Plan Review Details - Permit 20090247
Plan Review Stops For Permit 20090247
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-10-21 Cont ID  
Sent By jleahy Date 2020-10-21 Time 16:45 Rev Time 0.00
Received By jleahy Date 2020-10-21 Time 16:45 Sent To  
Notes
2020-10-21 16:46:42SLAB REVIEW DONE UNDER ELECTRICAL REVIEW JLEAHY

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-09-28 Cont ID  
Sent By rmcdouga Date 2020-09-28 Time 07:30 Rev Time 0.00
Received By rmcdouga Date 2020-09-28 Time 07:30 Sent To  
Notes
2020-09-28 07:34:13PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE ENGINEER THAT IS ON THE PRECAST GENERATOR SLAB
 AND ANCHORING PLANS, RONALD H. WILSON P.E. LICENSE NO.
 9710, HAS HAD HIS FL ENGINEERING LICENSE REVOKED SINCE
 2/28/2017. SUBMIT SIGNED AND SEALED GENERATOR PAD
 DRAWINGS FROM A CURRENTLY LICENSED FL ENGINEER. FS 471
 ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO HAVE
 THE ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE
 THE OPTION TO SUBMIT THE SIGNED AND SEALED PAPER
 VERSION OF DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE
 BEEN APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE AND SEAL IS
 REQUIRED TO BE ON THE DRAWINGS. NO PHOTOCOPY OR OTHER
 FACSIMILES OF THE SIGNATURE ARE ACCEPTABLE. FS 471 &
 61G15
  
 2) THE GENERATOR EXHAUST IS REQUIRED TO BE 10 FEET FROM
 ANY OPENINGS INTO THE BUILDING. FBC-R303.5
  
 3) THIS PROPERTY IS LOCATED IN A SPECIAL FLOOD HAZARD
 AREA, "AE" 7 FT NAVD88. THE GERERATOR IS REQUIRED TO BE
 LOCATED AT OR ABOVE THE FINISH FLOOR ELEVATION OF THE
 LOWEST OCCUPIABLE FLOOR OF THE RESIDENCE. FBC-R322.1.6

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-10-21 Cont ID  
Sent By jleahy Date 2020-10-21 Time 16:42 Rev Time 0.00
Received By jleahy Date 2020-10-21 Time 16:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-09-10 Cont ID  
Sent By cthroop Date 2020-09-10 Time 11:21 Rev Time 0.00
Received By cthroop Date 2020-09-10 Time 09:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-10-21 Cont ID  
Sent By jleahy Date 2020-10-21 Time 16:46 Rev Time 0.00
Received By jleahy Date 2020-10-08 Time 15:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-10-02 Cont ID  
Sent By ccarvaja Date 2020-10-02 Time 12:34 Rev Time 0.00
Received By ccarvaja Date 2020-09-09 Time 10:55 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-10-21 Cont ID  
Sent By jleahy Date 2020-10-21 Time 16:45 Rev Time 0.00
Received By jleahy Date 2020-10-21 Time 16:45 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-09-10 Cont ID  
Sent By cthroop Date 2020-09-10 Time 11:21 Rev Time 0.00
Received By cthroop Date 2020-09-10 Time 11:21 Sent To  
Notes
2020-09-28 07:35:29SEE BUILDING REVIEW COMMENTS REGARDING SIGNATURE.
2020-09-10 11:25:56PLAN REVIEW / SIGNATURES
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 RE: LOAD CALC'S AND ELECTRIC RISER
  
  
 DOCUMENTS SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED
 BY THE CONTRACTOR OR DESIGNER OF RECORD.
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5), CHPT. 471, F.S. & 61G15 AND CHPT.
 481, F.S. & 61G1.
  
 EITHER UPLOAD A SIGNED DOCUMENT OR DROP OFF (OR MAIL)
 ONE PAPER ORIGINAL:
  
 BUILDING DIVISION, FIRST FLOOR
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST
 WEST PALM BEACH, FL 33401
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2020-10-20 Cont ID  
Sent By rthermid Date 2020-10-20 Time   Rev Time 0.00
Received By rthermid Date 2020-10-20 Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2020-10-02 Cont ID  
Sent By rthermid Date 2020-10-02 Time   Rev Time  
Received By rthermid Date 2020-10-02 Time   Sent To I
Notes
2020-10-02 11:50:07ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 10/2/2020
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PLEASE PROVIDE THE SETBACKS OFTHE GENERATOR TO THE
 SIDE ROPERTY SETBACK. PURSUANT TO THE CITY OF WEST PALM
 BEACH ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDR),
 SECTION 94-305(B)(4): MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK. THE
 REQUIRED SIDE SETBACK IS 5 FEET, THE GENERATOR MUST BE
 A MINIMUM OF 1 FOOT FROM THE SIDE PROPERTY LINE.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD
 LIKE TO RESUBMIT ELECTRONICALY, EMAIL
 [email protected] AND REQUEST TO HAVE YOUR
 PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOGIN
 INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL.
 PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU
 ARE FINISHED UPLOADING.
  
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 RAFAELA THERMIDOR, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 TTY: 800.955.8771
 E: [email protected]
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved