 |
Plan Review Details - Permit 20090500
| Plan Review Stops For Permit 20090500 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
2 |
Status |
P |
Date |
2020-12-07 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2020-12-07 |
Time |
16:48 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2020-12-07 |
Time |
16:48 |
Sent To |
|
|
| Notes |
| 2020-12-07 16:49:03 | ADDRESS CHANGED TO REFLECT CORRECT SUITE 5325 GREENWOOD | | | AVE # 301 |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
F |
Date |
2020-09-28 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2020-09-28 |
Time |
08:32 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2020-09-28 |
Time |
08:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
4 |
Status |
P |
Date |
2021-01-13 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2021-01-13 |
Time |
10:10 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2021-01-13 |
Time |
10:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
3 |
Status |
F |
Date |
2021-01-05 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2021-01-05 |
Time |
10:23 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2021-01-05 |
Time |
09:46 |
Sent To |
|
|
| Notes |
| 2021-01-05 10:22:03 | COMMERCIAL ASBESTOS | | | | | | TO THE BUILDING CONTRACTOR: | | | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING: THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS | | | REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: | | | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | | RENOVATION.HTML | | | | | | THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO | | | [email protected]. THE INFORMATION SHOULD BE IN PDF | | | FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE | | | THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE. | | | |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
2 |
Status |
F |
Date |
2020-11-17 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2020-11-17 |
Time |
10:28 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2020-11-17 |
Time |
08:46 |
Sent To |
|
|
| Notes |
| 2020-11-17 10:24:41 | TO THE BUILDING CONTRACTOR: | | | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS | | | REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: | | | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | | RENOVATION.HTML | | | | | | THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO | | | [email protected]. THE INFORMATION SHOULD BE IN PDF | | | FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE | | | THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE. | | | | | | | | | |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
1 |
Status |
F |
Date |
2020-10-05 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2020-10-05 |
Time |
12:34 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2020-10-05 |
Time |
08:02 |
Sent To |
|
|
| Notes |
| 2020-10-05 12:34:27 | COMMERCIAL ASBESTOS | | | TO THE BUILDING CONTRACTOR: | | | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS | | | REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: | | | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | | RENOVATION.HTML | | | | | | THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO | | | [email protected]. THE INFORMATION SHOULD BE IN PDF | | | FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE | | | THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2021-01-13 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2021-01-13 |
Time |
10:13 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2021-01-13 |
Time |
10:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2021-01-05 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2021-01-05 |
Time |
10:26 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2021-01-05 |
Time |
09:46 |
Sent To |
|
|
| Notes |
| 2021-01-05 10:19:42 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION | | | SERVICES/ BUILDING DIVISION | | | 2017 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 20090500 | | | ADD: 5325 GREENWOOD AVE. SUITE: 300 | | | CONT: BLACK DIAMOND GENERAL CONTRACTOR | | | TEL: 561-746-3452 | | | E-MAIL: [email protected] | | | | | | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 3RD REVIEW | | | DATE: WED JAN. 05TH/2021 | | | ACTION:PASSED / BUILDING PROVISO | | | | | | 1) BUILDING PROVISO/ FUTURE REVISION REQUIRED. THE 1ST | | | FLOOR LIFE SAFETY PLAN SHOWS NEW MED GAS, NEW VACUUM | | | PUMP EQUIPMENT, BUT NO NEW WORK ON THE 2ND FLOOR, HOW | | | ARE THESE LINES GOING TO THE NEW AMBULATORY SURGICAL | | | CENTER ON THE 3RD FLOOR. 107/2/1/2 ADDITIONAL | | | INFORMATION IS REQUIRED. | | | | | | 2) NOTICE ONLY. NO ACTION NEEDED AT THIS TIME. THE | | | INSTALLATION OF A GENERATOR WILL BE UNDER A SEPARATE | | | PERMIT, NOT INCLUDED IN THIS REVIEW. SEPARATE PERMIT, | | | REVIEW AND ASSOCIATED FEES REQUIRED FOR NEW GENERATOR, | | | AND OR FENCING. | | | | | | 3) BUILDING PROVISO: FOR WELDED & BOLTED CONNECTIONS. | | | THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE | | | SPECIFICATIONS & WELDER OPERATOR PERFORMANCE | | | QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED | | | STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON | | | THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL | | | BE REQUIRED. REPORTS SUBMITTED TO BUILDING INSPECTOR AT | | | TIME OF FRAMING INSPECTION. | | | 2017 FBC-B 2204.1 WELDING | | | 1. WELD PROCEDURES SPECIFICATIONS | | | 2. QUALIFICATIONS OF WELDING PERSONAL | | | 2017 FBC-B 2204.2 BOLTING. | | | IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED, | | | PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD | | | AT | | | 561-805-6666. | | | | | | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID | | | 19 | | | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS | | | 561-718-9724. | | | | | | JAMES A. WITMER BN, PX, SFP, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6717 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2020-11-17 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2020-11-17 |
Time |
10:28 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2020-11-17 |
Time |
08:45 |
Sent To |
|
|
| Notes |
| 2020-11-17 10:23:31 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION | | | SERVICES/ BUILDING DIVISION | | | 2017 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 20090500 | | | ADD: 5325 GREENWOOD AVE. SUITE: 300 | | | CONT: DPR CONSTRUCTION | | | TEL: 858-210-9600 | | | E-MAIL: [email protected] | | | | | | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 2ND REVIEW | | | DATE: TUES. 17TH/2020 | | | ACTION: DENIED | | | | | | 1A-B) COMPLIED | | | | | | 1C) BUILDING PROVISO/ FUTURE REVISION REQUIRED. THE 1ST | | | FLOOR LIFE SAFETY PLAN SHOWS NEW MED GAS, NEW VACUUM | | | PUMP EQUIPMENT, BUT NO NEW WORK ON THE 2ND FLOOR, HOW | | | ARE THESE LINES GOING TO THE NEW AMBULATORY SURGICAL | | | CENTER ON THE 3RD FLOOR. 107/2/1/2 ADDITIONAL | | | INFORMATION IS REQUIRED. | | | | | | 1D) NOTICE ONLY. NO ACTION NEEDED AT THIS TIME. THE | | | INSTALLATION OF A GENERATOR WILL BE UNDER A SEPARATE | | | PERMIT, NOT INCLUDED IN THIS REVIEW. SEPARATE PERMIT, | | | REVIEW AND ASSOCIATED FEES REQUIRED FOR NEW GENERATOR, | | | AND OR FENCING. | | | | | | 2) COMPLIED. | | | | | | 3) COMPLIED. | | | | | | 4A)SEMI- COMPLIED. SHEET A-153 DOES INDICATE RATED | | | WALLS AND IDENTIFIES DOOR. SHEET A-701 DOES SHOW THE | | | DOOR SCHEDULE, IT APPEARS THERE ARE 2 DOORWAYS IN 1 | | | HOUR RATED WALLS WITH NO RATING, DOOR 3023 AND 3033-B. | | | 2017 FBC-B TABLE 716,5, | | | | | | 4B) COMPLIED. | | | | | | 5) COMPLID. | | | | | | 6) COMPLIED AND OR DEFERRED SUBMITTALS. | | | | | | 7A) COMPLIED. | | | | | | 7B)BUILDING PROVISO: FOR WELDED & BOLTED CONNECTIONS. | | | THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE | | | SPECIFICATIONS & WELDER OPERATOR PERFORMANCE | | | QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED | | | STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON | | | THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL | | | BE REQUIRED. REPORTS SUBMITTED TO BUILDING INSPECTOR AT | | | TIME OF FRAMING INSPECTION. | | | 2017 FBC-B 2204.1 WELDING | | | 1. WELD PROCEDURES SPECIFICATIONS | | | 2. QUALIFICATIONS OF WELDING PERSONAL | | | 2017 FBC-B 2204.2 BOLTING. | | | IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED, | | | PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD | | | AT | | | 561-805-6666. | | | | | | 8) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS | | | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT | | | REVIEW CYCLE. | | | | | | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID | | | 19 | | | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS | | | 561-718-9724. | | | | | | JAMES A. WITMER BN, PX, SFP, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6717 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2020-10-05 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2020-10-05 |
Time |
12:06 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2020-10-05 |
Time |
08:02 |
Sent To |
|
|
| Notes |
| 2020-10-05 12:36:44 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION | | | SERVICES/ BUILDING DIVISION | | | 2017 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 20090500 | | | ADD: 5325 GREENWOOD AVE. SUITE: 300 | | | CONT: DPR CONSTRUCTION | | | TEL: 858-210-9600 | | | E-MAIL: [email protected] | | | | | | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: MON. OCT. 05TH/2020 | | | ACTION: DENIED | | | | | | 1A) SHEET G-001 CODE ANALYSIS SHEET UNDER THE HEADING | | | VIII THE TOTAL OCCUPANT LOAD COUNT IS 216 NOT 226, IT | | | APPEARS TO BE A TYPO. 107.2.1.2 ADDITIONAL INFORMATION | | | IS REQUIRED. | | | | | | 1B) THE PERMIT APPLICATION AS WELL AS THE CODE ANALYSIS | | | ONLY LIST WORK TO BE COMPLETED UNDER THIS PERMIT AS | | | BEING ON THE 3RD FLOOR. SHEETS D101 THE 1ST FLOOR DEMO | | | AND SHEET LS101 THE 1ST FLOOR LIFE SAFETY SHEET. PLEASE | | | ADD THE 1ST FLOOR TO THE SCOPE OF WORK ON THE PERMIT | | | APPLICATION AS WELL AS THE CODE ANALYSIS SHEET. | | | | | | 1C) THE 1ST FLOOR LIFE SAFETY PLAN SHOWS NEW MED GAS, | | | NEW VACUUM PUMP EQUIPMENT, BUT NO NEW WORK ON THE 2ND | | | FLOOR, HOW ARE THESE LINES GOING TO THE NEW AMBULATORY | | | SURGICAL CENTER ON THE 3RD FLOOR. 107/2/1/2 ADDITIONAL | | | INFORMATION IS REQUIRED. | | | | | | 1D) THE INSTALLATION OF A GENERATOR WILL BE UNDER A | | | SEPARATE PERMIT, NOT INCLUDED IN THIS REVIEW. SEPARATE | | | PERMIT, REVIEW AND ASSOCIATED FEES REQUIRED FOR NEW | | | GENERATOR, AND OR FENCING. | | | | | | 2) SHEET G401-ADA STANDARDS. | | | 2A) PLEASE NOTE WE USE THE 2017 FBC-ACCESSIBILITY CODE | | | DEEMED THE EQUIVALENT TO THE ADA STANDARDS AND BLESSED | | | BY THE DEPARTMENT OF JUSTICE. IN ALL THE WATER CLOSET | | | DETAILS THE GRAB BARS ARE DIMENSIONED FROM THE | | | CENTERLINE. IN THE 2017 FBC-ACCESS. CODE SECTION 609.4 | | | POSITION OF GRAB BARS. GRAB BARS SHALL BE INSTALLED IN | | | A HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES | | | MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF | | | THE GRIPPING SURFACE, NOT CENTERLINE. | | | | | | 2B) THERE IS ALSO A DEPICTION OF AN ELECTRIC DRINKING | | | FOUNTAIN (SINGLE). 2017 FBC-ACCESSIBILITY CODE. 211.2 | | | MINIMUM NUMBER. NO FEWER THAN TWO DRINKING FOUNTAINS | | | SHALL BE PROVIDED. ONE DRINKING FOUNTAIN SHALL COMPLY | | | WITH 602.1 THROUGH 602.6 AND ONE DRINKING FOUNTAIN | | | SHALL COMPLY WITH 602.7. | | | | | | PROTRUDING OBJECTS 307.2 PROTRUSION LIMITS 307.2. | | | OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES AND NOT | | | MORE THAN 80 INCHES ABOVE THE FLOOR SHALL NOT PROTRUDE | | | MORE THAN 4 INCHES HORIZONTALLY INTO THE CIRCULATION | | | PATH. | | | | | | 602.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE COMPLYING | | | WITH 305, POSITIONED FOR A FORWARD APPROACH, AND KNEE | | | AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED. | | | | | | 2C) PLEASE ALSO TAKE NOTE TO THE SINGLE USER ACCESSIBLE | | | RESTROOM LABELED FIG. 10. THE 2017 FBC-ACCESS. CODE | | | 603.2.3 DOOR SWING AND EXCEPTION 2. I BELIEVE THIS HOW | | | YOU ARE STRIVING TO SHOW CODE COMPLIANCE. WHAT IS | | | MISSING IS THE REQUIRED CLEAR FLOOR SPACE BEYOND THE | | | ARC OF THE DOOR. IT IS USUALLY SHOWN AT A 45-DEGREE | | | ANGLE TO THE ENTRY DOOR. | | | | | | 3) SHEET LS 103 THE 3RD FLOOR HAS WHAT IS LABELED | | | PRE-OP/ PACU WHERE THERE ARE 10 OUTPATIENT BEDS. AFTER | | | SURGERY THESE BEDS ARE ALSO USED FOR THE PATIENT CARE/ | | | AND RECOVERY. THE PLANS LIST THIS AREA AS SMOKE | | | COMPARTMENT # 1 HAS AN AREA OF 5,919 SQ. FT. WHAT I AM | | | MISSING IS FOR AMBULATORY CARE FACILITIES WHERE THE | | | POTENTIAL FOR FOUR OR MORE CARE RECIPIENTS ARE TO BE | | | INCAPABLE OF SELF-PRESERVATION AT ANY TIME, WHETHER | | | RENDERED INCAPABLE BY STAFF OR STAFF ACCEPTED | | | RESPONSIBILITY FOR A CARE RECIPIENT ALREADY INCAPABLE, | | | SHALL BE SEPARATED FROM ADJACENT SPACES, CORRIDORS OR | | | TENANTS WITH FIRE PARTITIONS INSTALLED IN ACCORDANCE | | | WITH SECTION 708. | | | | | | 4A) 3RD FLOOR SHEETS LS103, THIRD FLOOR AREA PLAN | | | LS103A NOR THE A-103 THE 3RD FLOOR DIMENSION PLAN HAVE | | | DOOR IDENTIFICATION NUMBERS TO SEE SIZE AND DOOR | | | RATINGS. 716.5 OF THE 2017 FBC-B. | | | | | | 4B) PLEASE ALSO PROVIDE THE CORRIDOR WIDTHS IF | | | POSSIBLE, ON THE DIMENSION PLAN A-103, 3RD FLOOR | | | DIMENSION PLAN. | | | 2017 FBC-B TABLE 1020.2. | | | | | | | | | 5) SHEET A801 STAFF LOUNGE 3033 SHOW AN ACCESSIBLE | | | COUNTERTOP MICROWAVE WHEREAS THE DETAIL NOUR. 3037 | | | SHOWS THE MICROWAVE OUT OF THE REACH RANGES. PLEASE | | | SHOW COMPLIANCE WITH THE 2017 FBC-ACCESS. CODE: | | | | | | 308 REACH RANGES 308.2 FORWARD REACH. / 308.2.1 | | | UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH REACH. | | | 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2 | | | OBSTRUCTED HIGH REACH. | | | | | | 309 OPERABLE PARTS 309.3 HEIGHT. OPERABLE PARTS SHALL | | | BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES | | | SPECIFIED IN 308. 309.4 OPERATION. OPERABLE PARTS SHALL | | | BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT | | | GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE | | | REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS | | | (22.2 N) MAXIMUM. | | | | | | 6) SHEET S1 NOTES AND ROOF FRAMING PLAN: | | | 6A) WIND LOADS. THE PLAN STATES THE VULT IS 169 MPH AND | | | THE WIND VASD IS 102 MPH. I BELIEVE THIS MAYBE A TYPE | | | SINCE 170 VULT = 132 VASD. | | | | | | 6B) THE GIVEN EXPOSURE CATEGORY IS LABELED AS AN | | | EXPOSURE B. PLEASE NOTE TO THE NORTH THERE IS VACANT | | | LAND AND THEN ROYAL PALM MEMORIAL GARDENS A CEMETERY. | | | THE CITY ASSIGNS A SURFACE ROUGHNESS C. THIS CATEGORY | | | INCLUDES FLAT OPEN COUNTRY, GRASSLANDS.2017 FBC-B | | | 1609.4.2. | | | | | | 6C) THERE ARE NEW EXTERIOR DOOR OPENINGS AND NEW ROOF | | | EQUIPMENT BEING INSTALLED, PLEASE PROVIDE THE | | | COMPONENTS AND CLADDING PRESSURES FOR ROOF ZONES 1,2 & | | | 3 AS WELL AS WALL ZONES 4 & 5. FOR TRIBUTARY AREAS OF | | | 10 SQ. FT., 20 SQ. FT., 50 SQ. FT., & 100 SQ. FT. IN | | | VASD SINCE ALL PRODUCT APPROVALS ARE IN VASD. | | | | | | | | | | | | | | | | | | 6D) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS, | | | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT | | | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, | | | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS | | | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT | | | APPROVALS: | | | (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES. | | | (D) ROOFING PRODUCTS AND ASSEMBLIES, INCLUDING CURBS | | | (G) IF PRE-ENGINEERED A/C STANDS ARE BEING INSTALLED | | | | | | 6E) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY | | | ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES | | | FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL | | | LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF | | | ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR | | | BOTH INSULATION & THE BASE SHEET AS CALCULATED IN | | | COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117. | | | CALCULATION PREPARED, SIGNED AND SEALED BY A FLORIDA | | | REGISTERED PROFESSIONAL ENGINEER OR REGISTERED | | | ARCHITECT. 1609.6.4.4.1 COMPONENTS & CLADDING. | | | | | | 6F) 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, | | | THE CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE | | | AND DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS, | | | VENTING, FASTENING REQUIREMENTS, FLASHING REQUIREMENTS | | | AND WIND RESISTANCE RATING THAT ARE REQUIRED TO BE | | | INSTALLED. PRODUCT EVALUATION AND INSTALLATION SHALL | | | INDICATE COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR | | | THE SPECIFIC SITE. | | | | | | 6G) 2017 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL | | | EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO | | | WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND | | | PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA | | | BUILDING CODE, BUILDING. FBC-B-1609.6.4.4.1 COMPONENTS | | | AND CLADDING. WIND PRESSURE FOR EACH COMPONENT OR | | | CLADDING ELEMENT IS TO BE DESIGNED FOR WIND PRESSURES | | | COMPONENTS AND ATTACHMENTS. | | | | | | LATERAL FORCE-RESISTING SYSTEM. FOR ALL ROOF TOP | | | EQUIPMENT, CURBS, FANS OR A/C STANDS, AND OR VENTS, | | | DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL | | | AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE. | | | | | | 2017 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL | | | MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY | | | METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT | | | EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY | | | AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. | | | EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE | | | OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES | | | SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND | | | LOADS. | | | | | | 6H) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS | | | WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE | | | 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR | | | JURISDICTIONAL APPROVAL. | | | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | | SHOP DRAWINGS ETC.. | | | | | | DELEGATED ENGINEERING. 61G15-30.003 ENGINEERING | | | DOCUMENT CLASSIFICATION. FL 61G-15-30.006 (3) THE | | | DELEGATED ENGINEER SHALL FORWARD THE DELEGATED | | | ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR | | | REVIEW. | | | | | | 6I) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF | | | THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE | | | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE | | | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO | | | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. | | | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR | | | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED | | | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST | | | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS | | | FOR REVIEW BY THE BUILDING OFFICIAL. | | | | | | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE | | | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN | | | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD | | | THEM TO THE BUILDING OFFICIAL WITH A NOTATION | | | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE | | | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO | | | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL | | | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED | | | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING | | | OFFICIAL. | | | | | | 7A) THE STRUCTURAL SHEETS INDICATE NEW BAR JOIST ARE TO | | | BE INSTALLED. THE PLANS ARE SILENT AS TO HOW THEY WILL | | | BE INSTALLED. WILL THERE BE AREAS OF ROOFING AND B-DECK | | | BE REMOVED? 107.2.1.2. ADDITIONAL INFORMATION IS | | | REQUIRED. | | | | | | 7B) FOR WELDED & BOLTED CONNECTIONS. THE CONTRACTOR IS | | | REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS & | | | WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN | | | ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF | | | INSPECTION FOR FIELD WIELDING, ON THE JOB-SITE | | | WIELDING. THIRD PARTY CERTIFICATION WILL BE REQUIRED. | | | REPORTS SUBMITTED TO BUILDING INSPECTOR AT TIME OF | | | FRAMING INSPECTION. | | | 2017 FBC-B 2204.1 WELDING | | | 1. WELD PROCEDURES SPECIFICATIONS | | | 2. QUALIFICATIONS OF WELDING PERSONAL | | | 2017 FBC-B 2204.2 BOLTING. | | | IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED, | | | PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD | | | AT | | | 561-805-6666. | | | | | | 8) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS | | | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT | | | REVIEW CYCLE. | | | | | | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID | | | 19 | | | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS | | | 561-718-9724. | | | | | | JAMES A. WITMER BN, PX, SFP, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6717 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2020-10-08 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-10-08 |
Time |
15:35 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-10-08 |
Time |
10:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E-LOWVOLT |
ELECTRICAL LOW VOLTAGE |
| Rev No |
1 |
Status |
P |
Date |
2020-10-08 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-10-08 |
Time |
15:35 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-10-08 |
Time |
15:35 |
Sent To |
|
|
| Notes |
| 2020-10-08 15:37:35 | TELEPHONE, DATA, SECURITY, NURSE CALL JLEAHY |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2020-12-21 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2020-12-21 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2020-12-21 |
Time |
12:35 |
Sent To |
|
|
| Notes |
| 2020-12-21 12:42:25 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR | | | CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND/OR | | | FIRE SPRINKLER SYSTEMS BY APPLICABLE LICENSED | | | CONTRACTORS FOR CODE COVERAGE COMPLIANCE. | | | | | | | | | 2) ANY AND ALL WORK ON THE FIRE ALARM AND/OR FIRE | | | SPRINKLER SYSTEMS, INCLUDING DEMO, SHALL BE DONE UNDER | | | SEPARATE PERMITS AND SHOP DRAWINGS. | | | | | | | | | 3) THE EXISTING LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR | | | FIRE SPRINKLER SHALL BE MAINTAINED AND REMAIN ACTIVE | | | THROUGHOUT THE CONSTRUCTION PERIOD, INCLUDING DEMO. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | WEST PALM BEACH FIRE DEPARTMENT | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2020-09-29 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2020-09-29 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2020-09-29 |
Time |
13:09 |
Sent To |
|
|
| Notes |
| 2020-09-29 13:09:39 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR | | | CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND/OR | | | FIRE SPRINKLER SYSTEMS BY APPLICABLE LICENSED | | | CONTRACTORS FOR CODE COVERAGE COMPLIANCE. | | | | | | | | | 2) ANY AND ALL WORK ON THE FIRE ALARM AND/OR FIRE | | | SPRINKLER SYSTEMS, INCLUDING DEMO, SHALL BE DONE UNDER | | | SEPARATE PERMITS AND SHOP DRAWINGS. | | | | | | | | | 3) THE EXISTING LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR | | | FIRE SPRINKLER SHALL BE MAINTAINED AND REMAIN ACTIVE | | | THROUGHOUT THE CONSTRUCTION PERIOD, INCLUDING DEMO. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | WEST PALM BEACH FIRE DEPARTMENT | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2021-01-13 |
Time |
10:14 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2021-01-08 |
Time |
08:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2021-01-05 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2021-01-05 |
Time |
10:27 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2020-12-18 |
Time |
15:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2020-12-02 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2020-12-02 |
Time |
17:34 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2020-12-02 |
Time |
17:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2020-10-13 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-10-13 |
Time |
06:47 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-09-25 |
Time |
11:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
N |
Date |
2020-10-05 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2020-10-05 |
Time |
12:34 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2020-10-05 |
Time |
08:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2020-12-21 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-12-21 |
Time |
08:16 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2020-12-21 |
Time |
08:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2020-11-16 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-11-16 |
Time |
08:40 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2020-11-16 |
Time |
08:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2020-09-29 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-09-29 |
Time |
16:20 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2020-09-29 |
Time |
11:01 |
Sent To |
|
|
| Notes |
| 2020-09-29 16:21:39 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT-20090500 | | | | | | CODES IN EFFECT: | | | | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE SHOW THE VENTILATION FOR LOSS OF ELECTRICAL | | | POWER MEETS SECTION 6.1.1 OF ASHRAE 170-2008 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | | UPDATED. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
MEDGAS |
MEDICAL GAS |
| Rev No |
3 |
Status |
P |
Date |
2020-12-21 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2020-12-21 |
Time |
15:46 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2020-12-21 |
Time |
14:59 |
Sent To |
|
|
| Notes |
| 2020-12-21 15:47:26 | 12/18/20 REVIEWED FOR CODE COMPLIANCE (MEDICAL/GAS) | | | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | | PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES | | | FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, | | | STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT | | | THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK | | | OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | | AVOID VOIDING OF THE PERMIT. | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | |
|
|
| Review Stop |
MEDGAS |
MEDICAL GAS |
| Rev No |
2 |
Status |
F |
Date |
2020-12-02 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2020-12-02 |
Time |
17:30 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2020-11-30 |
Time |
10:21 |
Sent To |
|
|
| Notes |
| 2020-12-02 17:25:26 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL | | | MANUAL REVISED 2017 | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION | | | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH | | | EDITION | | | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION | | | NFPA 99 = HEALTH CARE FACILITIES CODE | | | FAC= FLORIDA ADMINISTRATIVE CODE | | | FS = FLORIDA STATUTES | | | | | | 20090500 5325 GREENWOOD AVE | | | | | | 2ND REVIEW | | | MEDICAL GAS COMMENTS: DENIED | | | | | | ORIGINAL COMMENT #1. COMPLIED | | | | | | ORIGINAL COMMENT #2. SECOND REQUEST: PER NFPA 99-15 | | | SECTION 5.1.3.1.8, PROVIDE NOTE REQUIRING SIGNAGE ON | | | THE ENTRY DOOR TO THE ROOM CONTAINING THE MEDICAL GAS | | | MANIFOLDS/CYLINDERS STATING | | | "POSITIVE PRESSURE GASES | | | NO SMOKING OR OPEN FLAME | | | ROOM MAY HAVE INSUFFICIENT OXYGEN | | | OPEN DOOR AND ALLOW ROOM TO VENTILATE BEFORE ENTERING" | | | TO BE CLEAR, PROVIDE SAID NOTE MAKING THE STATEMENT ON | | | THE PLAN. | | | | | | ORIGINAL COMMENT #3. SECOND REQUEST: PLAN SHEET A9.21; | | | ELEVATION OF HEADWALL NOTES A, O AND V OUTLETS. LEGEND | | | ONLY IDENTIFIES O AND V. PER WPB FBC 107.2, CLARIFY. | | | | | | ORIGINAL COMMENT #4. COMPLIED | | | | | | ORIGINAL COMMENT #5. COMPLIED; FURTHER ACTION REQUIRED. | | | PER WPB FBC 107.2.1, THIS REFERENCED DEFERRED SUBMITTAL | | | FOR MEDICAL GAS EQUIPMENT SHALL BE ADDED TO THE LIST OF | | | DEFERRED SUBMITTALS NOTE IN G1.01; DEFERRED SUBMITTALS. | | | | | | ORIGINAL COMMENT #6. COMPLIED | | | | | | ORIGINAL COMMENT #7. COMPLIED | | | | | | ORIGINAL COMMENT #8. COMPLIED | | | | | | ORIGINAL COMMENT #9. COMPLIED | | | | | | ORIGINAL COMMENT #10. COMPLIED | | | | | | ORIGINAL COMMENT #11. COMPLIED:FURTHER ACTION REQUIRED. | | | PER WPB FBC 107.2.1, PROVIDE PROVIDE NOTE ON PLAN | | | SHOWING VACUUM SYSTEM IS MONITORED FOR OXYGEN CONTENT | | | THAT IS ACQUIRED THROUGH THE WAGD TO COMPLY WITH NFPA | | | 99-15, SECTION 5.1.3.8.1.2(2) AND 5.1.3.8.3.1. SEE | | | PROJECT SPECIFICATION 22-60-00, SECTION 3.1, SUB | | | SECTION (S) | | | | | | ORIGINAL COMMENT #12. COMPLIED | | | | | | ORIGINAL COMMENT #13. COMPLIED: FURTHER ACTION | | | REQUIRED. PER WPB FBC 107.2.1, PROVIDE PROVIDE NOTE ON | | | PLAN TO REQUIRE DOCUMENTATION ON ALL PIPE, VALVES AND | | | FITTINGS PER NFPA 99-15 SECTION 5.1.10.1.6. SEE PROJECT | | | SPECIFICATION 22-60-00, SECTION 1.6, SUB SECTION (E) | | | | | | ORIGINAL COMMENT #14.COMPLIED: FURTHER ACTION REQUIRED. | | | PER WPB FBC 107.2.1, PROVIDE PROVIDE NOTE ON PLAN TO | | | REQUIRE BRAZING TECHNICIANS TO BE QUALIFIED AND | | | CERTIFIED IN ACCORDANCE WITH NFPA 99-15 SECTION | | | 5.1.10.11.11. SEE PROJECT SPECIFICATION 22-60-00, | | | SECTION 1.7, SUB SECTION (E) | | | | | | ORIGINAL COMMENT #15.COMPLIED | | | | | | ORIGINAL COMMENT #16. COMPLIED: FURTHER ACTION | | | REQUIRED. PER WPB FBC 107.2.1, PROVIDE PROVIDE NOTE ON | | | PLAN TO PROVIDE VALVE ID/SYSTEM IDENTIFICATION/COLOR | | | CODING SPECIFICATION PER NFPA 99-15 SECTION 5.1.11 | | | THROUGH 5.1.11.4. COMPLIED; SEE PROJECT SPECIFICATION | | | 22-60-00, SECTION 3.1, SUB SECTION (T) | | | | | | ORIGINAL COMMENT #17.COMPLIED | | | | | | END OF COMMENTS. | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | ALL PLANS TO BE SIGNED AND SEALED/DIGITALLY SIGNED AND | | | SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. | | | | | | | | | JERALD SMITH | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | EMAIL [email protected] | | | PHONE 561-246-0882 MOBILE | | | | | | 20090500 5325 GREENWOOD AVE | | | |
|
|
| Review Stop |
MEDGAS |
MEDICAL GAS |
| Rev No |
1 |
Status |
F |
Date |
2020-10-12 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2020-10-12 |
Time |
18:33 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2020-10-06 |
Time |
16:28 |
Sent To |
|
|
| Notes |
| 2020-10-08 17:11:48 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL | | | MANUAL REVISED 2017 | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION | | | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH | | | EDITION | | | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION | | | NFPA 99 = HEALTH CARE FACILITIES CODE | | | FAC= FLORIDA ADMINISTRATIVE CODE | | | FS = FLORIDA STATUTES | | | | | | | | | 1ST REVIEW | | | MEDICAL GAS COMMENTS: DENIED | | | | | | 1.NOTE O2, AIR (MEDICAL CA MANIFOLD AND CYLINDERS), | | | VACUUM AND N2 ON PLANS. PROJECT SPECS SPECIFICATION | | | 22-60-00 SECTION 1.1 DOES NOT REFERENCE N2. | | | | | | 2.PER NFPA 99-15 SECTION 5.1.3.1.8, PROVIDE NOTE | | | REQUIRING SIGNAGE ON THE ENTRY DOOR TO THE ROOM | | | CONTAINING THE MEDICAL GAS MANIFOLDS/CYLINDERS STATING | | | ?POSITIVE PRESSURE GASES | | | NO SMOKING OR OPEN FLAME | | | ROOM MAY HAVE INSUFFICIENT OXYGEN | | | OPEN DOOR AND ALLOW ROOM TO VENTILATE BEFORE ENTERING? | | | | | | 3.PLAN SHEET A9.21; ELEVATION OF HEADWALL NOTES A, O | | | AND V OUTLETS. LEGEND ONLY IDENTIFIES O AND V. PER WPB | | | FBC 107.2, CLARIFY. | | | | | | 4.PER WPB 107.2.1, PROVIDE SECOND FLOOR PLAN SHOWING | | | MED GAS PIPING CONNECTING FIRST AND THIRD FLOORS. | | | | | | 5.PROVIDE MANUFACTURER?S SPECIFICATION | | | SHEETS/INSTALLATION MANUAL FOR MEDICAL GAS EQUIPMENT | | | AND COMPONENTS. AS THE ACTUAL EQUIPMENT MANUFACTURER | | | (SEE 20032 PALM BEACH INTERNATIONAL SC SPECS DIVISION | | | 22-60-00 SUPPORTING DOCUMENT) MAY NOT HAVE BEEN | | | SELECTED AT THIS TIME, SAID DOCUMENTS MAY BE SUBMITTED | | | AS A DEFERRED SUBMITTAL IN ACCORDANCE WITH WPB FBC | | | 107.2.1 AND 107.3.4.1. SEE WPB FBC 107.3.4.2 DEFERRED | | | SUBMITTALS; FOR THE PURPOSES OF THIS SECTION, DEFERRED | | | SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF THE DESIGN | | | THAT ARE NOT SUBMITTED AT THE TIME OF THE APPLICATION | | | AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL | | | WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL | | | ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE BUILDING | | | OFFICIAL. THE REGISTERED DESIGN PROFESSIONAL IN | | | RESPONSIBLE CHARGE SHALL LIST THE DEFERRED SUBMITTALS | | | ON THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE | | | BUILDING OFFICIAL. THIS MAY BE DONE BY NOTING SUCH IN | | | THE RESPONSE LETTER TO THIS REVIEW. | | | | | | 6.DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE | | | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN | | | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD | | | THEM TO THE BUILDING OFFICIAL WITH A NOTATION | | | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE | | | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO | | | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL | | | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED | | | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING | | | OFFICIAL. | | | | | | 7.PER WPB FBC 107.2.1, PROVIDE RISER DIAGRAM OF PIPING | | | SYSTEMS FROM SOURCE TO OUTLETS, INCLUDE ALL IN-LINE | | | COMPONENTS | | | | | | 8.RE: 22-60-00, SECTION 2.7 (C) VACUUM PUMP RECEIVER IS | | | PROVIDED WITH AUTOMATIC TANK DRAIN. PER NFPA 99-15 | | | SECTION 5.1.3.7.3(4), RECEIVER SHALL BE PROVIDED WITH A | | | MANUAL DRAIN. THE AUTOMATIC TANK DRAIN MAY BE PROVIDED | | | IN ADDITION TO THE MANUAL DRAIN. | | | | | | 9.PER WPB FBC 107.2.1, PROVIDE LOCATION AND DETAIL | | | TERMINATION OF GAS MANIFOLD RELIEF VENT INCLUDING | | | ELEVATION AND ANCHORING DETAILS. SPECIFY MATERIAL AND | | | JOINTS FOR VENT. | | | | | | 10.PER WPB FBC 107.2.1, PROVIDE LOCATION AND DETAIL | | | TERMINATION OF VACUUM PUMP EXHAUST VENT INCLUDING | | | ELEVATION AND ANCHORING DETAILS. COMPLY WITH ALL | | | REQUIREMENTS OF NFPA 99-15, SECTIONS 5.1.3.7.6.2 | | | THROUGH 5.1.3.7.6.5. SPECIFY MATERIAL AND JOINTS FOR | | | VENT TO COMPLY WITH SECTION 5.1.3.7.6.6. | | | | | | 11.PER WPB FBC 107.2.1, PROVIDE DETAILS SHOWING HOW | | | VACUUM SYSTEM IS MONITORED FOR OXYGEN CONTENT THAT IS | | | ACQUIRED THROUGH THE WAGD TO SHOW COMPLIANCE WITH NFPA | | | 99-15, SECTION 5.1.3.8.1.2(2) AND 5.1.3.8.3.1. | | | | | | 12.RE: 22-60-00, SECTION 2.2 SUB SECTIONS | | | (B) TUBE SHALL BE ASTM B819 ACR/OXY PER NFPA 99-15 | | | SECTION 5.1.10.1.4. TUBE COMPLYING WITH ASTM B88 AND | | | B280 IS NOT ACCEPTABLE. | | | (C) DELETE | | | (D) PER NFPA 99-15 SECTION 5.1.10.2.1(1) MAY BE ASTM | | | B88, B280 OR B819. IF NOT B819, COMPLY WITH SECTION | | | 5.1.10.2.2.1. | | | | | | 13.REQUIRE DOCUMENTATION ON ALL PIPE, VALVES AND | | | FITTINGS PER NFPA 99-15 SECTION 5.1.10.1.6 | | | | | | 14.REQUIRE BRAZING TECHNICIANS TO BE QUALIFIED AND | | | CERTIFIED IN ACCORDANCE WITH NFPA 99-15 SECTION | | | 5.1.10.11.11 | | | | | | 15.RE: 22-60-00, SECTION 3.1 (D); NFPA 99-15 DOES NOT | | | ALLOW FOR TUBE BENDING. SEE SECTION 5.1.10.4.1 GENERAL | | | CONDITIONS. MAKE DIRECTIONAL CHANGES WITH APPROVED | | | FITTINGS AND JOINTS. | | | | | | 16.PROVIDE VALVE ID/SYSTEM IDENTIFICATION/COLOR CODING | | | SPECIFICATION PER NFPA 99-15 SECTION 5.1.11 THROUGH | | | 5.1.11.4. | | | | | | 17.PROVIDE NOTE ON PLANS TO REFER TO 20032 PALM BEACH | | | INTERNATIONAL SC SPECS DIVISION 22-60-00 FOR WRITTEN | | | MEDICAL GAS SPECIFICATIONS (PROVIDED IN SUPPORTING | | | DOCUMENTS) | | | | | | END OF COMMENTS. | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | ALL PLANS TO BE SIGNED AND SEALED/DIGITALLY SIGNED AND | | | SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. | | | | | | | | | JERALD SMITH | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | EMAIL [email protected] | | | PHONE 561-246-0882 MOBILE | | | | | | 20090500 5325 GREENWOOD AVE | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2020-12-21 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2020-12-21 |
Time |
14:57 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2020-12-21 |
Time |
14:57 |
Sent To |
|
|
| Notes |
| 2020-12-21 14:58:49 | 12/21/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING) | | | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | | PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES | | | FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, | | | STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT | | | THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK | | | OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | | AVOID VOIDING OF THE PERMIT. | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2020-12-02 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2020-12-02 |
Time |
15:26 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2020-11-30 |
Time |
10:21 |
Sent To |
|
|
| Notes |
| 2020-12-02 15:11:17 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL | | | MANUAL REVISED 2017 | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION | | | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH | | | EDITION | | | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION | | | NFPA 99 = HEALTH CARE FACILITIES CODE | | | FAC= FLORIDA ADMINISTRATIVE CODE | | | FS = FLORIDA STATUTES | | | | | | | | | 20090500 5325 GREENWOOD AVE | | | | | | 2ND REVIEW | | | PLUMBING COMMENTS: DENIED | | | A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS | | | REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW | | | PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL | | | PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST | | | BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW | | | APPROVAL. | | | | | | ORIGINAL COMMENT #1. IS THERE A STORM PIPING SYSTEM IN | | | THE BUILDING OR IS THE BUILDING BEING DRAINED BY | | | SCUPPERS AND A GUTTER SYSTEM. PER WPB FBC 107.2.1, | | | INDICATE ON THE ROOF PLAN HOW THE REQUIREMENTS OF FBC | | | PL CHAPTER 11 ARE BEING MET. SHOW EXISTING ROOF DRAINS, | | | OVERFLOW DRAINS AND/OR EXISTING GUTTERS. IF THERE IS AN | | | EXISTING STORM PIPING SYSTEM, THEN PROVIDE FOR | | | REFERENCE A COPY OF RECORD DRAWINGS FOR THE | | | INSTALLATION. | | | COMPLIED; PROVIDE A REFERENCE COPY OF RECORD DRAWINGS | | | FOR SHELL BUILDING. | | | | | | ORIGINAL COMMENT #2. COMPLIED | | | | | | ORIGINAL COMMENT #3. COMPLIED | | | | | | ORIGINAL COMMENT #4. COMPLIED: RE: PLAN G4.01, ADA | | | STANDARDS; | | | NEW COMMENT: G4.01, ADA STANDARDS; TYP. ACCESSIBLE | | | TOILET ELEVATIONS. SPACE BETWEEN SIDE WALL AND REAR | | | HAND RAIL SHALL BE 6 INCHES MAXIMUM, NOT 9 INCHES. | | | | | | ORIGINAL COMMENT #5. COMPLIED | | | | | | ORIGINAL COMMENT #6. PER WPB FBC 107.2.1 AND | | | 107.3.5.1.3, PROVIDE SIZED DOMESTIC WATER, SANITARY, | | | COMPRESSED AIR AND CLEAR WASTE WATER RISER DIAGRAMS. | | | PARTIALLY COMPLIED; SEE BELOW | | | A.WATER RISER DIAGRAM SHALL SHOW ALL VALVES, BACKFLOW | | | DEVICES, IN-LINE EQUIPMENT (I.E. RECIRCULATING PUMP, | | | THERMAL MIXING VALVE), WATER HEATER, POINTS OF | | | CONNECTION TO FIXTURES/EQUIPMENT AND OWNER SUPPLIED | | | EQUIPMENT AND TO EXISTING SOURCE OF COLD WATER. | | | PARTIALLY COMPLIED. SIZE ALL BRANCHES. PROVIDE FULL | | | OPEN VALVE AT TOP OF ALL WATER DOWNFEEDS PER FBC PL | | | 606.1(5). | | | B.SANITARY RISER DIAGRAM SHALL SHOW ALL TRAPS, FLOOR | | | DRAINS, HUB DRAINS, TRAP PRIMER CONNECTIONS, CLEANOUTS, | | | VENTS, POINTS OF CONNECTION TO FIXTURES/EQUIPMENT AND | | | OWNER SUPPLIED EQUIPMENT AND TO EXISTING SANITARY | | | RISER. IF AN EQUIPMENT ITEM SUCH AS AN ICE MACHINE | | | REQUIRES A DRAIN, THEN A WASTE RECEPTACLE AND INDIRECT | | | WASTE AND AIR GAP SHALL BE PROVIDED TO COMPLY WITH THE | | | PROVISIONS OF FBC PL CHAPTER 8. | | | PARTIALLY COMPLIED. SIZE ALL BRANCHES. FIXTURE DRAIN | | | SIZES NOT REQUIRED AS LONG AS THE SIZE IS NOTED ON | | | P0.01 FIXTURE CONNECTION SCHEDULE. IT IS NOTED HOWEVER | | | ON P0.01 FIXTURE CONNECTION SCHEDULE P-16 FLOOR SINK | | | THAT WASTE CONNECTION SIZE SHALL BE AS SHOWN. NO SIZING | | | OF P-16 FLOOR SINK(S) IS SHOWN. PER WPB FBC 107.2.1, | | | PROVIDE SIZING. PROVIDE NOTES SIMILAR TO WHAT WAS DONE | | | FOR THE WATER CONNECTIONS TO OWNER SUPPLIED EQUIPMENT | | | STATING HOW EQUIPMENT IS TO BE DRAINED (I.E. SIZED | | | INDIRECT WASTE TO FLOOR ADJACENT FLOOR SINK WITH AIR | | | GAP). | | | C.COMPRESSED AIR TO SHOW PIPE, VALVES, REGULATORS, | | | FILTERS AND FITTINGS, SOURCE COMPRESSOR AND POINT OF | | | CONNECTION TO EQUIPMENT BEING SERVICED. | | | PARTIALLY COMPLIED. SIZE ALL BRANCHES. SHOW ALL VALVES, | | | REGULATORS, FILTERS, SOURCE COMPRESSOR. ADDITIONALLY, | | | SHOW HOW OWNER SUPPLED AIR COMPRESSOR WILL BE DRAINED | | | OF CONDENSATE. PROVIDE DETAIL(S) FOR EQUIPMENT | | | CONNECTIONS AT SOURCE AND AT POINT OF USE. REFERENCE | | | ORIGINAL REVIEW COMMENT 17. RESPONSE THAT THERE IS NO | | | COMPRESSED AIR OTHER THAN MEDICAL GAS DOES NOT | | | CORRESPOND WITH THE SUBMITTED PLUMBING PLANS. P2.00 | | | WATER RISER DIAGRAM AND P1.03 BOTH SHOW COMPRESSED AIR | | | PIPING. P1.03 NOTES 1, 4, 13, 14, 15, 16, 17 AND 18 | | | ADDRESSES THE COMPRESSED AIR AS WELL AND NOTE 15 | | | REFERENCES AN OWNER SUPPLIED AIR COMPRESSOR. IF THERE | | | IS NO COMPRESSED AIR AS YOUR RESPONSE INDICATED, THEN | | | REMOVE ALL REFERENCE FROM THE PLAN. | | | D.CLEAR WASTEWATER RISER DIAGRAM SHALL SHOW ALL | | | EQUIPMENT POINTS OF CONNECTION, TRAPS, VENTS AND POINT | | | OF DISPOSAL. SECOND REQUEST: SIZED CLEAR WASTEWATER A/C | | | CONDENSATE DRAIN RISER DIAGRAM REQUIRED. | | | | | | ORIGINAL COMMENT #7. COMPLIED | | | | | | ORIGINAL COMMENT #8. COMPLIED | | | | | | ORIGINAL COMMENT #9. REQUIRE THIS REFERENCED DEFERRED | | | SUBMITTAL FOR OWNER PROVIDED EQUIPMENT SCHEDULE AND | | | MANUFACTURER'S SPECIFICATION/INSTALLATION MANUAL SHALL | | | BE ADDED TO THE LIST OF DEFERRED SUBMITTALS NOTE IN | | | G1.01; DEFERRED SUBMITTALS | | | | | | ORIGINAL COMMENT #10. COMPLIED | | | | | | ORIGINAL COMMENT #11. COMPLIED | | | | | | ORIGINAL COMMENT #12.RE: P0.01 PLUMBING FIXTURE | | | SCHEDULE; P-7 RECESSED BOX. WHAT KIND OF EQUIPMENT IS | | | BEING SERVICED? A COFFEE MAKER OR ICE MACHINE REQUIRES | | | A BACKFLOW PREVENTION DEVICE TO COMPLY WITH THE | | | REQUIREMENTS OF FBC PL 608 AND IN INSTANCES WHERE QUICK | | | CLOSING VALVES ARE UTILIZED, A WATER HAMMER ARRESTOR | | | CONFORMING TO ASSE 1010 SHALL BE INSTALLED. PER WPB FBC | | | 107.2.1, ANY REQUIRED BACKFLOW DEVICE AND/OR WATER | | | HAMMER ARRESTOR SHALL BE SPECIFIED AND SCHEDULED. | | | PARTIALLY COMPLIED; TO BE CLEAR, THERE ARE EIGHT (8) | | | EACH P-7 RECESSED OATEY 39151 WALL BOXES FOR | | | REFRIGERATOR ICE OR COFFEE MAKER COLD WATER | | | CONNECTIONS. CONNECTIONS TO COFFEE MAKERS REQUIRE | | | BACKFLOW PREVENTERS TO COMPLY WITH FBC PL 608. PER WPB | | | FBC 107.2.1, IDENTIFY THE PIECE OF EQUIPMENT THAT EACH | | | P-7 WILL SERVICE. PROVIDE NOTE REQUIRING BACKFLOW | | | PREVENTER FOR COFFEE MAKER CONNECTIONS OR ANY OTHER | | | EQUIPMENT THAT WOULD REQUIRE A BACKFLOW PREVENTER TO | | | COMPLY WITH FBC PL 608. SPECIFY SAID BACKFLOW | | | PREVENTER(S). | | | | | | ORIGINAL COMMENT #13. SECOND REQUEST: PROVIDE NOTE | | | REQUIRING INSULATION OF HOT WATER PER FBC EC C404.4. | | | REFER TO 20032 PALM BEACH INTERNATIONAL SC SPECS | | | SECTION 22-07-00 FOR INSULATION SPECIFICATIONS | | | (PROVIDED IN SUPPORTING DOCUMENTS) | | | PLEASE NOTE, I FOUND A NOTE ON P1.03, MEDICAL GAS | | | GENERAL NOTE REFERENCING SPECIFICATIONS, BUT NOTHING ON | | | PLUMBING PLANS REGARDING THE REQUIREMENT FOR HOT WATER | | | INSULATION. | | | | | | ORIGINAL COMMENT #14. SECOND REQUEST: PROVIDE NOTE: | | | "REFER TO 20032 PALM BEACH INTERNATIONAL SC SPECS | | | DIVISION 22-PLUMBING FOR PLUMBING SPECIFICATIONS" | | | (PROVIDED IN SUPPORTING DOCUMENTS) | | | PLEASE NOTE, I FOUND A NOTE ON P1.03, MEDICAL GAS | | | GENERAL NOTE REFERENCING SPECIFICATIONS, BUT NOTHING ON | | | PLUMBING PLANS REGARDING "REFER TO 20032 PALM BEACH | | | INTERNATIONAL SC SPECS DIVISION 22-PLUMBING FOR | | | PLUMBING SPECIFICATIONS" | | | | | | ORIGINAL COMMENT #15. PARTIALLY COMPLIED: PER WPB FBC | | | 107.2.1, SHOW (PLAN VIEW AND RISER DIAGRAM) HOW | | | DISPOSAL OF WASTEWATER FROM THE MEDICAL GAS VACUUM PUMP | | | RECEIVER TANK ON THE FIRST FLOOR WILL BE ACHIEVED; | | | PROVIDE DETAIL. COMPLY WITH FBC PL CHAPTERS 7,8 AND 9. | | | IF CONCRETE SLAB IS TO BE CUT AND REMOVED THEN PROVIDE | | | A SLAB REPAIR DETAIL ON THE PLANS. SHOW THE WIDTH OF | | | THE REPAIR, THE MINIMUM THICKNESS AND PSI OF THE | | | CONCRETE TO BE REPLACED. SHOW SIZE, LENGTH, SPACING (ON | | | CENTER), MINIMUM EMBEDMENT AND ANCHORING/ADHESIVE | | | MATERIAL FOR DOWELS. THE REPAIR SHALL ALSO INCLUDE | | | TERMITE TREATMENT OF THE SOIL AS WELL AS THE REQUIRED | | | VAPOR BARRIER OVER WELL COMPACTED SOIL. A COPY OF THE | | | TERMITE CERTIFICATE SHALL BE ONSITE FOR FINAL | | | INSPECTION. PROVIDE SANITARY AND WATER RISER DIAGRAMS. | | | A.SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE SIZED | | | SANITARY AND WATER RISER DIAGRAMS. SHOW REQUIRED TRAPS, | | | VALVES, ETC. | | | B.SECOND REQUEST: PER WPB FBC 107.2.1, IT SEEMS | | | APPARENT THAT CONCRETE SLAB IS TO BE CUT AND REMOVED; | | | PROVIDE A SLAB REPAIR DETAIL ON THE PLANS. SHOW THE | | | WIDTH OF THE REPAIR, THE MINIMUM THICKNESS AND PSI OF | | | THE CONCRETE TO BE REPLACED. SHOW SIZE, LENGTH, SPACING | | | (ON CENTER), MINIMUM EMBEDMENT AND ANCHORING/ADHESIVE | | | MATERIAL FOR DOWELS. THE REPAIR SHALL ALSO INCLUDE | | | TERMITE TREATMENT OF THE SOIL AS WELL AS THE REQUIRED | | | VAPOR BARRIER OVER WELL COMPACTED SOIL. A COPY OF THE | | | TERMITE CERTIFICATE SHALL BE ONSITE FOR FINAL | | | INSPECTION. | | | | | | ORIGINAL COMMENT #16. COMPLIED | | | | | | ORIGINAL COMMENT #17. PER WPB FBC 107.2.1, PROVIDE | | | MATERIAL SPECIFICATION FOR CLEAR WASTEWATER AND FOR THE | | | COMPRESSED AIR SYSTEM. PARTIALLY COMPLIED; REQUEST FOR | | | WASTEWATER IS COMPLIANT. RESPONSE THAT THERE IS NO | | | COMPRESSED AIR OTHER THAN MEDICAL GAS DOES NOT | | | CORRESPOND WITH THE SUBMITTED PLUMBING PLANS. P2.00 | | | WATER RISER DIAGRAM AND P1.03 BOTH SHOW COMPRESSED AIR | | | PIPING. P1.03 NOTES 1, 4, 13, 14, 15, 16, 17 AND 18 | | | ADDRESSES THE COMPRESSED AIR AS WELL AND NOTE 15 | | | REFERENCES AN OWNER SUPPLIED AIR COMPRESSOR. PER WPB | | | FBC 107.2.1, CLARIFY. | | | | | | | | | END OF COMMENTS. | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | ALL PLANS TO BE SIGNED AND SEALED/DIGITALLY SIGNED AND | | | SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. | | | | | | | | | JERALD SMITH | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | EMAIL [email protected] | | | PHONE 561-246-0882 MOBILE | | | | | | 20090500 5325 GREENWOOD AVE |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2020-10-12 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2020-10-06 |
Time |
15:55 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2020-10-01 |
Time |
15:25 |
Sent To |
|
|
| Notes |
| 2020-10-06 15:55:14 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL | | | MANUAL REVISED 2017 | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION | | | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH | | | EDITION | | | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION | | | NFPA 99 = HEALTH CARE FACILITIES CODE | | | FAC= FLORIDA ADMINISTRATIVE CODE | | | FS = FLORIDA STATUTES | | | | | | | | | 1ST REVIEW | | | PLUMBING COMMENTS: DENIED | | | A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS | | | REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW | | | PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL | | | PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST | | | BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW | | | APPROVAL. | | | | | | 1.IS THERE A STORM PIPING SYSTEM IN THE BUILDING OR IS | | | THE BUILDING BEING DRAINED BY SCUPPERS AND A GUTTER | | | SYSTEM. PER WPB FBC 107.2.1, INDICATE ON THE ROOF PLAN | | | HOW THE REQUIREMENTS OF FBC PL CHAPTER 11 ARE BEING | | | MET. SHOW EXISTING ROOF DRAINS, OVERFLOW DRAINS AND/OR | | | EXISTING GUTTERS. IF THERE IS AN EXISTING STORM PIPING | | | SYSTEM, THEN PROVIDE FOR REFERENCE A COPY OF RECORD | | | DRAWINGS FOR THE INSTALLATION. | | | | | | 2.HORIZONTAL SANITARY DRAINAGE PIPING IS SUSPENDED IN | | | THE CEILING OF THE SECOND FLOOR. PER WPB FBC 107.2.1, | | | PROVIDE SECOND FLOOR PLAN SHOWING ALL RATED WALLS THAT | | | SAID PIPING WILL PENETRATE. | | | | | | 3.PER WPB FBC 107.2.1, PROVIDE FIXTURE SCHEDULE SHOWING | | | MINIMUM REQUIRED PLUMBING FIXTURES AND QUANTITIES AND | | | ACTUAL TO SHOW COMPLIANCE WITH FBC PL 403.1 AND TABLE | | | 403.1. | | | | | | 4.RE: PLAN G4.01, ADA STANDARDS; IT IS NOTED THAT THIS | | | SHEET IS PROVIDED FOR GUIDANCE ONLY AS STATED ON THE | | | PLAN. PLEASE NOTE THAT FIGURE 10; TYPICAL TOILET | | | LAYOUTS, DOES NOT APPLY TO ANY OF THE CONFIGURATION IN | | | THE CONSTRUCTION DOCUMENTS. ACCESSIBILITY REQUIREMENTS | | | SHALL COMPLY WITH 2017 FLORIDA BUILDING CODE: | | | ACCESSIBILITY AS STATED ON PLAN SHEET G.001. PER WPB | | | FBC 107.2.1 AND FBC PL 404.1, PROVIDE FLOOR PLAN | | | DETAILS AND ELEVATION DETAILS OF ACCESSIBLE | | | TOILET/BATHING ROOMS, SHOWERS, DRINKING FOUNTAINS, AND | | | SINKS (SUBMITTED PLAN SHEETS A8.01 AND A8.51 PROVIDE | | | ADEQUATE ELEVATIONS FOR SINKS IN CASEWORK) AND SHOWING | | | COMPLIANCE WITH FBC ACC CHAPTERS 2, 3 AND 6. PLAN SHEET | | | A2.01 PROVIDES ENLARGED PLAN VIEWS OF TOILET/BATHING | | | ROOMS BUT SIZED CLEAR FLOOR SPACES ARE NOT EASILY | | | IDENTIFIED, TURNING SPACES ARE NOT SHOWN AND ELEVATIONS | | | OF THESE ROOMS SHOWING THE ACCESSIBILITY REQUIREMENTS | | | ARE NON-EXISTENT. LOCKER ROOM SHOWERS SHALL COMPLY WITH | | | FBC ACC 608.2.1, 608.3.1 AND 608.5.1. GRAB BARS SHALL | | | BE INSTALLED IN A HORIZONTAL POSITION, 33 INCHES | | | MINIMUM AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR | | | MEASURED TO THE TOP OF THE GRIPPING SURFACE, NOT | | | CENTERLINE PER FBC ACC 609.4. | | | | | | 5.PROVIDE ON THE ARCHITECTURAL OR LIFE SAFETY THIRD | | | FLOOR PLAN ALL FORWARD AND/OR PARALLEL APPROACH CLEAR | | | FLOOR SPACES FOR ACCESSIBLE SINKS IN CASEWORK AND THE | | | DRINKING FOUNTAIN(S). | | | | | | 6.PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE SIZED | | | DOMESTIC WATER, SANITARY, COMPRESSED AIR AND CLEAR | | | WASTE WATER RISER DIAGRAMS. | | | A.WATER RISER DIAGRAM SHALL SHOW ALL VALVES, BACKFLOW | | | DEVICES, IN-LINE EQUIPMENT (I.E. RECIRCULATING PUMP, | | | THERMAL MIXING VALVE), WATER HEATER, POINTS OF | | | CONNECTION TO FIXTURES/EQUIPMENT AND OWNER SUPPLIED | | | EQUIPMENT AND TO EXISTING SOURCE OF COLD WATER. | | | B.SANITARY RISER DIAGRAM SHALL SHOW ALL TRAPS, FLOOR | | | DRAINS, HUB DRAINS, TRAP PRIMER CONNECTIONS, CLEANOUTS, | | | VENTS, POINTS OF CONNECTION TO FIXTURES/EQUIPMENT AND | | | OWNER SUPPLIED EQUIPMENT AND TO EXISTING SANITARY | | | RISER. IF AN EQUIPMENT ITEM SUCH AS AN ICE MACHINE | | | REQUIRES A DRAIN, THEN A WASTE RECEPTACLE AND INDIRECT | | | WASTE AND AIR GAP SHALL BE PROVIDED TO COMPLY WITH THE | | | PROVISIONS OF FBC PL CHAPTER 8. | | | C.COMPRESSED AIR TO SHOW PIPE, VALVES, REGULATORS, | | | FILTERS AND FITTINGS, SOURCE COMPRESSOR AND POINT OF | | | CONNECTION TO EQUIPMENT BEING SERVICED. | | | D.CLEAR WASTEWATER RISER DIAGRAM SHALL SHOW ALL | | | EQUIPMENT POINTS OF CONNECTION, TRAPS, VENTS AND POINT | | | OF DISPOSAL. | | | | | | 7. PER WPB FBC 107.2.1, PROVIDE DETAIL(S) FOR CLEAR | | | WASTEWATER EQUIPMENT CONNECTIONS AND POINT OF DISPOSAL. | | | REGARDING THE A/C CONDENSATE DISCHARGING TO THE | | | JANITOR?S SINK; PER NFPA 99-15 SECTION 8.3.11.4, EXCESS | | | CLEAR WASTEWATER SHALL BE DISCHARGED TO A STORM SEWER | | | OR RECHARGED INTO THE WATER TABLE AS PERMITTED BY | | | APPLICABLE PLUMBING CODES. DEPENDING ON FUTURE | | | EQUIPMENT SUBMITTALS (I.E. STERILIZERS, ICE MACHINES, | | | ETC.) THIS MAY APPLY TO OTHER EQUIPMENT DRAINS AS WELL | | | AS THE AIR HANDLING UNIT CONDENSATE DRAINS. | | | ADDITIONALLY, WPB UTILITIES DEPARTMENT PROHIBITS | | | DISCHARGE OF CONDENSATE WASTE TO THE CITY SEWERS. PER | | | WPB FBC 107.2.1, PROVIDE POINT OF DISPOSAL OF THE CLEAR | | | WASTEWATER EITHER TO STORM OR GROUND. PROVIDE ROUTING | | | AND DETAIL FOR POINT OF DISPOSAL. | | | | | | 8.PER WPB FBC 107.2.1, PROVIDE A TRAP PRIMER DETAIL. | | | | | | 9.PER WPB FBC 107.2.1, PROVIDE A FULL SCHEDULE OF OWNER | | | PROVIDED EQUIPMENT. INDICATE ON THE SCHEDULE ALL | | | UTILITY SERVICE CONNECTION REQUIREMENTS INCLUDING BUT | | | NOT LIMITED TO WATER AND WASTE. PROVIDE MANUFACTURER?S | | | SPECIFICATIONS/INSTALLATION MANUAL FOR ALL OWNER | | | SUPPLIED EQUIPMENT. SAID DOCUMENTS MAY BE SUBMITTED AS | | | A DEFERRED SUBMITTAL IN ACCORDANCE WITH WPB FBC 107.2.1 | | | AND 107.3.4.1. SEE WPB FBC 107.3.4.2 DEFERRED | | | SUBMITTALS; FOR THE PURPOSES OF THIS SECTION, DEFERRED | | | SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF THE DESIGN | | | THAT ARE NOT SUBMITTED AT THE TIME OF THE APPLICATION | | | AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL | | | WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL | | | ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE BUILDING | | | OFFICIAL. THE REGISTERED DESIGN PROFESSIONAL IN | | | RESPONSIBLE CHARGE SHALL LIST THE DEFERRED SUBMITTALS | | | ON THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE | | | BUILDING OFFICIAL. THIS MAY BE DONE BY NOTING SUCH IN | | | THE RESPONSE LETTER TO THIS REVIEW. | | | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE | | | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN | | | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD | | | THEM TO THE BUILDING OFFICIAL WITH A NOTATION | | | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE | | | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO | | | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL | | | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED | | | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING | | | OFFICIAL. | | | | | | 10.RE: PLAN F1.1, ALL TOILET ROOMS, ROOMS 3032, 3041, | | | 3042 AND 3047 (JANITOR SERVICE SINKS AND CLINICAL | | | SERVICE SINK); WALLS AND PARTITIONS WITHIN 2 FEET (610 | | | MM) OF SERVICE SINKS, URINALS AND WATER CLOSETS SHALL | | | HAVE A SMOOTH, HARD, NONABSORBENT SURFACE, TO A HEIGHT | | | OF NOT LESS THAN 4 FEET (1219 MM) ABOVE THE FLOOR, AND | | | EXCEPT FOR STRUCTURAL ELEMENTS, THE MATERIALS USED IN | | | SUCH WALLS SHALL BE OF A TYPE THAT IS NOT ADVERSELY | | | AFFECTED BY MOISTURE PER FBC 1210.2.2. EPOXY AND PAINT | | | FINISHES DO NOT COMPLY WITH THE REQUIREMENTS OF THIS | | | SECTION. | | | | | | 11.RE: P0.01/ DETAIL H3, WATER HEATER SCHEMATIC; | | | A.REGARDING THE GALVANIZED NIPPLE, PER FBC PL 605.24.1, | | | JOINTS BETWEEN COPPER OR COPPER-ALLOY TUBING AND | | | GALVANIZED STEEL PIPE SHALL BE MADE WITH A BRASS | | | FITTING OR DIELECTRIC FITTING OR A DIELECTRIC UNION | | | CONFORMING TO ASSE 1079. THE COPPER TUBING SHALL BE | | | SOLDERED TO THE FITTING IN AN APPROVED MANNER, AND THE | | | FITTING SHALL BE SCREWED TO THE THREADED PIPE. | | | B.NOTE PERTAINING TO ASME RELIEF VALVE DISCHARGE PIPE | | | SHALL HAVE THE WORDS THROUGH AN AIR GAP ADDED AT THE | | | END OF THE SENTENCE | | | C.PER WPB FBC 107.2.1, SHOW TEMPERATURE OF HOT WATER | | | FEED FROM WATER HEATER AS 140 DEGREES F AND SHOW | | | DESIGNATED BRANCH TO MIXING VALVE (DETAIL H10). | | | D.PER FBC PL 504.7, PROVIDE A PAN FOR THE WATER HEATER. | | | COMPLY WITH FBC PL 504.7, 504.7.1 AND 504.7.2. PROVIDE | | | A HOUSEKEEPING PAD IF REQUIRED TO PROVIDE AMPLE | | | ELEVATION FOR DRAIN DISCHARGE TO FLOOR DRAIN. | | | E. PER WPB FBC 107.2.1, PROVIDE NOTE STATING | | | "WATER-HEATING EQUIPMENT NOT SUPPLIED WITH INTEGRAL | | | HEAT TRAPS AND SERVING NONCIRCULATING SYSTEMS SHALL BE | | | PROVIDED WITH HEAT TRAPS ON THE SUPPLY AND DISCHARGE | | | PIPING ASSOCIATED WITH THE EQUIPMENT" TO SHOW | | | COMPLIANCE WITH FBC EC C404.3. | | | | | | 12.RE: P0.01 PLUMBING FIXTURE SCHEDULE; P-7 RECESSED | | | BOX. WHAT KIND OF EQUIPMENT IS BEING SERVICED? A COFFEE | | | MAKER OR ICE MACHINE REQUIRES A BACKFLOW PREVENTION | | | DEVICE TO COMPLY WITH THE REQUIREMENTS OF FBC PL 608 | | | AND IN INSTANCES WHERE QUICK CLOSING VALVES ARE | | | UTILIZED, A WATER HAMMER ARRESTOR CONFORMING TO ASSE | | | 1010 SHALL BE INSTALLED. PER WPB FBC 107.2.1, ANY | | | REQUIRED BACKFLOW DEVICE AND/OR WATER HAMMER ARRESTOR | | | SHALL BE SPECIFIED AND SCHEDULED. | | | | | | 13. PROVIDE NOTE REQUIRING INSULATION OF HOT WATER PER | | | FBC EC C404.4. REFER TO 20032 PALM BEACH INTERNATIONAL | | | SC SPECS SECTION 22-07-00 FOR INSULATION SPECIFICATIONS | | | (PROVIDED IN SUPPORTING DOCUMENTS) | | | | | | 14. PROVIDE NOTE: "REFER TO 20032 PALM BEACH | | | INTERNATIONAL SC SPECS DIVISION 22-PLUMBING FOR | | | PLUMBING SPECIFICATIONS" (PROVIDED IN SUPPORTING | | | DOCUMENTS) | | | | | | 15.PER WPB FBC 107.2.1, SHOW (PLAN VIEW AND RISER | | | DIAGRAM) HOW DISPOSAL OF WASTEWATER FROM THE MEDICAL | | | GAS VACUUM PUMP RECEIVER TANK ON THE FIRST FLOOR WILL | | | BE ACHIEVED; PROVIDE DETAIL. COMPLY WITH FBC PL | | | CHAPTERS 7,8 AND 9. IF CONCRETE SLAB IS TO BE CUT AND | | | REMOVED THEN PROVIDE A SLAB REPAIR DETAIL ON THE PLANS. | | | SHOW THE WIDTH OF THE REPAIR, THE MINIMUM THICKNESS AND | | | PSI OF THE CONCRETE TO BE REPLACED. SHOW SIZE, LENGTH, | | | SPACING (ON CENTER), MINIMUM EMBEDMENT AND | | | ANCHORING/ADHESIVE MATERIAL FOR DOWELS. THE REPAIR | | | SHALL ALSO INCLUDE TERMITE TREATMENT OF THE SOIL AS | | | WELL AS THE REQUIRED VAPOR BARRIER OVER WELL COMPACTED | | | SOIL. A COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE | | | FOR FINAL INSPECTION. | | | | | | 16. REFER TO 20032 PALM BEACH INTERNATIONAL SC SPECS | | | DIVISION 22-PLUMBING SECTION 22-11-16 (B) ALLOWS WATER | | | PIPE ABOVE GRADE TO BE ASTM A53 GALVANIZED PIPE WITH | | | GROOVED COUPLINGS OR COPPER PRESS FITTINGS BY VIEGA. A) | | | IS IT YOUR INTENT TO ALLOW GALVANIZED PIPE AND FITTINGS | | | IN THE POTABLE WATER SYSTEM? B) PLEASE CLARIFY THE | | | OPTION FOR COPPER PRESS FITTINGS IN A GALVANIZED | | | SYSTEM. | | | | | | 17.PER WPB FBC 107.2.1, PROVIDE MATERIAL SPECIFICATION | | | FOR CLEAR WASTEWATER AND FOR THE COMPRESSED AIR SYSTEM. | | | | | | | | | | | | END OF COMMENTS. | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | ALL PLANS TO BE SIGNED AND SEALED/DIGITALLY SIGNED AND | | | SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. | | | | | | | | | JERALD SMITH | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | EMAIL [email protected] | | | PHONE 561-246-0882 MOBILE | | | | | | 20090500 5325 GREENWOOD AVE | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2020-12-21 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-12-21 |
Time |
08:34 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2020-12-21 |
Time |
08:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2020-11-16 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-11-16 |
Time |
08:49 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2020-11-16 |
Time |
08:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2020-10-13 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-10-13 |
Time |
06:47 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-10-13 |
Time |
06:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2020-10-01 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2020-10-01 |
Time |
|
Rev Time |
|
| Received By |
llouie |
Date |
2020-10-01 |
Time |
|
Sent To |
|
|
| Notes |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |