Plan Review Details - Permit 20090281
Plan Review Stops For Permit 20090281
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2020-09-17 Cont ID  
Sent By cpuell Date 2020-09-17 Time 11:17 Rev Time 0.00
Received By cpuell Date 2020-09-17 Time 11:17 Sent To  
Notes
***NONE***

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2020-09-09 Cont ID  
Sent By cpuell Date 2020-09-09 Time 12:27 Rev Time 0.00
Received By cpuell Date 2020-09-09 Time 12:27 Sent To  
Notes
2020-09-09 12:28:00PLEASE REACH OUT TO ME AT [email protected], TO ESTABLISH
 SINGLE UNIT NUMBER AND RETIRE THE OTHER UNIT.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2020-11-23 Cont ID  
Sent By jwitmer Date 2020-11-23 Time 14:15 Rev Time 0.00
Received By jwitmer Date 2020-11-23 Time 14:01 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-09-28 Cont ID  
Sent By jwitmer Date 2020-09-28 Time 08:03 Rev Time 0.00
Received By jwitmer Date 2020-09-28 Time 07:25 Sent To  
Notes
2020-09-28 08:03:48TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-11-23 Cont ID  
Sent By jwitmer Date 2020-11-23 Time 14:14 Rev Time 0.00
Received By jwitmer Date 2020-11-23 Time 14:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-09-28 Cont ID  
Sent By jwitmer Date 2020-09-28 Time 08:13 Rev Time 0.00
Received By jwitmer Date 2020-09-28 Time 07:26 Sent To  
Notes
2020-09-28 07:27:10WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20090281
 ADD: 1801 S. FLAGLER DR. # 1407
 CONT: GRUBER HALL CORP.
 TEL: 561-697-3401
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. SEPT. 28TH/ 2020
 ACTION: DENIED
  
 1) PLEASE NOTE THE PERMIT APPLICATION UNDER THE
 DESCRIPTION OF WORK IS LEFT BLANK? IT WOULD APPEAR TO
 BE AN INTERIOR DEMOLITION OF 2 SIDES BY SIDE UNITS THAT
 ARE TO BE ADJOINED WITH A UNITY OF TITLE. ONLY ONE
 SHEET SUBMITTED BUT, IN THE ARCHITECTS, TITLE BLOCK IT
 STATES RENOVATIONS TO THE UNITS IN QUESTION? 107.2.1.2
 ADDITIONAL INFORMATION IS REQUIRED?
  
 2) THE VALUE OF THE PERMIT IS IN QUESTION, IF THE
 PERMIT IS TO BE A INTERIOR DEMOLITION OF 2 UNITS ONLY,
 THE VALUE OF $5,000.00 MAY COVER THE COST OF ONE UNIT
 BUT NOT, 2 UNITS, WITH COST, INCLUDING DUMP FEES, OR
 DUMPSTER FEES, AND DESIGN TEAM COST (ARCHITECT) IT IS
 CLOSER TO $15, 000.00 IN VALUE.
 109.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDERESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 3) 2017 EXISTING BUILDING CODE METHOD OF PLAN
 DEVELOPMENT. 2017 EXISTING BUILD. CODE SECTION 301.1.
 THE REPAIRS, ALTERATIONS, CHANGE OF OCCUPANCY,
 ADDITIONS OR RELOCATION OF ALL EXISTING BUILDINGS SHALL
 COMPLY WITH ONE OF THE METHODS LISTED IN SECTIONS
 301.1.1 THROUGH 301.1.3 AS SELECTED BY THE DESIGNER OF
 RECORD.
  
 4) TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-12-08 Cont ID  
Sent By jleahy Date 2020-12-08 Time 15:38 Rev Time 0.00
Received By jleahy Date 2020-12-08 Time 15:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-12-04 Cont ID  
Sent By jleahy Date 2020-12-04 Time 16:24 Rev Time 0.00
Received By jleahy Date 2020-12-04 Time 16:17 Sent To  
Notes
2020-12-04 16:26:37ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 DRAIN PUMP IN BATH #3 NOT GFCI PROTECTED

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-10-02 Cont ID  
Sent By jleahy Date 2020-10-02 Time 07:51 Rev Time 0.00
Received By jleahy Date 2020-10-02 Time 07:50 Sent To  
Notes
2020-10-02 07:53:55ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 THIS PERMIT SEEMS TO BE FOR A DEMO, NO NEW PLANS HAVE
 BEEN SUBMITTED.
  
 FOR A DEMO ELECTRICAL NEEDS A SUBPERMIT FOR THE
 ELECTRICAL PORTION OF THE DEMO.
  
 DEMO
 ELECTRICAL PLAN REVIEW NEEDS AN ELECTRICAL PERMIT
 APPLICATION FOR APPROVAL. PLEASE EMAIL THE ELECTRICAL
 PERMIT APPLICATION TO [email protected] AND CC
 [email protected] SO I RECEIVE IT ALSO. WHEN THIS EMAIL
 IS RECEIVED ONE OF THE REVIEWERS WILL APPROVE THE PLAN
 REVIEW. THE ORIGINAL PERMIT APPLICATION MUST BE
 SUBMITTED WHEN THE PERMIT IS PICKED UP
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-09-21 Cont ID  
Sent By pleduc Date 2020-09-21 Time   Rev Time 0.00
Received By pleduc Date 2020-09-21 Time 15:31 Sent To  
Notes
2020-09-21 15:32:19FIRE HAS NO OBJECTION TO THE PROPOSED UNITY OF TITLE
 WITH THE FOLLOWING COMMENT:
  
 1) PROPER PERMITING FOR ALL CONSTRUCTION WORK IS
 REQUIRED.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-12-08 Cont ID  
Sent By lmarchan Date 2020-12-08 Time 16:00 Rev Time 0.00
Received By lmarchan Date 2020-12-07 Time 16:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-12-04 Cont ID  
Sent By jleahy Date 2020-12-04 Time 16:26 Rev Time 0.00
Received By jleahy Date 2020-11-19 Time 10:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-10-02 Cont ID  
Sent By jleahy Date 2020-10-02 Time 07:54 Rev Time 0.00
Received By jleahy Date 2020-09-17 Time 11:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-12-08 Cont ID  
Sent By medwards Date 2020-12-08 Time 15:13 Rev Time 0.00
Received By medwards Date 2020-12-08 Time 15:13 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-11-20 Cont ID  
Sent By medwards Date 2020-11-20 Time 16:37 Rev Time 0.00
Received By medwards Date 2020-11-20 Time 15:37 Sent To  
Notes
2020-11-20 16:37:311ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20090281
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) M1.1: INDICATES A 1-HOUR TENANT SEPARATION WALL
 BETWEEN THE UNIT AND THE MECHANICAL CLOSET HOUSING THE
 EXISTING FHP EM024-1VTC. PLEASE SHOW A DETAIL OF THE
 PROTECTION AT THE SUPPLY AND RETURN DUCTS PENETRATION
 OF THE RATED WALL. FBC M 607.5
  
 2) PLEASE SHOW THE RETURN PATH FROM THE LIVING SPACE
 GOING BACK TO THE MECHANICAL UNIT. FBC M 602.1
  
 3) IT APPEARS THAT THE WALL BETWEEN THE MECHANICAL
 SYSTEM AND THE LIVING SPACE IS A RATED WALL BUT THE
 MECHANICAL CLOSET IS NOT SEPARATED FROM THE CORRIDOR.
 PLEASE SHOW HOW THIS DOES NOT BRING AIR FROM THE
 CORRIDOR INTO THE MECHANICAL CLOSET. FBC M 601.2
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2020-11-30 Cont ID  
Sent By lcrespo Date 2020-11-30 Time 18:00 Rev Time 0.00
Received By lcrespo Date 2020-11-30 Time 17:52 Sent To  
Notes
2020-11-30 18:00:1411/30/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-12-08 Cont ID  
Sent By medwards Date 2020-12-08 Time 15:18 Rev Time 0.00
Received By medwards Date 2020-12-08 Time 15:18 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-11-23 Cont ID  
Sent By jwitmer Date 2020-11-23 Time 14:15 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-09-17 Cont ID  
Sent By shill Date 2020-09-17 Time 16:58 Rev Time 0.00
Received By shill Date 2020-09-17 Time 16:58 Sent To  
Notes
***NONE***