| 2020-09-12 08:49:35 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20090430 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE PLANS INDICATE AN EXISTING GAS METER. THE BTU |
| | LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE |
| | TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING |
| | SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING |
| | SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING |
| | SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS |
| | THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH |
| | APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH |
| | APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF |
| | PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE |
| | OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE |
| | EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE |
| | SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE |
| | REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES |
| | PER THE 2017 FBC FG SECS. 401.4, 401.8, 402.1, 402.2, |
| | 402.3 OR 2017 FBC RES. SECS. G2412.4, G2412.8, G2413.1, |
| | G2413.2, G2413.3. |
| | |
| | |
| | 2) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL |
| | BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC FG SECS. |
| | 401.8 THROUGH 402.6.1 AND TABLES 402.4 (1) THROUGH |
| | 402.4 (37) OR 2017 FBC RES. SEC. G2413. |
| | |
| | |
| | 3) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS |
| | METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2017 FBC |
| | FG SEC. 402.4.1 OR 2017 FBC RES. SEC. G2413.4.1. |
| | |
| | 4) SUBMIT MANUFACTURER?S SPECIFICATION |
| | SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO |
| | VERIFY COMPLIANCE WITH 2017 FBC FG SEC.305.1 OR 2017 |
| | FBC RES. SEC. G2408.1. |
| | |
| | 5) PLEASE LABEL THE SHUTOFF VALVE ON GAS ISOMERIC PER |
| | THE 2017 FBC RES. SEC. G2401.1.3. |
| | |
| | 6) INDICATE ON THE GAS DRAWING HOW THE PIPING THROUGH |
| | THE EXTERIOR WILL BE PROTECTED.(THE ?? GALV. PIPING FOR |
| | RANGE CONNECTING TO THE 1 ?? PE PIPING) WPB AMENDMENTS |
| | TO THE FBC SEC. 107.2.1. |
| | |
| | 7) SHOW THE BTU LOAD FOR THE FUTURE POOL HEATER. THIS |
| | VALUE MUST BE INCLUDED IN THE SIZING OF THE SYSTEM PER |
| | THE 2017 FBC FG SEC. 402.2 OR 2017 FBC RES. SEC G2413.2 |
| | MAXIMUM GAS DEMAND |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |