Plan Review Details - Permit 20090715
Plan Review Stops For Permit 20090715
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-10-22 Cont ID  
Sent By rmcphers Date 2020-10-22 Time 15:01 Rev Time 0.00
Received By rmcphers Date 2020-10-22 Time 15:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-10-08 Cont ID  
Sent By rmcphers Date 2020-10-08 Time 08:59 Rev Time 0.00
Received By rmcphers Date 2020-10-07 Time 14:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-10-06 Cont ID  
Sent By jleahy Date 2020-10-06 Time 16:24 Rev Time 0.00
Received By jleahy Date 2020-10-06 Time 16:06 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2020-10-01 Cont ID  
Sent By lcrespo Date 2020-10-01 Time 18:53 Rev Time 0.00
Received By lcrespo Date 2020-10-01 Time 18:53 Sent To  
Notes
2020-10-01 18:54:06GAS PLAN REVIEW, A GAS PLAN HAS NOT BEEN INCLUDED IN
 THIS SUBMITTAL PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN
 PERFORMED AT THIS TIME. A SEPARATE GAS PERMIT AND PLANS
 WILL BE REQUIRED FOR A CONTRACTOR TO PERFORM THE
 RELATED WORK. PROVIDE COMPLETE PLANS AND GAS RISER THAT
 REFLECTS THE ENTIRE SCOPE OF GAS WORK TO BE DONE PER
 THE WPB AMENDMENTS TO FBC SEC. 107.2.1.
  
 A SUB GAS PERMIT IS REQUIRED BY A LICENSED CONTRACTOR
 FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS TO THE FBC
 SEC. 105.1.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-10-22 Cont ID  
Sent By rmcphers Date 2020-10-22 Time 15:15 Rev Time 0.00
Received By rmcphers Date 2020-10-21 Time 11:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-10-08 Cont ID  
Sent By rmcphers Date 2020-10-08 Time 09:04 Rev Time 0.00
Received By rmcphers Date 2020-09-29 Time 07:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2020-10-01 Cont ID  
Sent By lcrespo Date 2020-10-01 Time 18:53 Rev Time 0.00
Received By lcrespo Date 2020-10-01 Time 17:02 Sent To  
Notes
2020-10-01 18:54:3510/01/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER/INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status N Date 2020-10-26 Cont ID  
Sent By rmcphers Date 2020-10-26 Time 11:18 Rev Time 0.00
Received By rmcphers Date 2020-10-26 Time 11:18 Sent To  
Notes
2020-10-26 11:20:02ROOFING = DEFERRED PERMIT

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2020-10-22 Cont ID  
Sent By rmcphers Date 2020-10-22 Time 15:02 Rev Time 0.00
Received By rmcphers Date 2020-10-22 Time 15:02 Sent To  
Notes
2020-10-22 15:15:09ROOFING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 2ND REVIEW
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) ROOFING PRODUCT APPROVAL (FL16732-R17) IS APPROVED
 FOR (HVHZ) ZONES ONLY - "HIGH VELOCITY HURRICANE ZONE"
 WHICH THE BUILDING CODE REFERS TO DADE AND BROWARD
 COUNTY ONLY. NOT APPROVED FOR WEST PALM BEACH.
 2) ROOFING PRODUCT APPROVAL (FL10626-R18) IS A ROOFING
 UNDERLAYMENT ONLY - WHICH IS USED FOR UNDER SHINGLES,
 TILE OR METAL ROOFING.
 3) ROOFING PRODUCT APPROVAL (NOA 18-1219.01) IS FOR USE
 ON A "CEMENTITIOUS WOOD FIBER" ROOF DECK - YOUR PLANS
 SHOW A " PLYWOOD" ROOF DECK.
 4) PLEASE PROVIDE A COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVAL FOR THE FLAT DECK ROOFING = PLEASE
 CIRCLE THE ROOFING SYSTEM NUMBER TO BE USED IN THE
 PRODUCT APPROVAL - IF NEEDED PLEASE PROVIDE SIGNED AND
 SEALED ADDITIONAL ATTACHMENT DETAILS FROM AN ARCHITECT
 OR ENGINEER FOR THE ROOF ZONES 2 AND 3 WHICH MAY
 REQUIRE A HIGHER WIND PRESSURE - SEE NOTES ON THE
 PRODUCT APPROVAL.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2020-10-08 Cont ID  
Sent By rmcphers Date 2020-10-08 Time 08:59 Rev Time 0.00
Received By rmcphers Date 2020-10-08 Time 08:59 Sent To  
Notes
2020-10-08 09:04:20ROOFING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE A COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVAL FOR THE FLAT DECK ROOFING = PLEASE
 CIRCLE THE ROOFING SYSTEM TO BE USED IN THE PRODUCT
 APPROVAL - IF NEEDED PLEASE PROVIDE SIGNED AND SEALED
 ADDITIONAL ATTACHMENT DETAILS FROM AN ARCHITECT OR
 ENGINEER FOR THE ROOF ZONES 2 AND 3 WHICH MAY REQUIRE A
 HIGHER WIND PRESSURE - SEE NOTES ON THE PRODUCT
 APPROVAL.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-10-08 Cont ID  
Sent By rmcphers Date 2020-10-08 Time 09:04 Rev Time 0.00
Received By rmcphers Date 2020-10-08 Time 09:04 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2020-10-07 Cont ID  
Sent By rthermid Date 2020-10-07 Time   Rev Time  
Received By rthermid Date 2020-10-07 Time   Sent To I
Notes
***NONE***