Plan Review Details - Permit 20090711
Plan Review Stops For Permit 20090711
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2020-12-08 Cont ID  
Sent By jwitmer Date 2020-12-08 Time 07:35 Rev Time 0.00
Received By jwitmer Date 2020-12-08 Time 07:31 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2020-12-06 Cont ID  
Sent By jwitmer Date 2020-12-06 Time 15:25 Rev Time 0.00
Received By jwitmer Date 2020-12-06 Time 15:12 Sent To  
Notes
2020-12-06 15:18:56COMMERCIAL ASBESTOS
  
 TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-11-03 Cont ID  
Sent By jwitmer Date 2020-10-27 Time 14:41 Rev Time 0.00
Received By jleahy Date 2020-10-27 Time 14:00 Sent To  
Notes
2020-10-27 14:38:56COMMERCIAL ASBESTOS
  
 TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-01-07 Cont ID  
Sent By jwitmer Date 2021-01-07 Time 08:14 Rev Time 0.00
Received By jwitmer Date 2021-01-07 Time 07:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-12-07 Cont ID  
Sent By jwitmer Date 2020-12-06 Time 15:30 Rev Time 0.00
Received By jwitmer Date 2020-12-06 Time 15:12 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-10-27 Cont ID  
Sent By jwitmer Date 2020-10-27 Time 14:43 Rev Time 0.00
Received By jwitmer Date 2020-10-27 Time 14:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-12-16 Cont ID  
Sent By jleahy Date 2020-12-16 Time 12:02 Rev Time 0.00
Received By jleahy Date 2020-12-16 Time 12:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-10-29 Cont ID  
Sent By jleahy Date 2020-10-29 Time 17:20 Rev Time 0.00
Received By jleahy Date 2020-10-29 Time 17:17 Sent To  
Notes
2020-10-29 17:42:41ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 1) IDENTIFICATION. WHERE A BUILDING OR STRUCTURE IS
 SUPPLIED BY MORE THAN ONE SERVICE, OR ANY COMBINATION
 OF BRANCH CI RCUITS, FEEDERS, AND SERVICES, A PERMANENT
 PLAQUE OR DIRECTORY SHALL BE INSTALLED AT EACH SERVICE
 DISCONNECT LOCATION DENOTING ALL OTHER SERVICES,
 FEEDERS, AND BRANCH CIRCUITS SUPPLYING THAT BUILDING OR
 STRUCTURE AND THE AREA SERVED BY EACH.
  
 2) 250.58 COMMON GROUNDING ELECTRODE WHERE AN AC SYSTEM
 IS CONNECTED TO A GROUNDING ELECTRODE IN OR AT A
 BUILDING OR STRUCTURE, THE SAME ELECTRODE SHALL BE USED
 TO GROUND CONDUCTOR ENCLOSURES AND EQUIPMENT IN OR ON
 THAT BUILDING OR STRUCTURE. WHERE SEPARATE SERVICES,
 FEEDERS, OR BRANCH CIR CUITS SUPPLY A BUILDING AND ARE
 REQUIRED TO BE CONNECTED TO A GROUNDING ELECTRODE(S),
 THE SAME GROUNDING ELECTRODE(S) SHALL BE USED. TWO OR
 MORE GROUNDING ELECTRODES THAT ARE BONDED TOGETHER
 SHALL BE CONSIDERED AS A SINGLE GROUNDING ELECTRODE
 SYSTEM IN THIS SENSE.
  
 3) CIRCUIT A-24 TO BE GFCI PROTECTED WITHIN 6" OF A
 SINK.
  
 4) CIRCUIT A-4 NOT SHOWN ON PLAN NEEDS TO BE GFCI
 PROTECTED 422.52

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2020-12-16 Cont ID  
Sent By jleahy Date 2020-12-16 Time 12:03 Rev Time 0.00
Received By jleahy Date 2020-12-16 Time 12:02 Sent To  
Notes
2020-12-16 12:03:32PHONE/DATA ONLY JLEAHY

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-10-08 Cont ID  
Sent By pleduc Date 2020-10-08 Time   Rev Time 0.00
Received By pleduc Date 2020-09-29 Time 13:30 Sent To  
Notes
2020-10-08 09:35:50FIRE PROVISO:
  
 ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM SYSTEM
 BY APPLICABLE LICENSED CONTRACTORS FOR CODE COVERAGE
 COMPLIANCE.
  
 ANY AND ALL WORK ON THE FIRE ALARM SYSTEM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS AND SHOP
 DRAWINGS.
  
 THE EXISTING FIRE ALARM SHALL BE MAINTAINED AND REMAIN
 ACTIVE THROUGHOUT THE CONSTRUCTION PERIOD, INCLUDING
 DEMO.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-01-14 Cont ID  
Sent By medwards Date 2021-01-14 Time 09:30 Rev Time 0.00
Received By medwards Date 2021-01-04 Time 14:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status P Date 2020-12-22 Cont ID  
Sent By lcrespo Date 2020-12-22 Time 07:58 Rev Time 0.00
Received By lcrespo Date 2020-12-01 Time 10:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-10-29 Cont ID  
Sent By jleahy Date 2020-10-29 Time 17:42 Rev Time 0.00
Received By jleahy Date 2020-09-28 Time 11:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2021-01-14 Cont ID  
Sent By medwards Date 2021-01-14 Time 09:29 Rev Time 0.00
Received By medwards Date 2021-01-14 Time 09:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2020-12-17 Cont ID  
Sent By medwards Date 2020-12-17 Time 09:13 Rev Time 0.00
Received By medwards Date 2020-12-17 Time 09:12 Sent To  
Notes
2020-12-17 09:13:101ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20090711
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-200 IDENTIFIES THE NEW AHU AS AHU-1, PLEASE
 LABEL THE NEW AHU AND CU ON SHEET M-100 AND ON THE
 MECHANICAL SIZING DOCUMENT TO MATCH SHEET M-200. FBC
 107.2.1
  
 2) THE MECHANICAL SIZING CALCULATIONS MUST BE DESIGNED
 TO WEST PALM BEACH LOCATION, NOT MIAMI. FBC EC C403.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-10-16 Cont ID  
Sent By medwards Date 2020-10-16 Time 15:55 Rev Time 0.00
Received By medwards Date 2020-10-16 Time 15:12 Sent To  
Notes
2020-10-16 15:55:341ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20090711
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
  
 1) UNDER THE AIR CONDITIONING SPLIT SYSTEM SCHEDULE IT
 APPEARS THAT BOTH CU-A AND AHU-A ARE NEW, PLEASE SHOW
 THE CALCULATIONS OF HEATING AND COOLING LOADS FOR THIS
 NEW SYSTEM. FBC EC C403.2.1
  
 2) THE OUTSIDE AIR CALCULATIONS DOES NOT SHOW AHU-A,
 PLEASE EXPLAIN. FBC M 403.3.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-12-22 Cont ID  
Sent By lcrespo Date 2020-12-22 Time 07:58 Rev Time 0.00
Received By lcrespo Date 2020-12-22 Time 07:05 Sent To  
Notes
2020-12-22 07:59:3512/22/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-10-14 Cont ID  
Sent By tklarge Date 2020-10-14 Time 10:59 Rev Time 0.00
Received By tklarge Date 2020-10-14 Time 06:16 Sent To  
Notes
2020-10-14 10:57:211) SHT. P200 - THE HOSE BIBB ON THE EXTERIOR REQUIRES
 AN INDIVIDUAL SHUTOFF VVALVE PER FBC-PLUMBING SEC.
 606.2.
 2) SHT. P200 - THE ICE MAKER ON THE REFRIGERATORR SHALL
 BE EQUIPPED WITH AND AIR ARRESTOR ANND A BACKFLOW
 DEVICE PER 604.9 & 608..3.
 3) SUBMIT MANUFACTURER'S SPECIFICATIOONS FOR THE SUMP &
 PUMP FOR THE BREAK ROOM SINK. WPB AMEND. TO FBC SEC.
 107.2.1.
 4) SUBMIT MANUFACTURER'S SPECS FOR THE SEP CABINET. A
 BACKFLOW PREVENTION DEVICE MAY BE REQUIRED FOR THE
 WATER CONNECTION.FBC-PLUMBING SEC. 608..3.
 5) SUBMIT MANUFACTURER'S SPECIICATIONS/ INSTALLATION
 DOCUMENTS FOR THE SIEMANS CHILLED WATER EQUIPMENT.WPB
 AMEND. TO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-01-07 Cont ID  
Sent By jwitmer Date 2021-01-07 Time 08:14 Rev Time 0.00
Received By jwitmer Date 2021-01-07 Time 07:59 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-12-17 Cont ID  
Sent By medwards Date 2020-12-17 Time 09:35 Rev Time 0.00
Received By medwards Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-10-20 Cont ID  
Sent By equinone Date 2020-10-20 Time 14:56 Rev Time 0.00
Received By equinone Date 2020-10-20 Time 14:56 Sent To  
Notes
***NONE***