Plan Review Details - Permit 20090230
Plan Review Stops For Permit 20090230
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-10-02 Cont ID  
Sent By shill Date 2020-10-02 Time 14:06 Rev Time 0.00
Received By rmcphers Date 2020-10-02 Time 14:06 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-09-12 Cont ID  
Sent By shill Date 2020-09-12 Time 15:19 Rev Time 0.00
Received By shill Date 2020-09-12 Time 15:16 Sent To  
Notes
2020-09-12 15:21:12****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. SYSTEM A3 IS PROPOSED (FLAT DECK) WHICH HAS A DESIGN
 PRESSURE LIMITATION OF -60; ENGINEERING IS REQUIRED FOR
 ZONES 2 AND 3. FBC R 301
  
 2. PLEASE REMOVE THE ASSEMBLIES FROM THE PRODUCT
 APPROVAL THAT WILL NOT BE UTILIZED; ONLY THE PROPOSED
 ASSEMBLY SHOULD REMAIN IN THE PDF AS WELL AS THE FIRST
 PAGES WHICH APPLY TO ALL ASSEMBLIES. FBC 107
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-10-19 Cont ID  
Sent By rmcphers Date 2020-10-19 Time 15:07 Rev Time 0.00
Received By rmcphers Date 2020-10-19 Time 14:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-10-02 Cont ID  
Sent By rmcphers Date 2020-10-02 Time 14:07 Rev Time 0.00
Received By rmcphers Date 2020-09-30 Time 18:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-09-12 Cont ID  
Sent By shill Date 2020-09-12 Time 15:21 Rev Time 0.00
Received By shill Date 2020-09-10 Time 11:45 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-10-19 Cont ID  
Sent By mcphers Date 2020-10-19 Time 15:07 Rev Time 0.00
Received By rmcphers Date 2020-10-19 Time 15:07 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-10-02 Cont ID  
Sent By rmcphers Date 2020-10-02 Time 14:06 Rev Time 0.00
Received By rmcphers Date 2020-10-02 Time 14:06 Sent To  
Notes
2020-10-02 14:07:24SIGNED AND SEALED ENGINEERING PROVIDED = SIGNED AND
 SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL
 SIGNATURE - PLEASE DROP OFF (CITY HALL DROP BOX) THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS ALONG
 WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE REASON
 FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN REVIEW
 REQUEST FORM CAN BE OBTAINED BY E MAILING [email protected]
 AND ASKING FOR THE FORM.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-09-12 Cont ID  
Sent By shill Date 2020-09-12 Time 15:21 Rev Time 0.00
Received By shill Date 2020-09-12 Time 15:21 Sent To  
Notes
2020-09-12 15:21:53SEE BUILDING REVIEW
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved