Plan Review Details - Permit 20090600
Plan Review Stops For Permit 20090600
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2020-10-09 Cont ID  
Sent By ccole Date 2020-10-09 Time 11:48 Rev Time 0.00
Received By ccole Date 2020-10-09 Time 07:06 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2020-10-01 Cont ID  
Sent By ccole Date 2020-10-01 Time 11:07 Rev Time 0.00
Received By ccole Date 2020-10-01 Time 07:54 Sent To  
Notes
2020-10-01 11:07:272ND REVIEW FBC-2017 FUEL GAS
 PERMIT- 20090600
 10/1/2020
  
 CODES IN EFFECT:
  
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 COMMENTS FROM THE 1ST REVIEW LISTED BELOW HAVE NOT BEEN
 COMPLETED ADDRESSED. NOTES HAVE BEEN ADDED TO THESE
 REMAINING COMMENTS.
  
 2) SHEET 1: PROVIDE A REVISED SURVEY DRAWING MARKED UP
 TO SHOW THE REQUIRED 10 FT. UG LP TANK CLEARANCE
 DISTANCES TO THE BUILDINGS AND ADJACENT PROPERTY LINES-
 TABLE 6.3.1.1 NFPA 58. PLEASE NOTE THAT IF THE TANK IS
 LOCATED WITHIN 10 FT. OF A PUBLIC VEHICULAR
 THOROUGHFARE OR PARKING LOCATION, THE SHELL FOR THE
 TANK SHALL BE 18 IN. BELOW GRADE OR VEHICULAR BARRIER
 PROTECTION WILL BE REQUIRED- SECTIONS 6.6.1.1 & 6.6.6.1
 (A). THE SUBMITTED SITE PLAN SHALL ALSO BE REVISED TO
 SHOW COMPLIANCE. FOR CLARITY PLEASE NOTE OR SHOW THE
 DISTANCE OF THE LP TANK TO THE POOL PAVILION AND TO ANY
 PERMANENT CONSTRUCTION ONSITE SUCH AS SHADE STRUCTURES.
  
 3) SHEET 1: THE UG LP TANK ANCHORING DETAIL WITH
 HYDROSTATIC LIFT CALCULATION SHALL BE SIGNED AND SEALED
 BY THE FL. LICENSED ENGINEER WHO PREPARED THE
 CALCULATIONS AND DRAWING- SECTION 6.6.1.6 NFPA 58, AND
 FLORIDA STATUTE 471.003. PLEASE NOTE THAT THERE IS
 MISSING INFORMATION IN THE DETAIL INCLUDING THE TYPE,
 SIZE AND NUMBER OF CABLES OR STRAPS; PROTECTION FOR THE
 TANKS FROM THE STRAPS OR TIES; THE TYPE, SIZE, AND
 NUMBER OF ANCHORS; AND THE DEPTH OF ANCHOR EMBEDMENT.
 MANUFACTURER'S SPECS FOR THE PRE-FAB SLAB SHALL ALSO BE
 SUBMITTED. PROTECTIVE SLEEVES FOR THE CABLES NOT SHOWN.
  
 5) SHEET 1: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR
 THE BBQ GRILLS AND THE FIRETABLES- SECTION 305.1 FBC
 FG. THE SPECS SHALL BE MARKED OR HIGHLIGHTED TO SHOW
 THE APPLIANCE'S LISTING, BTUH LOADS, AND REQUIRED GAS
 INPUT PRESSURES. THE REQUESTED SPECS WERE NOT
 SUBMITTED. SUBMIT CUT SHEETS SHOWING LISTINGS, BTUH
 LOADS, INPUT PRESSURES, AND INSTALLATION GUIDELINES.
 THE EQUIPMENT SHALL BE INSTALLED PER MANUFACTURER'S
 SPECIFICATIONS WITH REQUIRED CLEARANCES TO
 COMBUSTIBLES, OVERHEAD CONSTRUCTION, AND WITH PROPER
 VENTING. PLEASE SUBMIT ONLY THE RELATIVE DOCUMENTS FROM
 THE INSTALLATION MANUAL AND NOT THE ENTIRE MANUAL.
  
 6) SHEET 1 & 2: NO ARCHITECTURAL PLANS HAVE BEEN
 SUBMITTED FOR THE PROJECT UNDER THIS PERMIT.
 ARCHITECTURAL PLANS SHALL BE SUBMITTED THAT IDENTIFY
 THE STRUCTURE AND INDICATE IF IT IS OPEN OR ENCLOSED,
 THE TYPE OF CONSTRUCTION- NON-COMBUSTIBLE OR
 COMBUSTIBLE, AND IF THE APPLIANCES ARE BEING INSTALLED
 UNDER A ROOF OR OVERHEAD CONSTRUCTION. COMPLETE
 DIMENSIONED DETAILS FOR CONSTRUCTION OF THE BARS,
 COUNTERS, OR TABLES THE APPLIANCES WILL BE INSTALLED IN
 SHALL BE PROVIDED INCLUDING FRONT AND SIDE ELEVATION
 VIEWS- SECTION 107.2.1 WPB. PLEASE NOTE THAT A COMPLETE
 REVIEW OF THE APPLIANCE INSTALLATIONS AND REQUIRED
 VENTING SYSTEMS CANNOT BE ACCOMPLISHED AT THIS TIME,
 AND THAT A COMPLETE REVIEW MAY INCLUDE ACCESSIBILITY
 COMPLIANCES IIN ACCORDANCE WITH THE FLORIDA
 ACCESSIBILITY CODE-2017. SHEET A-5.4 SHOWS A VERTICAL
 PROPANE TANK. CLARIFY IF THIS TANK IS EXISTING OR TO BE
 INCLUDED IN THIS GAS PERMIT. WHAT APPLIANCES OR
 EQUIPMENT IS BEING SUPPLIED BY THE TANK- NO
 INFORMATION, NOTES OR DETAILS HAVE BEEN PROVIDED.
 LOCATION OF NOTE #14 NOT SHOWN ON THE DRAWINGS.
  
 7) SHEET 2, GAS ISOMETRIC DRAWING. SHEET 1 & 2: THE
 REVISED GAS RISER IS SHOWING HIGHER INDIVIDUAL BTUH
 LOADS FOR THE BBQ GRILLS AND FIRETABLES THAN THE LOADS
 SHOWN IN THE NOTES ON EACH SHEET: GRILLS- 120,000 BTUH
 EA., FIRETABLES- 100,000 EA. PLEASE CORRECT THE LOADS
 IN THE NOTES TO MATCH THE RISER.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-09-16 Cont ID  
Sent By ccole Date 2020-09-16 Time 15:58 Rev Time 0.00
Received By ccole Date 2020-09-16 Time 12:22 Sent To  
Notes
2020-09-16 15:59:121ST REVIEW FBC-2017 FUEL GAS
 PERMIT- 20090600
 9/16/2020
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 I HAVE RESEARCHED THE LICENSURE OF AMAURY GONZALEZ,
 WHOSE NAME AND SIGNATURE APPEARS AS THE QUALIFIER AND
 DESIGNER OF RECORD FOR THE PROJECT PLANS, AND I WAS NOT
 ABLE TO VERIFY THAT THE LICENSE #14826 LISTED ON THE
 PLAN IS VALID FOR USE IN PALM BEACH COUNTY AND
 QUALIFIES HIM TO DESIGN THE PLANS FOR THE PROJECT. MR.
 GONZALEZ'S LICENSE IN PALM BEACH COUNTY- #17356 EXPIRED
 ON 10/31/2018. I COULD NOT FIND LICENSE #14826 ON THE
 PB CONTRACTOR LICENSE CERTIFICATION WEBSITE. THE
 LICENSING PORTAL AT THE DBPR IDENTIFIES MR. GONZALEZ AS
 A CONSTRUCTION FINANCIAL OFFICER. PLEASE NOTE THE
 PERMIT APPLICATION DOES NOT PROVIDE THE REQUIRED
 LICENSED CONTRACTOR INFORMATION WHICH IS "TO BE
 DETERMINED" AT A LATER DATE PRIOR TO PERMIT ISSUANCE.
 THE PLANS HAVE FAILED FIRST REVIEW AT THIS TIME FOR THE
 DEFICIENCIES LISTED BELOW. REVISED PLANS SHALL EITHER
 BEAR THE INSTALLING CONTRACTOR'S FL. OR PB COUNTY
 LICENSE, TITLE BLOCK AND SIGNATURE; OR SHALL BEAR THE
 ELECTRONIC SIGNATURE AND SEAL OF A FL. LICENSED
 ENGINEER- FL. STATUTES 471.003, 471.025 AND FLORIDA
 ADMINISTRATIVE CODE SECTION 61G15-23.005.
  
 1) SHEET 1: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR
 THE 250-GALLON UG LP TANK AND TRAFFIC DOME SHOWING THE
 TANK AND DOME HAVE BEEN DESIGNED, FABRICATED, TESTED
 AND MARKED (STAMPED) IN ACCORDANCE WITH THE REGULATIONS
 AS REQUIRED BY THE REGULATORY AGENCIES AND COMPLIANCE
 STANDARDS LISTED IN SECTION 5.2.1.1 NFPA 58.
  
 2) SHEET 1: PROVIDE A REVISED SURVEY DRAWING MARKED UP
 TO SHOW THE REQUIRED 10 FT. UG LP TANK CLEARANCE
 DISTANCES TO THE BUILDINGS AND ADJACENT PROPERTY LINES-
 TABLE 6.3.1.1 NFPA 58. PLEASE NOTE THAT IF THE TANK IS
 LOCATED WITHIN 10 FT. OF A PUBLIC VEHICULAR
 THOROUGHFARE OR PARKING LOCATION, THE SHELL FOR THE
 TANK SHALL BE 18 IN. BELOW GRADE OR VEHICULAR BARRIER
 PROTECTION WILL BE REQUIRED- SECTIONS 6.6.1.1 & 6.6.6.1
 (A). THE SUBMITTED SITE PLAN SHALL ALSO BE REVISED TO
 SHOW COMPLIANCE.
  
 3) SHEET 1: THE UG LP TANK ANCHORING DETAIL WITH
 HYDROSTATIC LIFT CALCULATION SHALL BE SIGNED AND SEALED
 BY THE FL. LICENSED ENGINEER WHO PREPARED THE
 CALCULATIONS AND DRAWING- SECTION 6.6.1.6 NFPA 58, AND
 FLORIDA STATUTE 471.003. PLEASE NOTE THAT THERE IS
 MISSING INFORMATION IN THE DETAIL INCLUDING THE TYPE,
 SIZE AND NUMBER OF CABLES OR STRAPS; PROTECTION FOR THE
 TANKS FROM THE STRAPS OR TIES; THE TYPE, SIZE, AND
 NUMBER OF ANCHOR; AND THE DEPTH OF ANCHOR EMBEDMENT.
 MANUFATURER'S SPECS FOR THE PRE-FAB SLAB SHALL ALSO BE
 SUBMITTED
  
 4) SHEET 1: THE UG LP TANK SHALL BE PROTECTED AGAINST
 CORROSION BY INSTALLATION OF A CATHODIC PROTECTION
 SYSTEM CONSISTING OF A SACRIFICIAL ANODE OR AN
 IMPRESSED CURRENT ANODE PER SECTIONS 5.2.1.11 &
 6.6.6.1(I) NFPA 58. INDICATE THE TYPE OF PROTECTION,
 SUBMIT MANUFACTURER'S SPECIFICATIONS, AND INDICATE HOW
 IT WILL BE TESTED- SECTION 6.17.1.
  
 5) SHEET 1: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR
 THE BBQ GRILLS AND THE FIRETABLES- SECTION 305.1 FBC
 FG. THE SPECS SHALL BE MARKED OR HIGHLIGHTED TO SHOW
 THE APPLIANCE'S LISTING, BTUH LOADS, AND REQUIRED GAS
 INPUT PRESSURES.
  
 6) SHEET 1 & 2: NO ARCHITECTURAL PLANS HAVE BEEN
 SUBMITTED FOR THE PROJECT UNDER THIS PERMIT.
 ARCHITECTURAL PLANS SHALL BE SUBMITTED THAT IDENTIFY
 THE STRUCTURE AND INDICATE IF IT IS OPEN OR ENCLOSED,
 THE TYPE OF CONSTRUCTION- NON-COMBUSTIBLE OR
 COMBUSTIBLE, AND IF THE APPLIANCES ARE BEING INSTALLED
 UNDER A ROOF OR OVERHEAD CONSTRUCTION. COMPLETE
 DIMENSIONED DETAILS FOR CONSTRUCTION OF THE BARS,
 COUNTERS, OR TABLES THE APPLIANCES WILL BE INSTALLED IN
 SHALL BE PROVIDED INCLUDING FRONT AND SIDE ELEVATION
 VIEWS- SECTION 107.2.1 WPB. PLEASE NOTE THAT A COMPLETE
 REVIEW OF THE APPLIANCE INSTALLATIONS AND REQUIRED
 VENTING SYSTEMS CANNOT BE ACCOMPLISHED AT THIS TIME,
 AND THAT A COMPLETE REVIEW MAY INCLUDE ACCESSIBILITY
 COMPLIANCES IIN ACCORDANCE WITH THE FLORIDA
 ACCESSIBILITY CODE-2017.
  
 7) SHEET 2, GAS ISOMETRIC DRAWING:
 A) THE REGULATOR AT THE TANK IS A 1ST STAGE REGULATOR-
 REMOVE THE NOTE INDICATING 2ND STAGE REGULATOR WHICH
 ARE LOCATED AT THE APPLIANCES- SECTIONS 410.1 AND 410.2
 FBC FG.
 B) INDICATE THE MAKES AND MODEL NUMBERS OF THE
 REGULATORS AND SHOW THE OUTLET PRESSURE (IN. WC.) AT
 EACH APPLIANCE. SUBMIT MANUFACTURER'S SPECS FOR THE
 REGULATORS MARKED UP TO SHOW THE SELECTED MODELS, INLET
 AND OUTLET PIPE SIZES AND PRESSURES, AND ORIFICE SIZES-
 SECTION 410.1 & 410.2 FBC FG.
 C) INDICATE THE BURIAL DEPTH OF THE PE PIPING PER
 SECTION 404.12 AND SHOW A TRACER WIRE WILL BE INSTALLED
 ADJACENT TO THE PIPE- SECTION 404.17.3 FBC FG. PLEASE
 NOTE THAT THE PE MAY BE INSTALLED WITHOUT CONDUIT UNDER
 A PATIO OR DRIVEWAY BUT MUST BE ENCASED IN A CONDUIT IF
 INSTALLED UNDER A BUILDING- SEE SECTION 404.14.
 D) SHOW HOW THE PE PIPING RISER WILL CONNECT TO THE
 SCHEDULE 40 METALLIC PIPE PER SECTION 404.17.2 FBC FG.
 PLEASE NOTE THAT SPECS FOR ANODELESS RISERS AND
 PE/METALLIC PIPE CONNECTORS SHALL BE ASTM D2513
 CATEGORY 1 OR ASTM F1973 LISTED AND LABELED.
 E) PLEASE CLEARLY SHOW THE LOCATIONS OF THE REGULATORS
 AND SHUTOFF VALVES AT THE TANK AND THE APPLIANCES- THEY
 ARE BARELY VISIBLE ON THE DRAWING- SECTIONS 409.1 &
 410.1 & 410.2 FBC FG. SHOW THE LOCATIONS OF THE
 REQUIRED PIPE UNIONS WITHIN 1 FT. EACH SIDE OF THE
 REGULATORS- SECTION 410.2(7).
  
 8) THE $10,000 APPEARS LOW FOR THE SCOPE OF THE
 PROJECT. PLEASE PROVIDE A COPY OF A CONTRACT AND/OR
 ESTIMATES AND INVOICES TO VERIFY THE TOTAL COST OF THE
 PROJECT INCLUDING LABOR, MATERIALS, EQUIPMENT,
 APPLIANCES, SITE WORK, ARCHITECTURAL AND STRUCTURAL
 WORK, DESIGN FEES, AND OVERHEAD AND PROFIT- SECTION
 109.3 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2020-10-09 Time   Rev Time 0.00
Received By lmarchan Date 2020-10-08 Time 07:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-10-01 Time   Rev Time 0.00
Received By lmarchan Date 2020-09-30 Time 07:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-09-16 Time   Rev Time 0.00
Received By lmarchan Date 2020-09-15 Time 13:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status N Date 2020-10-09 Cont ID  
Sent By ccole Date 2020-10-09 Time 11:37 Rev Time 0.00
Received By ccole Date 2020-10-09 Time 07:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-10-01 Cont ID  
Sent By ccole Date 2020-10-01 Time 11:10 Rev Time 0.00
Received By ccole Date 2020-10-01 Time 07:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-09-16 Cont ID  
Sent By ccole Date 2020-09-16 Time 16:13 Rev Time 0.00
Received By ccole Date 2020-09-16 Time 16:12 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-10-09 Cont ID  
Sent By ccole Date 2020-10-09 Time 11:42 Rev Time 0.00
Received By ccole Date 2020-10-09 Time 07:06 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-10-01 Cont ID  
Sent By ccole Date 2020-10-01 Time 11:10 Rev Time 0.00
Received By ccole Date 2020-10-01 Time 11:10 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-09-16 Cont ID  
Sent By ccole Date 2020-09-16 Time 16:13 Rev Time 0.00
Received By ccole Date 2020-09-16 Time 12:23 Sent To  
Notes
2020-09-16 16:14:05I HAVE RESEARCHED THE LICENSURE OF AMAURY GONZALEZ,
 WHOSE NAME AND SIGNATURE APPEARS AS THE QUALIFIER AND
 DESIGNER OF RECORD FOR THE PROJECT PLANS, AND I WAS NOT
 ABLE TO VERIFY THAT THE LICENSE #14826 LISTED ON THE
 PLAN IS VALID FOR USE IN PALM BEACH COUNTY AND
 QUALIFIES HIM TO DESIGN THE PLANS FOR THE PROJECT. MR.
 GONZALEZ'S LICENSE IN PALM BEACH COUNTY- #17356 EXPIRED
 ON 10/31/2018. I COULD NOT FIND LICENSE #14826 ON THE
 PB CONTRACTOR LICENSE CERTIFICATION WEBSITE. THE
 LICENSING PORTAL AT THE DBPR IDENTIFIES MR. GONZALEZ AS
 A CONSTRUCTION FINANCIAL OFFICER. PLEASE NOTE THE
 PERMIT APPLICATION DOES NOT PROVIDE THE REQUIRED
 LICENSED CONTRACTOR INFORMATION WHICH IS "TO BE
 DETERMINED" AT A LATER DATE PRIOR TO PERMIT ISSUANCE.
 THE PLANS HAVE FAILED FIRST REVIEW AT THIS TIME FOR THE
 DEFICIENCIES LISTED BELOW. REVISED PLANS SHALL EITHER
 BEAR THE INSTALLING CONTRACTOR'S FL. OR PB COUNTY
 LICENSE, TITLE BLOCK AND SIGNATURE; OR SHALL BEAR THE
 ELECTRONIC SIGNATURE AND SEAL OF A FL. LICENSED
 ENGINEER- FL. STATUTES 471.003, 471.025 AND FLORIDA
 ADMINISTRATIVE CODE SECTION 61G15-23.005.