 14.7' NAVD 88. SHOW
 COMPLIANCE WITH THESE REQUIREMENTS ON THE PLANS.
 SPECIFY ALL ELEVATIONS IN NAVD 88.
 THREE ELEVATION CERTIFICATES ARE REQUIRED TO BE
 SUBMITTED. 1) A PRE-CONSTRUCTION ELEVATION CERTIFICATE
 BASED ON THE CONSTRUCTION PLANS IS REQUIRED BEFORE THE
 PERMIT IS ISSUED. 2) A BUILDING UNDER CONSTRUCTION
 ELEVATION CERTIFICATE WHEN FIRST FLOOR SLABS ARE
 POURED. 3) A FINISHED CONSTRUCTION ELEVATION WHEN THE
 JOB IS COMPLETE INCLUDING LANDSCAPING. THE FINAL
 ELEVATION CERTIFICATE IS REQUIRED TO BE SUBMITTED AND
 APPROVED BEFORE THE C.O. WILL BE ISSUE.
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2020-11-02 Cont ID  
Sent By rmcdouga Date 2020-11-02 Time 08:08 Rev Time 0.00
Received By rmcdouga Date 2020-11-02 Time 08:08 Sent To  
Notes
2020-11-02 08:08:22AS OF OCTOBER 5TH, 2017 THE CITY HAS ADOPTED NEW FLOOD
 INSURANCE RATE MAPS WHICH USE NAVD 88 AS THE VERTICAL
 DATUM. THE CITY ALSO ADOPTED A 2' FREEBOARD WHICH
 REQUIRES THE FINISH FLOOR AND EQUIPMENT TO BE A MINIMUM
 OF TWO FEET ABOVE THE BFE.
 ACCORDING TO THE FLOOD INSURANCE RATE MAP WHICH WAS
 ADOPTED ON OCTOBER 5, 2017 AND IS APPLICABLE TO THIS
 PROJECT, THE STRUCTURE IS IN AN AE FLOOD ZONE WHICH IS
 A SPECIAL FLOOD HAZARD AREA. THE BASE FLOOD ELEVATION
 FOR THE PROPERTY IS 12.7' NAVD 88. THE CITY OF WEST
 PALM BEACH HAS ADOPTED A FLOOD ORDINANCE THAT REQUIRES
 A TWO (2) FOOT FREE BOARD. THIS MEANS THAT THE LOWEST
 FLOOR AND ALL EQUIPMENT SERVICING THE BUILDING IS
 REQUIRED TO BE AT OR ABOVE 14.7' NAVD 88. SHOW
 COMPLIANCE WITH THESE REQUIREMENTS ON THE PLANS.
 SPECIFY ALL ELEVATIONS IN NAVD 88.
 THREE ELEVATION CERTIFICATES ARE REQUIRED TO BE
 SUBMITTED. 1) A PRE-CONSTRUCTION ELEVATION CERTIFICATE
 BASED ON THE CONSTRUCTION PLANS IS REQUIRED BEFORE THE
 PERMIT IS ISSUED. 2) A BUILDING UNDER CONSTRUCTION
 ELEVATION CERTIFICATE WHEN FIRST FLOOR SLABS ARE
 POURED. 3) A FINISHED CONSTRUCTION ELEVATION WHEN THE
 JOB IS COMPLETE INCLUDING LANDSCAPING. THE FINAL
 ELEVATION CERTIFICATE IS REQUIRED TO BE SUBMITTED AND
 APPROVED BEFORE THE C.O. WILL BE ISSUE.
  

Review Stop P PLUMBING
Rev No 5 Status P Date 2021-10-27 Cont ID  
Sent By lcrespo Date 2021-10-27 Time 13:06 Rev Time 0.00
Received By lcrespo Date 2021-10-27 Time 13:05 Sent To  
Notes
2021-10-27 13:08:0810/27/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2021-07-14 Cont ID  
Sent By lcrespo Date 2021-07-14 Time 13:23 Rev Time 0.00
Received By lcrespo Date 2021-07-14 Time 11:45 Sent To  
Notes
2021-07-14 13:24:0807/14/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2021-03-24 Cont ID  
Sent By lcrespo Date 2021-03-24 Time 17:09 Rev Time 0.00
Received By lcrespo Date 2021-03-23 Time 11:26 Sent To  
Notes
2021-03-24 16:42:4703/24/21 3RD PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PERMIT Z20010014, REFER TO EMAIL SENT TO ARCHITECT
 FROM MRS. S, HILL.
  
 2. DONE.
  
 3. DONE.
  
 4. DONE.
  
 5. DONE.
  
 6. DONE.
  
 7. DONE.
  
 8. DONE.
  
 9. DONE.
  
 10. DONE.
  
 11. DONE.
  
 12. DONE.
  
 13. DONE.
  
 14. DONE.
  
 15. DONE.
  
 A. DONE.
  
 B. DONE.
  
 C. DONE.
  
 D. DONE.
  
 16. DONE
  
 17. DONE
  
 18. ON SHEET A422,
 A. DONE.
  
 B. ON DETAIL 13 AND 15, THE GRAB BARS SHALL BE MEASURED
 TO THE TOP OF THE GRIPPING SURFACE PER THE 2017 FBC ACC
 SEC. 609.4. ON DETAIL 13 AND 18, PLEASE SHOW THE TOILET
 PAPER DISPENSERS 7? INCHES MINIMUM AND 9? INCHES
 MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO THE
 CENTERLINE OF DISPENSER PER THE 2017 FBC ACC SEC.
 604.7.
  
 C. DONE.
  
 19. DONE.
  
 NOTE, PLEASE CORRECT ALL ACCESSIBILITIES PAGES TO
 COINCIDE WITH EACH OTHER, TOO MANY TO ITEMIZE. THANK
 YOU.
  
 20. DONE.
  
 21. DONE.
  
 22. DONE ALL.
  
 A. DONE.
  
 B. DONE.
  
 C. DONE.
  
 D. DONE.
  
 E. DONE.
  
 23. DONE.
  
 24. DONE.
  
 25. DONE.
  
 26. DONE.
  
 27. DONE.
  
 28. ON SHEET P201,
  
 A. ALL TAGS ARE NOTED. PLEASE REMOVE CLOUDS FOR CLARITY
 PER THE WPB FBC 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 B. DONE.
  
 C. DONE.
  
 D. DONE.
  
 E. THE ELEVATORS MUST BE ON AN INDIRECT WASTE NOT TO
 THE SANITARY, SO PLEASE PROVIDE A DETAIL THAT SHOWS THE
 INDIRECT CONNECTION PER THE 2017 FBC SEC. P 1113.
  
 F. THE LINE IN THE STORAGE ROOM MUST HAVE A TRAP PRIMER
 AND A FUNNEL FOR THE INDIRECT WASTE FROM THE PUMP, AND
 IT NEEDS TO BE LOCATED AT THE STORAGE ROOM AND SHOW ON
 P801 AND SHOW ON P201 PER THE WPB FBC 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 29. ON SHEET P805;
  
 A. PLEASE PROVIDE THE GPM AND ROOF AREA IN FEET OF
 COVERED AREA FOR EACH RAIN LEADER STORMWATER RISER
 DIAGRAM FOR THE 2017 FBC SEC CALCULATIONS. P1106.
  
 B. PLEASE SHOW THE SLOPE OF ALL HORIZONTAL PIPES PER
 THE WPB FBC 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. SHOW THE HORIZONTAL PIPE SLOPE ON THE PLAN.
  
 30. DONE.
  
 31. DONE.
  
 PLEASE NOTE THAT A SHEET FOR THE CIVIL DRAWING IS
 REQUIRED ON THIS SET OF PLANS SUBMITTED IN COMMENT ONE.
  
 32. DONE.
  
 33. DONE.
  
 34. DONE.
  
 35. DONE.
  
 36. DONE.
  
 37. DONE.
  
 38. DONE.
  
 39. DONE.
  
 40. DONE.
  
 41. ON SHEET P801,
  
 A. DONE, PLEASE PROVIDE THIS VERBIAGE ON THIS PAGE FOR
 YOUR RESPONSE
  
 B. DONE, PLEASE REMOVE ALL CLOUDS ON THIS PAGE AND ALL
 OTHER PAGES ON THE PREVIOUS REVIEW THAT HAVE BEEN
 ADDRESSED FOR CLARITY PER THE WPB FBC 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 C. DONE.
  
 D. DONE.
  
 42. ON SHEETS P802,
  
 A. DONE.
  
 B. DONE.
  
 C. DONE.
  
 D. NOT TO CLEAR ON THIS TASK P201 WE COULD NOT FIND THE
 RESPONSE MADE, PLEASE CLARIFY PER THE WPB FBC 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 E. CONTINUATION POINTS ON P801 AND P502 ARE NOT CLEAR
 AND POINTING TO THE WRONG PIPES IN SOME CASES. PLEASE
 CORRECT TO REFECTION CONNECTION POINTS PER THE WPB FBC
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 43. DONE
  
 44. PLEASE REMOVE THE CLOUDS ON THE PLANS AS THESE ARE
 CONFUSING IN THE FIELD. THIS IS FOR FIELD CLARITY PER
 WPB FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 SUGGESTION TO PUT 801E AND 802W TO REFER RISER BETTER.
  
 45. DONE.
  
 46. DONE.
  
 47. DONE.
  
 48. DONE.
  
 49. DONE.
  
 50. DONE.
  
 51. DONE AS A NOTE.
  
 52. ON P601, ON THE INDIRECT CONNECTION FOR THE SUMP
 DETAIL, THREE IS SAID TO SANITARY, AND NO DIRECT DETAIL
 OR REFERENCE IS NOTED. PLEASE CORRECT PER THE WPB FBC
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 53. DONE.
  
 54. THE CIVIL PLANS ARE NOT PART OF THIS SUBMITTED SET
 PLANS AND ARE NOT AN ELECTRIC VERSION AS THEY ARE A
 PAPER PLAN. THOSE PLANS ARE FOR REVIEW AND ARE
 SUBMITTED FOR A DIFFERENT DEPARTMENT, AND WE WOULD NEED
 CIVIL SUBMITTED WITH THESE SETS. THE CHIEF PLAN
 EXAMINER WILL BE SENT OUT AN EMAIL CLARIFYING THIS
 REQUEST TO THE ARCHITECTURAL FIRM ON FILE.
 THE INFORMATION FOR THE GREASER INTERCEPTOR IS A ZONING
 REVIEW, AND AS REQUESTED IN THE PREVIOUS COMMENT, A
 CIVIL PLAN WAS ASKED FOR A REVIEW. CONTACT THE CITY'S
 ENGINEERING DEPT, AT 561-494-1040 FOR FURTHER
 INFORMATION ON STANDARD DRAWING GC-7.
  
 55. DONE.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-01-04 Cont ID  
Sent By lcrespo Date 2021-01-04 Time 12:11 Rev Time 0.00
Received By lcrespo Date 2020-12-31 Time 09:31 Sent To  
Notes
2021-01-04 15:39:5801/04/20 2ND PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. SECOND REQUEST, PLEASE SUBMIT A COMPLETE SET OF
 CIVIL DRAWINGS SHOWING THE WATER, SEWER, STORM
 DRAINAGE, AND GAS PIPING SYSTEMS. THE RESPONSE TO THIS
 REFERRING TO A ZONING PERMIT IS NOT ACCEPTABLE.
 REFERENCES TO THIS REVIEW ARE IMPERATIVE PER THE WPB
 AMENDMENTS TO FBC SEC. 107.2.1 AND 107.3.5.1.3.
  
 2. DONE
  
 3. DONE
  
 4. DONE
  
 5. DONE
  
 6. DONE
  
 7. ON SHEET A400 - BATHTUB DETAIL -THE EDGE OF THE GRAB
 BARS AT THE TUB'S FOOT, THE DIMENSION HAD A CLOUD OVER
 IT AND HARD TO READ. THE GRAB BAR ON THE SIDE OF THE
 1'-0 IS ON THE SAME LINE OF THE MEASUREMENT IT MAKES IT
 HARD TO READ. PLEASE CORRECT PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 8. DONE
  
 9. DONE
  
 10. DONE
  
 11. DONE
  
 12. DONE
  
 13. DONE
  
 14. DONE
  
 15. THE SECOND REQUEST,
  
 A. FOR SHEET A412, A414, A417, A422, A423 - IN THE
 DETAILS PERTAINING TO THE FOLLOWING SHOW THE DIMENSIONS
 REQUIRED FOR CLEAR FLOOR SPACES FOR THE HANDICAP
 ACCESSIBLE FIXTURES ON THE PLANS. COMPLY WITH
 FBC-ACCESSIBILITY CODE SECS. 604.3, 606.2. SHOW THE
 DIMENSION CLEAR FLOOR SPACE ADJACENT TO THE TUB OR
 SHOWER, LAV, AND WATER CLOSET.
  
 B. ON SHEET A410, A411, AND A416, DETAILS 13 SHOWS A
 VERTICAL GRAB BAR ON THE SHOWER AND NOT PERMITTED PER
 THE 2017 FBC ACC SEC. 609.4.
  
 C. ON SHEET A413 DETAIL 15, SHOWS A VERTICAL GRAB BAR
 ON THE SHOWER AND NOT PERMITTED PER THE 2017 FBC ACC
 SEC. 609.4.
  
 D. ON SHEET A420 AND A421, DETAILS 13, 15, AND 16 SHOW
 A VERTICAL GRAB BAR ON THE TUB AND NOT PERMITTED PER
 THE 2017 FBC ACC SEC. 609.4.
  
 16. DIMENSIONING NOT DONE
  
 17. DIMENSIONING NOT DONE
  
 18. ON SHEET A422,
  
 A. DIMENSIONING NOT DONE.
  
 B. ON DETAIL 15, GARB BARS FOR THE TUB SHOULD BE FROM
 THE TOP OF THE TUB TO THE FIRST GRAB BAR (8'-10"), AND
 THE BAK GRAB BAR IS 33" T0 36" MAX PER THE 2017 FBC
 SEC. ACC 607.4.2.
  
 C. ON DETAIL 16 LAV SHALL BE 34" TO TOP PLEASE SHOW PER
 THE 2017 FBC ACC SEC. 606.3.
  
 19. DIMENSIONING NOT DONE
  
 NOTE, PLEASE CORRECT ALL ACCESSIBILITIES PAGES TO
 COINCIDE WITH EACH OTHER, TOO MANY TO ITEMIZE. THANK
 YOU.
  
 20. DONE
  
 21. DONE
  
 22. SECOND REQUEST, SHEET A495;
  
 A. DETAIL 5; IN THE LAUNDRY ROOM, THE WASHER AND DRYER
 CLEAR FLOOR SPACE IS MISSING, AND THE DIMENSIONS ARE
 REQUIRED PER THE 2017 FBC-ACCESS. SECS. 305 SIZE.
  
 B. DETAIL 5; IN THE WOMEN'S AND MEN'S RESTROOMS ARE
 MISSING CLEAR FLOOR SPACE FOR THE WATER CLOSET, AND LAV
 AND ALL DIMENSIONS ARE REQUIRED PER THE 2017
 FBC-ACCESS. SECS. 305 SIZE.
  
 C. DETAIL 5; IN THE DRINKING FOUNTAIN IS MISSING CLEAR
 FLOOR SPACE, AND THE DIMENSIONS ARE REQUIRED PER THE
 2017 FBC-ACCESS. SECS. 305 SIZE.
  
 D. DETAIL 2; IN THE QQ ACCESS BATHROOM, THERE IS NO
 CLEAR FLOOR SPACE FOR THE WATER CLOSET, AND ALL
 DIMENSIONS ARE REQUIRED FOR TUB LAV AND TURNING RADIUS
 PER THE 2017 FBC-ACCESS. SECS. 305 SIZE.
  
 E. DETAILS 2, 3, AND 4 SHOW ICE BIN. PLEASE SHOW CLEAR
 FLOOR SPACE AND DIMENSIONS PER THE 2017 FBC-ACCESS.
 SECS. 305 SIZE. PLEASE PROVIDE DETAILS OF THE BIN THAT
 COMPLIES WITH REACHABILITY OFF THE DOOR PER THE 2017
 FBC ACC SEC. 308.
  
 23. COULD NOT FIND A FIRE STOP FROM THE ARCHITECT, SO
 PLEASE PROVIDE ALL DETAILS OF ALL THE COMPLETE ASSEMBLY
 ON UL 449 AND UL 605 SYSTEMS PER THE WPB FBC 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 24. DONE
  
 25. DONE
  
 26. WHICH PAGE OF NOTES, 7.
  
 A LINT INTERCEPTOR IS REQUIRED ON THE WASHING MACHINES
 IN THE GUEST AND STAFF LAUNDRY FACILITIES PER THE 2017
 FBC-PLUMBING SEC. P1003..6.
  
 27. DONE
  
 28. ON SHEET P201,
  
 A. PLEASE PLACE TAGS ON ALL THE RISERS (SANITARY UP) TO
 COINCIDE WITH RISERS ON ISOMETRIC DRAWING IN OTHER
 PAGES FOR THE CONTINUATION PER THE WPB FBC 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. ON-GRID E/8, THE THREE-INCH PARTIAL PIPES NEED TO BE
 LABELED TO WHERE THE CONTINUATION WILL BE. THE LAST
 COMMENT RESPONSE SAYS, ?PIPE INDICATES THE LOCATION OF
 THE DOWNSPOUT FROM PORTE-COCHERE ROOF GUTTER. PIPE WILL
 CONNECT TO STORM WATER PER CIVIL PLANS. SEE CIVIL PLANS
 FOR ADDITIONAL INFORMATION? PLEASE NOTE IT ON THE
 SECTION OF PIPE PER THE WPB FBC 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 C. THERE IS NO SANITARY CONNECTION FOR THIS BATHROOM
 GROUP IN GRID 10-11 AND C-D FOR UNIT 114. PLEASE
 CORRECT FOR ALL PAGES PER THE WPB FBC 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 D. THERE IS 4" SANITARY UP IN THE MIDDLE OF THE LOBBY
 GREAT ROOM THAT IS NOT IN A WALL AND THE CENTER OF THE
 ROOM. PLEASE MOVE TO A WALL PER THE WPB FBC 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 E. THE ELEVATORS HAVE INDIRECT WASTE. PLEASE PROVIDE A
 DETAIL PER THE 2017 FBC SEC. P 1113.
  
 F. PLEASE MOVE THE ELEVATOR INDIRECT WASTE PIPE TO THE
 STORAGE ROOM, SIZE, AND SHOW ON P801 PER THE WPB FBC
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 29. ON SHEET P805;
  
 A. PLEASE PROVIDE THE GPM AND ROOF AREA IN FEET OF
 COVERED AREA FOR EACH RAIN LEADER STORM WATER RISER
 DIAGRAM FOR THE 2017 FBC SEC CALCULATIONS. P1106.
  
 B. PLEASE SHOW THE SLOPE OF ALL HORIZONTAL PIPE PER THE
 WPB FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 SHOW THE HORIZONTAL PIPE SLOPE ON THE PLANS AND THE
 PIPE SIZE OF EACH SECTION OF PIPE. THE STORM DRAINAGE
 SYSTEM SHALL BE SIZED IN ACCORDANCE WITH FBC-PLUMBING
 SEC.1106. THE PARAPET WALL SHALL BE INCLUDED IN THE
 STORM DRAINAGE SYSTEM'S SIZING IN ACCORDANCE WITH
 SEC.1106.4. THE FLOW RATE THROUGH THE ROOF DRAIN SHALL
 BE CALCULATED IN ACCORDANCE WITH SEC.1105.
  
 30. DONE
  
 31. ON SHEET P201, P202, P203, P204, P301, P302, P303,
 AND P304, GRID 5-7, 15, 19 WHERE CHANGE AND NOT IN
 ORDER, ALSO D WAS MOVED UP TO FOLLOW A-8. PLEASE
 CORRECT FOR ALL PAGES PER THE WPB FBC 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 PLEASE NOTE THAT A SHEET FOR THE CIVIL DRAWING IS
 REQUIRED ON THIS SET OF PLANS SUBMITTED IN COMMENT ONE.
  
 32. DONE
  
 33. DONE
  
 34.DONE
  
 35. DONE
  
 36. DONE
  
 37. THE SECOND REQUEST, PLEASE PLACE RISER TAGS ON THE
 WATER RISER AS ON P201 FOR THE EARLIER COMMENT; ALL
 RISERS ON P801, P802, P803, AND P804 SHALL MATCH THE
 FLAT CROSS-REFERENCE AND CONTINUATION. PER THE WPB
 AMENDMENTS TO FBC SEC. 107.2.1. CONSTRUCTION DOCUMENTS
 SHALL BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE, AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES, AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
 SUCH DRAWINGS AND SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC, AND THE TECHNICAL CODES SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR SHALL THE TERM "LEGAL"
 OR IT IS EQUIVALENT BE USED AS A SUBSTITUTE FOR
 SPECIFIC INFORMATION.
  
 38.DONE
  
 39. DONE
  
 40. DONE
  
 41. ON SHEET P801,
  
 A. PLEASE SHOW P-TRAPS ON LAVATORIES, TUBS, AND SHOWERS
 ON ALL RISERS PER THE WPB FBC 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 B. PLEASE SHOW THE CONTINUATION POINTS OF ALL PARTIAL
 PIPING SECTIONS SHOWN ON BOTH RISER DIAGRAMS PER THE
 WPB FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 C. THERE ARE MANY FITTING ON THE ISOMETRIC SHOWN IN THE
 WITH NO FLOW DIRECTION. PLEASE NOTE THAT SANITARY
 FITTINGS ON ALL ISOMETRIC DRAWINGS SHALL BE INSTALLED
 TO GUIDE SEWAGE AND WASTE IN THE DIRECTION OF FLOW PER
 THE 2017 FBC SECTION 706.3 INSTALLATION OF FITTINGS.
  
 D. THERE ARE CROSS TEE FITTINGS ON THE BRANCHES TO THE
 UNIT, AND ALL CONNECTIONS AND CHANGES IN DIRECTION OF
 THE SANITARY DRAINAGE SYSTEM SHALL BE MADE WITH
 APPROVED DRAINAGE FITTINGS PER THE 2017 FBC SEC. P
 706.1 1 CONNECTIONS AND CHANGES IN DIRECTION.
  
 42. ON SHEETS P802,
 A. SECOND REQUEST, PLEASE SIZE ALL SECTIONS OF WASTE
 AND SENT THE SYSTEM ON ALL THE SANITARY RISERS PER THE
 2017 FBC TABLE 710.1. (1) AND WPB FBC 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. UNIT 114 IS NOT CONNECTED TO THE 6? LINE AS NOTED ON
 P201 AS WELL; PLEASE RE-SIZE IF NEEDED AND CORRECT PER
 THE WPB AMENDMENTS TO FBC SEC. 107.2.1.
  
 C. FLOOR DRAIN IN LAUNDRY ROOM NOT CONNECTED TO ITS
 FEED AND NEED TO SHOW P-TRAP PER THE WPB FBC 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 D. THE TAGS THAT REFER TO 801 AND 801 NEED TO BE SHOWN
 ON P 201 TO REFERENCING EACH OTHER PER THE WPB FBC
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 E. PLEASE LABEL AND PIPE THAT IS BRANCHING OFF THE MAIN
 TRUNK LINE TO ITS CONTINUATION POINT PER THE WPB FBC
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 43. DONE
  
 44. ON SHEET P802, THE SECOND REQUEST, THERE ARE
 SECTIONS OF PIPE MISSING ON THE SANITARY RISER DIAGRAM.
 PLEASE REFER TO COMMENT 28 FOR SECTION MISS, AND PLEASE
 REVISE THE DRAWING PER THE WPB FBC 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 45. ON SHEET P803 & P804 - HOSE BIBBS SHALL BE
 SEPARATELY VALVES PER FBC-PLUMBING SEC.606.2 (2) THERE
 IS A NOTE ON 803, BUT 804 HAS NO NOTE, PLEASE SHOW
 VALVE ON ISOMETRIC AND TO WHICH PAGE OF THE DETAIL IS
 THE HB-1 LOCATED PER THE WPB FBC 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 46. DONE
  
 47. DONE
  
 48. THE SERVICE SINKS HAVE BEEN MOVED AND NOTED, BUT
 THE SERVICE SINK (MOP SINK) SURROUNDING WALLS SHALL BE
 NON-ABSORBENT SURFACE IN ACCORDANCE WITH THE 2017 FBC
 BUILDING SEC. 1210.2.2 AND 2017 FBC SEC. P 310.3.
 PLEASE MAKE A NOTE ON THIS SHEET.
  
 49. ON SHEET P803 & P804 - DOWN FEED RISERS SHALL BE
 EQUIPPED WITH FULLY OPEN SHUTOFF VALVES PER
 FBC-PLUMBING SEC.606.1 (5). THE RESPONSE REFERS TO AN
 AIR VENT THAT WAS NOT FOUND ON P601; PLEASE ADD VALVES
 TO ISOMETRIC OR ANNOTATE FOR FIELD CLARITY PER THE WPB
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 50. DONE
  
 51. DONE AS A NOTE
  
 52. DONE BUT REQUIRES DETAIL AS REQUESTED IN A PREVIOUS
 COMMENT.
  
 53. DONE
  
 54. THE GREASER INTERCEPTOR REQUIRES A ZONING REVIEW,
 AND AS REQUESTED IN THE PREVIOUS COMMENT, A CIVIL PLAN
 WAS ASKED FOR A REVIEW. CONTACT THE CITY'S ENGINEERING
 DEPT, AT 561-494-1040 FOR FURTHER INFORMATION ON
 STANDARD DRAWING GC-7.
  
 55. DONE
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-11-02 Cont ID  
Sent By tklarge Date 2020-11-02 Time 13:08 Rev Time 0.00
Received By tklarge Date 2020-10-27 Time 03:58 Sent To  
Notes
2020-11-01 07:33:541) SUBMIT A COMPLETE SET OF CIVIL DRAWINGS SHOWING THE
 WATER, SEWER, STORM DRAINAGE AND GAS PIPING SYSTEMS.
 WPB AMEND. TO FBC SEC. 107.2.1, 107.3.5.1.3.
 2) SHT. A030 - CHAPTER 11 - ACCESSIBILITY NOTES - THERE
 IS A NOTE ON THE BOTTOM LEFT COLUMN THAT REFERS TO
 FLORIDA ACCESSIBILITY CODE SECTION 213.2 , EXCEPTION
 #2. THIS EXCEPTION REFERS TO HISTORIC BUILDINGS AND HAS
 NOTHING TO DO WITH THIS PROJECT. DELETE THIS FROM THE
 PLAN.THE NOTE ALSO REFERS TO SECTION 1107. SECTION 1107
 IN THE FBC-BUILDING IS NOTED AS "RESERVED" SO THIS IS
 ALSO NOT APPLICABLE.REMOVE THIS NOTE FROM THE PLAN.
 3) SHT. A400 - THE GRAB BARS SHALL BE MEASURED TO THE
 TOP OF THE GRIPPING SURFACE, NOT TO THE CENTERLINE.
 FBC-ACCESS. SEC. 609.4.
 4) THE PLANS SHOW THE INSTALLATION OF VERTICAL GRAB
 BARS ON SHT. A400 AND IN NUMEROUS OTHER DETAILS AND
 ELEVATIONS THROUGHOUT THE PLANS. SECTION 609.4 OF THE
 FBC-ACCESS. REQUIRES GRAB BARS TO BE INSTALLED IN THE
 HORIZONTAL POSITION. THERE IS NO EXCEPTION IN THE
 ACCESSIBILITY CODE ALLOWING FOR THE INSTALLATION OF
 GRAB BARS IN THE VERTICAL POSITION. DELETE THIS DETAIL
 FROM THE PLANS. REFER TO SHTS. A410 - A415 AMONG
 OTHERS.
 5) SHT. A400 - BATHTUB DETAIL - SHOWS CONTROLS NEXT TO
 THE TUB SPOUT AND ALSO A SET OF SHOWER CONTROLS.
 CLARIFY. THE CONTROLS SHALL BE LOCATED PER FBC-ACCESS.
 SEC. 607..5.
 6) SHT. A400 - BATHTUB DETAIL -THE REMOVABLE TUB SEAT
 SHALL COMPLY WITH FBC-ACCESS. SEC.610.2 AND FIGURE
 610.2. SHOW COMPLIANCE ON THE PLAN.
 7) SHT. A400 - BATHTUB DETAIL -THE EDGE OF THE GRAB
 BARS AT THE HEAD AND FOOT OF THE TUB SHALL BE LOCATED
 AT THE FRONT EDGE OF THE TUB BUT THE DETAIL SHOWS THE
 GRAB BARS SET BACK 4 INCHES FROM THE EDGE OF THE TUB.
 COMPLY WITH FBC-ACCESS. SEC. 607.4.2.2 & 607.4.2.3.
 8) SHT.A400 - HOUSEKEEPING/EVS CLOSET DETAIL - CLARIFY
 THE TYPE OF WALL SURFACE TO BE INSTALLED AROUND THE
 SERVICE SINKS. SECTION 1210.2.2. OF THE FBC-BUILDING
 REQUIRES WALLS AND PARTITIONS WITHIN 2 FEET OF SERVICE
 SINKS TO HAVE A SMOOTH, HARD, NONABSORBENT SURFACE, TO
 A HEIGHT OF NOT LESS THAN 4 FEET ABOVE THE FLOOR AND
 THE MATERIALS USED IN SUCH WALLS SHALL BE OF A TYPE
 THAT IS NOT ADVERSELY AFFECTED BY MOISTURE. EPOXY PAINT
 DOES MEET THE REQUIREMENTS OF THIS SECTION.
 9) SHT. A400 - TOILET/WATER CLOSETS DETAIL - SHOW THE
 MINIMUM HEIGHT OF THE TOILET PAPER DISPENSER. COMPLY
 WITH FBC-ACCCESS. SEC.604.7.
 10) SHOW THE REQUIRED CLEAR FLOOR SPACE FOR THE
 DRINKING FOUNTAINS AS REQUIRED BY FBC-ACCESS. SECS.305
 & 602.2.
 11) SHT. A400 - DRIINKING FOUNTAIN DETAIL - SHOW THE
 REQUIRED CLEARANCE UNDER THE DRINKING FOUNTAIN. THE
 CLEARANCE SHALL BE FROM THE FINISH FLOOR TO THE BOTTOM
 OF THE UNIT, NOT TO THE BOTTOM OFF THE BASIN. COMPLY
 WITH FBC-ACCESS. FOR KNEE AND TOE CLEARANCE.
 12) SHT. A400 - ACCESSIBLE TRANSFER SHOWER DETAIL -
 SHOW THE HEIGHT OF THE SHOWER CONTROLS ON THE PLAN TO
 THE CENTERLINE OF THE HANDLE. COMPLY WITH FBC-ACCESS.
 SEC. 608.5.1 & FIGURE 608.5.1.
 13) SHT. A400 - SUBMIT DETAILS ON THE TRANSFER SHOWER
 SEAT.THE SEAT SHALL COMPLY WITH FBC-ACCESS. SECS.
 610.3, 610.3.2.
 14) SHT. A400 - ROLL IN SHOWER DETAIL - SUBMIT DETAILS
 ON THE ROLL IN SHOWER SEAT. THE SEAT SHALL COMPLY WITH
 FBC-ACCESS. SEC.610.3, 610.3.1.
 15) SHT. A412 - DETAIL #1 - SHOW THE DIMENSIONS OF THE
 REQUIRED CLEAR FLOOR SPACES FOR THE HANDICAP ACCESSIBLE
 FIXTURES ON THE PLANS. COMPLY WITH FBC-ACCESSIBILITY
 CODE SECS.604.3, 606.2. SHOW THE CLEAR FLOOR SPACE
 ADJACENT TO THE SHOWER.
 16) SHT. A414 - SHOW THE DIMENSIONS OF THE REQUIRED
 CLEAR FLOOR SPACES FOR THE HANDICAP ACCESSIBLE FIXTURES
 ON THE PLANS. COMPLY WITH FBC-ACCESSIBILITY CODE
 SECS.604.3, 606.2. SHOW THE CLEAR FLOOR SPACE ADJACENT
 TO THE SHOWER. THE CLEAR FLOOR SPACE FOR THE LAVATORY
 SHALL BE POSITIONED FOR A FORWARD APPROACH PER SEC.
 606.2.
 17) SHT. A417 - SHOW THE DIMENSIONS OF THE REQUIRED
 CLEAR FLOOR SPACES FOR THE HANDICAP ACCESSIBLE FIXTURES
 ON THE PLANS. COMPLY WITH FBC-ACCESSIBILITY CODE
 SECS.604.3, 606.2. SHOW THE CLEAR FLOOR SPACE ADJACENT
 TO THE TUB. THE CLEAR FLOOR SPACE FOR THE LAVATORY
 SHALL BE POSITIONED FOR A FORWARD APPROACH PER SEC.
 606.2.
 18) SHT. A422 - SHOW THE DIMENSIONS OF THE REQUIRED
 CLEAR FLOOR SPACES FOR THE HANDICAP ACCESSIBLE FIXTURES
 ON THE PLANS. COMPLY WITH FBC-ACCESSIBILITY CODE
 SECS.604.3, 606.2. SHOW THE CLEAR FLOOR SPACE ADJACENT
 TO THE TUB.
 19) SHT. A423 - SHOW THE DIMENSIONS OF THE REQUIRED
 CLEAR FLOOR SPACES FOR THE HANDICAP ACCESSIBLE FIXTURES
 ON THE PLANS. COMPLY WITH FBC-ACCESSIBILITY CODE
 SECS.604.3, 606.2. SHOW THE CLEAR FLOOR SPACE ADJACENT
 TO THE TUB. THE CLEAR FLOOR SPACE FOR THE LAVATORY
 SHALL BE POSITIONED FOR A FORWARD APPROACH PER SEC.
 606.2.
 20) SUBMIT MANUFACTURER'S SSPECIFICATIONS FOR THE
 DRINKING FOUNTAIN/BOTTLE FILLER IN THE FITNESS ROOM.
 21) SHT. A450 - DETAIL #8 SHOWS THE LAVATORY WITH 2
 FEET OF CLEARANCE BELOW THE LAVATORY. A MINIMUM
 CLEARANCE OF 27 INCHES FROM THE FINISH FLOOR TO THE
 BOTTOM OF THE CABINET/APRONIS REQUIRED PER FBC-ACCESS.
 SEC. 306 FOR KNEE AND TOE CLEARANCE.
 22) SHT. A450 - LAUNDRY DETAIL - THE WASHER AND DRYER
 SHALL COMPLY WITH FBC-ACCESS. SECS. 309, 611.2, 611.3,
 611.4. SHOW COMPLIANCE ON THE PLANS.
 23) SUBMIT LISTED FIRESTOPPING DETAILS FOR NONMETALLIC
 PIPING THROUGH RATED WALLS AND FLOORS. THE DETAIL ON
 SHT. A805 APPEARS TO BE ONLY FOR DRAIN CONNECTIONS TO
 WATER CLOSETS AND THE DETAIL ON SHT. A806 FOR RATED
 WALL ASSEMBLIES IS FOR NONMETALLIC PIPE WITH A DIAMETER
 OF 2 INCHES OR LESS. ALSO, THE DETAILS ON SHT. P601 ARE
 VAGUE AND UNACCEPTABLE. SUBMIT THE COMPLETE UL ASSEMBLY
 DETAILS FOR THE UL 449 & UL 605 SYSTEMS. WPB AMEND. TO
 FBC SEC. 107.2.1.
 24) SHT. P001 - INDICATE ON THE PLAN WHAT STANDARD WAS
 USED IN THE SIZING OF THE GREASE INTERCEPTOR. THE
 INTERCEPTOR SHALL BE SIZED IN THE ACCORDANCE WITH ONE
 OF THE STANDARDS LISTED IN FBC-PLUMBING SEC.1003.3.4.
 OR RULE 64E-6 OF THE FL. ADMIN. CODE. THE EQUATION ON
 THE PLANS APPEARS TO BE INCOMPLETE.
 25) TEMPERED WATER IS REQUIRED TO THE LAVATORIES
 LOCATED IN PUBLIC TOILET FACILITIES. TEMPERED WATER
 SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B 125.3 PER FBC-PLUMBING SEC.416.5.
 26) A LINT INTERCEPTOR IS REQUIRED ON THE WASHING
 MACHINES IN THE GUEST AND STAFF LAUNDRY FACILITIES PER
 FBC-PLUMBING SEC.1003..6.
 27) A FLOOR DRAIN IS REQUIRED IN THE ROOM CONTAINING
 THE AUTOMATIC CLOTHES WASHERS PER FBC-PLUMBING
 SEC.412.4. THE DRAIN SHALL HAVE AN OUTLET OF NOT LESS
 THAN 3 INCHES.
 28) SHT. P201 - PLACE RISER TAGS ON THE RISERS. WPB
 AMEND. TO FBC SEC. 107.2.1.
 29) SUBMIT A COMPLETE STORM WATER RISER DIAGRAM. SHOW
 THE SLOPE OF THE HORIZONTAL PIPE ON THE PLANS AND THE
 PIPE SIZE OF EACH SECTION OF PIPE. THE STORM DRAINAGE
 SYSTEM SHALL BE SIZED IN ACCORDANCE WITH FBC-PLUMBING
 SEC.1106. THE PARAPET WALL SHALL BE INLUDED IN THE
 SIZING OF THE STORM DRAINAGE SYSTEM IN ACCORDANCE WWITH
 SEC.1106.4. THE FLOW RATE THROUGH THE ROOF DRAIN SHALL
 BE CALCULATED IN ACCORDANCE WITH SEC.1105.
 30) SHT. P201 - THE PLAN NOTES "6 INCH STORM TO CLEAR
 WATER WASTE" WITH ARROWS POINTING TO AN AREA BUT THERE
 IS NO PIPING SHOWN. CLARIFY. REFER TO GRID LINES D/4-5.
 CLARIFY.
 31) SHT. P201 - THERE IS A PARTIAL SECTION OF 3 INCH
 PIPE SHOWN AT GRID LINE E/8. SHOW CONTINUATION POINT
 AND TERMINATION POINT.
 32) THE RAIN WATER LEADERS AND THE OVERFLOW DRAINS
 SHALL DISCHARGE A MINIMUM OF ONE FOOT FROM THE
 STRUCTURE SIDEWALL. FBC-BUILDING SEC.1503.7.
 33) SHT. P201 SHOWS A 4 INCH SANITARY LINE AT GRID
 LINES A.8/18.2-19 AND THE SAME LINE IS SHOWN AS 3 INCH
 ON SHT. P801. CLARIFY.
 34) SHT. P201 - THE FLOOR DRAINS IN THE MEN'S AND
 WOMEN'S TOILET ROOMS ON THE FIRST FLOOR APPEAR TO
 EXCEED THE DISTANCE FROM A VENT PER FBC-PLUMBING TABLE
 9091.
 35) SHT. P203 - GENERAL NOTE #3 - SLOPE OF HORIZONTAL
 DRAINAGE PIPE SHALL COMPLY WITH FBC-PLUMBING SEC. 704.1
 & TABLE 704.1. REVISE THE NOTE.
 36) HOT WATER PIPING SHALL BE INSULATED PER FBC-ENERGY
 SEC. C404.4 & TABLE C403.2.10.INDICATE THE INSULATION
 THICKNESS FOR THE DIFFERENT PIPE SIZES ON THE PLANS.
 37) PLACE RISER TAGS ON THE WATER RISER. WPB AMEND. TO
 FBC SEC. 107.2.1.
 38) SHT. P301 - LABEL THE 1 1/2 INCH DHR LINE FOR THE
 UNISEX TOILET ROOM ON THE PLANS.
 39) SHT. P301 - THERE IS A SECTION OF SANITARY PIPE
 OVERLAYED IN THE GREAT ROOM AREA THAT DOES NOT
 BELONG.REVISE THE DRAWING .
 40) SHT. P301 SHOWS A 4 INCH DWHR UP AND SHT. P804
 SHOWS THIS LINE AS 4 INCH DCW UP. CLARIFY.
 41) SHT. P801 - THERE ARE SECTIONS OF PIPE MISSING ON
 THE KITCHEN SINKS (KS-1) AND ALSO ON US-1 AND OTHER
 AREAS, TRAPS NOT SHOWN ON LAVATORIES OR SHOWERS. SHOW
 THE CONTINUATION POINTS OF ALL PARTIAL SECTIONS OF
 PIPING SHOWN ON BOTH RISER DIAGRAMS. WPB AMEND. TO FBC
 SEC. 107.2.1.
 42) SHT. P801 & P802 - SIZE ALL SECTIONS OF THE WASTE
 AND VENT SYSTEM ON ALL THE SANITARY RISERS AND SHOW THE
 DRAINAGE FIXTURE LOAD ON THE RISERS AND THE TOTAL
 DRAINAGE FIXTURE LOAD ON THE MAIN LINE. COMPLY WITH
 FBC-PLUMBING TABLE 710.1 (1) & TABLE 710..1 (2) . WPB
 AMEND. TO FBC SEC. 107.2.1.
 43) SHT. P801 & P201 - THE FLOOR DRAINS IN THE STAFF
 AND GUEST LAUNDRIES AND ALSO IN THE PANTRY APPEAR TO
 EXCED THE DISTANCE FROM A VENT. COMPLY WITH
 FBC-PLUMBING TABLE 909.1.
 44) SHT. P802 - THERE ARE SECTIONS OF PIPE MISSING ON
 THE SANITARY RISER DIAGRAM. REVISE THE DRAWING.WPB
 AMEND. TO FBC SEC. 107.2.1.
 45) SHTS. P803 & P804 - HOSE BIBBS SHALL BE SEPARATELY
 VALVED PER FBC-PLUMBING SEC.606.2 (2).
 46) SHT. P803 - SHOW THE 1/2 INCH DHR LINE BY STORAGE
 ROOM EQ1.11 ON THE WATER RISER.
 47) SHT. P804 - IDENTIFY THE WASHING MACHINE IN THE
 STAFF LAUNDRY ON THE WATER RISER.(EQUIPMENT ROOM EQ
 1.2).
 48) THE PLUMBING SHEETS SHOW SERVICE SINKS ON LEVELS 2,
 3 & 4 BUT THEY ARE NOT SHOWN ON THE ARCHITECTURAL
 PLANS. CLARIFY.
 49) SHTS. P803 & P804 - DOWNFEED RISERS SHALL BE
 EQUIPPED WITH FULLL OPEN SHUTOFF VALVES PER
 FBC-PLUMBING SEC.606.1 (5).
 50) SHT. P803 - IDENTIFY THE WASHING MACHINE IN THE
 GUEST LAUNDRY ON THE WATER RISER.
 51) SHUTOFF VALVES ARE REQUIRED AT THE BASE OF RISERS 3
 INCH DHW & 4 INCH DCW
 52) THE FLOOR DRAIN IN THE ELEVATOR SHAFT SHALL BE
 INDIRECTLY CONNETED TO THE PLUMBING SYSTEM PER
 FBC-PLUMBING SEC. 3301.6.
 53) INDICATE ON THE PLAN IF THE ELEVATOR IS HYDRAULIC
 OR TRACTION TYPE. IF HYYDRAULIC, THE INSTALLATION OF
 THE FLOOR DRAIN IN THE PIT SHALL OMPLY WITH
 FBC-PLUMBING SEC.1003.4.
 54) SUBMIT A DETAIL OF THE GREASE INTERCEPTOR. THE
 GREASE INTERCEPTOR SHALL COMPLY WITH THE FL. ADMIN.CODE
 RULE 64E-6 AND THE CITY OF WEST PALM BEACH STANDARD
 DETAIL GS-7. CONTACT THE CITY'S ENGINEERING DEPT. AT
 561-494-1040 FOR FURTHER INFORMATION ON TANDARDD
 DRAWING GC-7.
 55) SWAY BRACING SHALL BE PROVIDED AT CHANGES IN
 DIRECTION GREATER THAN 45 DEGREES FOR DRAINAGE PIPE
 SIZES 4 INCHES AND LARGER PER FBC-PLUMBING SEC.308.6.
 SUBMIT DETAIL.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 3 Status N Date 2021-10-27 Cont ID  
Sent By lcrespo Date 2021-10-27 Time 13:06 Rev Time 0.00
Received By lcrespo Date 2021-10-27 Time 13:06 Sent To  
Notes
2021-10-27 13:08:44GREASE INTERCEPT IS NOT A TURNAROUND. THE CALCULATIONS
 UNDER THE PRIMARY PERMIT AND WE NEED TO FACILITATE THE
 PLUMBING REVIEW ON THE INTERCEPT PERMIT.
  
 A SEPARATE PERMIT AND REVIEW FROM PLUMBING AND
 ENGINEERING FOR THE GREASE INTERCEPTOR IS REQUIRED BY A
 LICENSED CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB
 AMENDMENTS TO THE FBC SEC. 105.1.

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 2 Status F Date 2021-07-14 Cont ID  
Sent By lcrespo Date 2021-07-14 Time 14:00 Rev Time 0.00
Received By lcrespo Date 2021-07-14 Time 11:45 Sent To  
Notes
2021-07-14 14:00:2607/14/21 3RD PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE SUBMIT A COMPLETE SET OF CIVIL DRAWING
 SHOWING THE LOCATION OF THE GREASE INTERCEPTOR PER THE
 WPB AMENDMENTS TO FBC SEC. 107.2.1, 107.3.5.1.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 1 Status F Date 2021-01-04 Cont ID  
Sent By lcrespo Date 2021-01-04 Time 16:01 Rev Time 0.00
Received By lcrespo Date 2021-01-04 Time 15:43 Sent To  
Notes
2021-01-04 16:02:3901/04/20 2ND PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE SUBMIT A COMPLETE SET OF CIVIL DRAWING
 SHOWING THE LOCATION OF THE GREASE INTERCEPTOR PER THE
 WPB AMENDMENTS TO FBC SEC. 107.2.1, 107.3.5.1.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2020-12-21 Cont ID  
Sent By rmcdouga Date 2020-12-21 Time 13:55 Rev Time 0.00
Received By rmcdouga Date 2020-12-21 Time 07:24 Sent To  
Notes
2020-12-21 13:55:24ROOFING PRODUCT APPROVALS ARE DEFERRED AND ARE TO BE
 SUBMITTED FOR APPROVAL PRIOR TO RECEIVING THE ROOFING
 SUB-PERMIT.
 NO PRODUCT APPROVALS WERE SUBMITTED FOR THE ROOFING
 MATERIALS:
 SEE SHEET A011
 1) TPO ROOFING MATERIAL FOR THE MAIN BUILDING. NOA NO.
 18-0501.03
 2) STANDING SEAM METAL ROOF FOR THE PORTE COCHERE. NOA
 NO. 17-1002.12
 3) ROOF COPING: NOA NO. 19-0430.02

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2020-11-02 Cont ID  
Sent By rmcdouga Date 2020-11-02 Time 07:36 Rev Time 0.00
Received By rmcdouga Date 2020-11-02 Time 07:36 Sent To  
Notes
2020-11-02 07:42:31NO PRODUCT APPROVALS WERE SUBMITTED FOR THE TPO ROOFING
 MATERIAL FOR THE MAIN BUILDING OR THE STANDING SEAM
 METAL ROOF FOR THE PORTE COCHERE.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2021-10-12 Cont ID  
Sent By rmcdouga Date 2021-10-12 Time 17:28 Rev Time 0.00
Received By rmcdouga Date 2021-10-12 Time 17:28 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2021-06-29 Cont ID  
Sent By rmcdouga Date 2021-06-29 Time 15:47 Rev Time 0.00
Received By rmcdouga Date 2021-06-29 Time 15:47 Sent To  
Notes
2021-06-29 15:47:26SOME OF THE ENGINEER'S SIGNATURES ARE INVALID AND HAVE
 BEEN REVOKED. SEE SEVERAL STRUCTURAL SHEETS, SOME OF
 THE ARCHITECTURAL SHEETS INCLUDING A100 AND THE
 STRUCTURAL CALCULATION PACKAGE IN THE SUPPORTING
 DOCUMENTS. ELECTRONICALLY SUBMITTED DRAWINGS ARE
 REQUIRED TO HAVE THE ARCHITECT OR ENGINEER'S DIGITAL
 SIGNATURE ON THEM. YOU ALSO HAVE THE OPTION TO SUBMIT
 THE SIGNED AND SEALED PAPER VERSION OF DRAWINGS. AFTER
 THE ELECTRONIC PLANS HAVE BEEN APPROVED, YOU CAN SUBMIT
 THE CORRESPONDING PAPER DRAWINGS AT THE BUILDING
 DEPARTMENT TO BE VERIFIED. THE ARCHITECT OR ENGINEER'S
 ORIGINAL HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO
 BE ON THE DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF
 THE SIGNATURE ARE ACCEPTABLE. FS 481 & 61G1 OR FS 471 &
 61G15

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-03-01 Cont ID  
Sent By medwards Date 2021-03-01 Time 09:49 Rev Time 0.00
Received By medwards Date 2021-03-01 Time 09:49 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-12-16 Cont ID  
Sent By medwards Date 2020-12-16 Time 17:07 Rev Time 0.00
Received By medwards Date 2020-12-16 Time 17:07 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-10-30 Cont ID  
Sent By medwards Date 2020-10-30 Time 08:51 Rev Time 0.00
Received By medwards Date 2020-10-30 Time 08:51 Sent To  
Notes
***NONE***

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 5 Status F Date 2021-10-07 Cont ID  
Sent By rmcdouga Date 2021-10-07 Time 17:06 Rev Time 0.00
Received By rmcdouga Date 2021-10-07 Time 17:06 Sent To  
Notes
2021-10-07 17:12:06THE THRESHOLD DOCUMENTS ARE INCOMPLETE. THE OWNER'S AND
 CONTRACTOR'S NOTARIZED SIGNATURES ARE MISSING FROM
 THEIR SECTION OF THE THRESHOLD DOCUMENTS.

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 4 Status F Date 2021-06-29 Cont ID  
Sent By rmcdouga Date 2021-06-29 Time 15:16 Rev Time 0.00
Received By rmcdouga Date 2021-06-29 Time 15:16 Sent To  
Notes
2021-06-29 15:19:28THE REQUIRED THRESHOLD NOTARIZED FORMS AND
 DOCUMENTATION HAS NOT BEEN SUBMITTED. THE FORMS IN THE
 THRESHOLD BOOKLET THAT WAS SUBMITTED HAVE NOT BEEN
 COMPLETED.
  
 THRESHOLD BUILDING / FL S. S. 553.71(7) "THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN
 (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS DEFINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 A) FBC (CITY AMENDMENTS)110.8.1 THRESHOLD INSPECTION
 PLAN. THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 B) THRESHOLD INSPECTOR: WPB AMENDMENT 110.8.1 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY 553.79(5)
 FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY
 THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED
 TO BE FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED
 AND RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED
 BEFORE PERMIT ISSUANCE WILL TAKE PLACE.
  
 C) THRESHOLD BLDG. REQUIRED STATEMENT: W.P.B. AMENDMENT
 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED
 TO BE SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF
 RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE
 ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM
 BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS
 AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS SECTION AND CHAPTER 633 FLORIDA STATUTES.
  
 D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME OF
 INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME
 MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED
 HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL
 REVIEW THE RESUME. AFTER THE RESUME IS REVIEWED, AN
 INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONSTRUCTION.
  
 F) NOTE: FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE.
  
 G) 110.8.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 H) PLEASE CALL THE CITY OF WEST PALM BEACH'S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700 FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 I) 110.8 THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR
 THRESHOLD INSPECTORS #25. ASSURE THAT THE DESIGNER HAS
 REQUIRED ON THE PLANS OR SPECIFICATIONS ONE MATERIAL,
 APPROVED FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND
 CEILINGS.
  
 J) PLEASE CONTACT ME WITH AN EMAIL ADDRESS AND I WILL
 BE HAPPY TO SEND YOU A COPY OF THE CURRENT (OCTOBER
 2018) GUIDELINES AND POLICIES FOR PROJECTS CONCERNING
 THRESHOLD/SPECIAL INSPECTORS AND RESIDENT INSPECTORS.
  
  
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 3 Status F Date 2021-03-08 Cont ID  
Sent By rmcdouga Date 2021-03-08 Time 10:01 Rev Time 0.00
Received By rmcdouga Date 2021-03-08 Time 10:01 Sent To  
Notes
2021-03-08 10:08:36NOT ALL OF THE REQUIRED THRESHOLD NOTARIZED FORMS AND
 INFORMATION WAS SUBMITTED. PLEASE CONTACT ME AT
 [email protected] WITH AN EMAIL ADDRESS AND I WILL SEND
 YOU THE CURRENT (OCTOBER 2018) GUIDELINES AND POLICIES
 FOR PROJECTS CONCERNING THRESHOLD/SPECIAL INSPECTORS
 AND RESIDENT INSPECTORS WITH ALL OF THE REQUIRED FORMS
 TO BE FILLED OUT, NOTARIZED AND SUBMITTED.
  
  
 THRESHOLD BUILDING / FL S. S. 553.71(7) "THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN
 (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS DEFINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 A) FBC (CITY AMENDMENTS)110.8.1 THRESHOLD INSPECTION
 PLAN. THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 B) THRESHOLD INSPECTOR: WPB AMENDMENT 110.8.1 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY 553.79(5)
 FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY
 THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED
 TO BE FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED
 AND RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED
 BEFORE PERMIT ISSUANCE WILL TAKE PLACE.
  
 C) THRESHOLD BLDG. REQUIRED STATEMENT: W.P.B. AMENDMENT
 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED
 TO BE SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF
 RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE
 ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM
 BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS
 AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS SECTION AND CHAPTER 633 FLORIDA STATUTES.
  
 D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME OF
 INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME
 MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED
 HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL
 REVIEW THE RESUME. AFTER THE RESUME IS REVIEWED, AN
 INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONSTRUCTION.
  
 F) NOTE: FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE.
  
 G) 110.8.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 H) PLEASE CALL THE CITY OF WEST PALM BEACH'S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700 FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 I) 110.8 THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR
 THRESHOLD INSPECTORS #25. ASSURE THAT THE DESIGNER HAS
 REQUIRED ON THE PLANS OR SPECIFICATIONS ONE MATERIAL,
 APPROVED FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND
 CEILINGS.
  
 J) PLEASE CONTACT ME WITH AN EMAIL ADDRESS AND I WILL
 BE HAPPY TO SEND YOU A COPY OF THE CURRENT (OCTOBER
 2018) GUIDELINES AND POLICIES FOR PROJECTS CONCERNING
 THRESHOLD/SPECIAL INSPECTORS AND RESIDENT INSPECTORS.
  
  
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status F Date 2020-12-21 Cont ID  
Sent By rmcdouga Date 2020-12-21 Time 14:03 Rev Time 0.00
Received By rmcdouga Date 2020-12-21 Time 14:03 Sent To  
Notes
2020-12-21 14:04:32THE REQUIRED THRESHOLD DOCUMENTS HAVE NOT BEEN
 SUBMITTED. SEE PREVIOUS REVIEW COMMENTS.

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2020-11-02 Cont ID  
Sent By rmcdouga Date 2020-11-02 Time 07:42 Rev Time 0.00
Received By rmcdouga Date 2020-11-02 Time 07:42 Sent To  
Notes
2020-11-02 08:10:30THRESHOLD BUILDING / FL S. S. 553.71(7) "THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN
 (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS DEFINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 A) FBC (CITY AMENDMENTS)110.8.1 THRESHOLD INSPECTION
 PLAN. THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 B) THRESHOLD INSPECTOR: WPB AMENDMENT 110.8.1 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY 553.79(5)
 FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY
 THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED
 TO BE FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED
 AND RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED
 BEFORE PERMIT ISSUANCE WILL TAKE PLACE.
  
 C) THRESHOLD BLDG. REQUIRED STATEMENT: W.P.B. AMENDMENT
 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED
 TO BE SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF
 RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE
 ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM
 BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS
 AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS SECTION AND CHAPTER 633 FLORIDA STATUTES.
  
 D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME OF
 INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME
 MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED
 HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL
 REVIEW THE RESUME. AFTER THE RESUME IS REVIEWED, AN
 INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONSTRUCTION.
  
 F) NOTE: FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE.
  
 G) 110.8.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 H) PLEASE CALL THE CITY OF WEST PALM BEACH'S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700 FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 I) 110.8 THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR
 THRESHOLD INSPECTORS #25. ASSURE THAT THE DESIGNER HAS
 REQUIRED ON THE PLANS OR SPECIFICATIONS ONE MATERIAL,
 APPROVED FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND
 CEILINGS.
  
 J) PLEASE CONTACT ME WITH AN EMAIL ADDRESS AND I WILL
 BE HAPPY TO SEND YOU A COPY OF THE CURRENT (OCTOBER
 2018) GUIDELINES AND POLICIES FOR PROJECTS CONCERNING
 THRESHOLD/SPECIAL INSPECTORS AND RESIDENT INSPECTORS.
  
  
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  

Review Stop Z ZONING
Rev No 5 Status P Date 2021-10-12 Cont ID  
Sent By llouie Date 2021-10-12 Time   Rev Time 0.00
Received By llouie Date 2021-10-12 Time   Sent To  
Notes
2021-10-12 08:45:25ZONING APPROVED WITH THE FOLLOWING PROVISOS:
  
 1.) SEPARATE PERMITS REQUIRED FOR: SIGNAGE,
 LANDSCAPING, SITE LIGHTING, FENCING, DUMPSTER
 ENCLOSURE, PARKING AREA PAVING AND STRIPING.
  
 2.) ANY CHANGE TO THE APPROVED PLANS SHALL REQUIRED A
 PLANNED DEVELOPMENT (PD) AMENDMENT SUBMISSION BY THE
 APPLICANT AND APPROVED BY THE DEVELOPMENT SERVICES
 DEPARTMENT - PLANNING DIVISION.

Review Stop Z ZONING
Rev No 4 Status P Date 2021-06-21 Cont ID  
Sent By llouie Date 2021-06-21 Time   Rev Time 0.00
Received By llouie Date 2021-06-21 Time   Sent To  
Notes
2021-06-21 12:06:48ZONING APPROVED WITH THE FOLLOWING PROVISOS:
  
 1.) SEPARATE PERMITS REQUIRED FOR: SIGNAGE,
 LANDSCAPING, SITE LIGHTING, FENCING, DUMPSTER
 ENCLOSURES, PARKING AREA PAVING/STRIPING.
  
 2.) ANY CHANGES TO THE APPROVED PLANS SHALL REQUIRE A
 PD AMENDMENT SUBMISSION BY THE APPLICANT AND APPROVAL
 BY THE DEVELOPMENT SERVICES DEPARTMENT - PLANNING
 DIVISION.

Review Stop Z ZONING
Rev No 3 Status F Date 2021-03-30 Cont ID  
Sent By llouie Date 2021-03-30 Time   Rev Time 0.00
Received By llouie Date 2021-03-30 Time   Sent To  
Notes
2021-03-30 10:30:44** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) THE SURVEY AND APPROVED PLAT DOCUMENTS ARE MISSING
 FROM THE PERMIT SUBMITTAL. THESE ARE CRITICAL
 COMPONENTS OF THE BUILDING PERMIT SET. PLEASE PROVIDE.
  
  
 NOTES:
  
 * ANY CHANGES WHICH DEVIATE FROM THE PLANS APPROVED BY
 THE CITY COMMISSION WILL REQUIRE AN AMENDMENT TO THE
 OCPD (OFFICE COMMERCIAL PLANNED DEVELOPMENT). THE
 AMENDMENT WILL REQUIRE REVIEW AND APPROVAL BY THE
 PLANNING DIVISION PRIOR TO THE APPROVAL OF SUCH CHANGES
 FOR BUILDING PERMIT.
  
 * SEPARATE PERMIT REQUIRED FOR LANDSCAPING.
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: HOLIDAY INN EXPRESS OCPD (REFERENCE: RESOLUTION
 NOS. 338-20 AND 339-20)
  
 * LEFT VOICE MESSAGE FOR COREY RUNTE OF CERTIFIED
 GENERAL CONTRACTORS ON 3/30/21 REQUESTING SURVEY AND
 PLAT DOCUMENTS AS PART OF THE BUILDING PERMIT SET/FILE.
 ALSO INFORMED THAT ANY CHANGES WILL REQUIRE PD
 AMENDMENT. FOLLOW-EMAIL PROVIDED.
  

Review Stop Z ZONING
Rev No 2 Status F Date 2020-12-07 Cont ID  
Sent By llouie Date 2020-12-07 Time   Rev Time 0.00
Received By llouie Date 2020-12-07 Time   Sent To  
Notes
2020-12-07 13:30:08** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) PROJECT REQUIRES APPROVAL FROM THE CITY COMMISSION.
 PROJECT IS CURRENTLY IN REVIEW AND PENDING APPROVAL
 (REFERENCE: PB CASE NO. 1846). [10/20 REPEAT COMMENT:
 APPLICATION PB NO. 1846 IS STILL PENDING; SCHEDULED FOR
 FIRST READING ON 12/14/20]
  
  
 NOTES:
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: PROPOSED REZONING TO OCPDD (HOLIDAY INN
 EXPRESS).
  

Review Stop Z ZONING
Rev No 1 Status F Date 2020-10-20 Cont ID  
Sent By llouie Date 2020-10-20 Time   Rev Time  
Received By llouie Date 2020-10-20 Time   Sent To  
Notes
2020-10-20 18:10:39** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) PROJECT REQUIRES APPROVAL FROM THE CITY COMMISSION.
 PROJECT IS CURRENTLY IN REVIEW AND PENDING APPROVAL
 (REFERENCE: PB CASE NO. 1846).
  
  
 NOTES:
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: PROPOSED REZONING TO OCPDD (HOLIDAY INN
 EXPRESS).
  