| 2020-10-19 18:30:31 | 010/19/20 2ND GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. THIS IS A RESTAURANT AND IT REQUIRES A CHANGE OF |
| | OCCUPANCY. THERE IS NO APPLICATION OR PERMITS FOR THIS |
| | SCOPE OF WORK. PLEASE PROVIDE WHAT TYPE OF OCCUPANCY |
| | THIS INTERIOR BUILD-OUT WILL BE AND THE OCCUPANCY LOAD |
| | WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 2. A GREASE TRAP MAY BE REQUIRED ALONG WITH SIZING, A |
| | SEPARATE PERMIT AND APPLICATION WILL BE NEED IF SO 2017 |
| | FBC P 1003.1. |
| | |
| | 3. SUBMIT PLANS SHOWING THE LOCATION OF THE TANK-LESS |
| | WATER HEATER AND THE LOCATION AND DISTANCE OF ANY |
| | OPERABLE DOORS OR WINDOWS IN RELATION TO THE WATER |
| | HEATER. THE LOCATION OF THE WATER HEATER SHALL COMPLY |
| | WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE |
| | HOUSE PLAN CAN BE HAND-DRAWN PER THE WPB AMENDMENTS TO |
| | THE FBC SEC. 107.2.1. INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 4. A SUB ELECTRICAL PERMIT IS REQUIRED FOR THE SOURCE |
| | OF IGNITION PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 105.1. |
| | |
| | 5. THE PHYSICAL ADDRESS OF THE PROJECT MUST BE ON PLANS |
| | IN FULL, NUMBER, STREET, CITY, STATE, AND ZIP CODE PER |
| | THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. |
| | |
| | 6. SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED GAS |
| | APPLIANCES. WHERE IS COMBUSTION AIR PROVIDED BY THE |
| | BUILDING?S MECHANICAL VENTILATION SYSTEM, THE SYSTEM |
| | SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN |
| | ADDITION TO THE REQUIRED VENTILATION AIR PER THE 2017 |
| | FBC FG SEC. 304.9.3. COMBINED COMBUSTION AIR AND |
| | VENTILATION AIR SYSTEM. |
| | |
| | 7. SUBMIT THE SIZING TABLE USED IN THE DESIGN FOR THE |
| | GAS SYSTEM OR PLACE A NOTE ON SET OF PLANS LISTING THE |
| | SIZING TABLES FROM GAS CODES OR ANOTHER STANDARD THAT |
| | WERE USED IN THE DESIGN OF THIS SYSTEM PER THE 2017 FBC |
| | FG SEC. 402.3. |
| | |
| | 8. THE EMERGENCY HOOD SHUT DOWN SHUTOFF VALVE SHALL BE |
| | BELOW THE CEILING. THE MANUAL SHUTOFF VALVE SHALL BE |
| | UPSTREAM. UNION TO BE DOWNSTREAM OF MANUAL VALVE. SECS. |
| | 10.4, 10.5 OF NFPA 96-08. |
| | |
| | 9. PROVIDE THE SIGNATURE OF ALL INFORMATION OF DATA |
| | SHALL BEAR THE PRINTED NAME OF THE SIGNATURE OF THE |
| | PERSON RESPONSIBLE FOR THE DESIGN PER THE WPB |
| | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |