Plan Review Details - Permit 20090500
Plan Review Stops For Permit 20090500
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2020-12-07 Cont ID  
Sent By cpuell Date 2020-12-07 Time 16:48 Rev Time 0.00
Received By cpuell Date 2020-12-07 Time 16:48 Sent To  
Notes
2020-12-07 16:49:03ADDRESS CHANGED TO REFLECT CORRECT SUITE 5325 GREENWOOD
 AVE # 301

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2020-09-28 Cont ID  
Sent By cpuell Date 2020-09-28 Time 08:32 Rev Time 0.00
Received By cpuell Date 2020-09-28 Time 08:32 Sent To  
Notes
2020-09-28 08:33:20PLEASE REACH OUT TO [email protected] TO DISCUSS SUITE
 ADDRESS

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 4 Status P Date 2021-01-13 Cont ID  
Sent By jwitmer Date 2021-01-13 Time 10:10 Rev Time 0.00
Received By jwitmer Date 2021-01-13 Time 10:01 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status F Date 2021-01-05 Cont ID  
Sent By jwitmer Date 2021-01-05 Time 10:23 Rev Time 0.00
Received By jwitmer Date 2021-01-05 Time 09:46 Sent To  
Notes
2021-01-05 10:22:03COMMERCIAL ASBESTOS
  
 TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING: THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2020-11-17 Cont ID  
Sent By jwitmer Date 2020-11-17 Time 10:28 Rev Time 0.00
Received By jwitmer Date 2020-11-17 Time 08:46 Sent To  
Notes
2020-11-17 10:24:41TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  
  
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-10-05 Cont ID  
Sent By jwitmer Date 2020-10-05 Time 12:34 Rev Time 0.00
Received By jwitmer Date 2020-10-05 Time 08:02 Sent To  
Notes
2020-10-05 12:34:27COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2021-01-13 Cont ID  
Sent By jwitmer Date 2021-01-13 Time 10:13 Rev Time 0.00
Received By jwitmer Date 2021-01-13 Time 10:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-01-05 Cont ID  
Sent By jwitmer Date 2021-01-05 Time 10:26 Rev Time 0.00
Received By jwitmer Date 2021-01-05 Time 09:46 Sent To  
Notes
2021-01-05 10:19:42WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20090500
 ADD: 5325 GREENWOOD AVE. SUITE: 300
 CONT: BLACK DIAMOND GENERAL CONTRACTOR
 TEL: 561-746-3452
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: WED JAN. 05TH/2021
 ACTION:PASSED / BUILDING PROVISO
  
 1) BUILDING PROVISO/ FUTURE REVISION REQUIRED. THE 1ST
 FLOOR LIFE SAFETY PLAN SHOWS NEW MED GAS, NEW VACUUM
 PUMP EQUIPMENT, BUT NO NEW WORK ON THE 2ND FLOOR, HOW
 ARE THESE LINES GOING TO THE NEW AMBULATORY SURGICAL
 CENTER ON THE 3RD FLOOR. 107/2/1/2 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 2) NOTICE ONLY. NO ACTION NEEDED AT THIS TIME. THE
 INSTALLATION OF A GENERATOR WILL BE UNDER A SEPARATE
 PERMIT, NOT INCLUDED IN THIS REVIEW. SEPARATE PERMIT,
 REVIEW AND ASSOCIATED FEES REQUIRED FOR NEW GENERATOR,
 AND OR FENCING.
  
 3) BUILDING PROVISO: FOR WELDED & BOLTED CONNECTIONS.
 THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON
 THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL
 BE REQUIRED. REPORTS SUBMITTED TO BUILDING INSPECTOR AT
 TIME OF FRAMING INSPECTION.
 2017 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT
 561-805-6666.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-11-17 Cont ID  
Sent By jwitmer Date 2020-11-17 Time 10:28 Rev Time 0.00
Received By jwitmer Date 2020-11-17 Time 08:45 Sent To  
Notes
2020-11-17 10:23:31WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20090500
 ADD: 5325 GREENWOOD AVE. SUITE: 300
 CONT: DPR CONSTRUCTION
 TEL: 858-210-9600
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. 17TH/2020
 ACTION: DENIED
  
 1A-B) COMPLIED
  
 1C) BUILDING PROVISO/ FUTURE REVISION REQUIRED. THE 1ST
 FLOOR LIFE SAFETY PLAN SHOWS NEW MED GAS, NEW VACUUM
 PUMP EQUIPMENT, BUT NO NEW WORK ON THE 2ND FLOOR, HOW
 ARE THESE LINES GOING TO THE NEW AMBULATORY SURGICAL
 CENTER ON THE 3RD FLOOR. 107/2/1/2 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 1D) NOTICE ONLY. NO ACTION NEEDED AT THIS TIME. THE
 INSTALLATION OF A GENERATOR WILL BE UNDER A SEPARATE
 PERMIT, NOT INCLUDED IN THIS REVIEW. SEPARATE PERMIT,
 REVIEW AND ASSOCIATED FEES REQUIRED FOR NEW GENERATOR,
 AND OR FENCING.
  
 2) COMPLIED.
  
 3) COMPLIED.
  
 4A)SEMI- COMPLIED. SHEET A-153 DOES INDICATE RATED
 WALLS AND IDENTIFIES DOOR. SHEET A-701 DOES SHOW THE
 DOOR SCHEDULE, IT APPEARS THERE ARE 2 DOORWAYS IN 1
 HOUR RATED WALLS WITH NO RATING, DOOR 3023 AND 3033-B.
 2017 FBC-B TABLE 716,5,
  
 4B) COMPLIED.
  
 5) COMPLID.
  
 6) COMPLIED AND OR DEFERRED SUBMITTALS.
  
 7A) COMPLIED.
  
 7B)BUILDING PROVISO: FOR WELDED & BOLTED CONNECTIONS.
 THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON
 THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL
 BE REQUIRED. REPORTS SUBMITTED TO BUILDING INSPECTOR AT
 TIME OF FRAMING INSPECTION.
 2017 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT
 561-805-6666.
  
 8) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-10-05 Cont ID  
Sent By jwitmer Date 2020-10-05 Time 12:06 Rev Time 0.00
Received By jwitmer Date 2020-10-05 Time 08:02 Sent To  
Notes
2020-10-05 12:36:44WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20090500
 ADD: 5325 GREENWOOD AVE. SUITE: 300
 CONT: DPR CONSTRUCTION
 TEL: 858-210-9600
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. OCT. 05TH/2020
 ACTION: DENIED
  
 1A) SHEET G-001 CODE ANALYSIS SHEET UNDER THE HEADING
 VIII THE TOTAL OCCUPANT LOAD COUNT IS 216 NOT 226, IT
 APPEARS TO BE A TYPO. 107.2.1.2 ADDITIONAL INFORMATION
 IS REQUIRED.
  
 1B) THE PERMIT APPLICATION AS WELL AS THE CODE ANALYSIS
 ONLY LIST WORK TO BE COMPLETED UNDER THIS PERMIT AS
 BEING ON THE 3RD FLOOR. SHEETS D101 THE 1ST FLOOR DEMO
 AND SHEET LS101 THE 1ST FLOOR LIFE SAFETY SHEET. PLEASE
 ADD THE 1ST FLOOR TO THE SCOPE OF WORK ON THE PERMIT
 APPLICATION AS WELL AS THE CODE ANALYSIS SHEET.
  
 1C) THE 1ST FLOOR LIFE SAFETY PLAN SHOWS NEW MED GAS,
 NEW VACUUM PUMP EQUIPMENT, BUT NO NEW WORK ON THE 2ND
 FLOOR, HOW ARE THESE LINES GOING TO THE NEW AMBULATORY
 SURGICAL CENTER ON THE 3RD FLOOR. 107/2/1/2 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 1D) THE INSTALLATION OF A GENERATOR WILL BE UNDER A
 SEPARATE PERMIT, NOT INCLUDED IN THIS REVIEW. SEPARATE
 PERMIT, REVIEW AND ASSOCIATED FEES REQUIRED FOR NEW
 GENERATOR, AND OR FENCING.
  
 2) SHEET G401-ADA STANDARDS.
 2A) PLEASE NOTE WE USE THE 2017 FBC-ACCESSIBILITY CODE
 DEEMED THE EQUIVALENT TO THE ADA STANDARDS AND BLESSED
 BY THE DEPARTMENT OF JUSTICE. IN ALL THE WATER CLOSET
 DETAILS THE GRAB BARS ARE DIMENSIONED FROM THE
 CENTERLINE. IN THE 2017 FBC-ACCESS. CODE SECTION 609.4
 POSITION OF GRAB BARS. GRAB BARS SHALL BE INSTALLED IN
 A HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE, NOT CENTERLINE.
  
 2B) THERE IS ALSO A DEPICTION OF AN ELECTRIC DRINKING
 FOUNTAIN (SINGLE). 2017 FBC-ACCESSIBILITY CODE. 211.2
 MINIMUM NUMBER. NO FEWER THAN TWO DRINKING FOUNTAINS
 SHALL BE PROVIDED. ONE DRINKING FOUNTAIN SHALL COMPLY
 WITH 602.1 THROUGH 602.6 AND ONE DRINKING FOUNTAIN
 SHALL COMPLY WITH 602.7.
  
 PROTRUDING OBJECTS 307.2 PROTRUSION LIMITS 307.2.
 OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES AND NOT
 MORE THAN 80 INCHES ABOVE THE FLOOR SHALL NOT PROTRUDE
 MORE THAN 4 INCHES HORIZONTALLY INTO THE CIRCULATION
 PATH.
  
 602.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE COMPLYING
 WITH 305, POSITIONED FOR A FORWARD APPROACH, AND KNEE
 AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
  
 2C) PLEASE ALSO TAKE NOTE TO THE SINGLE USER ACCESSIBLE
 RESTROOM LABELED FIG. 10. THE 2017 FBC-ACCESS. CODE
 603.2.3 DOOR SWING AND EXCEPTION 2. I BELIEVE THIS HOW
 YOU ARE STRIVING TO SHOW CODE COMPLIANCE. WHAT IS
 MISSING IS THE REQUIRED CLEAR FLOOR SPACE BEYOND THE
 ARC OF THE DOOR. IT IS USUALLY SHOWN AT A 45-DEGREE
 ANGLE TO THE ENTRY DOOR.
  
 3) SHEET LS 103 THE 3RD FLOOR HAS WHAT IS LABELED
 PRE-OP/ PACU WHERE THERE ARE 10 OUTPATIENT BEDS. AFTER
 SURGERY THESE BEDS ARE ALSO USED FOR THE PATIENT CARE/
 AND RECOVERY. THE PLANS LIST THIS AREA AS SMOKE
 COMPARTMENT # 1 HAS AN AREA OF 5,919 SQ. FT. WHAT I AM
 MISSING IS FOR AMBULATORY CARE FACILITIES WHERE THE
 POTENTIAL FOR FOUR OR MORE CARE RECIPIENTS ARE TO BE
 INCAPABLE OF SELF-PRESERVATION AT ANY TIME, WHETHER
 RENDERED INCAPABLE BY STAFF OR STAFF ACCEPTED
 RESPONSIBILITY FOR A CARE RECIPIENT ALREADY INCAPABLE,
 SHALL BE SEPARATED FROM ADJACENT SPACES, CORRIDORS OR
 TENANTS WITH FIRE PARTITIONS INSTALLED IN ACCORDANCE
 WITH SECTION 708.
  
 4A) 3RD FLOOR SHEETS LS103, THIRD FLOOR AREA PLAN
 LS103A NOR THE A-103 THE 3RD FLOOR DIMENSION PLAN HAVE
 DOOR IDENTIFICATION NUMBERS TO SEE SIZE AND DOOR
 RATINGS. 716.5 OF THE 2017 FBC-B.
  
 4B) PLEASE ALSO PROVIDE THE CORRIDOR WIDTHS IF
 POSSIBLE, ON THE DIMENSION PLAN A-103, 3RD FLOOR
 DIMENSION PLAN.
 2017 FBC-B TABLE 1020.2.
  
  
 5) SHEET A801 STAFF LOUNGE 3033 SHOW AN ACCESSIBLE
 COUNTERTOP MICROWAVE WHEREAS THE DETAIL NOUR. 3037
 SHOWS THE MICROWAVE OUT OF THE REACH RANGES. PLEASE
 SHOW COMPLIANCE WITH THE 2017 FBC-ACCESS. CODE:
  
 308 REACH RANGES 308.2 FORWARD REACH. / 308.2.1
 UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH REACH.
 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2
 OBSTRUCTED HIGH REACH.
  
 309 OPERABLE PARTS 309.3 HEIGHT. OPERABLE PARTS SHALL
 BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES
 SPECIFIED IN 308. 309.4 OPERATION. OPERABLE PARTS SHALL
 BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT
 GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE
 REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS
 (22.2 N) MAXIMUM.
  
 6) SHEET S1 NOTES AND ROOF FRAMING PLAN:
 6A) WIND LOADS. THE PLAN STATES THE VULT IS 169 MPH AND
 THE WIND VASD IS 102 MPH. I BELIEVE THIS MAYBE A TYPE
 SINCE 170 VULT = 132 VASD.
  
 6B) THE GIVEN EXPOSURE CATEGORY IS LABELED AS AN
 EXPOSURE B. PLEASE NOTE TO THE NORTH THERE IS VACANT
 LAND AND THEN ROYAL PALM MEMORIAL GARDENS A CEMETERY.
 THE CITY ASSIGNS A SURFACE ROUGHNESS C. THIS CATEGORY
 INCLUDES FLAT OPEN COUNTRY, GRASSLANDS.2017 FBC-B
 1609.4.2.
  
 6C) THERE ARE NEW EXTERIOR DOOR OPENINGS AND NEW ROOF
 EQUIPMENT BEING INSTALLED, PLEASE PROVIDE THE
 COMPONENTS AND CLADDING PRESSURES FOR ROOF ZONES 1,2 &
 3 AS WELL AS WALL ZONES 4 & 5. FOR TRIBUTARY AREAS OF
 10 SQ. FT., 20 SQ. FT., 50 SQ. FT., & 100 SQ. FT. IN
 VASD SINCE ALL PRODUCT APPROVALS ARE IN VASD.
  
  
  
  
  
 6D) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES.
 (D) ROOFING PRODUCTS AND ASSEMBLIES, INCLUDING CURBS
 (G) IF PRE-ENGINEERED A/C STANDS ARE BEING INSTALLED
  
 6E) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF
 ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR
 BOTH INSULATION & THE BASE SHEET AS CALCULATED IN
 COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117.
 CALCULATION PREPARED, SIGNED AND SEALED BY A FLORIDA
 REGISTERED PROFESSIONAL ENGINEER OR REGISTERED
 ARCHITECT. 1609.6.4.4.1 COMPONENTS & CLADDING.
  
 6F) 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE,
 THE CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE
 AND DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS,
 VENTING, FASTENING REQUIREMENTS, FLASHING REQUIREMENTS
 AND WIND RESISTANCE RATING THAT ARE REQUIRED TO BE
 INSTALLED. PRODUCT EVALUATION AND INSTALLATION SHALL
 INDICATE COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR
 THE SPECIFIC SITE.
  
 6G) 2017 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING. FBC-B-1609.6.4.4.1 COMPONENTS
 AND CLADDING. WIND PRESSURE FOR EACH COMPONENT OR
 CLADDING ELEMENT IS TO BE DESIGNED FOR WIND PRESSURES
 COMPONENTS AND ATTACHMENTS.
  
 LATERAL FORCE-RESISTING SYSTEM. FOR ALL ROOF TOP
 EQUIPMENT, CURBS, FANS OR A/C STANDS, AND OR VENTS,
 DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL
 AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE.
  
 2017 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 6H) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 DELEGATED ENGINEERING. 61G15-30.003 ENGINEERING
 DOCUMENT CLASSIFICATION. FL 61G-15-30.006 (3) THE
 DELEGATED ENGINEER SHALL FORWARD THE DELEGATED
 ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR
 REVIEW.
  
 6I) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 7A) THE STRUCTURAL SHEETS INDICATE NEW BAR JOIST ARE TO
 BE INSTALLED. THE PLANS ARE SILENT AS TO HOW THEY WILL
 BE INSTALLED. WILL THERE BE AREAS OF ROOFING AND B-DECK
 BE REMOVED? 107.2.1.2. ADDITIONAL INFORMATION IS
 REQUIRED.
  
 7B) FOR WELDED & BOLTED CONNECTIONS. THE CONTRACTOR IS
 REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION FOR FIELD WIELDING, ON THE JOB-SITE
 WIELDING. THIRD PARTY CERTIFICATION WILL BE REQUIRED.
 REPORTS SUBMITTED TO BUILDING INSPECTOR AT TIME OF
 FRAMING INSPECTION.
 2017 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT
 561-805-6666.
  
 8) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-10-08 Cont ID  
Sent By jleahy Date 2020-10-08 Time 15:35 Rev Time 0.00
Received By jleahy Date 2020-10-08 Time 10:39 Sent To  
Notes
***NONE***

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2020-10-08 Cont ID  
Sent By jleahy Date 2020-10-08 Time 15:35 Rev Time 0.00
Received By jleahy Date 2020-10-08 Time 15:35 Sent To  
Notes
2020-10-08 15:37:35TELEPHONE, DATA, SECURITY, NURSE CALL JLEAHY

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-12-21 Cont ID  
Sent By pleduc Date 2020-12-21 Time   Rev Time 0.00
Received By pleduc Date 2020-12-21 Time 12:35 Sent To  
Notes
2020-12-21 12:42:25THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND/OR
 FIRE SPRINKLER SYSTEMS BY APPLICABLE LICENSED
 CONTRACTORS FOR CODE COVERAGE COMPLIANCE.
  
  
 2) ANY AND ALL WORK ON THE FIRE ALARM AND/OR FIRE
 SPRINKLER SYSTEMS, INCLUDING DEMO, SHALL BE DONE UNDER
 SEPARATE PERMITS AND SHOP DRAWINGS.
  
  
 3) THE EXISTING LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR
 FIRE SPRINKLER SHALL BE MAINTAINED AND REMAIN ACTIVE
 THROUGHOUT THE CONSTRUCTION PERIOD, INCLUDING DEMO.
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE DEPARTMENT
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-09-29 Cont ID  
Sent By pleduc Date 2020-09-29 Time   Rev Time 0.00
Received By pleduc Date 2020-09-29 Time 13:09 Sent To  
Notes
2020-09-29 13:09:39THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND/OR
 FIRE SPRINKLER SYSTEMS BY APPLICABLE LICENSED
 CONTRACTORS FOR CODE COVERAGE COMPLIANCE.
  
  
 2) ANY AND ALL WORK ON THE FIRE ALARM AND/OR FIRE
 SPRINKLER SYSTEMS, INCLUDING DEMO, SHALL BE DONE UNDER
 SEPARATE PERMITS AND SHOP DRAWINGS.
  
  
 3) THE EXISTING LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR
 FIRE SPRINKLER SHALL BE MAINTAINED AND REMAIN ACTIVE
 THROUGHOUT THE CONSTRUCTION PERIOD, INCLUDING DEMO.
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE DEPARTMENT
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2021-01-13 Time 10:14 Rev Time 0.00
Received By lmarchan Date 2021-01-08 Time 08:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-01-05 Cont ID  
Sent By jwitmer Date 2021-01-05 Time 10:27 Rev Time 0.00
Received By jwitmer Date 2020-12-18 Time 15:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-12-02 Cont ID  
Sent By jesmith Date 2020-12-02 Time 17:34 Rev Time 0.00
Received By jesmith Date 2020-12-02 Time 17:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-10-13 Cont ID  
Sent By shill Date 2020-10-13 Time 06:47 Rev Time 0.00
Received By shill Date 2020-09-25 Time 11:40 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2020-10-05 Cont ID  
Sent By jwitmer Date 2020-10-05 Time 12:34 Rev Time 0.00
Received By jwitmer Date 2020-10-05 Time 08:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2020-12-21 Cont ID  
Sent By medwards Date 2020-12-21 Time 08:16 Rev Time 0.00
Received By medwards Date 2020-12-21 Time 08:16 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-11-16 Cont ID  
Sent By medwards Date 2020-11-16 Time 08:40 Rev Time 0.00
Received By medwards Date 2020-11-16 Time 08:40 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-09-29 Cont ID  
Sent By medwards Date 2020-09-29 Time 16:20 Rev Time 0.00
Received By medwards Date 2020-09-29 Time 11:01 Sent To  
Notes
2020-09-29 16:21:391ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20090500
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SHOW THE VENTILATION FOR LOSS OF ELECTRICAL
 POWER MEETS SECTION 6.1.1 OF ASHRAE 170-2008
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop MEDGAS MEDICAL GAS
Rev No 3 Status P Date 2020-12-21 Cont ID  
Sent By lcrespo Date 2020-12-21 Time 15:46 Rev Time 0.00
Received By lcrespo Date 2020-12-21 Time 14:59 Sent To  
Notes
2020-12-21 15:47:2612/18/20 REVIEWED FOR CODE COMPLIANCE (MEDICAL/GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop MEDGAS MEDICAL GAS
Rev No 2 Status F Date 2020-12-02 Cont ID  
Sent By jesmith Date 2020-12-02 Time 17:30 Rev Time 0.00
Received By jesmith Date 2020-11-30 Time 10:21 Sent To  
Notes
2020-12-02 17:25:26CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 NFPA 99 = HEALTH CARE FACILITIES CODE
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20090500 5325 GREENWOOD AVE
  
 2ND REVIEW
 MEDICAL GAS COMMENTS: DENIED
  
 ORIGINAL COMMENT #1. COMPLIED
  
 ORIGINAL COMMENT #2. SECOND REQUEST: PER NFPA 99-15
 SECTION 5.1.3.1.8, PROVIDE NOTE REQUIRING SIGNAGE ON
 THE ENTRY DOOR TO THE ROOM CONTAINING THE MEDICAL GAS
 MANIFOLDS/CYLINDERS STATING
 "POSITIVE PRESSURE GASES
 NO SMOKING OR OPEN FLAME
 ROOM MAY HAVE INSUFFICIENT OXYGEN
 OPEN DOOR AND ALLOW ROOM TO VENTILATE BEFORE ENTERING"
 TO BE CLEAR, PROVIDE SAID NOTE MAKING THE STATEMENT ON
 THE PLAN.
  
 ORIGINAL COMMENT #3. SECOND REQUEST: PLAN SHEET A9.21;
 ELEVATION OF HEADWALL NOTES A, O AND V OUTLETS. LEGEND
 ONLY IDENTIFIES O AND V. PER WPB FBC 107.2, CLARIFY.
  
 ORIGINAL COMMENT #4. COMPLIED
  
 ORIGINAL COMMENT #5. COMPLIED; FURTHER ACTION REQUIRED.
 PER WPB FBC 107.2.1, THIS REFERENCED DEFERRED SUBMITTAL
 FOR MEDICAL GAS EQUIPMENT SHALL BE ADDED TO THE LIST OF
 DEFERRED SUBMITTALS NOTE IN G1.01; DEFERRED SUBMITTALS.
  
 ORIGINAL COMMENT #6. COMPLIED
  
 ORIGINAL COMMENT #7. COMPLIED
  
 ORIGINAL COMMENT #8. COMPLIED
  
 ORIGINAL COMMENT #9. COMPLIED
  
 ORIGINAL COMMENT #10. COMPLIED
  
 ORIGINAL COMMENT #11. COMPLIED:FURTHER ACTION REQUIRED.
 PER WPB FBC 107.2.1, PROVIDE PROVIDE NOTE ON PLAN
 SHOWING VACUUM SYSTEM IS MONITORED FOR OXYGEN CONTENT
 THAT IS ACQUIRED THROUGH THE WAGD TO COMPLY WITH NFPA
 99-15, SECTION 5.1.3.8.1.2(2) AND 5.1.3.8.3.1. SEE
 PROJECT SPECIFICATION 22-60-00, SECTION 3.1, SUB
 SECTION (S)
  
 ORIGINAL COMMENT #12. COMPLIED
  
 ORIGINAL COMMENT #13. COMPLIED: FURTHER ACTION
 REQUIRED. PER WPB FBC 107.2.1, PROVIDE PROVIDE NOTE ON
 PLAN TO REQUIRE DOCUMENTATION ON ALL PIPE, VALVES AND
 FITTINGS PER NFPA 99-15 SECTION 5.1.10.1.6. SEE PROJECT
 SPECIFICATION 22-60-00, SECTION 1.6, SUB SECTION (E)
  
 ORIGINAL COMMENT #14.COMPLIED: FURTHER ACTION REQUIRED.
 PER WPB FBC 107.2.1, PROVIDE PROVIDE NOTE ON PLAN TO
 REQUIRE BRAZING TECHNICIANS TO BE QUALIFIED AND
 CERTIFIED IN ACCORDANCE WITH NFPA 99-15 SECTION
 5.1.10.11.11. SEE PROJECT SPECIFICATION 22-60-00,
 SECTION 1.7, SUB SECTION (E)
  
 ORIGINAL COMMENT #15.COMPLIED
  
 ORIGINAL COMMENT #16. COMPLIED: FURTHER ACTION
 REQUIRED. PER WPB FBC 107.2.1, PROVIDE PROVIDE NOTE ON
 PLAN TO PROVIDE VALVE ID/SYSTEM IDENTIFICATION/COLOR
 CODING SPECIFICATION PER NFPA 99-15 SECTION 5.1.11
 THROUGH 5.1.11.4. COMPLIED; SEE PROJECT SPECIFICATION
 22-60-00, SECTION 3.1, SUB SECTION (T)
  
 ORIGINAL COMMENT #17.COMPLIED
  
 END OF COMMENTS.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE SIGNED AND SEALED/DIGITALLY SIGNED AND
 SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20090500 5325 GREENWOOD AVE
  

Review Stop MEDGAS MEDICAL GAS
Rev No 1 Status F Date 2020-10-12 Cont ID  
Sent By jesmith Date 2020-10-12 Time 18:33 Rev Time 0.00
Received By jesmith Date 2020-10-06 Time 16:28 Sent To  
Notes
2020-10-08 17:11:48CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 NFPA 99 = HEALTH CARE FACILITIES CODE
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
 MEDICAL GAS COMMENTS: DENIED
  
 1.NOTE O2, AIR (MEDICAL CA MANIFOLD AND CYLINDERS),
 VACUUM AND N2 ON PLANS. PROJECT SPECS SPECIFICATION
 22-60-00 SECTION 1.1 DOES NOT REFERENCE N2.
  
 2.PER NFPA 99-15 SECTION 5.1.3.1.8, PROVIDE NOTE
 REQUIRING SIGNAGE ON THE ENTRY DOOR TO THE ROOM
 CONTAINING THE MEDICAL GAS MANIFOLDS/CYLINDERS STATING
 ?POSITIVE PRESSURE GASES
 NO SMOKING OR OPEN FLAME
 ROOM MAY HAVE INSUFFICIENT OXYGEN
 OPEN DOOR AND ALLOW ROOM TO VENTILATE BEFORE ENTERING?
  
 3.PLAN SHEET A9.21; ELEVATION OF HEADWALL NOTES A, O
 AND V OUTLETS. LEGEND ONLY IDENTIFIES O AND V. PER WPB
 FBC 107.2, CLARIFY.
  
 4.PER WPB 107.2.1, PROVIDE SECOND FLOOR PLAN SHOWING
 MED GAS PIPING CONNECTING FIRST AND THIRD FLOORS.
  
 5.PROVIDE MANUFACTURER?S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR MEDICAL GAS EQUIPMENT
 AND COMPONENTS. AS THE ACTUAL EQUIPMENT MANUFACTURER
 (SEE 20032 PALM BEACH INTERNATIONAL SC SPECS DIVISION
 22-60-00 SUPPORTING DOCUMENT) MAY NOT HAVE BEEN
 SELECTED AT THIS TIME, SAID DOCUMENTS MAY BE SUBMITTED
 AS A DEFERRED SUBMITTAL IN ACCORDANCE WITH WPB FBC
 107.2.1 AND 107.3.4.1. SEE WPB FBC 107.3.4.2 DEFERRED
 SUBMITTALS; FOR THE PURPOSES OF THIS SECTION, DEFERRED
 SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF THE DESIGN
 THAT ARE NOT SUBMITTED AT THE TIME OF THE APPLICATION
 AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL
 WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL
 ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE BUILDING
 OFFICIAL. THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE SHALL LIST THE DEFERRED SUBMITTALS
 ON THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE
 BUILDING OFFICIAL. THIS MAY BE DONE BY NOTING SUCH IN
 THE RESPONSE LETTER TO THIS REVIEW.
  
 6.DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 7.PER WPB FBC 107.2.1, PROVIDE RISER DIAGRAM OF PIPING
 SYSTEMS FROM SOURCE TO OUTLETS, INCLUDE ALL IN-LINE
 COMPONENTS
  
 8.RE: 22-60-00, SECTION 2.7 (C) VACUUM PUMP RECEIVER IS
 PROVIDED WITH AUTOMATIC TANK DRAIN. PER NFPA 99-15
 SECTION 5.1.3.7.3(4), RECEIVER SHALL BE PROVIDED WITH A
 MANUAL DRAIN. THE AUTOMATIC TANK DRAIN MAY BE PROVIDED
 IN ADDITION TO THE MANUAL DRAIN.
  
 9.PER WPB FBC 107.2.1, PROVIDE LOCATION AND DETAIL
 TERMINATION OF GAS MANIFOLD RELIEF VENT INCLUDING
 ELEVATION AND ANCHORING DETAILS. SPECIFY MATERIAL AND
 JOINTS FOR VENT.
  
 10.PER WPB FBC 107.2.1, PROVIDE LOCATION AND DETAIL
 TERMINATION OF VACUUM PUMP EXHAUST VENT INCLUDING
 ELEVATION AND ANCHORING DETAILS. COMPLY WITH ALL
 REQUIREMENTS OF NFPA 99-15, SECTIONS 5.1.3.7.6.2
 THROUGH 5.1.3.7.6.5. SPECIFY MATERIAL AND JOINTS FOR
 VENT TO COMPLY WITH SECTION 5.1.3.7.6.6.
  
 11.PER WPB FBC 107.2.1, PROVIDE DETAILS SHOWING HOW
 VACUUM SYSTEM IS MONITORED FOR OXYGEN CONTENT THAT IS
 ACQUIRED THROUGH THE WAGD TO SHOW COMPLIANCE WITH NFPA
 99-15, SECTION 5.1.3.8.1.2(2) AND 5.1.3.8.3.1.
  
 12.RE: 22-60-00, SECTION 2.2 SUB SECTIONS
 (B) TUBE SHALL BE ASTM B819 ACR/OXY PER NFPA 99-15
 SECTION 5.1.10.1.4. TUBE COMPLYING WITH ASTM B88 AND
 B280 IS NOT ACCEPTABLE.
 (C) DELETE
 (D) PER NFPA 99-15 SECTION 5.1.10.2.1(1) MAY BE ASTM
 B88, B280 OR B819. IF NOT B819, COMPLY WITH SECTION
 5.1.10.2.2.1.
  
 13.REQUIRE DOCUMENTATION ON ALL PIPE, VALVES AND
 FITTINGS PER NFPA 99-15 SECTION 5.1.10.1.6
  
 14.REQUIRE BRAZING TECHNICIANS TO BE QUALIFIED AND
 CERTIFIED IN ACCORDANCE WITH NFPA 99-15 SECTION
 5.1.10.11.11
  
 15.RE: 22-60-00, SECTION 3.1 (D); NFPA 99-15 DOES NOT
 ALLOW FOR TUBE BENDING. SEE SECTION 5.1.10.4.1 GENERAL
 CONDITIONS. MAKE DIRECTIONAL CHANGES WITH APPROVED
 FITTINGS AND JOINTS.
  
 16.PROVIDE VALVE ID/SYSTEM IDENTIFICATION/COLOR CODING
 SPECIFICATION PER NFPA 99-15 SECTION 5.1.11 THROUGH
 5.1.11.4.
  
 17.PROVIDE NOTE ON PLANS TO REFER TO 20032 PALM BEACH
 INTERNATIONAL SC SPECS DIVISION 22-60-00 FOR WRITTEN
 MEDICAL GAS SPECIFICATIONS (PROVIDED IN SUPPORTING
 DOCUMENTS)
  
 END OF COMMENTS.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE SIGNED AND SEALED/DIGITALLY SIGNED AND
 SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20090500 5325 GREENWOOD AVE
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2020-12-21 Cont ID  
Sent By lcrespo Date 2020-12-21 Time 14:57 Rev Time 0.00
Received By lcrespo Date 2020-12-21 Time 14:57 Sent To  
Notes
2020-12-21 14:58:4912/21/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-12-02 Cont ID  
Sent By jesmith Date 2020-12-02 Time 15:26 Rev Time 0.00
Received By jesmith Date 2020-11-30 Time 10:21 Sent To  
Notes
2020-12-02 15:11:17CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 NFPA 99 = HEALTH CARE FACILITIES CODE
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 20090500 5325 GREENWOOD AVE
  
 2ND REVIEW
 PLUMBING COMMENTS: DENIED
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 ORIGINAL COMMENT #1. IS THERE A STORM PIPING SYSTEM IN
 THE BUILDING OR IS THE BUILDING BEING DRAINED BY
 SCUPPERS AND A GUTTER SYSTEM. PER WPB FBC 107.2.1,
 INDICATE ON THE ROOF PLAN HOW THE REQUIREMENTS OF FBC
 PL CHAPTER 11 ARE BEING MET. SHOW EXISTING ROOF DRAINS,
 OVERFLOW DRAINS AND/OR EXISTING GUTTERS. IF THERE IS AN
 EXISTING STORM PIPING SYSTEM, THEN PROVIDE FOR
 REFERENCE A COPY OF RECORD DRAWINGS FOR THE
 INSTALLATION.
 COMPLIED; PROVIDE A REFERENCE COPY OF RECORD DRAWINGS
 FOR SHELL BUILDING.
  
 ORIGINAL COMMENT #2. COMPLIED
  
 ORIGINAL COMMENT #3. COMPLIED
  
 ORIGINAL COMMENT #4. COMPLIED: RE: PLAN G4.01, ADA
 STANDARDS;
 NEW COMMENT: G4.01, ADA STANDARDS; TYP. ACCESSIBLE
 TOILET ELEVATIONS. SPACE BETWEEN SIDE WALL AND REAR
 HAND RAIL SHALL BE 6 INCHES MAXIMUM, NOT 9 INCHES.
  
 ORIGINAL COMMENT #5. COMPLIED
  
 ORIGINAL COMMENT #6. PER WPB FBC 107.2.1 AND
 107.3.5.1.3, PROVIDE SIZED DOMESTIC WATER, SANITARY,
 COMPRESSED AIR AND CLEAR WASTE WATER RISER DIAGRAMS.
 PARTIALLY COMPLIED; SEE BELOW
 A.WATER RISER DIAGRAM SHALL SHOW ALL VALVES, BACKFLOW
 DEVICES, IN-LINE EQUIPMENT (I.E. RECIRCULATING PUMP,
 THERMAL MIXING VALVE), WATER HEATER, POINTS OF
 CONNECTION TO FIXTURES/EQUIPMENT AND OWNER SUPPLIED
 EQUIPMENT AND TO EXISTING SOURCE OF COLD WATER.
 PARTIALLY COMPLIED. SIZE ALL BRANCHES. PROVIDE FULL
 OPEN VALVE AT TOP OF ALL WATER DOWNFEEDS PER FBC PL
 606.1(5).
 B.SANITARY RISER DIAGRAM SHALL SHOW ALL TRAPS, FLOOR
 DRAINS, HUB DRAINS, TRAP PRIMER CONNECTIONS, CLEANOUTS,
 VENTS, POINTS OF CONNECTION TO FIXTURES/EQUIPMENT AND
 OWNER SUPPLIED EQUIPMENT AND TO EXISTING SANITARY
 RISER. IF AN EQUIPMENT ITEM SUCH AS AN ICE MACHINE
 REQUIRES A DRAIN, THEN A WASTE RECEPTACLE AND INDIRECT
 WASTE AND AIR GAP SHALL BE PROVIDED TO COMPLY WITH THE
 PROVISIONS OF FBC PL CHAPTER 8.
 PARTIALLY COMPLIED. SIZE ALL BRANCHES. FIXTURE DRAIN
 SIZES NOT REQUIRED AS LONG AS THE SIZE IS NOTED ON
 P0.01 FIXTURE CONNECTION SCHEDULE. IT IS NOTED HOWEVER
 ON P0.01 FIXTURE CONNECTION SCHEDULE P-16 FLOOR SINK
 THAT WASTE CONNECTION SIZE SHALL BE AS SHOWN. NO SIZING
 OF P-16 FLOOR SINK(S) IS SHOWN. PER WPB FBC 107.2.1,
 PROVIDE SIZING. PROVIDE NOTES SIMILAR TO WHAT WAS DONE
 FOR THE WATER CONNECTIONS TO OWNER SUPPLIED EQUIPMENT
 STATING HOW EQUIPMENT IS TO BE DRAINED (I.E. SIZED
 INDIRECT WASTE TO FLOOR ADJACENT FLOOR SINK WITH AIR
 GAP).
 C.COMPRESSED AIR TO SHOW PIPE, VALVES, REGULATORS,
 FILTERS AND FITTINGS, SOURCE COMPRESSOR AND POINT OF
 CONNECTION TO EQUIPMENT BEING SERVICED.
 PARTIALLY COMPLIED. SIZE ALL BRANCHES. SHOW ALL VALVES,
 REGULATORS, FILTERS, SOURCE COMPRESSOR. ADDITIONALLY,
 SHOW HOW OWNER SUPPLED AIR COMPRESSOR WILL BE DRAINED
 OF CONDENSATE. PROVIDE DETAIL(S) FOR EQUIPMENT
 CONNECTIONS AT SOURCE AND AT POINT OF USE. REFERENCE
 ORIGINAL REVIEW COMMENT 17. RESPONSE THAT THERE IS NO
 COMPRESSED AIR OTHER THAN MEDICAL GAS DOES NOT
 CORRESPOND WITH THE SUBMITTED PLUMBING PLANS. P2.00
 WATER RISER DIAGRAM AND P1.03 BOTH SHOW COMPRESSED AIR
 PIPING. P1.03 NOTES 1, 4, 13, 14, 15, 16, 17 AND 18
 ADDRESSES THE COMPRESSED AIR AS WELL AND NOTE 15
 REFERENCES AN OWNER SUPPLIED AIR COMPRESSOR. IF THERE
 IS NO COMPRESSED AIR AS YOUR RESPONSE INDICATED, THEN
 REMOVE ALL REFERENCE FROM THE PLAN.
 D.CLEAR WASTEWATER RISER DIAGRAM SHALL SHOW ALL
 EQUIPMENT POINTS OF CONNECTION, TRAPS, VENTS AND POINT
 OF DISPOSAL. SECOND REQUEST: SIZED CLEAR WASTEWATER A/C
 CONDENSATE DRAIN RISER DIAGRAM REQUIRED.
  
 ORIGINAL COMMENT #7. COMPLIED
  
 ORIGINAL COMMENT #8. COMPLIED
  
 ORIGINAL COMMENT #9. REQUIRE THIS REFERENCED DEFERRED
 SUBMITTAL FOR OWNER PROVIDED EQUIPMENT SCHEDULE AND
 MANUFACTURER'S SPECIFICATION/INSTALLATION MANUAL SHALL
 BE ADDED TO THE LIST OF DEFERRED SUBMITTALS NOTE IN
 G1.01; DEFERRED SUBMITTALS
  
 ORIGINAL COMMENT #10. COMPLIED
  
 ORIGINAL COMMENT #11. COMPLIED
  
 ORIGINAL COMMENT #12.RE: P0.01 PLUMBING FIXTURE
 SCHEDULE; P-7 RECESSED BOX. WHAT KIND OF EQUIPMENT IS
 BEING SERVICED? A COFFEE MAKER OR ICE MACHINE REQUIRES
 A BACKFLOW PREVENTION DEVICE TO COMPLY WITH THE
 REQUIREMENTS OF FBC PL 608 AND IN INSTANCES WHERE QUICK
 CLOSING VALVES ARE UTILIZED, A WATER HAMMER ARRESTOR
 CONFORMING TO ASSE 1010 SHALL BE INSTALLED. PER WPB FBC
 107.2.1, ANY REQUIRED BACKFLOW DEVICE AND/OR WATER
 HAMMER ARRESTOR SHALL BE SPECIFIED AND SCHEDULED.
 PARTIALLY COMPLIED; TO BE CLEAR, THERE ARE EIGHT (8)
 EACH P-7 RECESSED OATEY 39151 WALL BOXES FOR
 REFRIGERATOR ICE OR COFFEE MAKER COLD WATER
 CONNECTIONS. CONNECTIONS TO COFFEE MAKERS REQUIRE
 BACKFLOW PREVENTERS TO COMPLY WITH FBC PL 608. PER WPB
 FBC 107.2.1, IDENTIFY THE PIECE OF EQUIPMENT THAT EACH
 P-7 WILL SERVICE. PROVIDE NOTE REQUIRING BACKFLOW
 PREVENTER FOR COFFEE MAKER CONNECTIONS OR ANY OTHER
 EQUIPMENT THAT WOULD REQUIRE A BACKFLOW PREVENTER TO
 COMPLY WITH FBC PL 608. SPECIFY SAID BACKFLOW
 PREVENTER(S).
  
 ORIGINAL COMMENT #13. SECOND REQUEST: PROVIDE NOTE
 REQUIRING INSULATION OF HOT WATER PER FBC EC C404.4.
 REFER TO 20032 PALM BEACH INTERNATIONAL SC SPECS
 SECTION 22-07-00 FOR INSULATION SPECIFICATIONS
 (PROVIDED IN SUPPORTING DOCUMENTS)
 PLEASE NOTE, I FOUND A NOTE ON P1.03, MEDICAL GAS
 GENERAL NOTE REFERENCING SPECIFICATIONS, BUT NOTHING ON
 PLUMBING PLANS REGARDING THE REQUIREMENT FOR HOT WATER
 INSULATION.
  
 ORIGINAL COMMENT #14. SECOND REQUEST: PROVIDE NOTE:
 "REFER TO 20032 PALM BEACH INTERNATIONAL SC SPECS
 DIVISION 22-PLUMBING FOR PLUMBING SPECIFICATIONS"
 (PROVIDED IN SUPPORTING DOCUMENTS)
 PLEASE NOTE, I FOUND A NOTE ON P1.03, MEDICAL GAS
 GENERAL NOTE REFERENCING SPECIFICATIONS, BUT NOTHING ON
 PLUMBING PLANS REGARDING "REFER TO 20032 PALM BEACH
 INTERNATIONAL SC SPECS DIVISION 22-PLUMBING FOR
 PLUMBING SPECIFICATIONS"
  
 ORIGINAL COMMENT #15. PARTIALLY COMPLIED: PER WPB FBC
 107.2.1, SHOW (PLAN VIEW AND RISER DIAGRAM) HOW
 DISPOSAL OF WASTEWATER FROM THE MEDICAL GAS VACUUM PUMP
 RECEIVER TANK ON THE FIRST FLOOR WILL BE ACHIEVED;
 PROVIDE DETAIL. COMPLY WITH FBC PL CHAPTERS 7,8 AND 9.
 IF CONCRETE SLAB IS TO BE CUT AND REMOVED THEN PROVIDE
 A SLAB REPAIR DETAIL ON THE PLANS. SHOW THE WIDTH OF
 THE REPAIR, THE MINIMUM THICKNESS AND PSI OF THE
 CONCRETE TO BE REPLACED. SHOW SIZE, LENGTH, SPACING (ON
 CENTER), MINIMUM EMBEDMENT AND ANCHORING/ADHESIVE
 MATERIAL FOR DOWELS. THE REPAIR SHALL ALSO INCLUDE
 TERMITE TREATMENT OF THE SOIL AS WELL AS THE REQUIRED
 VAPOR BARRIER OVER WELL COMPACTED SOIL. A COPY OF THE
 TERMITE CERTIFICATE SHALL BE ONSITE FOR FINAL
 INSPECTION. PROVIDE SANITARY AND WATER RISER DIAGRAMS.
 A.SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE SIZED
 SANITARY AND WATER RISER DIAGRAMS. SHOW REQUIRED TRAPS,
 VALVES, ETC.
 B.SECOND REQUEST: PER WPB FBC 107.2.1, IT SEEMS
 APPARENT THAT CONCRETE SLAB IS TO BE CUT AND REMOVED;
 PROVIDE A SLAB REPAIR DETAIL ON THE PLANS. SHOW THE
 WIDTH OF THE REPAIR, THE MINIMUM THICKNESS AND PSI OF
 THE CONCRETE TO BE REPLACED. SHOW SIZE, LENGTH, SPACING
 (ON CENTER), MINIMUM EMBEDMENT AND ANCHORING/ADHESIVE
 MATERIAL FOR DOWELS. THE REPAIR SHALL ALSO INCLUDE
 TERMITE TREATMENT OF THE SOIL AS WELL AS THE REQUIRED
 VAPOR BARRIER OVER WELL COMPACTED SOIL. A COPY OF THE
 TERMITE CERTIFICATE SHALL BE ONSITE FOR FINAL
 INSPECTION.
  
 ORIGINAL COMMENT #16. COMPLIED
  
 ORIGINAL COMMENT #17. PER WPB FBC 107.2.1, PROVIDE
 MATERIAL SPECIFICATION FOR CLEAR WASTEWATER AND FOR THE
 COMPRESSED AIR SYSTEM. PARTIALLY COMPLIED; REQUEST FOR
 WASTEWATER IS COMPLIANT. RESPONSE THAT THERE IS NO
 COMPRESSED AIR OTHER THAN MEDICAL GAS DOES NOT
 CORRESPOND WITH THE SUBMITTED PLUMBING PLANS. P2.00
 WATER RISER DIAGRAM AND P1.03 BOTH SHOW COMPRESSED AIR
 PIPING. P1.03 NOTES 1, 4, 13, 14, 15, 16, 17 AND 18
 ADDRESSES THE COMPRESSED AIR AS WELL AND NOTE 15
 REFERENCES AN OWNER SUPPLIED AIR COMPRESSOR. PER WPB
 FBC 107.2.1, CLARIFY.
  
  
 END OF COMMENTS.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE SIGNED AND SEALED/DIGITALLY SIGNED AND
 SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20090500 5325 GREENWOOD AVE

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-10-12 Cont ID  
Sent By jesmith Date 2020-10-06 Time 15:55 Rev Time 0.00
Received By jesmith Date 2020-10-01 Time 15:25 Sent To  
Notes
2020-10-06 15:55:14CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 NFPA 99 = HEALTH CARE FACILITIES CODE
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1.IS THERE A STORM PIPING SYSTEM IN THE BUILDING OR IS
 THE BUILDING BEING DRAINED BY SCUPPERS AND A GUTTER
 SYSTEM. PER WPB FBC 107.2.1, INDICATE ON THE ROOF PLAN
 HOW THE REQUIREMENTS OF FBC PL CHAPTER 11 ARE BEING
 MET. SHOW EXISTING ROOF DRAINS, OVERFLOW DRAINS AND/OR
 EXISTING GUTTERS. IF THERE IS AN EXISTING STORM PIPING
 SYSTEM, THEN PROVIDE FOR REFERENCE A COPY OF RECORD
 DRAWINGS FOR THE INSTALLATION.
  
 2.HORIZONTAL SANITARY DRAINAGE PIPING IS SUSPENDED IN
 THE CEILING OF THE SECOND FLOOR. PER WPB FBC 107.2.1,
 PROVIDE SECOND FLOOR PLAN SHOWING ALL RATED WALLS THAT
 SAID PIPING WILL PENETRATE.
  
 3.PER WPB FBC 107.2.1, PROVIDE FIXTURE SCHEDULE SHOWING
 MINIMUM REQUIRED PLUMBING FIXTURES AND QUANTITIES AND
 ACTUAL TO SHOW COMPLIANCE WITH FBC PL 403.1 AND TABLE
 403.1.
  
 4.RE: PLAN G4.01, ADA STANDARDS; IT IS NOTED THAT THIS
 SHEET IS PROVIDED FOR GUIDANCE ONLY AS STATED ON THE
 PLAN. PLEASE NOTE THAT FIGURE 10; TYPICAL TOILET
 LAYOUTS, DOES NOT APPLY TO ANY OF THE CONFIGURATION IN
 THE CONSTRUCTION DOCUMENTS. ACCESSIBILITY REQUIREMENTS
 SHALL COMPLY WITH 2017 FLORIDA BUILDING CODE:
 ACCESSIBILITY AS STATED ON PLAN SHEET G.001. PER WPB
 FBC 107.2.1 AND FBC PL 404.1, PROVIDE FLOOR PLAN
 DETAILS AND ELEVATION DETAILS OF ACCESSIBLE
 TOILET/BATHING ROOMS, SHOWERS, DRINKING FOUNTAINS, AND
 SINKS (SUBMITTED PLAN SHEETS A8.01 AND A8.51 PROVIDE
 ADEQUATE ELEVATIONS FOR SINKS IN CASEWORK) AND SHOWING
 COMPLIANCE WITH FBC ACC CHAPTERS 2, 3 AND 6. PLAN SHEET
 A2.01 PROVIDES ENLARGED PLAN VIEWS OF TOILET/BATHING
 ROOMS BUT SIZED CLEAR FLOOR SPACES ARE NOT EASILY
 IDENTIFIED, TURNING SPACES ARE NOT SHOWN AND ELEVATIONS
 OF THESE ROOMS SHOWING THE ACCESSIBILITY REQUIREMENTS
 ARE NON-EXISTENT. LOCKER ROOM SHOWERS SHALL COMPLY WITH
 FBC ACC 608.2.1, 608.3.1 AND 608.5.1. GRAB BARS SHALL
 BE INSTALLED IN A HORIZONTAL POSITION, 33 INCHES
 MINIMUM AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR
 MEASURED TO THE TOP OF THE GRIPPING SURFACE, NOT
 CENTERLINE PER FBC ACC 609.4.
  
 5.PROVIDE ON THE ARCHITECTURAL OR LIFE SAFETY THIRD
 FLOOR PLAN ALL FORWARD AND/OR PARALLEL APPROACH CLEAR
 FLOOR SPACES FOR ACCESSIBLE SINKS IN CASEWORK AND THE
 DRINKING FOUNTAIN(S).
  
 6.PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE SIZED
 DOMESTIC WATER, SANITARY, COMPRESSED AIR AND CLEAR
 WASTE WATER RISER DIAGRAMS.
 A.WATER RISER DIAGRAM SHALL SHOW ALL VALVES, BACKFLOW
 DEVICES, IN-LINE EQUIPMENT (I.E. RECIRCULATING PUMP,
 THERMAL MIXING VALVE), WATER HEATER, POINTS OF
 CONNECTION TO FIXTURES/EQUIPMENT AND OWNER SUPPLIED
 EQUIPMENT AND TO EXISTING SOURCE OF COLD WATER.
 B.SANITARY RISER DIAGRAM SHALL SHOW ALL TRAPS, FLOOR
 DRAINS, HUB DRAINS, TRAP PRIMER CONNECTIONS, CLEANOUTS,
 VENTS, POINTS OF CONNECTION TO FIXTURES/EQUIPMENT AND
 OWNER SUPPLIED EQUIPMENT AND TO EXISTING SANITARY
 RISER. IF AN EQUIPMENT ITEM SUCH AS AN ICE MACHINE
 REQUIRES A DRAIN, THEN A WASTE RECEPTACLE AND INDIRECT
 WASTE AND AIR GAP SHALL BE PROVIDED TO COMPLY WITH THE
 PROVISIONS OF FBC PL CHAPTER 8.
 C.COMPRESSED AIR TO SHOW PIPE, VALVES, REGULATORS,
 FILTERS AND FITTINGS, SOURCE COMPRESSOR AND POINT OF
 CONNECTION TO EQUIPMENT BEING SERVICED.
 D.CLEAR WASTEWATER RISER DIAGRAM SHALL SHOW ALL
 EQUIPMENT POINTS OF CONNECTION, TRAPS, VENTS AND POINT
 OF DISPOSAL.
  
 7. PER WPB FBC 107.2.1, PROVIDE DETAIL(S) FOR CLEAR
 WASTEWATER EQUIPMENT CONNECTIONS AND POINT OF DISPOSAL.
 REGARDING THE A/C CONDENSATE DISCHARGING TO THE
 JANITOR?S SINK; PER NFPA 99-15 SECTION 8.3.11.4, EXCESS
 CLEAR WASTEWATER SHALL BE DISCHARGED TO A STORM SEWER
 OR RECHARGED INTO THE WATER TABLE AS PERMITTED BY
 APPLICABLE PLUMBING CODES. DEPENDING ON FUTURE
 EQUIPMENT SUBMITTALS (I.E. STERILIZERS, ICE MACHINES,
 ETC.) THIS MAY APPLY TO OTHER EQUIPMENT DRAINS AS WELL
 AS THE AIR HANDLING UNIT CONDENSATE DRAINS.
 ADDITIONALLY, WPB UTILITIES DEPARTMENT PROHIBITS
 DISCHARGE OF CONDENSATE WASTE TO THE CITY SEWERS. PER
 WPB FBC 107.2.1, PROVIDE POINT OF DISPOSAL OF THE CLEAR
 WASTEWATER EITHER TO STORM OR GROUND. PROVIDE ROUTING
 AND DETAIL FOR POINT OF DISPOSAL.
  
 8.PER WPB FBC 107.2.1, PROVIDE A TRAP PRIMER DETAIL.
  
 9.PER WPB FBC 107.2.1, PROVIDE A FULL SCHEDULE OF OWNER
 PROVIDED EQUIPMENT. INDICATE ON THE SCHEDULE ALL
 UTILITY SERVICE CONNECTION REQUIREMENTS INCLUDING BUT
 NOT LIMITED TO WATER AND WASTE. PROVIDE MANUFACTURER?S
 SPECIFICATIONS/INSTALLATION MANUAL FOR ALL OWNER
 SUPPLIED EQUIPMENT. SAID DOCUMENTS MAY BE SUBMITTED AS
 A DEFERRED SUBMITTAL IN ACCORDANCE WITH WPB FBC 107.2.1
 AND 107.3.4.1. SEE WPB FBC 107.3.4.2 DEFERRED
 SUBMITTALS; FOR THE PURPOSES OF THIS SECTION, DEFERRED
 SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF THE DESIGN
 THAT ARE NOT SUBMITTED AT THE TIME OF THE APPLICATION
 AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL
 WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL
 ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE BUILDING
 OFFICIAL. THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE SHALL LIST THE DEFERRED SUBMITTALS
 ON THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE
 BUILDING OFFICIAL. THIS MAY BE DONE BY NOTING SUCH IN
 THE RESPONSE LETTER TO THIS REVIEW.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 10.RE: PLAN F1.1, ALL TOILET ROOMS, ROOMS 3032, 3041,
 3042 AND 3047 (JANITOR SERVICE SINKS AND CLINICAL
 SERVICE SINK); WALLS AND PARTITIONS WITHIN 2 FEET (610
 MM) OF SERVICE SINKS, URINALS AND WATER CLOSETS SHALL
 HAVE A SMOOTH, HARD, NONABSORBENT SURFACE, TO A HEIGHT
 OF NOT LESS THAN 4 FEET (1219 MM) ABOVE THE FLOOR, AND
 EXCEPT FOR STRUCTURAL ELEMENTS, THE MATERIALS USED IN
 SUCH WALLS SHALL BE OF A TYPE THAT IS NOT ADVERSELY
 AFFECTED BY MOISTURE PER FBC 1210.2.2. EPOXY AND PAINT
 FINISHES DO NOT COMPLY WITH THE REQUIREMENTS OF THIS
 SECTION.
  
 11.RE: P0.01/ DETAIL H3, WATER HEATER SCHEMATIC;
 A.REGARDING THE GALVANIZED NIPPLE, PER FBC PL 605.24.1,
 JOINTS BETWEEN COPPER OR COPPER-ALLOY TUBING AND
 GALVANIZED STEEL PIPE SHALL BE MADE WITH A BRASS
 FITTING OR DIELECTRIC FITTING OR A DIELECTRIC UNION
 CONFORMING TO ASSE 1079. THE COPPER TUBING SHALL BE
 SOLDERED TO THE FITTING IN AN APPROVED MANNER, AND THE
 FITTING SHALL BE SCREWED TO THE THREADED PIPE.
 B.NOTE PERTAINING TO ASME RELIEF VALVE DISCHARGE PIPE
 SHALL HAVE THE WORDS THROUGH AN AIR GAP ADDED AT THE
 END OF THE SENTENCE
 C.PER WPB FBC 107.2.1, SHOW TEMPERATURE OF HOT WATER
 FEED FROM WATER HEATER AS 140 DEGREES F AND SHOW
 DESIGNATED BRANCH TO MIXING VALVE (DETAIL H10).
 D.PER FBC PL 504.7, PROVIDE A PAN FOR THE WATER HEATER.
 COMPLY WITH FBC PL 504.7, 504.7.1 AND 504.7.2. PROVIDE
 A HOUSEKEEPING PAD IF REQUIRED TO PROVIDE AMPLE
 ELEVATION FOR DRAIN DISCHARGE TO FLOOR DRAIN.
 E. PER WPB FBC 107.2.1, PROVIDE NOTE STATING
 "WATER-HEATING EQUIPMENT NOT SUPPLIED WITH INTEGRAL
 HEAT TRAPS AND SERVING NONCIRCULATING SYSTEMS SHALL BE
 PROVIDED WITH HEAT TRAPS ON THE SUPPLY AND DISCHARGE
 PIPING ASSOCIATED WITH THE EQUIPMENT" TO SHOW
 COMPLIANCE WITH FBC EC C404.3.
  
 12.RE: P0.01 PLUMBING FIXTURE SCHEDULE; P-7 RECESSED
 BOX. WHAT KIND OF EQUIPMENT IS BEING SERVICED? A COFFEE
 MAKER OR ICE MACHINE REQUIRES A BACKFLOW PREVENTION
 DEVICE TO COMPLY WITH THE REQUIREMENTS OF FBC PL 608
 AND IN INSTANCES WHERE QUICK CLOSING VALVES ARE
 UTILIZED, A WATER HAMMER ARRESTOR CONFORMING TO ASSE
 1010 SHALL BE INSTALLED. PER WPB FBC 107.2.1, ANY
 REQUIRED BACKFLOW DEVICE AND/OR WATER HAMMER ARRESTOR
 SHALL BE SPECIFIED AND SCHEDULED.
  
 13. PROVIDE NOTE REQUIRING INSULATION OF HOT WATER PER
 FBC EC C404.4. REFER TO 20032 PALM BEACH INTERNATIONAL
 SC SPECS SECTION 22-07-00 FOR INSULATION SPECIFICATIONS
 (PROVIDED IN SUPPORTING DOCUMENTS)
  
 14. PROVIDE NOTE: "REFER TO 20032 PALM BEACH
 INTERNATIONAL SC SPECS DIVISION 22-PLUMBING FOR
 PLUMBING SPECIFICATIONS" (PROVIDED IN SUPPORTING
 DOCUMENTS)
  
 15.PER WPB FBC 107.2.1, SHOW (PLAN VIEW AND RISER
 DIAGRAM) HOW DISPOSAL OF WASTEWATER FROM THE MEDICAL
 GAS VACUUM PUMP RECEIVER TANK ON THE FIRST FLOOR WILL
 BE ACHIEVED; PROVIDE DETAIL. COMPLY WITH FBC PL
 CHAPTERS 7,8 AND 9. IF CONCRETE SLAB IS TO BE CUT AND
 REMOVED THEN PROVIDE A SLAB REPAIR DETAIL ON THE PLANS.
 SHOW THE WIDTH OF THE REPAIR, THE MINIMUM THICKNESS AND
 PSI OF THE CONCRETE TO BE REPLACED. SHOW SIZE, LENGTH,
 SPACING (ON CENTER), MINIMUM EMBEDMENT AND
 ANCHORING/ADHESIVE MATERIAL FOR DOWELS. THE REPAIR
 SHALL ALSO INCLUDE TERMITE TREATMENT OF THE SOIL AS
 WELL AS THE REQUIRED VAPOR BARRIER OVER WELL COMPACTED
 SOIL. A COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE
 FOR FINAL INSPECTION.
  
 16. REFER TO 20032 PALM BEACH INTERNATIONAL SC SPECS
 DIVISION 22-PLUMBING SECTION 22-11-16 (B) ALLOWS WATER
 PIPE ABOVE GRADE TO BE ASTM A53 GALVANIZED PIPE WITH
 GROOVED COUPLINGS OR COPPER PRESS FITTINGS BY VIEGA. A)
 IS IT YOUR INTENT TO ALLOW GALVANIZED PIPE AND FITTINGS
 IN THE POTABLE WATER SYSTEM? B) PLEASE CLARIFY THE
 OPTION FOR COPPER PRESS FITTINGS IN A GALVANIZED
 SYSTEM.
  
 17.PER WPB FBC 107.2.1, PROVIDE MATERIAL SPECIFICATION
 FOR CLEAR WASTEWATER AND FOR THE COMPRESSED AIR SYSTEM.
  
  
  
 END OF COMMENTS.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE SIGNED AND SEALED/DIGITALLY SIGNED AND
 SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20090500 5325 GREENWOOD AVE
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-12-21 Cont ID  
Sent By medwards Date 2020-12-21 Time 08:34 Rev Time 0.00
Received By medwards Date 2020-12-21 Time 08:34 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-11-16 Cont ID  
Sent By medwards Date 2020-11-16 Time 08:49 Rev Time 0.00
Received By medwards Date 2020-11-16 Time 08:49 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-10-13 Cont ID  
Sent By shill Date 2020-10-13 Time 06:47 Rev Time 0.00
Received By shill Date 2020-10-13 Time 06:43 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2020-10-01 Cont ID  
Sent By llouie Date 2020-10-01 Time   Rev Time  
Received By llouie Date 2020-10-01 Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved