Plan Review Details - Permit 20090362
Plan Review Stops For Permit 20090362
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-09-30 Cont ID  
Sent By ppetty Date 2020-09-30 Time 10:42 Rev Time 0.00
Received By ppetty Date 2020-09-30 Time 10:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-09-28 Cont ID  
Sent By ppetty Date 2020-09-28 Time 09:58 Rev Time 0.00
Received By ppetty Date 2020-09-28 Time 09:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-09-16 Cont ID  
Sent By ppetty Date 2020-09-16 Time 14:26 Rev Time 0.00
Received By ppetty Date 2020-09-16 Time 13:03 Sent To  
Notes
2020-09-16 14:27:24PLEASE SEE F/D NOTES

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2020-09-29 Cont ID  
Sent By pleduc Date 2020-09-29 Time   Rev Time 0.00
Received By pleduc Date 2020-09-29 Time 13:31 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-09-25 Cont ID  
Sent By pleduc Date 2020-09-25 Time   Rev Time 0.00
Received By pleduc Date 2020-09-25 Time 16:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-09-15 Cont ID  
Sent By pleduc Date 2020-09-15 Time   Rev Time 0.00
Received By pleduc Date 2020-09-15 Time 13:52 Sent To  
Notes
2020-09-15 14:07:53THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THE FOLLOWING COMMENTS AND CODE SECTIONS ARE BEING
 SUBMITED IN AN EFFORT TO HELP REDUCE FALSE/NUISANCE
 FIRE ALARMS, ESPECIALLY WITH DEVICES LOCATED WHERE THEY
 ARE NOT REQUIRED.
  
 THERE ARE INDICATIONS OF SMOKE DETECTORS AND PULL
 STATIONS LOCATED THROUGHOUT THE OCCUPANCIES.
  
 SMOKE DETECTORS AND PULLS STATIONS MAY NOT BE REQUIRED
 AS PROPOSED.
  
 PER NFPA 101, CH 42 STORAGE OCCUPANCIES
  
 42.8 SPECIAL PROVISIONS FOR PARKING STRUCTURES.
  
 42.8.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
 42.8.3.4.1 GENERAL. A FIRE ALARM SYSTEM SHALL BE
 REQUIRED IN
 ACCORDANCE WITH SECTION 9.6 FOR PARKING STRUCTURES,
 EXCEPT AS
 MODIFIED BY 42.3.4.1.1, 42.3.4.1.2, AND 42.3.4.1.3.
 42.8.3.4.1.1 PARKING STRUCTURES NOT EXCEEDING AN
 AGGREGATE FLOOR
 AREA OF 100,000 FT2 (9300 M2) SHALL NOT BE REQUIRED TO
 HAVE A FIRE
 ALARM SYSTEM.
 42.8.3.4.1.2 OPEN PARKING STRUCTURES SHALL NOT BE
 REQUIRED TO HAVE
 A FIRE ALARM SYSTEM.
 42.8.3.4.1.3 PARKING STRUCTURES PROTECTED THROUGHOUT BY
 AN
 APPROVED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH
 SECTION
 9.7 SHALL NOT BE REQUIRED TO HAVE A FIRE ALARM SYSTEM.
  
 42.8.3.4.2 INITIATION. INITIATION OF THE REQUIRED FIRE
 ALARM SYSTEM
 SHALL BE BY ONE OF THE FOLLOWING MEANS:
 (1) MANUAL MEANS IN ACCORDANCE WITH 9.6.2.1(1)
 (2) APPROVED AUTOMATIC FIRE DETECTION SYSTEM IN
 ACCORDANCE WITH
 9.6.2.1(2) THROUGHOUT THE BUILDING, PLUS A MINIMUM OF
 ONE
 MANUAL FIRE ALARM BOX IN ACCORDANCE WITH 9.6.2.6
  
 (3) APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH 9.6.2.1(3) THROUGHOUT THE BUILDING,
 PLUS A
 MINIMUM OF ONE MANUAL FIRE ALARM BOX IN ACCORDANCE WITH
 9.6.2.6
  
 NFPA 101, CH 9
  
 9.6.2 SIGNAL INITIATION.
 9.6.2.1 WHERE REQUIRED BY OTHER SECTIONS OF THIS CODE,
 ACTUATION
 OF THE FIRE ALARM SYSTEM SHALL OCCUR BY ANY OR ALL OF
 THE FOLLOWING
 MEANS OF INITIATION BUT SHALL NOT BE LIMITED TO SUCH
 MEANS:
 (1) MANUAL FIRE ALARM INITIATION
 (2) AUTOMATIC DETECTION
 (3) EXTINGUISHING SYSTEM OPERATION
  
 9.6.2.6* FOR FIRE ALARM SYSTEMS USING AUTOMATIC FIRE
 DETECTION OR
 WATERFLOW DETECTION DEVICES TO INITIATE THE FIRE ALARM
 SYSTEM IN
 ACCORDANCE WITH CHAPTERS 11 THROUGH 43, NOT LESS THAN
 ONE MANUAL
 FIRE ALARM BOX, LOCATED AS REQUIRED BY THE AUTHORITY
 HAVING
 JURISDICTION, SHALL BE PROVIDED TO INITIATE A FIRE
 ALARM SIGNAL.
  
 NFPA 101, CH 13 EXISTING ASSEMBLY
  
 13.3.4.2 INITIATION.
 13.3.4.2.1 INITIATION OF THE REQUIRED FIRE ALARM SYSTEM
 SHALL BE BY
 BOTH OF THE FOLLOWING MEANS, AND THE SYSTEM SHALL BE
 PROVIDED
 WITH AN EMERGENCY POWER SOURCE:
 (1) MANUAL MEANS IN ACCORDANCE WITH 9.6.2.1(1), UNLESS
 OTHERWISE PERMITTED BY ONE OF THE FOLLOWING:
 (A) THE REQUIREMENT OF 13.3.4.2.1(1) SHALL NOT APPLY
 WHERE
 INITIATION IS BY MEANS OF AN APPROVED AUTOMATIC FIRE
 DETECTION SYSTEM IN ACCORDANCE WITH 9.6.2.1(2) THAT
 PROVIDES FIRE DETECTION THROUGHOUT THE BUILDING.
 (B) THE REQUIREMENT OF 13.3.4.2.1(1) SHALL NOT APPLY
 WHERE
 INITIATION IS BY MEANS OF AN APPROVED AUTOMATIC
 SPRINKLER SYSTEM IN ACCORDANCE WITH 9.6.2.1(3) THAT
 PROVIDES FIRE DETECTION AND PROTECTION THROUGHOUT THE
 BUILDING.
 (2) WHERE AUTOMATIC SPRINKLERS ARE PROVIDED, INITIATION
 OF THE
 FIRE ALARM SYSTEM BY SPRINKLER SYSTEM WATERFLOW, EVEN
 WHERE
 MANUAL FIRE ALARM BOXES ARE PROVIDED IN ACCORDANCE WITH
 13.3.4.2.1(1)
 13.3.4.2.2 THE INITIATING DEVICE SHALL BE CAPABLE OF
 TRANSMITTING AN
 ALARM TO A RECEIVING STATION, LOCATED WITHIN THE
 BUILDING, THAT IS
 CONSTANTLY ATTENDED WHEN THE ASSEMBLY OCCUPANCY IS
 OCCUPIED.
 13.3.4.2.3* IN ASSEMBLY OCCUPANCIES WITH OCCUPANT LOADS
 OF MORE
 THAN 300, AUTOMATIC DETECTION SHALL BE PROVIDED IN ALL
 HAZARDOUS
 AREAS THAT ARE NOT NORMALLY OCCUPIED, UNLESS SUCH AREAS
 ARE
 PROTECTED THROUGHOUT BY AN APPROVED AUTOMATIC SPRINKLER
 SYSTEM
 IN ACCORDANCE WITH SECTION 9.7.
  
 THERE DOES NOT APPEAR TO BE SMOKE DETECTOR PROTECTION
 REQUIRED WITHIN THE CODE AS LONG AS THERE IS FIRE
 SPRINKLER PROTECTION IN THOSE AREAS.
  
 THE NUMBER OF PULL STATIONS CAN BE REDUCED TO ONE IN
 EACH AREA AS LONG AS THE FIRE SPRINKLER ACTIVATION
 ACTIVATES THE FIRE ALARM SYSTEM.
  
 PLEASE REVIEW AND CORRECT AS REQUIRED BY CODE OR
 PROVIDE A DETAILED NARRATIVE ANALYSIS OF YOUR POSITION.
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-09-30 Cont ID  
Sent By ccarvaja Date 2020-09-30 Time 10:43 Rev Time 0.00
Received By ppetty Date 2020-09-28 Time 15:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-09-30 Cont ID  
Sent By ppetty Date 2020-09-28 Time 09:59 Rev Time 0.00
Received By ppetty Date 2020-09-24 Time 15:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-09-18 Cont ID  
Sent By ccarvaja Date 2020-09-18 Time 15:15 Rev Time 0.00
Received By ccarvaja Date 2020-09-11 Time 11:33 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-09-28 Cont ID  
Sent By medwards Date 2020-09-28 Time 07:52 Rev Time 0.00
Received By medwards Date 2020-09-28 Time 07:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-09-18 Cont ID  
Sent By medwards Date 2020-09-18 Time 15:01 Rev Time 0.00
Received By medwards Date 2020-09-18 Time 14:40 Sent To  
Notes
2020-09-18 15:02:40SEE FIRE REVIEWERS COMMENTS.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-09-30 Cont ID  
Sent By ppetty Date 2020-09-30 Time 10:43 Rev Time 0.00
Received By ppetty Date 2020-09-30 Time 10:43 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-09-28 Cont ID  
Sent By medwards Date 2020-09-28 Time 07:55 Rev Time 0.00
Received By medwards Date 2020-09-28 Time 07:52 Sent To  
Notes
2020-09-28 07:56:39DESIGNER MUST DIGITALLY SIGN AND SEAL SHEET FA-01
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-09-18 Cont ID  
Sent By medwards Date 2020-09-18 Time 15:07 Rev Time 0.00
Received By medwards Date 2020-09-18 Time 15:07 Sent To  
Notes
***NONE***