Plan Review Details - Permit 20090835
Plan Review Stops For Permit 20090835
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2020-11-02 Cont ID  
Sent By ccole Date 2020-11-02 Time 08:35 Rev Time 0.00
Received By ccole Date 2020-11-02 Time 07:16 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2020-10-05 Cont ID  
Sent By ccole Date 2020-10-05 Time 08:24 Rev Time 0.00
Received By ccole Date 2020-10-05 Time 07:11 Sent To  
Notes
2020-10-05 08:24:302ND REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20090835
 10/2020
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 COMMENTS FROM THE 1ST REVIEW LISTED BELOW HAVE NOT BEEN
 COMPLETELY ADDRESSED. NOTES IN CAP LETTERS HAVE BEEN
 ADDED FOR FURTHER CLARIFICATION.
  
 2) GAS ISOMETRIC DRAWING:
 A) SHOW THE LENGTH, THE TYPE, AND SIZE OF PIPING FROM
 THE METER TO THE 1ST TEE, AND FROM THE 1ST TEE TO THE
 2ND TEE- SECTION G2413.4.1 & G2413.4.2 FBC RES. PLEAE
 CLARIFY: THE CORRECTED RISER SHOWS 2"- 3/4" @ METER. IF
 THE MAIN SUPPLY PIPE AT THE METER IS 3/4", IT IS
 UNDERSIZED TO SUPPLY 919,000 BTU'S PER TABLE G2413.4(2)
 [402.4(5)] FBC RES. FUEL GAS. A MINIMUM 1" PIPE IS
 REQUIRED.
  
 C) SUBMIT UPDATED SPECS FOR THE 22KW GENERATOR. I HAVE
 CHECKED THE UPDATED SPECS FOR THE GENERAC 22 KW MODEL
 AND THEY INDICATE A FULL LOAD OF 306,000 BTUH FOR
 NATURAL GAS. PLEASE CORRECT THE LOAD SHOWN ON THE
 RISER. THE SPECS SUBMITTED UNDER THE GENERATOR PERMIT-
 20070872 INDICATE THE 22KW HAS A 306,000 BTUH CAPACITY-
 PLEASE CORRECT THE RISER.
  
 D) THE GENERAC SPECS SHOW A NATURAL GAS INPUT PRESSURE
 OF 3.5- 7 IN. W.C. PLEASE SHOW THE LOCATION OF THE
 REQUIRED REGULATOR AT THE GENERATOR TO REDUCE PRESSURE.
 INDICATE THE MAKE AND MODEL OF THE SELECTED REGULATOR
 ON THE RISER. SUBMIT MARKED UP OR HIGHLIGHTED REGULATOR
 SPECS SHOWING THE MODEL, INLET AND OUTLET PRESSURES,
 SPRING SELECTION, AND ORIFICE SIZE- SECTION G2421.1 &
 G2421.2. SHOW THE REQUIRED PIPE UNIONS AT THE
 REGULATOR. AS NOTED IN COMMENT 1 THE SUBMITTED REG.
 SPECS ARE FOR LP GAS. NEW REGULATOR SPECS HAVE BEEN
 SUBMITTED HOWEVER THE SPECS AND THE RISER DRAWING HAVE
 NOT BEEN MARKED UP- PLEASE COMPLY.
  
 3) PLEASE NOTE THE GENERATOR (UNDER SEPARATE PERMIT)
 SHALL BE INSTALLED A MINIMUM OF 5' AWAY FROM
 COMBUSTIBLE WALLS- SEC. 4.1.4 NFPA 37, AND A MINIMUM OF
 10' FROM MECHANICAL OR GRAVITY AIR INTAKES (WINDOW AND
 DOOR OPENINGS) INTO THE BUILDING- SEC. R303.5.1 FBC
 RES. THE SUBMITTED SURVEY FOR GENERATOR PERMIT-
 20070872 INDICATE THE GENERATOR AT 5' FROM WINDOWS AND
 DOORS- 10' IS REQUIRED PER SECTION R303.5.1 FBC RES.
  
 4) THERE IS A 0 VALUE FOR THE PROPOSED GAS PIPING
 INSTALLATION. PLEASE SUBMIT A COPY OF A SIGNED CONTRACT
 AND/OR COPIES OF INVOICES AND ESTIMATES SHOWING THE
 TOTAL COST OF THE INSTALLATION INCLUDING VALUE OF
 LABOR, MATERIALS, EQUIPMENT, SITE WORK, DESIGN FEES,
 AND OVERHEAD AND PROFIT- SECTION 109.3 WPB. NO RESPONSE
 PROVIDED TO THE COMMENT. IF THE COST OF THE GAS
 INSTALLATION WAS INCLUDED IN THE GENERATOR PERMIT,
 PLEASE PROVIDE COPIES OF THE PRIMARY AND SUB-CONTRACTS
 TO VERIFY.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-09-24 Cont ID  
Sent By ccole Date 2020-09-24 Time 13:39 Rev Time 0.00
Received By ccole Date 2020-09-24 Time 11:35 Sent To  
Notes
2020-09-24 13:39:501ST REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20090835
 9/24/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE SUBMITTED PE SIZING TABLE FOR LP GAS, THE LP GAS
 REGULATOR SPECS, AND THE LP TANK SPECS ARE NOT
 ACCEPTED- THE RISER SHOWS A NATURAL GAS SYSTEM- SEC.
 107.2.1 WPB.
  
 2) GAS ISOMETRIC DRAWING:
  
 A) SHOW THE LENGTH, THE TYPE, AND SIZE OF PIPING FROM
 THE METER TO THE 1ST TEE, AND FROM THE 1ST TEE TO THE
 2ND TEE- SECTION G2413.4.1 & G2413.4.2 FBC RES.
  
 B) PIPE SIZING SHALL BE IN ACCORDANCE WITH SECTION
 G2413.3 FBC RES. PLEASE INDICATE THE METHOD USED PER
 SECTIONS G2413.4.1 LONGEST LENGTH, OR G2413.4.2 BRANCH
 LENGTH. INDICATE THE TABLES USED TO SIZE THE SCHEDULE
 40 METALLIC AND PE PIPING- SEE TABLES G2413.4(1)-
 G2413.4(8). PLEASE NOTE IF USING THE LONGEST LENGTH
 METHOD TO SIZE THE SCHED. 40 METALLIC, THE MAIN PIPE
 FROM THE METER TO THE 1ST TEE, ACCORDING TO TABLE
 G2413.4(1) SHALL BE MINIMUM 2 IN. FOR A 919,000 BTUH
 LOAD AT 130 FT. DEVELOPED LENGTH. USING THE LONGEST
 LENGTH METHOD TO SIZE THE PE PIPING FROM THE TEE TO THE
 GENERATOR, ACCORDING TO TABLE G2413.4(7) A MINIMUM
 1-1/2 IN. PIPE IS REQUIRED FOR THE 306.000 BTUH LOAD.
 THE PLAN INDICATES A 1 IN. PIPE WHICH WILL BE
 UNDERSIZED.
  
 C) SUBMIT UPDATED SPECS FOR THE 22KW GENERATOR. I HAVE
 CHECKED THE UPDATED SPECS FOR THE GENERAC 22KW MODEL
 AND THEY INDICATE A FULL LOAD OF 306,000 BTUH FOR
 NATURAL GAS. PLEASE CORRECT THE LOAD SHOWN ON THE
 RISER.
  
 D) THE GENERAC SPECS SHOW A NATURAL GAS INPUT PRESSURE
 OF 3.5- 7 IN. W.C. PLEASE SHOW THE LOCATION OF THE
 REQUIRED REGULATOR AT THE GENERATOR TO REDUCE PRESSURE.
 INDICATE THE MAKE AND MODEL OF THE SELECTED REGULATOR
 ON THE RISER. SUBMIT MARKED UP OR HIGHLIGHTED REGULATOR
 SPECS SHOWING THE MODEL, INLET AND OUTLET PRESSURES,
 SPRING SELECTION, AND ORIFICE SIZE- SECTION G2421.1 &
 G2421.2. SHOW THE REQUIRED PIPE UNIONS AT THE
 REGULATOR. AS NOTED IN COMMENT 1 THE SUBMITTED REG.
 SPECS ARE FOR LP GAS.
  
 E) INDICATE HOW THE PE PIPING RISER WILL MAKE
 CONNECTION AT THE GENERATOR PER SECTIONS G2415.17.1 &
 G2415.17.2. PLEASE NOTE THAT SPECS FOR ANODELESS
 RISERS, PE/METALLIC PIPE CONNECTORS, OR FLEX CONNECTORS
 SHALL BE LISTED AND LABELED. SUBMIT SPECS OR PLACE A
 NOTE THEY WILL BE ONSITE FOR INSPECTION.
  
 F) INDICATE A DRIP LEG WILL BE INSTALLED AND PROVIDE A
 SYMBOL TO SHOW THE LOCATION- SECTION G2419.2 FBC RES.
  
 3) PLEASE NOTE THE GENERATOR (UNDER SEPARATE PERMIT)
 SHALL BE INSTALLED A MINIMUM OF 5' AWAY FROM
 COMBUSTIBLE WALLS- SEC. 4.1.4 NFPA 37, AND A MINIMUM OF
 10' FROM MECHANICAL OR GRAVITY AIR INTAKES (WINDOW AND
 DOOR OPENINGS) INTO THE BUILDING- SEC. R303.5.1 FBC
 RES.
  
 4) THERE IS A 0 VALUE FOR THE PROPOSED GAS PIPING
 INSTALLATION. PLEASE SUBMIT A COPY OF A SIGNED CONTRACT
 AND/OR COPIES OF INVOICES AND ESTIMATES SHOWING THE
 TOTAL COST OF THE INSTALLATION INCLUDING VALUE OF
 LABOR, MATERIALS, EQUIPMENT, SITE WORK, DESIGN FEES,
 AND OVERHEAD AND PROFIT- SECTION 109.3 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2020-11-02 Time   Rev Time 0.00
Received By ccarvaja Date 2020-10-30 Time 00:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-10-05 Time   Rev Time 0.00
Received By lmarchan Date 2020-10-02 Time 11:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-09-24 Time   Rev Time 0.00
Received By lmarchan Date 2020-09-21 Time 15:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status N Date 2020-11-02 Cont ID  
Sent By ccole Date 2020-11-02 Time 08:35 Rev Time 0.00
Received By ccole Date 2020-11-02 Time 07:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-10-05 Cont ID  
Sent By ccole Date 2020-10-05 Time 08:28 Rev Time 0.00
Received By ccole Date 2020-10-05 Time 07:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-09-24 Cont ID  
Sent By ccole Date 2020-09-24 Time 13:39 Rev Time 0.00
Received By ccole Date 2020-09-24 Time 11:35 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-11-02 Cont ID  
Sent By ccole Date 2020-11-02 Time 08:35 Rev Time 0.00
Received By ccole Date 2020-11-02 Time 07:16 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-10-05 Cont ID  
Sent By ccole Date 2020-10-05 Time 08:29 Rev Time 0.00
Received By ccole Date 2020-10-05 Time 07:11 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-09-24 Cont ID  
Sent By ccole Date 2020-09-24 Time 13:42 Rev Time 0.00
Received By ccole Date 2020-09-24 Time 11:35 Sent To  
Notes
***NONE***