Plan Review Details - Permit 20090505
Plan Review Stops For Permit 20090505
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2021-03-16 Cont ID  
Sent By cpuell Date 2021-03-16 Time 08:57 Rev Time 0.00
Received By cpuell Date 2021-03-16 Time 08:57 Sent To  
Notes
2021-03-16 08:57:53SUITE 112

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2021-03-15 Cont ID  
Sent By cpuell Date 2021-03-15 Time 16:13 Rev Time 0.00
Received By cpuell Date 2021-03-15 Time 16:13 Sent To  
Notes
2021-03-15 16:14:44PLEASE EMAIL [email protected], NEED TO ESTABLISH SUITE
 NUMBER.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2020-09-11 Cont ID  
Sent By cpuell Date 2020-09-11 Time 15:44 Rev Time 0.00
Received By cpuell Date 2020-09-11 Time 15:44 Sent To  
Notes
2020-09-11 15:44:47PLEASE EMAIL [email protected] TO DISCUSS SUITE NUMBER

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-03-30 Cont ID  
Sent By rmcphers Date 2021-03-30 Time 07:45 Rev Time 0.00
Received By rmcphers Date 2021-03-30 Time 07:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-10-21 Cont ID  
Sent By rmcphers Date 2020-10-21 Time 08:14 Rev Time 0.00
Received By rmcphers Date 2020-10-21 Time 08:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-10-02 Cont ID  
Sent By rmcphers Date 2020-10-02 Time 09:43 Rev Time 0.00
Received By rmcphers Date 2020-10-02 Time 09:43 Sent To  
Notes
2020-10-02 09:46:42SIGN
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) DRAWINGS NEED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER THAT CALCULATED THE WIND DESIGN.
 2) DRAWINGS NEED TO SHOW THE ATTACHMENT TYPE, SIZE AND
 ON CENTER SPACING TO THE EXISTING BUILDING STRUCTURE.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-10-22 Cont ID  
Sent By equinone Date 2020-10-22 Time 10:01 Rev Time 0.00
Received By equinone Date 2020-10-22 Time 09:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-10-01 Cont ID  
Sent By jleahy Date 2020-10-01 Time 14:13 Rev Time 0.00
Received By jleahy Date 2020-10-01 Time 14:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-03-30 Cont ID  
Sent By lmarchan Date 2021-03-30 Time 17:03 Rev Time 0.00
Received By lmarchan Date 2021-03-12 Time 14:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-10-29 Cont ID  
Sent By jleahy Date 2020-10-29 Time 07:55 Rev Time 0.00
Received By jleahy Date 2020-10-09 Time 15:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-10-09 Cont ID  
Sent By lmarchan Date 2020-10-09 Time 06:56 Rev Time 0.00
Received By lmarchan Date 2020-09-16 Time 10:26 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-03-30 Cont ID  
Sent By rmcphers Date 2021-03-30 Time 07:45 Rev Time 0.00
Received By rmcphers Date 2021-03-30 Time 07:45 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-10-21 Cont ID  
Sent By rmcphers Date 2020-10-21 Time 08:14 Rev Time 0.00
Received By rmcphers Date 2020-10-21 Time 08:14 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-10-02 Cont ID  
Sent By rmcphers Date 2020-10-02 Time 09:46 Rev Time 0.00
Received By rmcphers Date 2020-10-02 Time 09:46 Sent To  
Notes
2020-10-02 09:48:16SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR -
 IF YOUR ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL
 SIGNATURE - PLEASE DROP OFF (CITY HALL DROP BOX) THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS ALONG
 WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE REASON
 FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN REVIEW
 REQUEST FORM CAN BE OBTAINED BY E MAILING [email protected]
 AND ASKING FOR THE FORM.
  

Review Stop Z ZONING
Rev No 3 Status P Date 2021-03-30 Cont ID  
Sent By eschneid Date 2021-03-30 Time 15:39 Rev Time 0.25
Received By eschneid Date 2021-03-30 Time 15:07 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2020-10-28 Cont ID  
Sent By eschneid Date 2020-10-28 Time 11:45 Rev Time 0.50
Received By eschneid Date 2020-10-28 Time 10:43 Sent To  
Notes
2020-10-28 11:45:47FAILED
  
 PROVIDE WRITTEN RESPONSES TO COMMENTS.
  
 PLEASE NOTE THAT THE WAIVER I LETTER FROM CITYPLACE
 RETAIL, LLC, MUST SPECIFICALLY APPROVE THE WAIVERS THAT
 THEY ARE APPROVING. THE LETTER THAT WAS SUBMITTED (FOR
 A SECOND TIME) JUST AUTHORIZED THE CONTRACTOR TO DO THE
 WORK.
  
 BLADE SIGN C (WEST FACADE)
  
 1) REPEAT COMMENT: THE ROSEMARY SQUARE TENANT SIGN
 CRITERIA LIMIT WALL MOUNTED BLADE SIGN PANELS TO HAVE A
 MAXIMUM SIGN FACE OF FOUR (4) SQUARE FEET. THE PROPOSED
 SIGN IS 4.04 SQUARE FEET IN AREA. CITYPLACE RETAIL MAY
 APPROVE IN WRITING A WAIVER I TO INCREASE IN THE SIGN
 SQUARE FOOTAGE BY 25 PERCENT, WHICH WOULD PERMIT THIS
 SIGN AT THE PROPOSED SIZE.
  
 2) REPEAT COMMENT: THE ROSEMARY SQUARE TENANT SIGN
 CRITERIA REQUIRE THAT THE SIGN COPY AREA SHALL MAINTAIN
 A MARGIN AT LEAST THREE (3) INCHES FROM ANY EDGE OF THE
 PERCEIVED SIGN AREA (TOP, SIDES AND BOTTOM). PROVIDE A
 DETAIL OF THE SIGN FACE THAT VERIFIES THIS REQUIREMENT.
  
 3) REPEAT COMMENT: THE ROSEMARY SQUARE TENANT SIGN
 CRITERIA PERMIT THE PUSH THROUGH LETTERS TO HAVE HALO
 ILLUMINATION. PLEASE VERIFY THAT THE PROPOSED LETTERS
 WILL HAVE HALO ILLUMINATION AND NOT BE ILLUMINATED
 LETTERS. IF THE LETTERS ARE TO BE ILLUMINATED (WHICH
 THEY APPEAR TO BE CONTRARY TO THE "HALO ILLUMINATED"
 NOTE ON THE SIGN TYPE TABLE), THEN CITYPLACE RETAIL
 MUST APPROVE IN WRITING A WAIVER I TO PERMIT THE
 ALTERNATE ILLUMINATION STYLE.
  
 4) REPEAT COMMENT: THE ROSEMARY SQUARE TENANT SIGN
 CRITERIA REQUIRES THAT ALL CONDUIT, CROSSOVERS, WIRING
 NECESSARY FOR THE SIGN'S ELECTRICAL CONNECTION TO BE
 CONCEALED AND NOT VISIBLE TO THE PUBLIC. THE PLANS DO
 NOT CLEARLY SHOW THAT THE WIRING IS LOCATED WITHIN THE
 MOUNTING TUBES LEADING TO THE INTERIOR OF THE SIGN
 PANEL. THIS NEEDS TO BE CLARIFIED.
  
 5) REPEAT COMMENT: THE ROSEMARY SQUARE TENANT SIGN
 CRITERIA REQUIRE THAT RIVETS, SCREWS AND OTHER
 FASTENERS THAT EXTEND TO VISIBLE SURFACES SHALL BE
 FLUSH, FILLED AND FINISHED SO AS TO BE UNNOTICEABLE.
 THE BOLT HEADS THAT EXTEND PAST THE MOUNTING PLATE DO
 NOT MEET THIS STANDARD. IF THE BOLT HEADS MUST EXTEND
 PAST THE MOUNTING PLATE, THEY NEED TO BE CONCEALED BY
 CAPS MATCHING THE COLOR OF THE MOUNTING PLATE.
  
 6) REPEAT COMMENT: THE ROSEMARY SQUARE TENANT SIGN
 CRITERIA REQUIRE THAT ALL INSTALLATION COMPONENTS
 CONSIST OF ANODIZED ALUMINUM. PROVIDE ON THE PLANS
 VERIFICATION THAT THE MOUNTING PLATE AND TUBES,
 INCLUDING DECORATIVE FINIAL, ARE ANODIZED ALUMINUM.
  
 7) UPDATED COMMENT: THE ROSEMARY SQUARE TENANT SIGN
 CRITERIA REQUIRE THE STUD MOUNTS TO BE SERIES 316
 STAINLESS STEEL ANCHOR BOLTS. PROVIDE VERIFICATION OF
 THIS REQUIREMENT ON THE PLANS. ----- THE PLANS ADDED
 THAT 1/4 INCH TAPCONS WILL BE USED. TAPCONS SO NOT
 APPEAR TO BE MANUFACTURED WITH 316 STAINLESS STEEL, SO
 THEY MAY NOT BE USED.
  
 8) REPEAT COMMENT: THE ROSEMARY SQUARE TENANT SIGN
 CRITERIA LIMITS THE SIGN COPY TO TRADE NAMES ONLY. THE
 LISTING OF MERCHANDISE OR DESCRIPTIONS OF CATEGORY OR
 THE ELABORATION OF THE COMPANY'S PRODUCTS OR SERVICES
 (THE TO GO SERVICE) IS ONLY PERMITTED AS A WAIVER I. A
 WAIVER I REQUIRES WRITTEN APPROVAL FROM CITYPLACE
 RETAIL.
  
 BLADE SIGN G (NORTH FACADE)
  
 1) REPEAT COMMENT: THE ROSEMARY SQUARE TENANT SIGN
 CRITERIA REQUIRE THAT THE SIGN COPY AREA SHALL MAINTAIN
 A MARGIN AT LEAST THREE (3) INCHES FROM ANY EDGE OF THE
 PERCEIVED SIGN AREA (TOP, SIDES AND BOTTOM). PROVIDE A
 DETAIL OF THE SIGN FACE THAT VERIFIES THIS REQUIREMENT.
  
 2) REPEAT COMMENT: THE ROSEMARY SQUARE TENANT SIGN
 CRITERIA PERMIT THE PUSH THROUGH LETTERS TO HAVE HALO
 ILLUMINATION. PLEASE VERIFY THAT THE PROPOSED LETTERS
 WILL HAVE HALO ILLUMINATION AND NOT BE ILLUMINATED
 LETTERS. IF THE LETTERS ARE TO BE ILLUMINATED, THEN
 CITYPLACE RETAIL MUST APPROVE IN WRITING A WAIVER I TO
 PERMIT THE ALTERNATE ILLUMINATION STYLE.
  
 3) REPEAT COMMENT: THE ROSEMARY SQUARE TENANT SIGN
 CRITERIA REQUIRES THAT ALL CONDUIT, CROSSOVERS, WIRING
 NECESSARY FOR THE SIGN'S ELECTRICAL CONNECTION TO BE
 CONCEALED AND NOT VISIBLE TO THE PUBLIC. THE PLANS DO
 NOT CLEARLY SHOW THAT THE WIRING IS LOCATED WITHIN THE
 MOUNTING TUBES LEADING TO THE INTERIOR OF THE SIGN
 PANEL. THIS NEEDS TO BE CLARIFIED.
  
 4) REPEAT COMMENT: THE ROSEMARY SQUARE TENANT SIGN
 CRITERIA REQUIRE THAT RIVETS, SCREWS AND OTHER
 FASTENERS THAT EXTEND TO VISIBLE SURFACES SHALL BE
 FLUSH, FILLED AND FINISHED SO AS TO BE UNNOTICEABLE.
 THE BOLT HEADS THAT EXTEND PAST THE MOUNTING PLATE DO
 NOT MEET THIS STANDARD. IF THE BOLT HEADS MUST EXTEND
 PAST THE MOUNTING PLATE, THEY NEED TO BE CONCEALED BY
 CAPS MATCHING THE COLOR OF THE MOUNTING PLATE.
  
 5) REPEAT COMMENT: THE ROSEMARY SQUARE TENANT SIGN
 CRITERIA REQUIRE THAT ALL INSTALLATION COMPONENTS
 CONSIST OF ANODIZED ALUMINUM. PROVIDE ON THE PLANS
 VERIFICATION THAT THE MOUNTING PLATE AND TUBES,
 INCLUDING DECORATIVE FINIAL, ARE ANODIZED ALUMINUM.
  
 6) UPDATED COMMENT: THE ROSEMARY SQUARE TENANT SIGN
 CRITERIA REQUIRE THE STUD MOUNTS TO BE SERIES 316
 STAINLESS STEEL ANCHOR BOLTS. PROVIDE VERIFICATION OF
 THIS REQUIREMENT ON THE PLANS. ----- THE PLANS ADDED
 THAT 1/4 INCH TAPCONS WILL BE USED. TAPCONS SO NOT
 APPEAR TO BE MANUFACTURED WITH 316 STAINLESS STEEL, SO
 THEY MAY NOT BE USED.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2020-10-08 Cont ID  
Sent By eschneid Date 2020-10-08 Time 15:34 Rev Time 0.75
Received By eschneid Date 2020-10-08 Time 15:34 Sent To  
Notes
2020-10-08 15:37:56FAILED
  
 PROVIDE WRITTEN RESPONSES TO COMMENTS.
  
 BLADE SIGN C (WEST FACADE)
  
 1) THE ROSEMARY SQUARE TENANT SIGN CRITERIA LIMIT WALL
 MOUNTED BLADE SIGN PANELS TO HAVE A MAXIMUM SIGN FACE
 OF FOUR (4) SQUARE FEET. THE PROPOSED SIGN IS 4.04
 SQUARE FEET IN AREA. CITYPLACE RETAIL MAY APPROVE IN
 WRITING A WAIVER I TO INCREASE IN THE SIGN SQUARE
 FOOTAGE BY 25 PERCENT, WHICH WOULD PERMIT THIS SIGN AT
 THE PROPOSED SIZE.
  
 2) THE ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRE
 THAT THE SIGN COPY AREA SHALL MAINTAIN A MARGIN AT
 LEAST THREE (3) INCHES FROM ANY EDGE OF THE PERCEIVED
 SIGN AREA (TOP, SIDES AND BOTTOM). PROVIDE A DETAIL OF
 THE SIGN FACE THAT VERIFIES THIS REQUIREMENT.
  
 3) THE ROSEMARY SQUARE TENANT SIGN CRITERIA PERMIT THE
 PUSH THROUGH LETTERS TO HAVE HALO ILLUMINATION. PLEASE
 VERIFY THAT THE PROPOSED LETTERS WILL HAVE HALO
 ILLUMINATION AND NOT BE ILLUMINATED LETTERS. IF THE
 LETTERS ARE TO BE ILLUMINATED, THEN CITYPLACE RETAIL
 MUST APPROVE IN WRITING A WAIVER I TO PERMIT THE
 ALTERNATE ILLUMINATION STYLE.
  
 4) THE ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRES
 THAT ALL CONDUIT, CROSSOVERS, WIRING NECESSARY FOR THE
 SIGN'S ELECTRICAL CONNECTION TO BE CONCEALED AND NOT
 VISIBLE TO THE PUBLIC. THE PLANS DO NOT CLEARLY SHOW
 THAT THE WIRING IS LOCATED WITHIN THE MOUNTING TUBES
 LEADING TO THE INTERIOR OF THE SIGN PANEL. THIS NEEDS
 TO BE CLARIFIED.
  
 5) THE ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRE
 THAT RIVETS, SCREWS AND OTHER FASTENERS THAT EXTEND TO
 VISIBLE SURFACES SHALL BE FLUSH, FILLED AND FINISHED SO
 AS TO BE UNNOTICEABLE. THE BOLT HEADS THAT EXTEND PAST
 THE MOUNTING PLATE DO NOT MEET THIS STANDARD. IF THE
 BOLT HEADS MUST EXTEND PAST THE MOUNTING PLATE, THEY
 NEED TO BE CONCEALED BY CAPS MATCHING THE COLOR OF THE
 MOUNTING PLATE.
  
 6) HE ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRE THAT
 ALL INSTALLATION COMPONENTS CONSIST OF ANODIZED
 ALUMINUM. PROVIDE ON THE PLANS VERIFICATION THAT THE
 MOUNTING PLATE AND TUBES, INCLUDING DECORATIVE FINIAL,
 ARE ANODIZED ALUMINUM.
  
 7) THE ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRE THE
 STUD MOUNTS TO BE SERIES 316 STAINLESS STEEL ANCHOR
 BOLTS. PROVIDE VERIFICATION OF THIS REQUIREMENT ON THE
 PLANS.
  
 8) THE ROSEMARY SQUARE TENANT SIGN CRITERIA LIMITS THE
 SIGN COPY TO TRADE NAMES ONLY. THE LISTING OF
 MERCHANDISE OR DESCRIPTIONS OF CATEGORY OR THE
 ELABORATION OF THE COMPANY?S PRODUCTS OR SERVICES (THE
 TO GO SERVICE) IS ONLY PERMITTED AS A WAIVER I. A
 WAIVER I REQUIRES WRITTEN APPROVAL FROM CITYPLACE
 RETAIL.
  
 BLADE SIGN G (NORTH FACADE)
  
 1) THE ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRE
 THAT THE SIGN COPY AREA SHALL MAINTAIN A MARGIN AT
 LEAST THREE (3) INCHES FROM ANY EDGE OF THE PERCEIVED
 SIGN AREA (TOP, SIDES AND BOTTOM). PROVIDE A DETAIL OF
 THE SIGN FACE THAT VERIFIES THIS REQUIREMENT.
  
 2) THE ROSEMARY SQUARE TENANT SIGN CRITERIA PERMIT THE
 PUSH THROUGH LETTERS TO HAVE HALO ILLUMINATION. PLEASE
 VERIFY THAT THE PROPOSED LETTERS WILL HAVE HALO
 ILLUMINATION AND NOT BE ILLUMINATED LETTERS. IF THE
 LETTERS ARE TO BE ILLUMINATED, THEN CITYPLACE RETAIL
 MUST APPROVE IN WRITING A WAIVER I TO PERMIT THE
 ALTERNATE ILLUMINATION STYLE.
  
 3) THE ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRES
 THAT ALL CONDUIT, CROSSOVERS, WIRING NECESSARY FOR THE
 SIGN'S ELECTRICAL CONNECTION TO BE CONCEALED AND NOT
 VISIBLE TO THE PUBLIC. THE PLANS DO NOT CLEARLY SHOW
 THAT THE WIRING IS LOCATED WITHIN THE MOUNTING TUBES
 LEADING TO THE INTERIOR OF THE SIGN PANEL. THIS NEEDS
 TO BE CLARIFIED.
  
 4) THE ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRE
 THAT RIVETS, SCREWS AND OTHER FASTENERS THAT EXTEND TO
 VISIBLE SURFACES SHALL BE FLUSH, FILLED AND FINISHED SO
 AS TO BE UNNOTICEABLE. THE BOLT HEADS THAT EXTEND PAST
 THE MOUNTING PLATE DO NOT MEET THIS STANDARD. IF THE
 BOLT HEADS MUST EXTEND PAST THE MOUNTING PLATE, THEY
 NEED TO BE CONCEALED BY CAPS MATCHING THE COLOR OF THE
 MOUNTING PLATE.
  
 5) THE ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRE
 THAT ALL INSTALLATION COMPONENTS CONSIST OF ANODIZED
 ALUMINUM. PROVIDE ON THE PLANS VERIFICATION THAT THE
 MOUNTING PLATE AND TUBES, INCLUDING DECORATIVE FINIAL,
 ARE ANODIZED ALUMINUM.
  
 6) THE ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRE THE
 STUD MOUNTS TO BE SERIES 316 STAINLESS STEEL ANCHOR
 BOLTS. PROVIDE VERIFICATION OF THIS REQUIREMENT ON THE
 PLANS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  