Plan Review Details - Permit 20090598
Plan Review Stops For Permit 20090598
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2021-01-06 Cont ID  
Sent By jgomez Date 2021-01-06 Time 15:26 Rev Time 0.00
Received By jgomez Date 2021-01-06 Time 15:10 Sent To  
Notes
2021-01-07 15:27:14PARKING SPACES WITH CAR CHARGES APPROVED FOR LUCID
 MOTORS USE ONLY. NOT FOR PUBLIC USE. SEE COPY OF ZONING
 COMMENTS BELOW.
  
 12/23/20- PASSED
 1) THE LUCID INVENTORY PARKING/CHARGING IS NOT APPROVED
 FOR THE PUBLIC (LUCID CAR OWNERS) ACCESS/CHARGING; AND
 CUSTOMERS ARE NOT PERMITTED TO BE BROUGHT TO THIS AREA
 BY SALESMEN TO REVIEW CARS THAT ARE NOT IN THE
 SHOWROOM, BEING ATEST DRIVE, ETC.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2020-12-22 Cont ID  
Sent By jgomez Date 2020-12-22 Time 15:41 Rev Time 0.00
Received By jgomez Date 2020-12-22 Time 15:38 Sent To  
Notes
2020-12-22 16:17:28BUILDING REVIEW COMMENTS:
  
 1-DISCUSSED THE REVISED PLANS WITH ROBERT BROWN
 (BUILDING OFFICIAL). HE SAID, REVISED PLANS WILL BE OK
 WITH LETTER FROM LUCID MOTORS CLARIFYING OVERALL
 OPERATIONS. WHO WILL THE ONLY PEOPLE TO HAVE ACCESS TO
 THESE PARKING SPACES AND WHAT WOULD BE THEIR SPECIFIC
 FUNCTION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-12-08 Cont ID  
Sent By jgomez Date 2020-12-08 Time 15:09 Rev Time 0.00
Received By jgomez Date 2020-12-08 Time 11:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-10-28 Cont ID  
Sent By jgomez Date 2020-10-28 Time 10:19 Rev Time 0.00
Received By jgomez Date 2020-10-27 Time 13:23 Sent To  
Notes
2020-10-27 13:38:52SECOND BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE.
  
 ORIGINAL COMMENT:
 1- PROPOSED PARKING SPACES WITH CAR CHARGES DON'T
 PROVIDE ANY INFORMATION SHOWING COMPLIANCE WITH THE FBC
 ACCESSIBILITY CODE. IS THERE ANY PARKING SPACE WITH A
 CAR CHARGER ASSIGNED FOR HANDICAPPED PEOPLE?. IS THERE
 ANY SPACE VAN ACCESSIBLE?.
 SEC. 504 FBC-EXISTING BUILDING. SEC. 806 FBC-EXISTING
 BUILDING. SEC. 202.3 FBC-ACCESSIBILITY AND SEC. 103
 FBC-ACCESSIBILITY.
  
 RESPONSE:
 ARCHITECT'S RESPONSE LETTER AND FLOOR PLANS WERE
 PRESENTED TO ROBERT BROWN (BUILDING OFFICIAL) FOR
 APPROVAL. IT WAS NOT APPROVED. THE LETTER AND THE PLANS
 SUBMITTED DON'T PROVIDE THE INFORMATION REQUESTED BY
 ROBERT BROWN WHEN I FIRST SHOW HIM THE PROPOSED
 ALTERATION FOR BUILDING OFFICIAL INTERPRETATION. I
 DISCUSSED ROBERT BROWN'S INTERPRETATION WITH VALENTINA
 LEONI FROM MARMOL RADZINER AIA OVER THE PHONE. I
 INFORMED HER THAT ROBERT BROWN WOULD APPROVE THE
 PROPOSED "STORAGE ONLY" PARKING SPACES WITHOUT HAVING A
 DEDICATED ADA SPACE IF THE PLANS AND A LETTER FROM
 LUCID MOTORS CLEARLY SHOW HOW THE SPACES WERE
 CONTROLLED TO AVOID USE BY THE GENERAL PUBLIC OR LUCID
 MOTORS CLIENTS IF THEY ARE IN THE AREA AND ARE IN NEED
 OF CHARGING THEIR CARS. INFORMATION SUBMITTED DOESN'T
 SHOW CONTROL OF THESE SPACES.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-10-06 Cont ID  
Sent By jgomez Date 2020-10-06 Time 13:39 Rev Time 0.00
Received By jgomez Date 2020-10-05 Time 13:00 Sent To  
Notes
2020-10-06 13:39:43BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE.
  
 1- PROPOSED PARKING SPACES WITH CAR CHARGES DON'T
 PROVIDE ANY INFORMATION SHOWING COMPLIANCE WITH THE FBC
 ACCESSIBILITY CODE. IS THERE ANY PARKING SPACE WITH A
 CAR CHARGER ASSIGNED FOR HANDICAPPED PEOPLE?. IS THERE
 ANY SPACE VAN ACCESSIBLE?.
 SEC. 504 FBC-EXISTING BUILDING. SEC. 806 FBC-EXISTING
 BUILDING. SEC. 202.3 FBC-ACCESSIBILITY AND SEC. 103
 FBC-ACCESSIBILITY.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2021-01-05 Cont ID  
Sent By jleahy Date 2021-01-05 Time 11:28 Rev Time 0.00
Received By jleahy Date 2021-01-05 Time 10:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2020-12-21 Cont ID  
Sent By jleahy Date 2020-12-21 Time 09:33 Rev Time 0.00
Received By jleahy Date 2020-12-21 Time 09:32 Sent To  
Notes
2020-12-21 09:39:20ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 VALUE OF WORK IS NOT $15,000 PLEASE SUBMIT A REASONABLE
 VALUE OF THE WORK.
  
 PERMIT STILL STATES IT IS FOR RESTRIPING OF PARKING
 GARAGE.
  
 ELECTRICAL PERMIT REQUIRED FOR ELECTRICAL WORK.
  
 PLEASE SHOW WHERE POWER IS COMING FROM ON THE RISER
 DIAGRAM, SHOW DISCONNECT AT POINT OF FEEDER ENTERING
 THE GARAGE FACITILTY. SHOW OTHER BUILDING, FEEDER,
 DISCONNECT, TRANSFORMER, AND THE PANEL........ SHOW
 THESE ON A PLAN FOR LAYOUT OF JOB.
  
 PLEASE SUBMIT A PANEL SCHEDULE FOR PANEL CS
  
 PLEASE SUBMIT SIGNAGE COPY OF SIGNS FOR SERVICE AND
 FEEDERS IN SAME BUILDING FROM DIFFERENT SOURCES. FOR
 FIRE DEPT. SHOWING LOCATION OF MAINS

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2020-12-03 Cont ID  
Sent By jleahy Date 2020-12-03 Time 15:15 Rev Time 0.00
Received By jleahy Date 2020-12-01 Time 16:11 Sent To  
Notes
2020-12-03 15:27:48ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 1) A DISCONNECT SHALL BE INSTALLED AT THE POINT OF
 ENTRANCE TO THE BUILDING FOR THE FEEDER FROM THE OTHER
 BUILDING.
  
 2) PLEASE SUPPLY A RISER DIAGRAM SHOWING MAIN TO
 TRANSFORMER, LOCATION OF PANEL CS, LOCATION OF
 TRANSFORMER TX-CS PLEASE SHOW BREAKERS SIZE AND SIZE OF
 WIRES. SIGNS SHALL BE PLACED AT BOTH THE FEEDER
 DISCONNECT'S ENTRANCE INTO THE GARAGE AND ANOTHER SIGN
 LOCATED AT THE MAIN SERVICE FOR THE GARAGE INDICATING
 THAT ANOTHER MEANS OF DISCONNECT IS LOCATED ON THE
 PREMISES AND WHERE IT IS LOCATED. POWER DISCONNECT HAVE
 TO READILLY AVAILABLE IN ORDER TO DISCONNECT THE ENTIRE
 ELECTRICAL SYSTEM TO THE GARAGE.
  
 3) VALUE OF JOB IS TO INCLUDE THE CHARGERS PLUS ALL
 MATERIALS AND LABOR FOR A COMPLETE JOB. (25000)
  
 4) AIC RATING FOR THE SERVICE TO THIS PROJECT 110.9,
 110.10
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER
 561-805-6713
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-10-27 Cont ID  
Sent By jleahy Date 2020-10-27 Time 15:00 Rev Time 0.00
Received By jleahy Date 2020-10-27 Time 15:00 Sent To  
Notes
2020-10-27 15:13:29ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PLANS FOR THIS JOB ARE VERY HARD TO UNDERSTAND. YOUR
 PLANS ARE NOT CLEAR AND HARD TO READ. I JUST NOW
 REALIZED THAT YOU ARE BRINGING ANOTHER FEEDER FROM
 ANOTHER SERVICE INTO THE GARAGE. PLEASE INDICATE NEC
 COMPLIANCE.
  
 1) SERVICE FOR CHARGERS WILL NEED TO BE GROUPED WITH
 THE MAINS FOR THE GARAGE. 230.2, 225.30
  
 2) PLEASE SUPPLY A RISER DIAGRAM SHOWING MAIN TO
 TRANSFORMER, LOCATION OF PANEL CS, LOCATION OF
 TRANSFORMER TX-CS
  
 3) VALUE OF JOB IS TO INCLUDE THE CHARGERS PLUS ALL
 MATERIALS AND LABOR FOR A COMPLETE JOB. (25000)
  
 4) AIC RATING FOR THE SERVICE TO THIS PROJECT 110.9,
 110.10
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER
 561-805-6713
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-09-25 Cont ID  
Sent By jleahy Date 2020-09-25 Time 16:51 Rev Time 0.00
Received By jleahy Date 2020-09-25 Time 16:14 Sent To  
Notes
2020-09-25 18:06:11ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) LOAD CALCULATION HOW DID THE 100A CHARGERS GET A VA
 RATING OF 24,960VA FOR THE LOAD CALULATIONS? ARTICLE
 220
 HOW DID CHARGES 6 GET TO A LOAD OF 99840VA? 16,640
 EACH? PLEASE EXPLAIN.
  
 2) VALUE OF WORK SHOWN IS LOW FOR THIS INSTALLATION,
 PLEASE INCLUDE ALL MATERIALS AND LABOR FOR THE VALUE.
  
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 3) DISTANCE FROM THE SERVICE TO THE PANEL FOR THE
 CHARGERS IS WHAT DISTANCE? 215.2 IT #1
  
 4) SUBMIT CHARGER CUT SHEETS. 110.3
  
 5) SHOW SERVIE RISER FOR CHARGING STATIONS PANEL,
 BRANCH, GROUNDING. 215.5
  
 4) VD CA;CULATION WAS BASED ON 320 AMPERES HOW DID YOU
 GET TO 320A ??

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-10-23 Cont ID  
Sent By pleduc Date 2020-10-23 Time   Rev Time 0.00
Received By pleduc Date 2020-10-23 Time 10:44 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-09-24 Cont ID  
Sent By pleduc Date 2020-09-24 Time   Rev Time 0.00
Received By pleduc Date 2020-09-24 Time 10:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2021-01-06 Cont ID  
Sent By jgomez Date 2021-01-06 Time 15:26 Rev Time 0.00
Received By jgomez Date 2020-12-29 Time 15:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-12-23 Cont ID  
Sent By ajones Date 2020-12-23 Time 09:15 Rev Time 0.00
Received By ajones Date 2020-12-16 Time 16:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-12-15 Cont ID  
Sent By lmarchan Date 2020-12-15 Time 14:03 Rev Time 0.00
Received By lmarchan Date 2020-11-25 Time 06:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-10-29 Cont ID  
Sent By cpuell Date 2020-10-29 Time 18:26 Rev Time 0.00
Received By cpuell Date 2020-10-22 Time 07:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-10-06 Cont ID  
Sent By jgomez Date 2020-10-06 Time 13:45 Rev Time 0.00
Received By jgomez Date 2020-09-23 Time 07:28 Sent To I
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2020-12-21 Cont ID  
Sent By jleahy Date 2020-12-21 Time 09:41 Rev Time 0.00
Received By jleahy Date 2020-12-21 Time 09:41 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-12-08 Cont ID  
Sent By jgomez Date 2020-12-08 Time 15:10 Rev Time 0.00
Received By jgomez Date 2020-12-08 Time 15:10 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-10-23 Cont ID  
Sent By equinone Date 2020-10-23 Time 09:21 Rev Time 0.00
Received By equinone Date 2020-10-23 Time 09:21 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-10-06 Cont ID  
Sent By jgomez Date 2020-10-06 Time 13:44 Rev Time 0.00
Received By jgomez Date 2020-10-06 Time 13:42 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2020-12-23 Cont ID  
Sent By ajones Date 2020-12-23 Time 09:09 Rev Time 0.00
Received By ajones Date 2020-12-23 Time 09:09 Sent To  
Notes
2020-12-23 09:15:5112/23/20- PASSED
 1) THE LUCID INVENTORY PARKING/CHARGING IS NOT APPROVED
 FOR THE PUBLIC (LUCID CAR OWNERS) ACCESS/CHARGING; AND
 CUSTOMERS ARE NOT PERMITTED TO BE BROUGHT TO THIS AREA
 BY SALESMEN TO REVIEW CARS THAT ARE NOT IN THE
 SHOWROOM, BEING ATEST DRIVE, ETC.

Review Stop Z ZONING
Rev No 3 Status F Date 2020-12-15 Cont ID  
Sent By eschneid Date 2020-12-15 Time 10:11 Rev Time 0.50
Received By eschneid Date 2020-12-08 Time 10:17 Sent To  
Notes
2020-12-15 10:34:37FAILED
  
 1) THE LUCID INVENTORY PARKING/CHARGING IS NOT APPROVED
 FOR PUBLIC (LUCID CAR OWNERS) ACCESS/CHARGING;
 THEREFORE, ZONING WILL NOT APPROVE THE REVISION.
 ADDITONALLY, CUSTOMERS ARE NOT PERMITTED TO BE BROUGHT
 TO THIS AREA BY SALESMEN TO REVIEW CARS THAT ARE NOT IN
 THE SHOWROOM, BEGIN A TEST DRIVE, ETC.
  
 2) THE INSTALLATION OF THE WIDER SPACE AND THE ACCESS
 AISLE FOR AN ADA SPACE ENCROACHES INTO, AND MAKES THE
 ADJACENT NON LUCID SPACE A NON-CODE COMPLIANT SIZE,
 WHICH REMOVES THIS SPACE FROM THE OVERALL PARKING
 AVAILABILITY.
  
 3) THE CONVERSION OF TWO NORMAL PARKING SPACES TO AN
 ADA SPACE AND THE ACCESS AISLE ON THE WEST SIDE OF THE
 DRIVE AISLE RESULTS IN THE REMOVAL OF A PARKING SPACE.
  
 4) EVEN THOUGH COMMENT #1 DOES NOT PERMIT THE USE OF
 THESE SPACES BY THE PUBLIC OR ACCESS BY CUSTOMERS (THUS
 NOT REQUIRING ADA) CITY RETAIL HAS NOT AUTHORIZED THE
 REMOVAL ON ADDITIONAL PARKING SPACES NOR HAS STAFF
 REVIEWED HOW THIS WOULD AFFECT THE OVERALL PARKING
 INVENTORY FOR ROSEMARY SQUARE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2020-10-29 Cont ID  
Sent By eschneid Date 2020-10-29 Time 16:55 Rev Time 0.25
Received By eschneid Date 2020-10-29 Time 16:44 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2020-10-06 Cont ID  
Sent By eschneid Date 2020-10-06 Time 09:56 Rev Time 0.75
Received By eschneid Date 2020-10-06 Time 09:56 Sent To  
Notes
2020-10-06 10:48:32FAILED
  
 PROVIDE WRITTEN RESPONSES TO COMMENTS.
  
 1) PLEASE VERIFY WHAT THE SPECIFIC PROPOSED USE OF
 THESE SPACES IS.
  
 2) THE WHEEL STOPS, LOCATED THREE FEET FROM THE FRONT
 OF THE SPACE, DOES NOT CONFORM TO CITY REQUIREMENTS FOR
 SPACES WHERE CARS ARE LOCATED. THE REMAINING 15 FEET IS
 NOT AN ADEQUATE DEPTH TO ENSURE THAT THE BACK OF THE
 CARS EXTEND OUT OF THE SPACE AND BLOCK THE DRIVE AISLE.
 THE CITY REQUIREMENT IS THAT WHEEL STOPS BE TWO FEET
 FROM THE END OF THE PARKING SPACE.
  
 3) THE SPACE WITH THE BOLLARD AND PIPE NEEDS TO BE
 DESIGNATED AND USED ONLY FOR COMPACT LUCID CARS (SPACE
 16 FEET IN DEPTH) OR IT MAY NOT BE USED AS A FULL SIZED
 VEHICLE IN THIS SPACE WOULD ENCROACH INTO THE REQUIRED
 DRIVE AISLE.
  
 4) THE CITY REQUIRES THE DIVIDER LINES TO BE WHITE. THE
 PROPOSED LIQUORICE COLOR IS NOT PERMITTED.
  
 5) THE HANGING SIGNAGE REQUIRES PERMITS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
 [email protected]
  
  
  
  