| 2020-09-13 16:01:21 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20090264 |
| | ADD: 5600 N. FLAGLER DR. # 606 |
| | CONT: LEGACY BROTHERS CONSTRUCTION |
| | TEL: 912-657-5758 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: SUN. SEPT. 13TH/2020 |
| | ACTION: DENIED |
| | |
| | 1A) DISCREPANCY IN THE FLOOR PLAN SUBMITTED, SCOPE OF |
| | WORK AND THE UPLOADED FILES. THE FLOOR PLAN SHOWS IN |
| | THE MASTER BATH A TUB AND A ? BATH WITH A LAVATORY AND |
| | WATER CLOSET. THE SCOPE OF WORK INDICATES THE REPLACE |
| | TUB FOR NEW, BUT THE FILE UPLOADED SHOWS A NEW SHOWER |
| | PAN BASE. ADDITIONAL INFORMATION IS REQUIRED.107.2.1.2. |
| | |
| | 1B) IF THERE IS A CHANGE FROM A TUB TO A SHOWER WILL |
| | THE SAME WASTE BE USED, OR WILL THERE BE A NEW HOLE |
| | CORED THROUGH THE FLOOR? IF THERE IS TO BE A NEW HOLE |
| | BORED THROUGH THE FLOOR THE FLOOR WILL NEED TO BE |
| | X-RAYED TO SEE THE LOCATION OF THE POST-STRESSED |
| | CABLES. |
| | |
| | 1C) FOR A NEW PENETRATION THROUGH THE FLOOR SLAB PLEASE |
| | PROVIDE THE THROUGH PENETRATION FIRE STOP SYSTEM IN |
| | COMPLIANCE WITH THE 2017 FBC-B SECTION 714.4.1.1. |
| | |
| | 1D) PLEASE ALSO PROVIDE WHAT TYPE OF PLEASE PROVIDE THE |
| | THROUGH PENETRATION FIRE STOP SYSTEM WILL BE USED IN |
| | THE OLD HOLE LEFT BY THE OLD DRAIN LINE. 2017 FBC-B |
| | SECTION 714.4.1.1. |
| | |
| | 1E) IN EITHER CASE TUB OR SHOWER PLEASE PROVIDE WHAT |
| | TYPE OFF BACKER BOARD WILL BE INSTALLED ON EITHER THE |
| | SHOWER OR TUB. 2017 FBC-B SHOWERS & TUBS 1210.3. SHOWER |
| | COMPARTMENTS AND BATHTUBS WITH INSTALLED SHOWER HEADS |
| | SHALL BE FINISHED WITH A NONABSORBENT SURFACE TO A |
| | HEIGHT NOT LESS THAN 72 INCHES ABOVE THE DRAIN INLET. |
| | |
| | 2) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 |
| | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |