| Plan Review Stops For Permit 20090458 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2020-10-20 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-10-20 |
Time |
08:50 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-10-20 |
Time |
08:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2020-09-25 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-09-25 |
Time |
14:05 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-09-25 |
Time |
13:36 |
Sent To |
|
|
| Notes |
| 2020-09-25 14:15:54 | SFR REMODEL | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PLEASE SHOW THE CEILING HEIGHT AT THE BOTTOM OF THE | | | AC SOFFIT TO COMPLY WITH FBC R305.1MINIMUM HEIGHT.(7 | | | FEET) | | | 2) PLEASE SHOW THE REQUIRED DRYWALL AT THE AC CLOSET | | | CEILING AND WALLS TO COMPLY WITH FBC R302.7UNDER-STAIR | | | PROTECTION. | | | ENCLOSED ACCESSIBLE SPACE UNDER STAIRS SHALL HAVE | | | WALLS, UNDER-STAIR SURFACE AND ANY SOFFITS PROTECTED ON | | | THE ENCLOSED SIDE WITH 1/2-INCH (12.7 MM) GYPSUM BOARD. | | | 3) PLEASE PROVIDE A COMPLETE MIAMI DADE OR FLORIDA | | | STATE PRODUCT APPROVAL FOR THE NEW EXTERIOR WINDOW. | | | (FRONT PAGES AND THE INSTALLATION INSTRUCTIONS) | | | 4) PLEASE SHOW THE WIND DESIGN DATA USED FOR THE WIND | | | DESIGN. FBC R301.2.1 | | | 5) PLEASE SHOW THE REQUIRED WIND PRESSURES FOR THE NEW | | | WINDOW OPENING. | | | 6) PLEASE PROVIDE FIREPLACE DETAILS TO COMPLY WITH FBC | | | R CHAPTER 10. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2020-10-19 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-10-19 |
Time |
17:29 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-10-19 |
Time |
17:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2020-09-23 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-09-23 |
Time |
14:17 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-09-23 |
Time |
14:01 |
Sent To |
|
|
| Notes |
| 2020-09-23 14:17:32 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | NEW DOOR IN LAUNDRY ROOM MISSING LIGHT FIXTURE FOR | | | EXTERIOR OF BUILDING. E3903.3 | | | | | | DESK AREA IN KITCHEN WOULD NEED TO BE TREATED AS | | | COUNTERTOP SPACES FOR OUTLET SPACING. |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
2 |
Status |
P |
Date |
2020-10-27 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2020-10-27 |
Time |
15:25 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2020-10-27 |
Time |
15:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
P |
Date |
2020-09-25 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2020-09-25 |
Time |
13:31 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2020-09-25 |
Time |
13:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2020-10-29 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-10-29 |
Time |
07:56 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-10-09 |
Time |
10:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2020-09-25 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-09-25 |
Time |
14:26 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-09-16 |
Time |
10:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2020-10-13 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-10-13 |
Time |
10:56 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2020-10-13 |
Time |
10:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2020-09-17 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-09-17 |
Time |
09:01 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2020-09-17 |
Time |
08:38 |
Sent To |
|
|
| Notes |
| 2020-09-17 09:01:19 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT-20090458 | | | | | | CODES IN EFFECT: | | | | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | | EDITION 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE PROVIDE A COMPLETE SCOPE OF WORK FOR THE | | | MECHANICAL SYSTEM. IS THIS A LIKE FOR LIKE CHANGE OUT | | | OF THE 1ST FLOOR AHU AND C/U? IF SO PLEASE SUBMIT THE | | | LIKE FOR LIKE CHANGE OUT FORM. IF IT IS NOT THEN | | | PROVIDE THE ENERGY AND MANUAL J CALCULATIONS. FBC FS | | | 107.2.1 | | | | | | 2) PLEASE SHOW THE DRYER DUCT AND HOW IT WILL BE | | | TERMINATED TO THE EXTERIOR. FBC RES M1502 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | | UPDATED. | | | | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2020-10-13 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2020-10-13 |
Time |
08:25 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2020-10-13 |
Time |
07:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2020-09-18 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2020-09-18 |
Time |
14:07 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2020-09-18 |
Time |
13:01 |
Sent To |
|
|
| Notes |
| 2020-09-18 14:09:29 | 1ST REVIEW FBC-2017 RES. | | | PERMIT- 20090458 | | | 9/18/2020 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | | EDITION 2017 | | | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET MP1: PROVIDE A WATER RISER DRAWING SHOWING HOT | | | AND COLD WATER PIPE CONNECTIONS TO THE NEW ISLAND SINK, | | | DISHWASHER, AND REFRIGERATOR ICE MAKER LINE- SECTIONS | | | 107.2.1 & 107.3.5.3 WPB. PLEASE SHOW LOCATIONS OF | | | REQUIRED WATER HAMMER ARRESTORS FOR THE DISHWASHER AND | | | ICE MAKER LINES- SECTION P2903.5; AND MEANS OF BACKFLOW | | | PREVENTION FOR SUPPLY LINES TO THE DISHWASHER AND ICE | | | MAKER- SECTIONS P2717.1 AND P2902.1 FBC RES. | | | | | | 2) MP1: SHOW SANITARY DRAIN AND WATER SUPPLY TIE-INS | | | FOR THE RELOCATED WASHING MACHINE. IF USING THE | | | EXISTING WASHING MACHINE BOX AND STANDPIPE PLEASE | | | INDICATE ON THE PLANS, OR PROVIDE ISOMETRIC DRAWINGS | | | FOR NEW STANDPIPE AND VALVE BOX INSTALLATIONS- SECTIONS | | | 107.2.1 & 107.3.5.3 WPB. SHOW THE ACCESSIBLE VALVE BOX | | | LOCATION- SECTION P2903.9.3 FBC RES. | | | | | | 3) PLEASE PLACE A NOITE TO INDICATE THE ABANDONED | | | SANITARY DRAIN PIPE AT THE DEMOLISHED SINK SHALL BE | | | PROPERLY CAPPED PER SECTIONS P2503.5.2 AND P3001.1. FBC | | | RES. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2020-10-20 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-10-20 |
Time |
08:50 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-10-20 |
Time |
08:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2020-09-25 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-09-25 |
Time |
14:24 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-09-25 |
Time |
14:24 |
Sent To |
|
|
| Notes |
| 2020-09-25 14:26:17 | DEMO PLAN, CONSTRUCTION PLAN AND PLUMBING PLAN = SIGNED | | | AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR | | | ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. | | | DRAWINGS DO NOT SHOW IN "ADOBE READER" AS | | | DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR | | | ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL | | | SIGNATURE - PLEASE DROP OFF (CITY HALL DROP BOX) THE | | | ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS ALONG | | | WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE REASON | | | FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN REVIEW | | | REQUEST FORM CAN BE OBTAINED BY E MAILING [email protected] | | | AND ASKING FOR THE FORM. |
|
|