| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | |
| | 1) VALUE |
| | CITY OF WPB CHPT. 1 VALUE |
| | 109.3 BUILDING PERMIT VALUATIONS. |
| | |
| | 1A. THE STATED VALUE APPEARS LOW FOR THE PROPOSED SCOPE |
| | OF WORK. |
| | 1B. THE PERMIT VALUATION AND PERMIT FEE MUST BE |
| | COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED |
| | CONTRACTOR WOULD PROVIDE. THIS INCLUDES ALL LABOR, |
| | MATERIALS AND RENTALS OF EQUIPMENT TO PERFORM THE SCOPE |
| | OF WORK. |
| | 1C. YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY |
| | THE OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT |
| | RENTAL TO VERIFY VALUE. |
| | |
| | FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE |
| | BUILDING OFFICIAL |
| | |
| | 2) PROVIDE COMPLETE SET OF GENERATOR SPECIFICATIONS FOR |
| | THE PROPOSED GENERAC 21KW GENERATOR. |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | |
| | 3) THE PROPOSED PRE-CAST GEN PAD REQUIRES STRUCTURAL |
| | DESIGN DETAILS PREPARED BY A DESIGN PROFESSIONAL. |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | |
| | 4) PROVIDE WIND DESIGN WIND LOADS FOR THE GENERATOR PER |
| | FBC 107.3.5.3 AND R301.2 |
| | R301.2.1 WIND DESIGN CRITERIA. |
| | BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN |
| | ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING |
| | THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED |
| | FROM FIGURE R301.2(4). |
| | |
| | 5) PROVIDE SITE SPECIFIC DESIGN WIND LOADS. |
| | R301.2.1 WIND DESIGN CRITERIA. |
| | BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN |
| | ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING |
| | THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED |
| | FROM FIGURE R301.2(4). |
| | |
| | A THOROUGH REVIEW CANNOT BE COMPLETED AT THIS TIEM. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | |
| | |
| | |