Plan Review Details - Permit 20090297
Plan Review Stops For Permit 20090297
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status N Date 2020-09-24 Cont ID  
Sent By rmcphers Date 2020-09-24 Time 13:50 Rev Time 0.00
Received By rmcphers Date 2020-09-24 Time 13:50 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-09-24 Cont ID  
Sent By rmcphers Date 2020-09-24 Time 13:50 Rev Time 0.00
Received By rmcphers Date 2020-09-24 Time 13:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-01-04 Cont ID  
Sent By equinone Date 2021-01-04 Time 10:53 Rev Time 0.00
Received By equinone Date 2021-01-04 Time 10:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-09-17 Cont ID  
Sent By fgiaquin Date 2020-09-17 Time 22:18 Rev Time 0.00
Received By fgiaquin Date 2020-09-17 Time 21:41 Sent To  
Notes
2020-09-17 22:18:14ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. UPLOADED PLAN BLURRY AND NOT LEGIBLE.
  
 2. DIGITALLY SUBMITTED PLANS MUST BE DIGITALLY SIGNED
 AND SEALED BY DESIGN PROFESSIONAL WITH THIRD PARTY
 VERIFICATION.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-09-15 Cont ID  
Sent By pleduc Date 2020-09-15 Time   Rev Time 0.00
Received By pleduc Date 2020-09-15 Time 09:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-03-01 Cont ID  
Sent By medwards Date 2021-03-01 Time 10:11 Rev Time 0.00
Received By medwards Date 2021-02-19 Time 14:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-01-04 Cont ID  
Sent By equinone Date 2021-01-04 Time 10:54 Rev Time 0.00
Received By equinone Date 2020-12-21 Time 15:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-09-24 Cont ID  
Sent By rmcphers Date 2020-09-24 Time 14:06 Rev Time 0.00
Received By rmcphers Date 2020-09-05 Time 20:11 Sent To  
Notes
2020-09-11 20:11:45CONVERTED TO DIGITAL. JG

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2020-09-24 Cont ID  
Sent By rmcphers Date 2020-09-24 Time 14:05 Rev Time 0.00
Received By rmcphers Date 2020-09-24 Time 14:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2021-03-02 Cont ID  
Sent By medwards Date 2021-03-01 Time 10:06 Rev Time 0.00
Received By medwards Date 2021-03-01 Time 09:50 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2020-12-22 Cont ID  
Sent By medwards Date 2020-12-22 Time 08:02 Rev Time 0.00
Received By medwards Date 2020-12-22 Time 08:02 Sent To  
Notes
2020-12-22 08:02:291ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20090297
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SHOW RETURN AIR PATH FROM LOBBY BACK TO THE
 AHU. FBC M 601.6
  
 2) PLEASE SHOW THE DRYER LOCATION AND THE EXHAUST
 TERMINATION LOCATION IN RELATION TO THE OUTDOOR AIR
 TERMINATION LOCATION. FBC M 501.3.1 (3)
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-09-16 Cont ID  
Sent By medwards Date 2020-09-16 Time 10:34 Rev Time 0.00
Received By medwards Date 2020-09-16 Time 10:14 Sent To  
Notes
2020-09-16 10:36:32PLEASE PROVIDE A MECHANICAL SCOPE OF WORK ALONG WITH A
 DRAWING OF THE EXISTING MECHANICAL SYSTEM. IS THERE
 ANYDUCT WORK TO BE MOVED INTO THE NEW ROOMS AND FRONT
 WAITING AREA?
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2020-09-14 Cont ID  
Sent By lcrespo Date 2020-09-14 Time 10:41 Rev Time 0.00
Received By lcrespo Date 2020-09-14 Time 10:41 Sent To  
Notes
2020-09-14 10:42:0509/14/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status N Date 2021-03-01 Cont ID  
Sent By medwards Date 2021-03-01 Time 10:10 Rev Time 0.00
Received By medwards Date 2021-03-01 Time 10:10 Sent To  
Notes
2021-03-01 10:10:50NO NEW DRAWINGS WERE UPLOADED. ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-12-21 Cont ID  
Sent By medwards Date 2020-12-21 Time 16:19 Rev Time 0.00
Received By medwards Date 2020-12-21 Time 16:19 Sent To  
Notes
2020-12-21 16:20:21ORIGINAL PAPER DRAWING APPROVED AND ROUTED TO STORAGE.
 ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-09-11 Cont ID  
Sent By jgomez Date 2020-09-11 Time 20:12 Rev Time 0.00
Received By jgomez Date 2020-09-11 Time 20:11 Sent To  
Notes
2020-09-11 20:12:46DRAWING A-1/E-1 HAS THE ENGINEER'S ORIGINAL
 SEAL/SIGNATURE. JG.

Review Stop Z ZONING
Rev No 1 Status P Date 2020-09-21 Cont ID  
Sent By kalexand Date 2020-09-21 Time 10:19 Rev Time 0.00
Received By kalexand Date 2020-09-21 Time 10:19 Sent To I
Notes
***NONE***