| Plan Review Stops For Permit 20090386 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2021-06-15 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-06-15 |
Time |
14:17 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-06-15 |
Time |
14:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2021-03-31 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-03-31 |
Time |
09:20 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-03-31 |
Time |
09:20 |
Sent To |
|
|
| Notes |
| 2021-03-31 09:22:37 | POOL | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PLEASE SHOW THE LOCATION OF THE (POOL BARRIER) | | | SCREEN ENCLOSURE OR THE FENCE - FBC R4501.17 | | | RESIDENTIAL SWIMMING BARRIER REQUIREMENT. | | | RESIDENTIAL SWIMMING POOLS SHALL COMPLY WITH SECTIONS | | | R4501.17.1 THROUGH R4501.17.3. | | | EXCEPTION: A SWIMMING POOL WITH AN APPROVED SAFETY POOL | | | COVER COMPLYING WITH ASTM F1346. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2020-10-07 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-10-07 |
Time |
14:44 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-10-07 |
Time |
14:14 |
Sent To |
|
|
| Notes |
| 2020-10-07 14:44:45 | POOL | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PLEASE UPDATE NOTES ON THE DRAWINGS - SHOW THAT A | | | POOL BARRIER IS REQUIRED PER FBC R4501.17 RESIDENTIAL | | | SWIMMING BARRIER REQUIREMENT. | | | RESIDENTIAL SWIMMING POOLS SHALL COMPLY WITH SECTIONS | | | R4501.17.1 THROUGH R4501.17.3. | | | EXCEPTION: A SWIMMING POOL WITH AN APPROVED SAFETY POOL | | | COVER COMPLYING WITH ASTM F1346. | | | 2) ALL DRAWINGS NEED TO BE SIGNED AND SEALED BY THE | | | ARCHITECT OR ENGINEER. | | | | | | FYI = SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO | | | BE DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR | | | ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR - | | | IF YOUR ARCHITECT OR ENGINEER DOES NOT HAVE AN | | | ELECTRONIC OR DIGITAL SIGNATURE - PLEASE DROP OFF (CITY | | | HALL DROP BOX) THE ORIGINAL SIGNED AND SEALED | | | DRAWINGS/DOCUMENTS ALONG WITH A "PLAN REVIEW REQUEST | | | FORM" EXPLAINING THE REASON FOR SUBMITTING THE DOCUMENT | | | OR DRAWINGS. PLAN REVIEW REQUEST FORM CAN BE OBTAINED | | | BY E MAILING [email protected] AND ASKING FOR THE FORM. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2021-06-03 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-06-03 |
Time |
09:28 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-06-03 |
Time |
09:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2021-03-24 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-03-24 |
Time |
08:19 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-03-24 |
Time |
08:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2020-09-23 |
|
|
Cont ID |
|
| Sent By |
ppetty |
Date |
2020-09-23 |
Time |
10:47 |
Rev Time |
0.00 |
| Received By |
ppetty |
Date |
2020-09-23 |
Time |
10:47 |
Sent To |
|
|
| Notes |
| 2020-09-23 10:51:42 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1.PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE | | | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE | | | IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2 | | | | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | | SHEETS. | | | | | | SINCERELY, | | | | | | PHIL PETTY | | | CHIEF ELECTRICAL INSPECTOR , ELECTRICAL PLANS EXAMINER | | | | | | 561-805-6742 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2021-06-15 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-06-15 |
Time |
14:17 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-05-25 |
Time |
13:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2021-05-05 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2021-05-05 |
Time |
09:02 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2021-03-17 |
Time |
15:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2020-10-07 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-10-07 |
Time |
14:45 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-09-22 |
Time |
16:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2021-05-27 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-05-27 |
Time |
13:47 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-05-27 |
Time |
13:46 |
Sent To |
|
|
| Notes |
| 2021-05-27 13:48:03 | 05/27/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING/POOL) | | | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | | PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES | | | FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, | | | STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT | | | THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK | | | OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | | AVOID VOIDING OF THE PERMIT. | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2021-03-19 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-03-19 |
Time |
08:14 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-03-19 |
Time |
07:56 |
Sent To |
|
|
| Notes |
| 2021-03-19 08:16:24 | 03/19/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING/POOL) | | | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | | PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES | | | FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, | | | STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT | | | THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK | | | OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | | AVOID VOIDING OF THE PERMIT. | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2020-09-23 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2020-09-23 |
Time |
11:09 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2020-09-23 |
Time |
07:55 |
Sent To |
|
|
| Notes |
| 2020-09-23 11:10:43 | 09/23/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING/POOL) | | | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | | PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES | | | FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, | | | STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT | | | THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK | | | OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | | AVOID VOIDING OF THE PERMIT. | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2021-06-15 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-06-15 |
Time |
14:17 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-06-15 |
Time |
14:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2021-03-31 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-03-31 |
Time |
09:23 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-03-31 |
Time |
09:23 |
Sent To |
|
|
| Notes |
| 2021-03-31 09:24:59 | DRAWING LABELED "002 PLAN 2.PDF " IN PROJECTDOX = | | | | | | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR | | | ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. | | | DRAWINGS DO NOT SHOW IN "ADOBE READER" AS | | | DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR | | | ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR | | | DIGITAL SIGNATURE - YOU CAN MAIL IN OR DROP OFF THE | | | ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE | | | FRONT DESK IN THE BUILDING DEPT. AT THE CITY HALL |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2020-09-23 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2020-09-23 |
Time |
11:04 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2020-09-23 |
Time |
11:04 |
Sent To |
|
|
| Notes |
| 2020-09-23 11:05:12 | SIGNED AND SEALED DRAWINGS NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR | | | ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR - | | | IF YOUR ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL | | | SIGNATURE - PLEASE DROP OFF (CITY HALL DROPBOX) THE | | | ORIGINAL SIGNED AND SEALED DOCUMENT ALONG WITH A "PLAN | | | REVIEW REQUEST FORM" EXPLAINING THE REASON FOR | | | SUBMITTING THE DOCUMENT OR DRAWINGS. THE PLAN REVIEW | | | REQUEST FORM CAN BE OBTAINED BY EMAILING [email protected] AND | | | ASKING FOR THE FORM. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2021-05-04 |
|
|
Cont ID |
|
| Sent By |
kalexand |
Date |
2021-05-04 |
Time |
17:08 |
Rev Time |
0.00 |
| Received By |
kalexand |
Date |
2021-05-04 |
Time |
17:08 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2020-10-02 |
|
|
Cont ID |
|
| Sent By |
kalexand |
Date |
2020-10-02 |
Time |
13:50 |
Rev Time |
0.00 |
| Received By |
kalexand |
Date |
2020-10-02 |
Time |
13:50 |
Sent To |
I |
|
| Notes |
|
|