| 2020-09-28 17:59:09 | 1ST REVIEW FBC-2017 RES. |
| | PERMIT- 20090828 |
| | 9/28/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) GAS RISER DRAWING: RECORDS RESEARCH FOR 7521 MONTE |
| | VERDE LN SHOW GAS PERMIT #0030680 ISSUED 3/15/2000 FOR |
| | GAS PIPE INSTALLATIONS TO INTERIOR APPLIANCES AND |
| | EXTERIOR POOL HEATER AND BBQ GRILL. THE APPROVED RISER |
| | DRAWING INDICATES A TOTAL LOAD OF 612,000 BTU'S: POOL |
| | HEATER- 405,000. GRILL- 50,000. RANGE- 60,000. DRYER- |
| | 22,000. WATER HEATER- 75,000. REVISE THE RISER TO SHOW |
| | THE COMPLETE PIPING SYSTEM INCLUDING PIPE RUNS TO ALL |
| | NEW AND EXISTING APPLIANCES AND EQUIPMENT, AND SHOW THE |
| | CORRECT TOTAL AND INDIVIDUAL LOADS OF THE SYSTEM- |
| | SECTIONS G2412.3, G2412.4, & G2413.2 FBC RES. PLEASE |
| | NOTE THE RISER DRAWING INDICATES THE MAIN SUPPLY IS |
| | 1-1/4 IN. GALVANIZED. |
| | |
| | A) PLEASE IDENTIFY THE TYPE OF EACH SECTION OF PIPE AND |
| | PROVIDE THE SIZING TABLES USED ON THE DRAWING- SECTION |
| | G2413.4 AND TABLES G2413.4(1)- G2413.4(8) FBC RES. |
| | |
| | B) SUBMIT UPDATED SPECS FOR THE 22KW GENERATOR. I HAVE |
| | CHECKED THE UPDATED SPECS FOR THE GENERAC 22KW MODEL |
| | AND THEY INDICATE A FULL LOAD OF 306,000 BTUH FOR |
| | NATURAL GAS. PLEASE CORRECT THE LOAD ON THE RISER- |
| | SECTION 107.2.1 WPB. |
| | |
| | C) PLEASE CLARIFY THE LOCATION AND MAKE AND MODEL OF |
| | THE REGULATOR AT THE GENERATOR- IT IS HARD TO SEE ON |
| | THE RISER. PLEASE INDICATE THAT PIPE UNIONS WILL BE |
| | INSTALLED WITHIN 1 FT. OF EITHER SIDES OF THE |
| | REGULATOR. SUBMIT MARKED OR HIGHLIGHTED REGULATOR SPECS |
| | SHOWING THE SELECTED MODEL IS RATED FOR OUTDOOR USE, |
| | AND SHOW THE INLET AND OUTLET PRESSURES AND ORIFICE |
| | SIZE- SECTION G2421.1 & 2421.2 (1-7). |
| | |
| | 2) PLEASE NOTE THE GENERATOR (UNDER SEPARATE PERMIT |
| | #20070263) SHALL BE INSTALLED A MINIMUM OF 5' AWAY FROM |
| | COMBUSTIBLE WALLS- SEC. 4.1.4 NFPA 37, AND A MINIMUM OF |
| | 10' FROM MECHANICAL OR GRAVITY AIR INTAKES (WINDOW AND |
| | DOOR OPENINGS) INTO THE BUILDING- SEC. R303.5.1 FBC |
| | RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | |