| Plan Review Stops For Permit 20090410 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2021-01-12 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2021-01-12 |
Time |
10:39 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2021-01-12 |
Time |
10:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2020-12-17 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-12-17 |
Time |
07:50 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-12-17 |
Time |
07:49 |
Sent To |
|
|
| Notes |
| 2020-12-17 07:54:10 | PARTIAL DEMO | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) REVISED PERMIT APPLICATION TO PARTIAL DEMO - PLEASE | | | REVISE THE SURVEY BY CIRCLING THE STRUCTURE TO BE | | | DEMOED AND WRITING THE SCOPE OF WORK ON THE SURVEY. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2020-10-23 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-10-23 |
Time |
12:21 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-10-23 |
Time |
10:57 |
Sent To |
|
|
| Notes |
| 2020-10-23 11:28:33 | SFR ADDITION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) BUILDING PERMIT APPLICATION NEEDS TO BE REVISED TO | | | MATCH THE DRAWINGS - JOB DESCRIPTION SHOULD STATE | | | BEDROOM ADDITION NOT PATIO - JOB VALUE FOR THE ADDITION | | | SHOULD BE SHOWN AS IF BEING BUILT BY A CONTRACTOR | | | (INCLUDE ALL LABOR AND MATERIAL PRICING). | | | 2) PLEASE SHOW THE EXISTING HOUSE FLOOR PLAN - NEEDED | | | TO DETERMINE IF THE ADDITION IS BLOCKING A REQUIRED | | | EXISTING BEDROOM EMERGENCY EGRESS. | | | 3) DRAWINGS NEED TO BE SIGNED AND DATED BY THE ENGINEER | | | SHOWN. FBC 107.2.1 | | | 4) DRAWINGS NEED TO SHOW THE WIND DESIGN CRITERIA USED | | | FOR DESIGN FBC R301.2.1 | | | 5) PROVIDE A WINDOW AND DOOR SCHEDULE SHOWING SIZES. | | | 6) SHOW THE EXTERIOR WALL COVERING TO COMPLY WITH FBC | | | R703.1 (CANNOT BE DRYWALL AS SHOWN) | | | 7) PLEASE PROVIDE STRUCTURAL CALCULATIONS THAT SHOWS | | | FOUNDATIONS, BEARING WALLS, ROOF FRAMING SYSTEMS AND | | | EXTERIOR SHEATHINGS SHOWN COMPLY WITH FBC 1601 | | | 8) PROVIDE A ROOF FRAMING PLAN SHOWING ALL REQUIRED | | | WIND UPLIFT STRAPPING DETAILS, SHEATHING DETAILS ETC TO | | | COMPLY WITH FBC CHAPTER 23 | | | 9) PLEASE PROVIDE ROOFING SYSTEM PRODUCT APPROVAL. | | | 10) PLEASE SHOW ROOF SLOPE. | | | 11) PLEASE SHOW WALL AND CEILING INSULATION "R" VALUE | | | TO COMPLY WITH FBC ENERGY CODE. | | | 12) PLEASE PROVIDE A SITE PLAN SHOWING THE FOLLOWING - | | | 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED | | | WITH THE APPLICATION FOR PERMIT | | | SHALL BE ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE | | | THE SIZE AND LOCATION OF NEW | | | CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE, | | | DISTANCES FROM LOT LINES, THE ESTABLISHED | | | STREET GRADES AND THE PROPOSED FINISHED GRADES, | | | DEPICTING THE PROPOSED LOT DRAINAGE AND, | | | AS APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND | | | DESIGN FLOOD ELEVATIONS; AND IT SHALL BE | | | DRAWN IN ACCORDANCE WITH AN ACCURATE AND INCLUDED ON A | | | BOUNDARY LINE SURVEY. | | | 13) PLEASE PROVIDE COMPLETE MIAMI DADE OR FLORIDA STATE | | | PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS, DOORS, | | | ROOFING SYSTEMS (FRONT PAGES AND THE INSTALLATION | | | INSTRUCTIONS). | | | 14) SHOW SMOKE DETECTORS TO COMPLY WITH FBC R314 | | | 15) MAY NOT BE A COMPLETE LIST OF CORRECTIONS - | | | DRAWINGS ARE NOT COMPLETE SEE FBC WPB AMENDMENTS | | | 107.3.5.3 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2020-09-24 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-09-24 |
Time |
11:16 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-09-24 |
Time |
11:15 |
Sent To |
|
|
| Notes |
| 2020-09-24 11:20:07 | PATIO | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) DRAWINGS ARE NOT CLEAR - DRAWING SAYS ADDITION - IS | | | THIS JUST A CONCRETE SLAB NO WALLS NO ROOF? - PLEASE | | | WRITE ON THE DRAWING - NO ROOF- NO WALLS. OR PROVIDE | | | DETAILS OF THE WALLS AND ROOF TO COMPLY WITH FBC | | | R301.2.1 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2021-01-06 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-01-06 |
Time |
14:21 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-01-06 |
Time |
14:21 |
Sent To |
|
|
| Notes |
| 2021-01-06 14:22:19 | FOR DEMO ONLY JLEAHY |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2021-01-05 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-01-05 |
Time |
11:48 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-01-05 |
Time |
11:40 |
Sent To |
|
|
| Notes |
| 2021-01-05 11:49:27 | SEE COMMENTS FROM 12/21/20 REVIEW JLEAHY |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2020-12-21 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-12-21 |
Time |
07:20 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-12-21 |
Time |
07:17 |
Sent To |
|
|
| Notes |
| 2020-12-21 07:32:09 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | PLEASE SHOW ALL NEW ELECTRICAL WORK. LOCATION OF | | | OUTLETS, LIGHTING, AND SMOKE ALARMS. | | | | | | FOR DWELLING UNITS, ATTACHED GARAGES, AND DETACHED | | | GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL | | | SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED ON | | | THE EXTERIOR SIDE OF OUTDOOR ENTRANCES/EXITS WITH GRADE | | | LEVEL ACCESS. PROVIDE CORRECTION. NEC 210.70(A)(2)(B), | | | FBC RE3903.3 | | | | | | E3901.2.1 SPACING. RECEPTACLES SHALL BE INSTALLED SO | | | THAT NO POINT MEASURED HORIZONTALLY ALONG THE FLOOR | | | LINE OF ANY WALL SPACE IS MORE THAN 6 FEET (1829 MM), | | | FROM A RECEPTACLE OUTLET. [210.52(A)(1)] | | | | | | PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED PER | | | CODE. SHOW ON PLAN ALL EXISTING ALARMS. IF NONE ARE | | | EXISTING OR NOT TO CODE, SHOW AS NEW INSTALLATIONS. FBC | | | R314.3, FBC 107.2.1 | | | | | | ALL 120-VOLT, SINGLE PHASE, 15 AND 20 AMPERE BRANCH | | | CIRCUITS SUPPLYING OUTLETS IN DWELLING UNIT KITCHENS, | | | LAUNDRY ROOMS, FAMILY ROOMS, DINING ROOMS, LIVING | | | ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS, | | | RECREATION ROOMS, CLOSETS, HALLWAYS, OR SIMILAR AREAS | | | OR ROOMS, SHALL HAVE AFCI PROTECTION. NEC 210.12; FBC | | | RE3902.16 | | | | | | ALL 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE | | | RECEPTACLES INSTALLED IN THE LOCATIONS SPECIFIED IN | | | 210.8(A)(1) THROUGH (10) SHALL HAVE GROUND-FAULT | | | CIRCUITINTERRUPTER PROTECTION FOR PERSONNEL. FBC RE3902 | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2020-10-22 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-10-22 |
Time |
17:28 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-10-22 |
Time |
17:23 |
Sent To |
|
|
| Notes |
| 2020-10-22 17:29:32 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | NO ELECTRICAL SHOWN. | | | | | | PLEASE SUBMIT A PLAN WITH THE ELECTRICAL ON IT. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2021-01-05 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-01-05 |
Time |
12:50 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2020-12-14 |
Time |
17:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2020-12-04 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2020-12-04 |
Time |
15:35 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2020-10-14 |
Time |
10:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2020-09-24 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-09-24 |
Time |
11:21 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-09-10 |
Time |
15:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
N |
Date |
2021-01-12 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2021-01-12 |
Time |
10:39 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2021-01-12 |
Time |
10:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2020-10-23 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-10-23 |
Time |
12:21 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-10-23 |
Time |
12:21 |
Sent To |
|
|
| Notes |
| 2020-10-23 12:21:52 | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | | | | UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE | | | RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | | [email protected] . | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
N |
Date |
2020-12-17 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-12-16 |
Time |
07:11 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2020-12-16 |
Time |
07:05 |
Sent To |
|
|
| Notes |
| 2020-12-16 07:24:19 | BASED ON THE DEMO PERMIT SUBMITTED ON 12/13/2020 THIS | | | WAS AN ILLEGAL STRUCTURE ON THE BACK OF THE HOME. THE | | | DEMO PERMIT IS FOR THE TEAR DOWN AND REMOVAL OF THIS | | | ILLEGAL STRUCTURE. NO MECHANICAL WORK REQUIRED. ME | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2020-10-26 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-10-26 |
Time |
13:00 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2020-10-26 13:31:49 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT-20090410 | | | | | | CODES IN EFFECT: | | | | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | | EDITION 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE SEE BUILDING REVIEWER?S COMMENTS. | | | | | | 2) THE APPLICATION STATES THIS IS A PATIO. IF THIS IS | | | NOT JUST A PATIO AND IS NOW AN ADDITION PLEASE PROVIDE | | | THE ENERGY CALCULATIONS AND THE MANUAL J CALCULATIONS | | | FOR THE NEW ADDITION. FBC EC 101.5.1.1.2; FBC RES | | | M1401.3 | | | | | | 3) PLEASE PROVIDE A MECHANICAL DRAWING FOR THE | | | MECHANICAL SYSTEM FOR THE NEW ADDITION. FBC 107.2 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | | UPDATED. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2021-01-07 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-01-05 |
Time |
12:50 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-01-05 |
Time |
12:00 |
Sent To |
|
|
| Notes |
| 2021-01-05 12:50:33 | PERMIT ONLY FOR DEMO WORK, HARD CAPS REQUIRED BELOW | | | GROUND. | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2020-12-15 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2020-12-15 |
Time |
10:13 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2020-12-15 |
Time |
10:13 |
Sent To |
|
|
| Notes |
| 2020-12-15 10:14:27 | 12/15/20 2ND PLUMBING REVIEW**DENIED** WITH COMMENTS | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | SECOND REQUEST PER ALL ITEMS BELOW AS FOLLOW; | | | | | | 1. A SUB PLUMBING PERMIT IS REQUIRED BY A LICENSED | | | CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS | | | TO THE FBC SEC. 105.1. | | | | | | 2. PLUMBING RISER DIAGRAM REQUIRED PER THE WPB | | | AMENDMENTS TO THE FBC SEC. 107.3.5.3 (11) RESIDENTIAL | | | PLUMBING. | | | | | | 3. YOUR PERMIT SAYS A PROPOSED PATIO BUT YOU HAVE A | | | DRAWING FOR A BATHROOM AND A BEDROOM PLEASE PROVIDE A | | | SCOPE OF WORK TO BE DONE PER THE WPB AMENDMENTS TO THE | | | FBC SEC. 107.2.1.4 QUALITY OF BUILDING PLANS. | | | | | | 4. SIGNED AND SEALED DRAWINGS NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR | | | ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR - | | | IF YOUR ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL | | | SIGNATURE - PLEASE DROP OFF (CITY HALL DROPBOX) THE | | | ORIGINAL SIGNED AND SEALED DOCUMENT ALONG WITH A "PLAN | | | REVIEW REQUEST FORM" EXPLAINING THE REASON FOR | | | SUBMITTING THE DOCUMENT OR DRAWINGS. THE PLAN REVIEW | | | REQUEST FORM CAN BE OBTAINED BY EMAILING [email protected] AND | | | ASKING FOR THE FORM. | | | | | | 5. PLEASE PROVIDE THE SIGNATURE OF ALL INFORMATION, | | | DRAWINGS, SPECIFICATIONS, AND ACCOMPANYING DATA THAT | | | SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE PERSON | | | RESPONSIBLE FOR THE DESIGN PER THE WPB AMENDMENTS TO | | | THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION | | | DOCUMENTS. | | | | | | 6. PLEASE PROVIDE WHERE THE SOURCE OF HOT WATER IS | | | COMING FROM PER THE 2017 FBC SEC. R 2722.2. | | | | | | 7. IN FRONT OF A WATER CLOSET TO A FIXTURE, THERE SHALL | | | BE A CLEARANCE OF NOT LESS THAN 21 INCHES CLEARANCE PER | | | THE 2017 FBC SEC. R P2705.1. | | | | | | 8. THE CLAIMED VALUE APPEARS TO BE UNDERESTIMATED ON | | | THE APPLICATION, PLEASE PROVIDE A BONA FIDE SIGNED | | | CONTRACT PER THE WPB AMENDMENTS TO THE FBC SEC. 109.3 | | | BUILDING PERMIT VALUATIONS. | | | | | | 9. PLEASE ADDRESS ALL BUILDING COMMENTS. | | | | | | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. | | | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2020-10-21 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2020-10-21 |
Time |
17:15 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2020-10-21 |
Time |
17:15 |
Sent To |
|
|
| Notes |
| 2020-10-21 17:15:52 | 10/21/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | 1. A SUB PLUMBING PERMIT IS REQUIRED BY A LICENSED | | | CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS | | | TO THE FBC SEC. 105.1. | | | | | | 2. PLUMBING RISER DIAGRAM REQUIRED PER THE WPB | | | AMENDMENTS TO THE FBC SEC. 107.3.5.3 (11) RESIDENTIAL | | | PLUMBING. | | | | | | 3. YOUR PERMIT SAYS A PROPOSED PATIO BUT YOU HAVE A | | | DRAWING FOR A BATHROOM AND A BEDROOM PLEASE PROVIDE A | | | SCOPE OF WORK TO BE DONE PER THE WPB AMENDMENTS TO THE | | | FBC SEC. 107.2.1.4 QUALITY OF BUILDING PLANS. | | | | | | 4. SIGNED AND SEALED DRAWINGS NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR | | | ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR - | | | IF YOUR ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL | | | SIGNATURE - PLEASE DROP OFF (CITY HALL DROPBOX) THE | | | ORIGINAL SIGNED AND SEALED DOCUMENT ALONG WITH A "PLAN | | | REVIEW REQUEST FORM" EXPLAINING THE REASON FOR | | | SUBMITTING THE DOCUMENT OR DRAWINGS. THE PLAN REVIEW | | | REQUEST FORM CAN BE OBTAINED BY EMAILING [email protected] AND | | | ASKING FOR THE FORM. | | | | | | 5. PLEASE PROVIDE THE SIGNATURE OF ALL INFORMATION, | | | DRAWINGS, SPECIFICATIONS, AND ACCOMPANYING DATA THAT | | | SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE PERSON | | | RESPONSIBLE FOR THE DESIGN PER THE WPB AMENDMENTS TO | | | THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION | | | DOCUMENTS. | | | | | | 6. PLEASE PROVIDE WHERE THE SOURCE OF HOT WATER IS | | | COMING FROM PER THE 2017 FBC SEC. R 2722.2. | | | | | | 7. IN FRONT OF A WATER CLOSET TO A FIXTURE, THERE SHALL | | | BE A CLEARANCE OF NOT LESS THAN 21 INCHES CLEARANCE PER | | | THE 2017 FBC SEC. R P2705.1. | | | | | | 8. THE CLAIMED VALUE APPEARS TO BE UNDERESTIMATED ON | | | THE APPLICATION, PLEASE PROVIDE A BONA FIDE SIGNED | | | CONTRACT PER THE WPB AMENDMENTS TO THE FBC SEC. 109.3 | | | BUILDING PERMIT VALUATIONS. | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
3 |
Status |
N |
Date |
2021-01-12 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2021-01-12 |
Time |
10:39 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2021-01-12 |
Time |
10:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2020-12-17 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-12-17 |
Time |
07:54 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-12-17 |
Time |
07:54 |
Sent To |
|
|
| Notes |
| 2020-12-17 07:55:06 | SEE BUILDING PLAN REVIEW |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2020-10-23 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-10-23 |
Time |
12:22 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-10-23 |
Time |
12:22 |
Sent To |
|
|
| Notes |
| 2020-10-23 12:23:16 | SEE BUILDING PLAN REVIEW |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2021-01-12 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2021-01-12 |
Time |
10:40 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2021-01-12 |
Time |
10:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
F |
Date |
2020-12-17 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-12-17 |
Time |
07:55 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-12-17 |
Time |
07:55 |
Sent To |
|
|
| Notes |
| 2020-12-17 07:56:08 | SEE BUILDING PLAN REVIEW |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2020-10-23 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-10-23 |
Time |
12:22 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-10-23 |
Time |
12:22 |
Sent To |
|
|
| Notes |
| 2020-10-23 12:22:32 | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR | | | ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. | | | DRAWINGS DO NOT SHOW IN "ADOBE READER" AS | | | DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR | | | ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR | | | DIGITAL SIGNATURE - PLEASE DROP OFF (CITY HALL DROP | | | BOX) THE ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS | | | ALONG WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE | | | REASON FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN | | | REVIEW REQUEST FORM CAN BE OBTAINED BY E MAILING | | | [email protected] AND ASKING FOR THE FORM. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2020-09-24 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-09-24 |
Time |
11:20 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-09-24 |
Time |
11:20 |
Sent To |
|
|
| Notes |
| 2020-09-24 11:20:38 | SEE BUILDING PLAN REVIEW |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
N |
Date |
2021-01-04 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2021-01-04 |
Time |
15:14 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2021-01-04 |
Time |
15:14 |
Sent To |
|
|
| Notes |
| 2021-01-04 15:15:03 | PERMIT CHANGED TO REMOVE UNPERMITTED WORK SO NO ZONING | | | REQ'D. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2020-12-04 |
|
|
Cont ID |
|
| Sent By |
kalexand |
Date |
2020-12-04 |
Time |
08:23 |
Rev Time |
0.00 |
| Received By |
kalexand |
Date |
2020-12-04 |
Time |
08:23 |
Sent To |
I |
|
| Notes |
| 2020-12-04 09:17:40 | ZONING PLAN REVIEW | | | ________________________________________ | | | | | | DATE OF REVIEW: | | | ________________________________________ | | | | | | REVIEW STATUS: FAILED | | | ________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | | REVIEW COMMENTS: | | | | | | 1. PLANS DO NOT MATCH APPLICATION. PLEASE CLARIFY WHAT | | | IS BEING PROPOSED. | | | 2. IF AN ADDITIONAL BEDROOM IS BEING PROPOSED PLEASE | | | NOTE THAT PURSUANT TO ZLDR ARTICLE XIX: DWELLING UNIT: | | | ALL ROOMS IN THE DWELLING UNIT MUST BE ACCESSIBLE FROM | | | THE INTERIOR OF THE UNIT. | | | 3. PLEASE INDICATE SETBACK DIMENSIONS FROM THE | | | NARROWEST POINT BETWEEN THE PROPOSED ADDITION AND | | | PROPERTY LINE. PUSUANT TO ZLDR SEC. 94-72 THE MINIMUM | | | SIDE SETBACK IS 5FT. | | | ________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD | | | LIKE TO RESUBMIT ELECTRONICALLY, EMAIL | | | [email protected] AND REQUEST TO HAVE YOUR | | | PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOG | | | IN INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL. | | | PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU | | | ARE FINISHED UPLOADING. | | | ________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | KIZZI ALEXANDRE, ASSOCIATE PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | P: 561.822.1442 | | | TTY: 800.955.8771 | | | E: [email protected] | | | | | | W: WPB.ORG | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2020-09-21 |
|
|
Cont ID |
|
| Sent By |
kalexand |
Date |
2020-09-21 |
Time |
10:33 |
Rev Time |
0.00 |
| Received By |
kalexand |
Date |
2020-09-21 |
Time |
10:33 |
Sent To |
I |
|
| Notes |
|
|