Plan Review Details - Permit 20090719
Plan Review Stops For Permit 20090719
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2020-11-02 Cont ID  
Sent By cpuell Date 2020-11-02 Time 10:52 Rev Time 0.00
Received By cpuell Date 2020-11-02 Time 10:52 Sent To  
Notes
***NONE***

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2020-10-29 Cont ID  
Sent By cpuell Date 2020-10-29 Time 19:30 Rev Time 0.00
Received By cpuell Date 2020-10-29 Time 19:29 Sent To  
Notes
2020-10-29 19:30:28@ ADDRESS SHOULD BE CREATED FOR THIS JOB, APPLICANT
 REACHED OUT TO ME.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-11-18 Cont ID  
Sent By rmcphers Date 2020-11-18 Time 09:20 Rev Time 0.00
Received By rmcphers Date 2020-11-18 Time 09:18 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-10-30 Cont ID  
Sent By rmcphers Date 2020-10-30 Time 11:19 Rev Time 0.00
Received By rmcphers Date 2020-10-30 Time 11:14 Sent To  
Notes
2020-10-30 11:19:04ANTENNA - POLE
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) WIND DESIGN CALCULATIONS FOR THE FOUNDATION PG.02 OF
 08 SHOWS WIND SPEED AS 135MPH - DESIGN WIND SPEED
 SHOULD BE 150MPH PER FBC WPB AMENDMENTS 120.1.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-01-07 Cont ID  
Sent By jleahy Date 2021-01-07 Time 17:32 Rev Time 0.00
Received By jleahy Date 2021-01-07 Time 17:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-11-17 Cont ID  
Sent By equinone Date 2020-11-17 Time 09:25 Rev Time 0.00
Received By equinone Date 2020-11-17 Time 08:38 Sent To  
Notes
2020-11-17 09:26:44CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED. PLEASE SEE COMMENTS BELOW:
  
 1) ELECTRICAL RISER DIAGRAM: FEEDER TO RAYCAP PANEL. IS
 IT 2#3 PLUS 1#10 GROUND? PLEASE CORRECT.
 2) PANEL SCHEDULES: POWER PANEL BREAKER SHOWS A 30 AMPS
 BREAKER FOR FEEDER TO RAYCAP PANEL BUT RAYCAP PANEL HAS
 A 60 A MAIN BREAKER. ALSO, FEEDER TO RAYCAP PANEL SEEMS
 TO BE #10 IN RISER DIAGRAM. PLEASE CLARIFY AND CORRECT
 FOR CONSISTENCY.
 3) POLE ELEVATION TYPICAL: PLEASE FILL IN CONDUCTOR
 SIZE WHERE IT STATES ?INSTALL (3) ## THWN WIRE.
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 SINCERELY,
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-11-02 Cont ID  
Sent By jleahy Date 2020-11-02 Time 13:17 Rev Time 0.00
Received By jleahy Date 2020-11-02 Time 13:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-01-07 Cont ID  
Sent By jleahy Date 2021-01-07 Time 17:33 Rev Time 0.00
Received By jleahy Date 2020-12-23 Time 08:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-11-18 Cont ID  
Sent By rmcphers Date 2020-11-18 Time 09:20 Rev Time 0.00
Received By rmcphers Date 2020-11-04 Time 16:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-11-02 Cont ID  
Sent By jleahy Date 2020-11-02 Time 13:17 Rev Time 0.00
Received By jleahy Date 2020-10-19 Time 11:37 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-01-07 Cont ID  
Sent By jleahy Date 2021-01-07 Time 17:33 Rev Time 0.00
Received By jleahy Date 2021-01-07 Time 17:33 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-11-18 Cont ID  
Sent By rmcphers Date 2020-11-18 Time 09:20 Rev Time 0.00
Received By rmcphers Date 2020-11-18 Time 09:20 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-10-30 Cont ID  
Sent By rmcphers Date 2020-10-30 Time 11:19 Rev Time 0.00
Received By rmcphers Date 2020-10-30 Time 11:19 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2020-11-16 Cont ID  
Sent By eschneid Date 2020-11-16 Time 15:56 Rev Time 0.25
Received By eschneid Date 2020-11-16 Time 14:57 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2020-10-28 Cont ID  
Sent By eschneid Date 2020-10-28 Time 14:40 Rev Time 0.25
Received By eschneid Date 2020-10-28 Time 14:40 Sent To  
Notes
2020-10-28 14:43:06FAILED
  
 1) PROVIDE ALL ELECTRICAL PLANS SHOWING THE CONCEALED
 POLE DESIGN. EX. THE RISER DIAGRAM SHOWS THE EXTERIOR
 MOUNT CONCRETE POLE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]