Plan Review Details - Permit 20090828
Plan Review Stops For Permit 20090828
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2020-10-07 Cont ID  
Sent By ccole Date 2020-10-07 Time 10:37 Rev Time 0.00
Received By ccole Date 2020-10-07 Time 10:37 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2020-10-05 Cont ID  
Sent By ccole Date 2020-10-05 Time 09:36 Rev Time 0.00
Received By ccole Date 2020-10-05 Time 09:36 Sent To  
Notes
2020-10-05 09:37:381ST REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20090828
 9/28/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REVISED GAS RISER:
  
 A) PROVIDE THE PIPE SIZING TABLE FOR THE 1 IN. PE
 PIPING. IF YOU ARE USING THE LOW PRESSURE TABLES IN THE
 FBC FG, BOTH LOW PRESSURE TABLES- 402.4(20) OR
 402.4(21) INDICATE THE 1.25, 1, AND ? IN. PE PIPES ARE
 UNDERSIZED.
  
 B) TABLE 402.4(4) FOR THE GALVANIZED PIPE HAS A HIGH
 PRESSURE DROP OF 6.0 IN. W.C. WHICH IS A HIGH DROP FOR
 A RESIDENTIAL SYSTEM WHICH TYPICALLY HAS APPLIANCES
 WITH LOW PRESSURE INPUTS AROUND 5- 7 IN.W.C. PLEASE
 REFER TO SECTION 402.5 FBC FG, OR SECTION G2413.5 FBC
 RES. FUEL GAS.
  
 C) IT APPEARS THE ADDITIONAL LOAD OF THE GENERATOR MAY
 REQUIRE EITHER THE PE EXISTING PIPES TO BE INCREASED IN
 SIZE, OR THE METER MAY REQUIRE AN UPGRADE TO A 2 PSI
 SYSTEM.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-09-28 Cont ID  
Sent By ccole Date 2020-09-28 Time 17:58 Rev Time 0.00
Received By ccole Date 2020-09-28 Time 16:44 Sent To  
Notes
2020-09-28 17:59:091ST REVIEW FBC-2017 RES.
 PERMIT- 20090828
 9/28/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) GAS RISER DRAWING: RECORDS RESEARCH FOR 7521 MONTE
 VERDE LN SHOW GAS PERMIT #0030680 ISSUED 3/15/2000 FOR
 GAS PIPE INSTALLATIONS TO INTERIOR APPLIANCES AND
 EXTERIOR POOL HEATER AND BBQ GRILL. THE APPROVED RISER
 DRAWING INDICATES A TOTAL LOAD OF 612,000 BTU'S: POOL
 HEATER- 405,000. GRILL- 50,000. RANGE- 60,000. DRYER-
 22,000. WATER HEATER- 75,000. REVISE THE RISER TO SHOW
 THE COMPLETE PIPING SYSTEM INCLUDING PIPE RUNS TO ALL
 NEW AND EXISTING APPLIANCES AND EQUIPMENT, AND SHOW THE
 CORRECT TOTAL AND INDIVIDUAL LOADS OF THE SYSTEM-
 SECTIONS G2412.3, G2412.4, & G2413.2 FBC RES. PLEASE
 NOTE THE RISER DRAWING INDICATES THE MAIN SUPPLY IS
 1-1/4 IN. GALVANIZED.
  
 A) PLEASE IDENTIFY THE TYPE OF EACH SECTION OF PIPE AND
 PROVIDE THE SIZING TABLES USED ON THE DRAWING- SECTION
 G2413.4 AND TABLES G2413.4(1)- G2413.4(8) FBC RES.
  
 B) SUBMIT UPDATED SPECS FOR THE 22KW GENERATOR. I HAVE
 CHECKED THE UPDATED SPECS FOR THE GENERAC 22KW MODEL
 AND THEY INDICATE A FULL LOAD OF 306,000 BTUH FOR
 NATURAL GAS. PLEASE CORRECT THE LOAD ON THE RISER-
 SECTION 107.2.1 WPB.
  
 C) PLEASE CLARIFY THE LOCATION AND MAKE AND MODEL OF
 THE REGULATOR AT THE GENERATOR- IT IS HARD TO SEE ON
 THE RISER. PLEASE INDICATE THAT PIPE UNIONS WILL BE
 INSTALLED WITHIN 1 FT. OF EITHER SIDES OF THE
 REGULATOR. SUBMIT MARKED OR HIGHLIGHTED REGULATOR SPECS
 SHOWING THE SELECTED MODEL IS RATED FOR OUTDOOR USE,
 AND SHOW THE INLET AND OUTLET PRESSURES AND ORIFICE
 SIZE- SECTION G2421.1 & 2421.2 (1-7).
  
 2) PLEASE NOTE THE GENERATOR (UNDER SEPARATE PERMIT
 #20070263) SHALL BE INSTALLED A MINIMUM OF 5' AWAY FROM
 COMBUSTIBLE WALLS- SEC. 4.1.4 NFPA 37, AND A MINIMUM OF
 10' FROM MECHANICAL OR GRAVITY AIR INTAKES (WINDOW AND
 DOOR OPENINGS) INTO THE BUILDING- SEC. R303.5.1 FBC
 RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-10-05 Cont ID  
Sent By ccole Date 2020-10-05 Time 09:37 Rev Time 0.00
Received By ccole Date 2020-10-05 Time 09:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-09-28 Cont ID  
Sent By ccole Date 2020-09-28 Time 17:59 Rev Time 0.00
Received By ccole Date 2020-09-24 Time 07:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-10-05 Cont ID  
Sent By ccole Date 2020-10-05 Time 09:37 Rev Time 0.00
Received By ccole Date 2020-10-05 Time 09:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-09-28 Cont ID  
Sent By ccole Date 2020-09-28 Time 17:59 Rev Time 0.00
Received By ccole Date 2020-09-28 Time 16:44 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-10-07 Cont ID  
Sent By ccole Date 2020-10-07 Time 10:37 Rev Time 0.00
Received By ccole Date 2020-10-07 Time 10:37 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-10-05 Cont ID  
Sent By ccole Date 2020-10-05 Time 09:38 Rev Time 0.00
Received By ccole Date 2020-10-05 Time 09:36 Sent To  
Notes
2020-10-05 09:39:16THE CONTRACTOR OR QUALIFIER WHO PREPARED THE DRAWING
 SHALL PROVIDE HIS/HER SIGNATURE ON IT- SECTION 107.2.1
 WPB, AND FLORIDA STATUTES 471.003(2)(H) & 471.025.
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-09-28 Cont ID  
Sent By ccole Date 2020-09-28 Time 17:59 Rev Time 0.00
Received By ccole Date 2020-09-28 Time 16:45 Sent To  
Notes
2020-09-28 18:00:37THE CONTRACTOR OR QUALIFIER WHO PREPARED THE DRAWING
 SHALL PROVIDE HIS/HER SIGNATURE ON IT- SECTION 107.2.1
 WPB, AND FLORIDA STATUTES 471.003(2)(H) & 471.025.
  
  